Load Calculation for Portal Frame Shed

Shed Length = 78.00 m


Shed Half Width = 18.00 m
Eave Height, he = 6.90 m
Ridge Height, hr = 8.70 m
Slope Angle = 5.71 degree

Live load on Shed roof = 0.58 kN/m2


Dead Load:
Roof Sheet Thickness = 0.6 mm
Weight = 4.71 kg/m2
= 0.046 kN/m2

Purlin Section HB A t
C or Z purlin = 202 mm X 65 mm X 16 mm X 1.5 mm
= 546 mm2 0.000546 m2
Weight = 4.29 kg/m
= 0.042 kN/m
Purlin Spacing = 1.00 m
Inclined Half width = 18.09 m
Purlin Numbers = 19
For Full width Purlin Numbers = 38
Total Length of Purlin = 2964.00 m
Total Weight of Purlin = 124.58 kN
Per Unit Area = 0.044 kN/m2

So, Dead Load From Sheet wt = 0.0906 kN/m2


Collateral Load for Roof = 0.00 kN/m2 If Hanging(HVAC or Other) Load Considered.
Previous Frame distance = 6m
Next Frame distance = 6m
Distributory Width for the frame = 6m
Previous Gable End Post distance = 6m
Next Gable End Post distance = 6m For Gable End Post
Gable End Distributory Width = 6m
Linear Live Load on the frame = 3.48 kN/m
Linear Dead Load on the frame = 0.543 kN/m
Linear CL on the frame = 0.00 kN/m

Wind Load:
Wind Perpendicular to Ridge
Windward Wall = 4.2 kN/m
Windward Roof = -4.8 kN/m
Leward Roof = -3 kN/m
Leward Wall = -3 kN/m
Side Wall = -3.96 kN/m
Wind Parallel to Ridge
Both Roof = -4.8 kN/m
Last Both Rafter = -2.4 kN/m
Windward Wall = 4.2 kN/m
Leward Wall = -2.4 kN/m
Side Wall = -3.96 kN/m
Load Considered.
0.4
0.42
0.45
0.47
0.5
0.6
Roof Load Case1- Wind Dir 0,-Cpe Internal Suction
ZONE Name Net Pressure
A Windward Roof -0.80 kN/m2
B Leward Roof -0.50 kN/m2

Wall Load Case1- Wind Dir 0,-Cpe Internal Suction


ZONE Name Net Pressure
MAX(A1,A2,A3) Windward Wall 0.43 kN/m2
B Leward Wall -0.50 kN/m2
C=D Side Wall -0.66 kN/m2
DESIGN WIND
ZONE
Roof Load Case2- Wind Dir 0, +Cpe Internal Pressure A
ZONE Name Net Pressure B
A Windward Roof 0.02 kN/m2 MAX(A1,A2,A3)
B Leward Roof 0.02 kN/m2 B
C=D
Wall Load Case2- Wind Dir 0,+Cpe Internal Pressure
ZONE Name Net Pressure
MAX(A1,A2,A3) Windward Wall 0.70 kN/m2
B Leward Wall -0.21 kN/m2
C=D Side Wall -0.36 kN/m2
DESIGN WIND LOAD
Name Design Pressure
Windward Roof -0.80 kN/m2 '+ve' sign means load direction inward. Usually outward (-ve value)
Leward Roof -0.50 kN/m2 '+ve' sign means load direction inward. Usually outward (-ve value)
Windward Wall 0.70 kN/m2
Leward Wall -0.50 kN/m2
Side Wall -0.66 kN/m2
ually outward (-ve value)
ually outward (-ve value)
Roof Load Case3- Wind Dir 90, -Cpe Internal Suction
ZONE Name Net Pressure
Max (A,B,C) Both Roof -0.80 kN/m2
Last Bay D Last Both Roof -0.40 kN/m2

Wall Load Case3- Wind Dir 90, -Cpe Internal Suction


ZONE Name Net Pressure
Max (A1,A2,A3,A4) Windward Wall 0.42 kN/m2
B Leward Wall -0.40 kN/m2
C=D Side Wall -0.66 kN/m2
DESIGN WIN
Roof Load Case4- Wind Dir 90, +Cpe Internal Pressure ZONE
ZONE Name Net Pressure A
Max (A,B,C) Both Roof 0.02 kN/m2 B
Last Bay D Last Both Roof 0.02 kN/m2 MAX(A1,A2,A3)
B
Wall Load Case4- Wind Dir 90, +Cpe Internal Pressure C=D
ZONE Name Net Pressure
Max (A1,A2,A3,A4) Windward Wall 0.70 kN/m2
B Leward Wall -0.10 kN/m2
C=D Side Wall -0.36 kN/m2
DESIGN WIND LOAD
Name Design Pressure
Both Roof -0.80 kN/m2 '+ve' sign means load direction inward. Usually outward (-ve value)
Last Both Roof -0.40 kN/m2 '+ve' sign means load direction inward. Usually outward (-ve value)
Windward Wall 0.70 kN/m2
Leward Wall -0.40 kN/m2
Side Wall -0.66 kN/m2
ually outward (-ve value)
ually outward (-ve value)