Professional Documents
Culture Documents
SECTION 15920 Pneumatic Controls Rev 0
SECTION 15920 Pneumatic Controls Rev 0
~\
\ dl\~~1
~~ ~~ -<_':HtJ..I.b1\
-- w~\ ~--11
SECTION 15920:
KINGDOM
OFSAUDIARABIA
~~~I 41,rtJ1i61ooJl
RoyalCommission
forJubail& Yanbu cw.4~~1~1
SECTION 15920
PNEUMATIC CONTROLS
TABLE OF CONTENTS
PART 1 GENERAL............................................................................................................ 1
1.05 REFERENCES..................................................................................................... 3
1.06 SUBMITTALS....................................................................................................... 5
2.06 SENSORS.......................................................................................................... 14
3.04 INSTALLATION.................................................................................................. 26
3.09 TESTING............................................................................................................ 34
PART 1 GENERAL
A. This Section describes the minimum requirements for HVAC pneumatic control
system.
B. Pneumatic control shall maintain the required heating, ventilating, and cooling
(HVAC) conditions by performing the functions and sequences of operations
required. Pneumatic control shall provide safe operation of the dedicated system(s).
D. Wherever the word Contractor appears in this Section it means the Control
Contractor.
A. This Section includes Pneumatic Control equipment and components for HVAC
systems.
B. Plumbing system major equipment such as pumps, water level transmitter, etc. for
water and waste drainage system.
C. Fire Protection System such as fire pumps, jockey pump, alarm system and other
related items for fire protection system.
D. Medical equipment and gas system and all other major mechanical system.
A. The pneumatic control system work shall include all labor, materials, tools,
equipment, interfaces, administration, engineering, submittals, samples,
transportation, shipping, handling, installation, temporary protection, cleaning, cutting
and patching; labeling, calibration, testing, verification, documentation, supervision,
warranties, services, and items as specified in Contract Documents which are
required for a complete, fully functional, ready for operation and commissioned
pneumatic control system.
B. Control systems shall be complete, including all controllers, indicating devices, all
pneumatic piping, and all other equipment, apparatus and accessories required to
operate mechanical systems and to perform specified functions.
1. Provide all necessary relays, mounting brackets, air gages, switches and
accessories required, even though not specifically called for, so as to result in
complete workable and ready systems.
etc.
5. Provide training and demonstrations for the systems specified in this Section.
1. Mechanical Contractor (rather than Control Contractor) shall furnish and install
all taps and other mechanical interfaces required for control equipment
mounting into piping and duct systems.
2. Mechanical Contractor shall install all in-line mounted devices, such as valves,
dampers, wells, flow meters, etc., furnished by this Contractor.
3. Electrical Contractor shall provide circuit breakers, junction boxes, and wiring
required to provide electrical power to local junction box from electrical
distribution panels.
X. Section 15955 Testing, Adjusting and Balancing of Air and Hydronic System
1.05 REFERENCES
A. The referred codes and standards are intended to provide an acceptable level of
quality for materials, products and workmanship. In case of conflict between these
standards and the text of this Specification, the Specification text shall govern.
B. The latest revision of the referred codes and standards shall be used wherever
applicable. In case of conflict, the Contractor shall propose equipment, materials and
processes conforming to one group of codes and standards.
3. ANSI/ASME B16.26 Cast Copper Alloy fittings for Flared Copper Tubes
2. ASME (BPV VIII) Boiler and Pressure Vessel Code, Section VIII -
Rules for Construction of Pressure Vessels
1. NEMA PB 1 Panelboards
2. UL 67 Panelboards
1.06 SUBMITTALS
A. The Contractor shall submit to the Royal Commission, under the provisions of
SECTION 01330, the following items for review and approval before commencing
Work:
1. Compliance Statement
2. Preconstruction Submittals
a) Material, equipment, and fixture lists shall be submitted for control and
instrumentation systems.
3. Product Data
4. Shop Drawings
Schematic Drawings.
5. Coordination Drawings
a) Mark and detail exact location of inline devices, wells, and taps to be
installed by the Mechanical Contractor on Coordination Drawings.
6. As-Built Drawings
b) Show vendor furnished and field modified as-built control drawings and
sequence of operation descriptions.
7. Laminated Diagrams
8. Manufacturer's Instructions
9. Test Equipment
a) Provide list of all tools, special tools and equipment to be used during
commissioning.
11. Training
d) Warranty certificates.
a) Manual shall contain full support documentation, which shall include, but
not be limited to, the following:
1) General description and specifications.
