Gate Valve Is Used To Open and Close The Flow Only. Not Commonly Used in Flow Control With The Following Components

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 7

1- Purpose of using Gate Valve on stream

Gate Valve is used to open and close the flow only. Not commonly used in
flow control with the following components.

2- Operation (open-closed) of Gate Valve


3- The Hydrostatic Test for Gate Valve requires 3 parts, Shell,
Seat, and Backseat 

The hydro-testing according to API 598. The valve standard is ASME B16.34
***Gate Valve – Hydrotest Backseat; 

The Hydrostatic Backseat Test must be tested at a pressure of not less


than 1.1 times the Maximum Operating Pressure by fully opening the
valve and releasing the gland of the gate valve to check for leaks through
the Backseat.
***Gate Valve – Hydrotest Shell; 

Hydrostatic Shell Test must be tested at a pressure not less than 1.5 times
the Maximum Operating Pressure by opening the valve partially open
and tightening the gland to get the pressure. Then check for leaks through
Shell.
***Gate Valve – Hydrotest Seat; 

Hydrostatic Closure Test or Seat Test, continue to test from Shell Test at the
pressure not less than 1.1 times of Maximum Operating Pressure by closing
the valve fully closed and then checking the leak through Seat and Disk.
Both tests must be done on two (2) – Side of Gate Valve.
***Valve – Pressure Test Duration; 

Valve ‘s minimum hydrostatic/pneumatic pressure test, according to the table


in API 598, where the test duration is the time we spend checking the valve
leak after The pressure can be maintained at Test pressure.