Professional Documents
Culture Documents
3209-Tds-Acs-00-Rprt-Bq3 - 02.12.2021
3209-Tds-Acs-00-Rprt-Bq3 - 02.12.2021
3209-Tds-Acs-00-Rprt-Bq3 - 02.12.2021
A CABINET FANS
Supply, installation, testing & commissioning of single skin Cabinet type Inline fans suitable for installing in any position
in the vertical or horizontal ducts. The casing shall be constructed of galvanised steel . The fan shall be DIDW with
forward/Backward curved impeller fitted with maintenance free external rotor motor. The motor shall be suitable for
1 220 + 10% volt single phase 50 cycles AC supply. In addition all fresh air fans shall be provided with prefilters &
necessary accessories to mount the filters. (The fan shall have low sound level not exceeding 40 DBA at three metre
distance). Quoted rate to include cabling of suitable length and switch along with all acessories to give power supply to
the fan.
Supplying, installing, testing and commissioning of hot air / smoke exhaust fans for kitchen exhaust. Fan shall be Epoxy
coated SISW forward/backward curved AMCA Certified (Air & Sound) direct or belt driven type. Fan should be Three
stage balanced upto G2.5. Fan shall be suitable for smoke / hot air exhaust application & thermally rated for 250ºC for
2 hours as per [BS-7346 Part-2 : 1090] Class-B. Motor & drive arrangement shall be mounted outside, so that it is not
2 exposed to smoke / hot air stream. Motors shall be suitable for 415 +10% volts, 50 cycles , 3 phase AC supply and
static pressure shall be as indicated. All fans shall be suitable for outdoor duty & shall have fire proof flexible
connection at inlet and outlet. Suitable spring / vibration isolators to provided along with the fans. Spring mount
Isolater to have above 90% Efficiency.
Backward curved
2.01 14TH FLOOR KIOSK -01 E.A. FAN 3300 cfm @ 40 mm WG 1 Nos.
2.02 14TH FLOOR KIOSK -02 E.A. FAN 2400 cfm @ 40 mm WG 1 Nos.
2.03 14TH FLOOR KIOSK -03 E.A. FAN 2400 cfm @ 40 mm WG 1 Nos.
2.04 14TH FLOOR KIOSK -04 E.A. FAN 1600 cfm @ 40 mm WG 1 Nos.
Supply, Installation, Testing and Commissioning of Kitchen Exhaust air Scrubber each comprising of extract air intake
3 section, electrostatic precipitation technology, dry type air cleaner to remove oil, smoke and fumes from exhaust air,
as per the following specifications.
Electrostatic section shall be made of 16 gauge galvanised sheet, high bake epoxy powder coated, washable type
aluminium mesh filters, stainless steel spiked ionizers to create high voltage DC field, aluminum collector plates which
should be alternatively charged positive and negative with large collecting area with 14" deep cell, to work as magnet
for charged smoke and oil particles. Average efficiency of 90-95% in single pass as per ASHRAE test method.
Electrostatic Precipitator should be able to charge particles from 0.01 micron to 10 microns through solid state power
supply. Collector cell should be of permanent type and incorporate slide out facility for easy removal for cleaning.
Power supplies shall be 100% solid state UL Listed, Module of capacity above 3000 CFM shall be equipped with Pulse
width modulating (PWM)The system should be fitted with interlock switch for safety . The system should allow
connection to a fan section to achieve 500 FPM velocity across the air cleaner.
3 Grills
Supply, installation, testing and balancing of powder coated extruded aluminum grilles (0 / 15 / 30 Deg) without
volume control dampers in accordance with the approved shop drawings and specifications. Color to be as approved 75 Sqmt.
by the Architect.
Supply, installation, testing and commissioning of motorised fire damper complete with control panel, inter connecting
4 wiring at locations shown in approved shop drawings and as per specifications. Fire Damper to be UL555 listed and to
have at least 1½ hour fire rating.
4.1 Fire Dampers 15 Sqmt
4.2 Actuators (3NM) 12 Nos
4.3 Actuators (5NM) RO Nos
4.4 Actuators (8NM) 10 Nos
4.5 Actuators (10NM) RO Nos
4.6 Control Panel (with IP 65 Enclosure) & Wiring 22 Nos
Note : - Dampers and accessories to be suitable for smoke exhaust purpose & the panel to be capable of receiving a
signal from PLC panel / Fire alarm.
Supply, installation, testing and comissiong of starter panel (IP 54 Rating) with DOL/Star Delta/VFD starter of required
capacity incoming switch gear (MPCB), overload relay , control accessories like Elmex connectors, ferrules etc. with
1 ON/OFF push button & indicating lamps (ON/OFF/TRIP), facility of control wiring for remote operation. Also potential
free contacts to be provided for BMS. The panels to be designed considering 'Type 2' coordination.
1.01 0.55 kW DOL Starter Panel For Fresh Air Fan for 14TH FLOOR KIOSK -01 3300 cfm 1 Nos
1.02 0.75 kW DOL Starter Panel For ELECTRICAL ROOM EXHAUST FAN 4200 cfm 2 Nos
1.03 3.0 kW DOL Starter Panel For 14TH FLOOR KIOSK E.A. FAN 18000 cfm 2 Nos
1.04 3.0 kW DOL Starte Panel For 14TH FLOOR KIOSK F.A. FAN 18000 cfm 2 Nos
1.05 1.1 kW DOL Starter Panel For 14TH FLOOR KIOSK -01 E.A. FAN 3300 cfm 1 Nos
1.06 0.75 kW DOL Starter Panel For 14TH FLOOR KIOSK -02 E.A. FAN 2400 cfm 1 Nos
1.07 0.75 kW DOL Starter Panel For 14TH FLOOR KIOSK -03 E.A. FAN 2400 cfm 1 Nos
1.08 0.55 kW DOL Starter Panel For 14TH FLOOR KIOSK -04 E.A. FAN 1600 cfm 1 Nos
1.09 0.55 kW DOL Starter Panel For 11th to 13th Floor Toilet FA Fan 2400 cfm 6 Nos
1.10 0.55 kW DOL Starter Panel For 11th to 13th Floor Toilet EA Fan 2600 cfm 6 Nos
1.11 0.55 kW DOL Starter Panel For 14th Floor Dishwash Area FA Fan 3000 cfm 1 Nos
1.12 0.55 kW DOL Starter Panel For 14th Floor Dishwash Area EA Fan 3000 cfm 1 Nos
L.T. Power Cables
Supply, handling, laying proper connections testing and commissioning of following sizes of 1.1 kV grade XLPE
2
insulated Armored Copper/ Aluminum conductor cables in an approved manner as required.
2.1 3C X 4 Sq.mm. XLPE, FRLS, Armoured Cable with Copper Conductor. 640 Rmt
4 Earthing Conductor
Supplying, laying of following mentioned earthing conductors connecting the following continuous earth conductors.