Professional Documents
Culture Documents
User Manual: PFO.9 1K/1.5K/2K/3K Online UPS
User Manual: PFO.9 1K/1.5K/2K/3K Online UPS
1-3. Installation
system (e.g.
Do not connect appliances or devices which would overload the UPS
laser printers) to the UPS output sockets.
Place cables in such a way that no one can step on or trip over them.
Do not connect domestic appliances such as hair dryers to UPS output sockets.
The UPS can be operated by any individuals with no previous experience.
Connect the UPS system only to an earthed shockproof outlet which must be easily
accessible and close to the UPS system.
Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your
computer) to connect the UPS system to the building wiring outlet (shockproof
outlet).
Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS
system.
When installing the equipment, it should ensure that the sum of the leakage current
of the UPS and the connected devices does not exceed 3.5mA.
1-4. Operation
• Do not disconnect the mains cable on the UPS system or the building wiring outlet
(shockproof socket outlet) during operations since this would cancel the protective
earthing of the UPS system and of all connected loads.
e The UPS system features its own, internal current source (batteries). The UPS output
sockets or output terminals block may be electrically live even if the UPS system is not
connected to the building wiring outlet.
• In order to fully disconnect the UPS system, first press the OFF/Enter buttonto
disconnect the mains.
• Prevent no fluids or other foreign objects from inside of the UPS system•
1-5. Maintenance, service and faults
The UPS system operates with hazardous voltages. Repairs may be carried out only
by qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the mains
(building wiring outlet), components inside the UPS system are still connectedto the
battery and electrically live and dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries
and verify that no current is present and no hazardous voltage exists in the terminals
of high capability capacitor such as BUS-capacitors.
Only persons are adequately familiar with batteries and with the required
precautionary measures may replace batteries and supervise operations.
Unauthorized persons must be kept well away from the batteries.
Caution - risk of electric shock. The battery circuit is not isolated from the input
voltage. Hazardous voltages may occur between the battery terminals and the
ground. Before touching, please verify that no voltage is present!
Batteries may cause electric shock and have a high short-circuit current. Please take
the precautionary measures specified below and any other measures necessary when
working with batteries:
—remove wristwatches, rings and other metal objects
use only tools with insulated grips and handles.
When changing batteries, install the same number and same type of batteries.
Do not attempt to dispose of batteries by burning them. This could cause battery
explosion.
Do not open or destroy batteries. Escaping electrolytecan cause injury to the skin
and eyes. It may be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire
hazards.
Do not dismantle the UPS system.
2
2. Installation and setu
please inspect the
NOTE: Before installation, unit. Be sure that nothing inside the packageis
damaged. Please keep the original package in a safe place for future use.
NOTE: There are two different types of online UPS: standard and long-run models. Please
table.
refer to the followin model
Model Model
1K IKL
1.5K 1.5KL Long-run
Standard
2K 2KL
3K 3KL
10
(S))
India Type
IEC Type Schuko Type
connect to non-critical loads.
1. Programmable outlets:
receptacles: connect to mission-critical loads.
2. Output
3. AC input
4. Input circuit breaker
protection
5. Network/Fax/Modemsurge
connector (EPO)
6. Emergency power off function
7. USB communication port
8. RS-232 communication port
9. SNMP intelligent slot
available for L model)
10. External battery connection (only
11. Output terminal
12. Output circuit breaker
13. Input terminal
2. Maintain an ambient temperature range of OOC to 450C for UPS optimal operation.For
every 50C above 450C, the UPS will derate 12% of nominal capacity at full load.The
highest working temperature requirement for UPS operation is 500C.
3. It's required to maintain maximum altitude of 1000m to keep UPS normal operationat full
load UPS. If it's used in high altitude area, please reduce connected load. Altitudederating
power with connected loads for UPS normal operation is listed as below:
4. Place UPS:
It's equipped with fan for cooling. Therefore,
well-ventilatedarea. It's required place the UPS in a
in the frontof the UPS and to maintain minimum clearance of 100mm
300mm in the back and two sides of the UPS for
heat dissipationand easy-maintenance.
