Blower Current R Y B
CX2 55 60 58
CX3 45 46.4 41.5
Pressure Remarks and action points
Suction Discharge
0.4 4 Boiler supply temerature OK
Header temperature is OK , however the Delta t
is Found to be high in secondary circuit, It
indicate some Heat transfer or Flow issue in
2.8 4.6 secondary circuit which needs to be further
cross checked with design alongwith action on
following Points..
2.4 4.2
3 4.8
1 CX2 Pully size incresed inplace of design for incresing the air flow.
2 CX2 radiator changed as high capacity(2200 kcal) in place of 1000 kcal.
3 CX3 Top side panel chamber found leakage.
4 CX3 Pipe line size is 2inch as per design but in others zone, Line size is 3"
5 Temp control valve not installed in CX2 zone.