K85005-0132 - VS Series Submittal Guide
K85005-0132 - VS Series Submittal Guide
K85005-0132 - VS Series Submittal Guide
Analog Control
Technology that saves lives
VS Series
Submittal Guide
VS Series
Initiating
Devices
Intelligent fire alarm solutions
up to 1,000 addressable points
Notification
Appliances
Hazardous Location
Devices
Door Holders
& Relays
Se
e w w.
hat’s l e no
p os s ib
Analog Control
Technology that saves lives
VS Series
Project: ___________________________
Contact: ___________________________
Date: ___________________________
Initiating
Devices
Thank you for giving us the opportunity to provide this submittal for an VS Series
Life Safety System. VS Series combines analog addressable detection with
technologically advanced sensor diagnostic capabilities. Together these innovations
offer unsurpassed stability, reliability, and flexibility.
Notification
Appliances
presentation of related system components and devices. Products we are
submitting for your consideration are indicated by a checkmark in the margins
of the pages that follow.
Hazardous Location
product information, are available electronically at www.kidde-esfire.com.
Devices
Thank you for giving us the opportunity to provide this submittal. Please
do not hesitate to contact us should you require further information.
_____________________________
Door Holders
& Relays
VS Series Initiating Notification Hazardous Location Door Holders
Analog Control Devices Appliances Devices & Relays
iii
VS Series
up to 1,000 addressable points
Intelligent fire alarm solutions
Submittal Guide
VS Series Submittal Guide
Intelligent fire alarm solutions for small buildings
SERIES
Intelligent Fire Alarm Solutions
Analog Control
VS Series
Cohesive, VS Series Analog
Specifications.................................................................... 2
1
Initiating
Devices
Accessories..................................................................... 12
buildings.
Intelligent Initiating Devices 13
With control panels, devices, and accessories all Optical and Combination Detectors................................. 14
Fire/CO Detectors........................................................... 15
engineered to work in unison, VS Series systems
Detector Bases............................................................... 16
provide reliable performance and the advanced Duct Detectors................................................................ 17
Input/Output Modules..................................................... 18
features you need for successful installation and
Manual Pull Stations........................................................ 22
worry-free operation. Best of all, VS Series leaves
Notification
Appliances
you in control – not hemmed in by a limited product Notification Appliances 23
line. Kidde’s extensive range of fire alarm products LED Compact Strobes, Horns & Horn-strobes................ 25
LED Wall Strobes, Horns & Horn-Strobes........................ 26
gives you the freedom to tailor each system to the LED Ceiling Strobes, Horns, Horn-Strobes...................... 27
particular needs of the building – and the budget LED Wall Speakers & Speaker-Strobes............................ 28
LED Ceiling Speakers, Horns & Strobes.......................... 29
of the building owner – while a robust feature set Low Frequency Horns and Horn-Strobes........................ 30
Hazardous Location
leaves plenty of room for upgrades, expansions, Outdoor Horns & Strobes................................................ 31
Outdoor Speakers & Strobes........................................... 32
and retrofits long into the future.
Firefighters’ Telephones................................................... 33
But innovative features tell only part of the
Devices
Harsh Environment Signals.............................................. 34
Audible Signals................................................................ 35
story: when you specify VS Series you’re getting
Accessories..................................................................... 36
more than outstanding value in a fire alarm panel;
you’re benefitting from a whole family of control, Hazardous Location Devices 37
Initiating Devices............................................................. 38
detection, and notification appliances finely tuned
Notification Appliances.................................................... 39
to work together – engineered and tested to func-
tion as a single unified system. Door Holders & Relays 40
Door Holders
Relays............................................................................. 40
ing the needs of the future, VS Series is the chang- SPDT Relays................................................................... 41
ing face of small building fire detection today.
v
VS
VS Series
SERIES
Analog Control
Specifications p. 2
Control Panels p. 3
Analog Control
Option Cards p. 4
VS Series
Power Supplies p. 6
Remote annunciation p. 8
Accessories p. 10
Initiating
Devices
VS Series life safety systems are a powerful intelligent solu- Clear-cut remote annunciation
tion for small to mid-sized buildings. Advanced analog tech- Remote annunciation is a strong suit of VS Series. Up to
nology delivers the benefits of flexible system installation, eight annunciators can be installed on a single system.
while a clean and easy-to-operatate user interface makes Compatible annunciators include a range of LED and LCD
panel operation and system maintenance quick and intuitive. models that provide zone or point annunciation, as well as
common control capabilities.