5. ConnectTo Transformer
Transformer
Transfortner
connect transformer to output of the UPS. Otherwise, it will cause UPS internal
pleasedo NOT
UPS to enter to fault mode. Please connect transformer to input of the UPS.
fault and force
External Battery Pack
6. Connect to
Step 4: Communicationconnection
Communication port:
USBport RS-232port Intelligent slot
TO allow for unattended UPS shutdown/start-up and status monitoring, connect the
COmmunicationcable one end to the USB/RS-232 port and the other to the communication
pott of your PC. With the monitoring software installed, you can schedule UPS
shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When
installing either SNMP or AS400 card in the UPS, it will provide advanced communicationand
monitoring options.
Step 5: Network connection
Network/Fax Phone surge port
Connect a single modem/phone/fax line into surge-protected "IN" outlet on the back panelof
line
the UPS unit. Connect from "OUT" outlet to the equipment with another modem/fax/phone
cable.
1. Insert the included installationCD into CD-ROM drive and then follow the on-screen
instructions to proceed software installation. If there no screen shows I minuteafter
inserting the CD, please execute setup.exe file for initiating software installation.
2. Follow the on-screen instructions to install the software. icon
3. When your computer restarts, the monitoring software will appear as an orange plug
located jn the system tray, near the clock.
6
3. O erations
3-1. Button o eration
Button Function
Turn on the UPS: Press and
hold ON/Mute button for at
least 2 secondsto
Mute the alarm: After the UPS is
turned on in battery mode, press
hold this button for at least 3 and
seconds to disable or enable the alarm
ON/Mute system. But it's not applied to the
situations when warnings or errors
Button
Up key: Press this button to display previous
selection in UPS setting
Switch to UPS self-test mode: Press ON/Mute buttons
for 3 secondsto
enter UPS self-testin while in AC mode ECO mode or
convertermode.
Turn off the UPS: Press and hold this button at least 2 seconds
to turnoff
the UPS. UPS will be in standby mode under power normal or transfer
OFF/Enter to
Bypass mode if the Bypass enable setting by pressing this button.
Button
Confirm selection key: Press this button to confirm selection in UPS
settin mode.
Switch LCD message: Press this button to change the LCD messagefor
input voltage, input frequency, battery voltage, output voltage and
output frequency. It will return back to default display when pausingfor
Select 10 seconds.
Button Setting mode: Press and hold this button for 3 seconds to enter UPS
setting mode when Standby and Bypass mode.
Down key: Press this button to display next selection in UPS setting
mode.
Switch to bypass mode: When the main power is normal, press ON/Mute
and Select buttons simultaneously for 3 seconds. Then UPS will enterto
bypass mode. This action will be ineffective when the inputvoltageis out
ON/Mute
of acceptable range.
+ Select Exit setting mode or return to the upper menu: When working in
setting
Button seconds
mode, press ON/Mute and Select buttons simultaneouslyfor 0.2 two
these
to return to the upper menu. If it's already in top menu, press
buttons at the same time to exit the settin mode.
8.8«A
Batteryinfo
8.813888V:: Load Info
ernss
SHORT
progra mable
Mode Opetation Outlet Info
Info
7
Display Function
Backup time information
Indicates the estimated backup time.
H: hours M: minute S: second
Configuration and fault information
Indicates the configuration items, and the configuration items are listed in
8.8 details in section 3-5.
A Indicates the warning and fault codes, and the codes are listed in details in
8.8 ccL.A section 3-7 and 3-8.
Mule o ration
Indicates that the UPS alarm is disabled.
Output information
ac
Vdc Indicates the output voltage and output frequency.
Hz Vac: AC voltage, Vdc: DC voltage, Hz: frequency
Load information
Indicates the load level by 0-24%, 2549%, 50-74% and 75-100%.
