Professional Documents
Culture Documents
09 - 3al 42451 Aaaa Tnaaa
09 - 3al 42451 Aaaa Tnaaa
IED MANUAL
SECTION 4
START UP
Contents
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1 INSTALLATION OF NETWORK MANAGEMENT SOFTWARE . . . . . . . . . . . . . 7
2 INITIALIZATION OF A MULTIPLEXER SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3 INITIALIZATION OF A LINE SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4 SYSTEM TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.1 2 Mbit/s Multiplexer (1510MX / 1511MX) . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.1.1 Test Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.1.2 Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.2 Common Alarm System (CNCC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.2.1 Test Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.2.2 Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figures
Figure 1 Setup of test equipment for nonEMC 1510MX / 1511MX . . . . . . . . . . . 17
Figure 2 Setup of test equipment for EMC 1510MX / 1511MX . . . . . . . . . . . . . . . 18
Figure 3 Setup of test equipment for CNCC on nonEMC alarm subrack . . . . . . 23
Figure 4 Setup of test equipment for CNCC on nonEMC multiplexer subrack . 23
Figure 5 Setup of test equipment for CNCC on EMC multiplexer subrack . . . . . 24
Preface
Scope This section gives the instructions to be followed for starting up the
systems.
Disk Installation For a detailed description of the installation procedure, refer to the
Procedure corresponding manual.
Follow this procedure to install a given software set:
Step Action
1 Start Windows.
2 Insert the first disk of the NECTAS/NOCTAS software set
in disk drive A:.
3 Click on the Start button.
4 Select the Run option.
5 Type a:\setup + Enter or Return and follow the on-
screen instructions.
CDROM Installation For a detailed description of the installation procedure, refer to the
Procedure corresponding manual.
Follow this procedure to install a given software set:
Step Action
1 Start Windows.
2 Insert the CDROM in the CDROM drive.
3 Click on the Start button.
4 Select the Run option.
5 Type d:\setup + Enter or Return and follow the on-
screen instructions.
CRC Error Monitoring The CRC error monitoring procedure has to be enabled or
Procedure disabled, according to the requirements of the remote system. The
status has to be the same on the two sides of each link,
irrespective of the actual monitoring being on or off.
Error Mapping The selection of the signalling type of each channel depends upon
the equipped Channel and Signalling Unit (CSU) for that channel.
The possible signalling types for the equipped CSU's are given in
the Appendix of the IED manual (document code: 3AL 42451
AAAA-ANAAA).
Setting Network The gain setting, balance network matching and setting of other
Parameters configurable board parameters is realized according to the local
requirements and the possibilities on each CSU. For the available
options on the equipped CSU's, refer to the corresponding
descriptions in the Appendix of the IED manual (document code:
3AL 42451 AAAA-ANAAA).
For the channel mapping, the channel signals on the CSU's are
connected to the 2 Mbit/s signal on the PCM controller unit in 2
steps:
On a CSU the channel signals are converted in PCM signals
and connected to the internal buses under the control of the
Common Trunk Circuit (CTC). The connection of the channel
signals to the bus channels can be determined in two ways
now, depending upon the equipped CTC version on the
CSU's:
On the CSU's with a nonprogrammable CTC (CTC1,
CTC2), the connection of the channel signals to the bus
channels is fixed. It is determined by the position of the
unit on the subrack or desktop housing.
On the CSU's with a programmable CTC (CTC3), the
connection of the channel signals to the bus channels can
be chosen freely by means of manmachine commands
via a service terminal.
The position of the channel signals on the 2 Mbit/s PCM
signal can be chosen freely by means of the Time Space
Switch (TSS) on the PCM controller unit. This channel mapping
is contained in the system configuration. Different system
configurations, with specific routing, signalling type and gain
settings per channel, can be stored simultaneously in the
memory (refer to Section 4: Operation).
Step Action
1 Display the system configuration (either the active one
or an inactive one), which will be used.
2 When the configuration is not correct, adapt the
following:
If the configuration is already operational on the
multiplexer, all the channels to be adapted can be
disabled in order not to disturb traffic.
Add, remove or replace channel units.
Modify the channel mapping.
Modify the signalling type.
Modify the channel gain.
Modify the balance network or other configurable
parameters (only for units with CTC3, see remark
below).
3 Display the system configuration and verify if it is
correct.
4 Activate the configuration in order to make the system
operate according to this configuration and to permit
traffic again.
CNCC The CNCC can collect all supervisory information from the
equipments, which is stored and processed by the CNCC to derive
the necessary alarms and statistics. Via a CT and the necessary
associated software, the user can send and receive information
to/from the CNCC, locally with the Finterface or remotely with the
Q2interface.
4 SYSTEM TEST
Introduction When all connections are realized (according to Section 3:
Electrical Installation) and the battery voltage is applied to the
systems (by activating the automatic fuses on the installation
module), the systems will generate alarm indications as they do
not receive a Pulse Code Modulation (PCM) input signal.
In order to avoid this, the 2 Mbit/s outputs of the systems can be
linked to the inputs. In this way all alarm indications should
disappear. If not, refer to the Technical manual Section 6: Fault
location.
Topics Section
2 Mbit/s multiplexer 4.1
Common alarm system (CNCC) 4.2
Note The test sheets are available in Section 5 of the IED manual.
2 Mbit/s multiplexer
1 2 3 4 5 6 7 8 9 10 11 12 13
Portable PC
Portable PC
Audio Channel Test IED manual Section 5 1510MX / 1511MX, page 4 and 5
Test setup:
For 4wire channel units the 2 Mbit/s signal should be
looped on the PCMC by means of the loop cord.
For 2wire channel units 2 systems are required: make a
2 Mbit/s connection between the PCMC units of both
systems.
Connect the audio test set to the relevant channel inputs
and outputs.
Frequency response (∆loss versus frequency):
Measurement of the frequency response in relation to a
reference frequency of 813 Hz and a reference level of
0 dBmO.
Crosstalk:
Selective measurement (813 Hz) of crosstalk levels occurring
in other channels than the transmit channel at an input level
of 0 dBm0. The measured values should not exceed
65 dBm0.
Alarm subrack
1 2 3 4
Portable PC
Software:
1320 NX
CNCC
151x MX
1 2 3 4 5 6 7 8 9 10 11 12 13
Portable PC
Software:
1320 NX
CNCC
151x MX
Portable PC
Software:
1320 NX
CNCC
151x MX
Abbreviations
AIS Alarm Indication Signal
CNCC Common Network Controller Circuit
CRC Cyclic Redundancy Check
CSU Channel and Signalling Unit
CT Craft Terminal
CTC Common Trunk Circuit
ECT Equipment Craft Terminal
MS Microsoft
NECTAS Network Element Craft Terminal Application Software
NOCTAS Network Office Craft Terminal Application Software
OCT Office Craft Terminal
PC Personal Computer
PCM Pulse Code Modulation
PCMC PCM Controller
SLS Subscriber Line System
TSS Time Space Switch