2) Complete material lists and schedules of all equipment and each
type of control device, designation, location, function, set-point
range and set-point at start-up, as applicable. Including air supply
source, mechanical refrigeration-type air dryer, pneumatic
operators.
3) Installation and initial checkout procedures.
4) Adjustment procedures, calibration tolerances and inspection
period of all components.
5) Controller configuration and parameter setting procedures, as
applicable.
6) Step-by-step procedures required for each HVAC control systems
start-up, operation, shutdown, recovery and fault diagnosis.
7) Preventive maintenance requirements and a maintenance
checklist.
8) Cleaning methods and recommended cleaning materials.
9) Signal identification and timing diagrams.
10) Spare parts list data, including required tool kits and suggested
method of repairs such as field repair, factory repair or item
replacement.
11) Troubleshooting procedures, diagrams and guidelines.
12) Detailed schematics and assembly drawings.
A. The Contractor shall be responsible for the quality of work and shall develop and
propose programs and methods of construction and testing to achieve the specified
quality to the approval of the Royal Commission in accordance with
SECTION 01450.
B. The entire control systems shall be the product of a single manufacturer and no
mixing of components will be acceptable unless specifically approved in writing by
the Royal Commission.
C. Quality Assurance
1. Criteria
a) The Contractor shall have in-place facility within 100 km with technical
staff, spare parts inventory for the next 5 years, and necessary test and
diagnostic equipment to support the control systems.
5. Verification of Dimensions
a) The Contractor shall become familiar with details of work, shall verify
dimensions in the field, and shall advise the Royal Commission of any
7. Commissioning Procedures
a) Control system equipment, valves, dampers, panels, etc. shall bear the
manufacturer's nameplate.
b) Electrical Standards
1) Provide electrical components of pneumatic control systems
which have been UL-listed and labeled.
c) NEMA Compliance
1) Comply with NEMA standards pertaining to components and
devices for pneumatic control systems.
d) NFPA Compliance
1) Comply with NFPA 90A, where applicable to controls and control
sequences.
2) Pneumatic controls shall conform to FM/UL listed.
11. Demonstration
a) Training
1) Provide a qualified instructor to conduct training courses for
designated personnel in maintenance and operation of HVAC
control systems.
2) Orientation training to the specific system being installed under
the Contract.
3) Training shall be based on the operation and maintenance
manuals and control system training manual.
4) Furnish audiovisual equipment and other training materials and
supplies.
3. Contractor
B. In the absence of any of the above, best accepted industry practice shall be
employed throughout.
A. The Contractor shall deliver, handle and store equipment and material units in
accordance with SECTIONS 01650 and 01660, as well as the following
requirements:
2. Handling
3. Storage
4. Protection
PART 2 PRODUCTS
2.01 GENERAL
A. All goods and products covered by these Specifications shall be procured, when
available, from an in-Kingdom manufacturer. Procurement of all goods and products
manufactured out-of-Kingdom must be approved by the Royal Commission.
E. Values for setpoints, ranges, accuracies, sensitivities, etc. stated below are general
in nature. Exact values shall be specified based on particular individual applications.
2.02 THERMOSTATS
A. Space Thermostats
6. Room thermostats controlling heating and cooling devices shall have 3 modes
of operation (heating, null or dead band, and cooling).
10. Ranges
2. Equipped with adjustable sensitivity and shall be capable of having the control
point and reset range adjusted in the field.
3. Each instrument shall have 50 mm air gages on the main, pilot, and branch
connection.
4. All such thermostats sensing mixture air, hot deck, cold deck, coil discharge, or
fan discharge air temperature shall be equipped with flexible averaging bulb
sensing elements of a length no shorter than the width of the equipment where
they are located so as to sense a true average temperature. Minimum length
on averaging bulbs shall be 2.5 m. Pneumatic transmission, when utilized
shall be submitted for checking and approval.
1. Manual reset, line voltage type with 6 m flexible sensing elements responding
to highest temperature along entire length.
2.03 HUMIDISTAT
A. Room Humidistat
3. Sensors installed in a room and in accessible area shall have integral digital
display with the state of art technology.
5. Cover shall match room thermostat cover and shall be with display.
B. Duct-Mounted Humidistat
2.04 ACTUATORS
A. General
2. They shall be of ample size to develop a torque 50% greater than required by
the load imposed on them, but not less than 1695 N m (15 in. lb) minimum.
1. Rolling diaphragm, spring loaded, piston type with spring range as required
and start point adjustment, positioning relay or both.