8
3-3. Audible Alarm
Battery Mode Sounding every 5 seconds
Low Battery Sounding every 2 seconds
Overload Sounding every second
Fault Continuously sounding
Bypass Mode Sounding every 10 seconds
enn Enable
ENA
Disable
DIS dl %
Escape
ESC ESC
High loss
Low loss
LLS LL5 Battery
BAT bRE Battery AH
BAH bRhl Charger current
CHA CHFI Charger boost voltage
Li
CBV Cb Charger float voltage
CFV Converter
ON
EPO
ON
Temperature
Charger
unstable
Bypass frequency
EEPROMerror
Replacement
Battery
BR
88 g B and
parameter
parameter 2 each program.
for
or values
3
pajameter
2 0
parameter
• 01: Out ut volta e settin
Interface Settin
Parameter3: Output voltage
For 200/208/220/230/240 VAC models, you may choose the
following output voltage:
200: presents output voltage is 200Vac
208: presents output voltage is 208Vac
220: presents output voltage is 220Vac
230: presents output voltage is 230Vac (Default)
e-3LY 240: presents output voltage is 240Vac
For 100/110/115/120/127VAC models, you may choose the
following output voltage:
100: presents output voltage is 100Vac
110: presents output voltage is 110Vac
115: presents output voltage is 115Vac
120: presents output voltage is 120Vac (Default)
127: resentsout ut volta e is 127Vac
• 02: Fre uen Converterenable disable
Interface Settin
Parameter 2 & 3: Enable or disable converter mode. You
may choose the following two options:
CF ENA: converter mode enable
CF DIS: converter mode disable (Default)
• 07:Bypassvoltagerange setting
Interface Settin
Parameter 2 & 3: Set the acceptable high voltagepoint
and acceptable low voltage point for Bypass mode by
pressing the Down key or Up key.
HLS: Bypass high voltage point
For 200/208/220/230/240 VAC models:
230-264: setting the high voltage point in parameter3 from
230Vacto 264Vac.(Default: 264Vac)
For 100/110/115/120/127VAC models:
120-140: setting the high voltage point in parameter 3 from
120Vacto 140Vac. (Default: 132Vac)
LLS: Bypass low voltage point
For 200/208/220/230/240 VAC models:
170-220: setting the low voltage point in parameter 3 from
170Vac to 220Vac. (Default: 170Vac)
For 100/110/115/120/127VAC models:
85-115: setting the low voltage point in
parameter 3 from
• 08:Bypassfrequency 85Vacto 115Vac. Default: 85Vac
range setting
Interface
Settin
Parameter 2 & 3: Set the
and acceptable low acceptable high frequencypoint
frequency point for Bypass mode by
pressing the Down key
S 590», HLS: Bypass high or Up key.
For 50Hzoutput frequency point
frequency models:
51-55Hz: setting the
55HZ(Default: 53.0Hz) frequency high loss pyint from 51Hz to
For 60Hzoutput
61-65Hz: settin frequency models:
the fr from61Hzto
11
65Hz(Default: 63.0Hz)
LLS: Bypass low Frequency point
For 50Hz output frequency models:
45-49Hz: setting the frequency low loss point from 45Hz to
49HZ(Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz: setting the frequency low loss point from 55Hz to
59Hz Default: 57.0Hz
• 09: Programmable outlets enable/disable
Interface Setting
Parameter 3: Enable or disable programmable outlets.
ENA: Programmable outlets enable
d 15 DIS: Programmable outlets disable (Default)
12
Boost voltage setting
14:Charger charger boost voltage.
Interface parameter 3: Set up the boost voltage from2.25
2.25-2.40: setting the charger
2.36V/cell)
(Default:
V/cell to 2.40V/cell.
voltage setting
• 15:ChargerFloat Setting float voltage.
Interface Parameter 3: Set up the charger voltage from2.20
float
2.20-2.33: setting the charger
2.28V/cell)
11 V/cell to 2.33V/cell. (Default:
• 00:Exitsetting
Interface Settin
Exit the setting mode.
Eff
13
Standby mode UPS is powered off and no output supply power,
but still can charge batteries.
o
Fault mode When a fault has occurred, the ERROR icon and
the fault code will be displayed. r
3-7. Faults Reference Code
Fault event Fault code Icon Fault event Fault code Icon
SHORT
Bus start fail 01 x Inverter out ut short 14
Bus over 02 x Batte volta e too hi h 27
Bus under 03 x Batte volta e too low 28
Inverter soft start fail 11 x Over tem rature 41 x
Inverter volta e hi h 12 x Overload 43
Inverter volta e Low 13 x Char er failure 45 x
15
Symptom Possible cause Remedy
Fault code is shown as 14 and the The UPS shut down Check output wiring and if
icon is lighting on LCD automatically because connected devices are in
display and alarm is continuously short circuit occurs on the
short circuit status.
soundin UPS output.
