Professional Documents
Culture Documents
Connection MV Network
Connection MV Network
FAKULTAS TEKNIK
PROGRAM STUDI TEKNIK ELEKTRO
Pertemuan 2
CONNECTION MV NETWORK
Maman Pribadi, ST.
DESAIN SISTEM KELISTRIKAN INDUSTRI
CONNECTION MV NETWORK
Tujuan pembelajaran DSKI ( Pertemuan 2 )
Mahasiswa dapat memahami Power supply at medium voltage
Mahasiswa dapat memahami Procedure for the establishment of a
new substation
Mahasiswa dapat memahami The consumer substation with LV
metering
Mahasiswa dapat memahami Choice and use of MV equipment
and MV/LV transformer
Mahasiswa dapat memahami Substation including generators and
parallel operation of transformers
Mahasiswa dapat memahami Types and constitutional of MV/LV
distribution substations
Referensi
Electrical Instalation Guide, Schneider Electric, 2018
Persyaratan Umum Instalasi Listrik 2000, SNI 04-0225-2000
Instalasi Listrik Arus Kuat, P. Van Harten, 1974
Pertemuan 2
Power supply at medium voltage
The term "medium voltage" is commonly used
for distribution systems with voltages above 1
kV and generally applied up to and including
52 kV. For technical and economic reasons,
the service voltage of medium voltage
distribution networks rarely exceeds 35 kV.
Pertemuan 2
Pertemuan 2
Pertemuan 2
Pertemuan 2
Main requirements for power supply at
Medium Voltage and typical architectures
Ur, rated voltage, rms value, kV
This is the maximum rms value of voltage that
the equipment can withstand permanently. 24
kV rms for example
Ud, rated power frequency withstand voltage,
rms value, kV during 1mn
The level of rms over-voltages that the
equipment may withstand during 1 minute.
50kV rms for example
Main requirements for power supply at
Medium Voltage and typical architectures
Up: rated lightning impulse withstand voltage,
peak value, kV
The lightning over-voltages that the equipment
may withstand. 125kV for example
Un, service voltage, rms value, kV
Is the voltage at which the MV utility distribution
network is operated. For example, some
networks are operated at Un 20KV. In this case,
switchgear of at least 24 kV rated voltage shall be
installed.
Rated voltage values according to IEC 60071-1
Main requirements for power supply at
Medium Voltage and typical architectures
As the rated voltage Ur indicates the maximum
value of the "highest system voltage" of networks for
which the equipment may be used, the service
voltage Un really existing in the network, including its
possible variations shall remain below the rated
voltage.
Rated normal current Ir, rms value, A
Rated short-time withstand current Ik, rms value, kA
Rated peak withstand current Ip, peak value, kA
Pertemuan 2
Rated current values according to IEC 62271-1
Ir, rated normal current, rms value, A: this is the rms value of
current that equipment may withstand permanently, without
exceeding the temperature rise allowed in the standards. 630
A rms for example.
Ip, rated peak withstand current, peak value, kA: this is the
peak value of the short circuit current that the equipment may
withstand. It is used to define the electrodynamic withstand of
the equipment, 30 kA peak for example
Pertemuan 2
Four typical architectures can be defined for an
electrical installation connected to a MV distribution :
Single MV/LV power transformer with metering at LV level
Pertemuan 2
Four typical architectures can be defined for an
electrical installation connected to a MV distribution :
Single MV/LV power transformer with metering at MV
level
Pertemuan 2
Four typical architectures can be defined for an
electrical installation connected to a MV distribution :
Several MV/LV transformers, all located in the main
substation
Pertemuan 2
Four typical architectures can be defined for an
electrical installation connected to a MV distribution :
Installation including several secondary substations
supplied by an internal MV distribution
Pertemuan 2
The consumer substation with LV metering
Pertemuan 2
Pertemuan 2
Pertemuan 2
Examples of general arrangements of LV
metering substations
Pertemuan 2
Pertemuan 2
“ Semoga bermanfaat, Barokalloh “
Pertemuan 2