1. Rolling diaphragm, piston type with adjustable stops and spring return, sized to
operate with sufficient reserve power to provide smooth modulating action or
2-position action.
D. Pilot Positioners
1. Starting point adjustable from 13.8 to 82.7 kPa (2 to 12 psi) and operating
span adjustable from 34.5 to 89.6 kPa (5 to 13 psi).
2.05 SENSORS
A. General
construction.
1. 1- or 2-pipe, direct acting, corrosion resistant rod and tube for air and liquid.
D. Duct-Mounted Sensors
1. Rigid and/or averaging sensor type, 20.7 to 103.4 kPa (3 to 15 psi) linear
output signal.
E. Humidity Sensor
A. Controllers shall be 2-pipe devices which use main air supplied to controller and
pneumatic relay to produce the controller output signal.
B. Controllers shall have field selectable local and remote adjustable setpoints, and an
adjustable proportional band for (proportional) control or an adjustable differential for
binary (2-position or floating) control.
C. Controllers shall have single- or dual-input ports as required for the application and
field selectable direct or reverse action for inputs. Dual input controllers shall have
adjustable secondary input authority.
D. Controllers shall have integral gage or test connections for testing, or indication of
input and output signals.
A. Receiver Controllers
1. 2-pipe, high capacity, proportional thermostats with liquid filled single point or
averaging elements sensing, adjustable setpoint and throttling range,
replaceable filter, and Fahrenheit or Celsius scales for all adjustments.
C. Sensor Controllers
D. Pressure Controllers
1. 1-pipe pressure and differential pressure controllers with single or dual bellows
to control steam, air, and non-corrosive gas or liquid where shown on the plans
or required by the sequence of operations. With adjustable setpoints and
throttling ranges, scale indications, and siphons.
E. Safety Controllers
A. General
1. Selection
3. Air Capacity
b) Size duplex system air compressors for 50% run time and simplex
systems, and for 33% run time with full system control load.
2. The assembled package shall include all major components, controls and a
sound attenuation enclosure.
3. The unit shall only require mounting to a foundation, hook up to system piping,
connection to the oil/ water separator, and power connection.
C. Air Compressors
4. Units shall have belt guards and meet ANSI B19.3 Safety Standards.
5. Provide 10-micron replaceable cartridge intake filter, and relief and shutoff
valves for each compressor.
D. Motors
2. Motors 350 W (½ hp) and larger shall be 3-phase (or shall match available job
site power supply).
4. Provide automatic lead/lag controller, which shall switch lead compressor after
each running cycle. Alternator shall be capable of bringing on both
compressors if one cannot handle load, and either shall continue to function on
failure of the other.
1. Air storage tank shall be ASME BPV SEC VIII constructed and stamped for
pressure 50% greater than operating pressure but not less than 1034 kPa
(150 psi).
2. Provide air storage tank complete with pressure gage, safety valve and drain
valve.
3. Tank shall be of sufficient volume so that the run time is not more than 50% for
duplex or 33% for simplex units.
F. Vibration Isolators
G. Air Dryer
3. Refrigerant air dryer shall reduce the compressed air dew point temperature,
at 138 kPa (20 psi) output pressure, to 0°C (32°F) with average tank pressure
of 552 kPa (80 psig) and ambient air temperature between 12.8 and 35°C
(55 and 95°F). Consult manufacturer for 50°C (122°F) ambient.
4. Provide dryer with an automatic condensate drain trap with a manual override
feature.
1. Provide dry-type combination intake air filter and silencer with baked enamel
steel housing and manual drain cock.
1. Provide dry type filter, 99% efficient in removing oil and solid particles at
0.03 micron rating, with baked enamel steel housing and manual drain valve.
2. Provide visual indicator to show when oil filter element should be changed.
1. Automatic condensate drain, 138 to 1380 kPa (20 to 200 psi) operating
pressure, with manual drain override.
station, valved bypass, relief valve, drain cock, fittings and required piping.
2. Reducing valve shall be field adjustable type with capacity and range as
required by the control systems.
1. ASME code rated, labeled for high pressure side and sized for installed
capacity of pressure regulators at low pressure.
1. Tubing
2. Fitting
3. Joints
1. The flexible pipe connections shall be designed for 1034 kPa and 120°C
(150 psi and 250°F) service.
3. The connectors shall be suitable for the service intended and shall have
threaded or soldered ends.
A. Control Panels
1. General
c) Control panels shall be provided with lighting inside the panel, having
IP 55/56 protection class and NEMA 4X enclosures.