Fault code is shown as 01, 02, 03, A UPS internal fault has Contact your dealer
11, 12, 13 and 41 on LCD display occurred. There are two
and alarm is continuously possible results:
sounding. 1. The load is still supplied,
but directly from AC power
via bypass.
2. The load is no longer
su liedb wer.
Battery backup time is shorter Batteries are not fully Charge the batteries for at
than nominal value. charged least 5 hours and then
check capacity. If the
problem still persists,
consult our dealer.
Batteries defect Cc ntact your dealer to
re )lace the battery.
Fault code is shown as 45 on LCD The charger does
not have Cc ntact your dealer.
display. At the same time, alarm is output and battery
voltage
continuousl soundin is less than IOV PC.
Storaée
Before storing, charge the UPS 5 hours.
Store the UPS covered
location. During storage, recharge the and upright in a cool, dry
battery in accordance with
Storage Temperature the following table:
Recharge Frequency
-25 0C - 40 0C Every 3 months Charging Duration
40 0C - 450C Even/ 2 months 1-2 hours
1-2 hours
16
6. S ecifications
MODEL 1.5K L 2K L 3K L
CAPACITY* 1000V 900W 1500V 1350W 2000V 1800W 3000VA 2700W
INPUT
160VAC/140VAC/120VAC/110VAC ± 5 % or 80VAC/70VAC/60VAC/55VAC
Low Line Transfer ± 5%
based on load centage 70-60% 60%-0
Low Line 175VAC/155VAC/135VAC/125VAC
Voltage Comeback
± 5 % or 87VACU77VAC/67VAC/62VAC
± 5%
Range H h Line Transfer 300 VAC 5 0/oor 150 VAC ± 5 %
High Line
290 VAC ± 5 % or 145 VAC ± 5 %
40Hz 70 Hz
Phase Sin le ase with round
PowerFactor 0.99 @ full load
5% @ 205-245VAC or IOON130VAC
THDi
THDU< 1.6% In t and full linear load condition with batte full char ed
OUTPUT
Outputvoltage 200/208/220/230/240VAC or 100/110/115/120/127 VAC
AC Voltage Regulation ± 1% (Batt.Mode)
FrequencyRange
47 53 Hz or 57 63 Hz
S chronizedRan e
FrequencyRange (Batt.
50 0.1 Hz or 60Hz ± 0.1 Hz
Current Crest Ratio
HarrnonicDistortion 2 % THD (Linear Load) ; 4 % THD (Non-linear Load)
AC Mode to Batt.
Transfer Zero
Mode
Time
Inverter to B ss < 4 ms
Waveform Batt. Mode Pure Sinewave
EFFICIENCY
AC Mode
Ba Mode 89% 89% 89%
BATTERY
12V 12V 9AH 12V 7AH 12V 9AH 7AH
Numbers 3 3 6 6 8
Standard
Model Rechar Time 4 hours recover to 90% ca ci ical
Cha i Current 1.5 A max.
41.0 VOC ± 1% 82.1 VDC +1 0/0 82.1VOC ±
109.6VDC
Battery Type &
Long-run Numbers Depending on the capacity of external batteries
Model Chari Current 1.0 2.0 4.0 6.0 A 8.0 A max. Selectablevia LCD
Chari Vol e 41.0 VDC± 1% 82.1 VDC 82.1 VOC ±
109.6VDC
PHYSICAL
Standard Dimension, D X W 397 x 145 x 220 421 x 190 x 318
Model X H mm
Net We ht k s 12.5 13.8 25.8 27 32.8
Long-run Dimension, D X W 397 x 145 x 220
X H mm) 421 x 190 x 318
Model
NetWe ht k s 5.8 12 13.8
ENVIRONMENT
atjon Humidi 20-95 % RH O- 400C non-condensin
NoiseImel Less than 50dBA 1 Meter With fan s control
MANAGEMENT
smart RS-532 or USB su Win 2000 2003 P is 2008 7 8 Linuxand MAC
Optmal SNMP Power m.oegement from SNMP managecppé web browser
or
• QPOOty to of capacity In Frequency converter mode and to when the output voltage is to IOOVAC,200VAC
Produa speciflcatjonsare subject to change without rurther notice.
17