2. Cabinet Construction
c) Alloy frames shall be fabricated from extruded shapes with all corners
securely riveted and supported by an internal angle bracket.
d) Surfaces shall be free of scale, welding slag, and dirt, and shall be flat
without waves. Handling during installation shall not distort or buckle the
cabinet.
g) Finished cutouts and holes shall be free of burrs and sharp edges.
j) Access doors shall be provided with hinges, latches, and locks. Cabinet
frames shall be sufficiently sturdy to prevent doors from sagging when
open. Doors shall be hinged the entire length of the cabinet.
k) Keys shall be furnished and shall be common to all access door locks.
3. Finish
c) Priming and finish painting shall not be more than 8 hours after cleaning.
When painting is not started within 8 hours after cleaning, surfaces shall
be re-cleaned before painting.
d) Final coat shall be enamel, alkyd or gloss; of low VOC (volatile organic
content). Color for external surfaces shall be as per the Royal
Commission selection. Soft gloss white paint shall be used for interior
surfaces.
c) Panels shall contain all gages, regulators, etc., with all instruments
associated with each unit mounted on a common sub-panel inside the
cabinet.
d) All indicating air gages shall be arranged for flush mounting on the panel
face.
A. Transmitters
1. Temperature Transmitters
c) Linearity
1) Within ± 1% for 10°C (50°F) span, with 10°C (50°F) temperature
range.
2) ± 0.5% of range for 93°C (200°F) span.
2. Humidity Transmitters
3. Pressure Transmitters
a) 1- or 2-pipe direct acting indicating type for gas, liquid or steam service,
range suitable for system, proportional electronic output.
b) Scale range 0.0025 to 1.5 kPa (0.01 to 6.0 in. wg) positive or negative,
and sensitivity of 0.125 Pa (0.0005 in. wg).
6. Material
a) Cover/Housing
1) Glass-filled polycarbonate, NEMA 3, IP53.
b) Capsule Material
1) Type 316 stainless steel.
c) Housing/Body Material
1) Carbon steel, Type 316 stainless steel.
C. Pneumatic Relays
operation.
D. Switches
F. Indicators
1. Thermometers
2. Pressure Gages
b) Pressure gages shall be used to indicate supply and outlet air pressures
of automatic control instruments and shall be the manufacturer's
standard.
c) Gage ranges and faces shall be suitable for unit being controlled.
A. Special tools shall be provided as required for the operation and adjustment of
controllers, instruments or other control system devices.
B. Include pneumatic tools for medical gas system, industrial gas system, such as
torque wrench, etc.
PART 3 EXECUTION
3.01 GENERAL
B. All engineering, field installation and test shall be done by personnel in the direct
employment of the pneumatic control manufacturer.
A. Install control equipment, wiring and air piping in neat and workmanlike manner to
the satisfaction of the Royal Commission and in accordance with manufacturer's
recommendations.
B. Install equipment, piping, and wiring/conduit parallel to, or at right angles to, building
lines.
3.04 INSTALLATION
1. General
B. Air Piping
3. Each header and sub-header shall include a spare outlet valve, an isolating
valve and a drain valve at the lowest point.
4. A supply branch shall supply only one instrument. Branches shall be fed from
headers or sub-headers.
5. Run tubing and wire connecting devices on or in control cabinets parallel with
the sides of the cabinet neatly racked to permit tracing.
7. Support copper tubing with maximum unsupported length of 910 mm (36 in.).
11. Do not run tubing and electrical power conductors in the same conduit.
12. Tank drain, manual and automatic drains shall be piped to nearest floor drain.
13. Identification
a) Permanently label each field pneumatic tube at each end with unique
descriptive identification.
C. Vibration Isolation
3. Provide sufficient slack and flexible connections to allow for vibration of piping
and equipment.
6. Multiple runs shall conform to the same isolation requirements, but mounting
details shall be submitted for approval.
D. Equipment Mounting
2. Provide instrument air tubing with check and hand valves to equipment and
expansion tanks.
E. Instruments Mounting
1. General
2. Room Thermostats
a) Check and verify location of thermostats with plans and room details
before installation.
3. Sensors
a) Use of sensors shall be limited to its duty, e.g., duct sensor shall not be
used in lieu of room sensor.
4. Flow Switches
5. Actuators
a) Provide valves with position indicators and with pilot positioners where
F. Gages
1. Install pressure gages on branch lines at each receiver controller and signal
lines at each transmitter excepting individual room controllers.
2. Pressure gages shall be mounted so that gage can be easily seen from eye
level.
G. Control Panels
1. Mount panels complete with floor or wall brackets and structural supports, at a
height as directed and approved.
A. Coordination
a) Controls Contractor shall coordinate with, and provide full time on-site
technical support to test and balance HVAC Testing, Adjusting and
Balancing (TAB) personnel.
B. Sequencing
C. Clearance
2. Control system installation shall not interfere with the clearance requirements
for mechanical and electrical system maintenance.
D. Accessibility
2. Do not run tubing and conduit concealed under insulation or inside ducts.
A. Cleaning
B. Identifying
1. Number code or color code control air piping for future identification and
servicing.
2. Label and identify control air piping, instruments, control panels and equipment
as specified. Coordinate with SECTIONS 15051 and 15075.
D. Protection
A. Work, materials, and equipment shall comply with rules and regulations of applicable
codes and standards.
B. Continually monitor field installation for code compliance and workmanship quality.
C. Code Conformance
D. The Contractor shall arrange for work inspection by the Royal Commission over the
work.
E. Training
A. General
1. Configure the control system after air and hydronic systems have been
balanced, minimum damper positions have been set and a report has been
issued.
1. Allow sufficient time for start-up and commissioning prior to placing control
systems in permanent operation.
D. Test Plan
1. Obtain approval of the field test plan for each phase of testing before
beginning that phase of testing.
4. Testing shall include both field verification tests and performance tests.
1. Field verification test plan shall consist of detailed instructions for complete
testing to prove performance of the HVAC system and electric/electronic
control system.
2. The Contractor shall submit a checklist of the items for the test.
2. These test phases shall cover the same phases as those for the verification
tests.
4. The test plan shall consist of detailed step-by-step instructions for complete
testing to prove control system maintains setpoints, control loops are tuned,
and controllers are programmed for the correct sequence of operation.
5. The test plan shall also cover test requirements specified in par. 3.09 C,
Performance Test.
2. The statement, certified by the control system provider, states that the installed
system has been calibrated, tested and is ready for the performance
verification test.
3. All data showing setpoints and final adjustments of controls shall be provided.
4. Refer to par. 1.06 A.10 for tests documentation and reporting required to be
submitted.
5. Test Reporting
3.09 TESTING
A. General
1. The Contractor shall perform start-up tests for pneumatic control system to
ensure that the described control system components are installed and
functioning per this Specification.
2. The Contractor shall adjust, calibrate, measure, configure, set alarms, and
otherwise perform all necessary actions to ensure that the systems function as
specified and shown in the sequence of operation and other Contract
Documents.
4. Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment, and retest.
5. Load swing test shall be performed under various conditions to prove the
guaranteed figures for various controlled parameters.
7. During and after completion of the field tests, and again after the verification
tests, identify, determine causes, replace, repair or calibrate equipment (minor
fault) that fails to meet the Specification.
B. Verification Testing
1. System Inspection
a) The Contractor shall perform field check for all instrumentation and
control equipment and systems.
b) With the system shut down, it shall be verified that main air and power
are available where required and that all output devices are in their
fail-safe and normal positions.
c) Each local indicator panel shall be inspected to verify that all displays
indicate shutdown conditions.
2. Tubing Tests
b) Tubing shall be purged with dry, oil-free compressed air to rid system of
impurities generated during joint making and installation and to remove
atmospheric moisture before connecting control instruments.
d) Pressure test control air piping at 200 kPa (30 psi) or 1.5 times the
operating pressure.
c) All test equipment and instruments shall have been calibrated within the
6 month of use. Each field calibrated instrument shall have calibration
certification sheets filled in by the calibrating technician for review by the
Royal Commission.
e) Recalibrate or replace.
b) Verify proper operation of the actuators and positioners for all actuated
devices. Verify that actuators move from zero to full stroke in the proper
direction.
c) Verify that all sequenced actuators move the connected device in the
proper direction from one extreme position to the other, where
applicable.
d) Record actual spring ranges and normal positions for all modulating
control valves and dampers. Include documentation in the test report.
C. Performance Test
2. Conduct the performance test during 1 week of continuous HVAC and control
systems operation and before final acceptance of work.
3. Specifically, the performance test shall demonstrate that the HVAC system
operates properly through the complete sequence of operation (e.g., seasonal,
occupied and unoccupied, warm up, etc.), for specified control sequences.
6. Demonstrate that the control system performs the correct sequence of control.
1. The Contractor shall verify the performance of the control systems by running
a continuous test, after the system has been completely tested, adjusted and
debugged for 7 days, before final acceptance of work.
END OF SECTION