The smart choice
VS Series also supports graphic annunciation with optional
Notification
VS Series electronic device addressing eliminates the tedium
Appliances
RA Graphic Annunciator interface modules. Each interface
of setting dipswitches, and innovative programming features
provides common control, indicators, and 32 LEDS.
allow the system designer to customize powerful built-in
features to precisely suit the needs of the building owner. A complete line of accessories
VS Series life safety systems are supported by a complete
Flexibility built right in line of intelligent detectors, modules and related equipment,
Two fully-programmable front panel switch/LED combina- each of which is fully tuned and tested to operate in concert
tions provide an added measure of flexibility. Their slide-in with one another to provide highly reliable service and years
labels take the mystery out of custom applications, and of trouble-free operation.
present a clean finished appearance.
Hazardous Location
Perfect for retrofits
VS Series is particularly well-suited to retrofit applications.
Devices
All connections are made over standard wiring – no shielded
cable required. This means that in most situations existing
wiring can be used to upgrade a legacy control panel to
VS Series technology without the expense or disruption of
rewiring the entire building.
1
VS
SERIES
Analog Control
Analog Control
System Layout
VS Series
VS4
Any combination of two single- or dual device loop modules
Standard Loop: 250 points (one expansion slot) V-SLC2 Expander, Loop 1 of 2: 250 points
Up to 125 sensors and 125 modules per loop (one expansion slot)
V-SLC2-1 Expander Loop: 250 points (one expansion slot) V-SLC2 Expander, Loop 2 of 2: 250 points
Up to 20,000 feet of wiring per loop
Four Class B or two optional Class A NACs Four Class B or two optional Class A NACs
Optional 10 A or 6.5 A Booster
Ethernet (SA-ETH)**
DACT/Dialer (SA-DACT) Up to eight remote annunciators
RS-232 (SA-232) Sixteen Conventional IDCs,
Relays: Two Form C, one Form A two additional NACs with RZI16-2 module
Each VS4 panel has room for up to two device loop controller modules in any combination
of single or dual 250-device loops. VS4 comes with one loop that supports up to 125 detectors and 125 modules.
**SA-ETH supports: (1) remote connectivity for diagnostics & programming, (2) Central station monitoring to Sur-Gard IP Receivers.
VS1
Two Class B or two optional Class A NACs Loop supports up to 64 intelligent devices of any type.
Optional 10 A or 6.5 A Booster Power Supply
2
VS
VS Series
SERIES
Analog Control
SUBMIT
Control Panels
Analog Control
VS Series
Standard Features
The attractive appearance of VS Series control panels means
they won’t be a blemish on an expensive architectural design.
Their gently curved door fronts offer a distinctive flair with avail-
able red or silver finishes. Controls are discreetly inset behind a
striking black bezel.
VS1 VS4
• Auto-programming speeds installation time
• Supports VS Series analog addressable modules and detectors Dimensions
Surface mounting holes Backbox with Backbox with door and
• Form C contacts for alarm and trouble, Form A for supervisory D2 D3 door attached trim ring attached
Initiating
D7
Devices
• Supports GSA-REL Releasing Module
Notification
Appliances
*Add 1-1/2 in. (3.81 cm) to D1 and D5 dimensions for trim kit.
Hazardous Location
VS4-GF Four loop system, one 250-point loop. 110v, gray door, LED strips, French Canada.
VS4-R Four loop system with one 250-point loop installed. 110v, red door.
VS4-R-2 Four loop system with one 250-point loop installed. 230v, red door.
Devices
VS4-G-PG Four loop system with one 250-point loop installed. 110v, gray door, Portuguese.
VS4-G-SP Four loop system with one 250-point loop installed. 110v, gray door, Spanish.
VS4-RD Four loop system, one 250-point loop installed. 110v, red door, with dialer.
SA-TRIM2 VS4 Flush mount trim, black.
VS1-G-2-SP One loop system with one 64-point loop installed. 230v, gray door, Spanish.
& Relays
VS1-GD One loop system, one 64-point loop installed. 110v, gray door, with dialer.
VS1-GL One loop system, one 64-point loop installed. 110v, gray door, English Canada.
VS1-GL-F One loop system, one 64-point loop installed. 110v, gray door, French Canada.
VS1-R One loop system with one 64-point loop installed. 110v, red door.
VS1-R-2 One loop system with one 64-point loop installed. 230v, red door.
VS1-RD One loop system, one 64-point loop installed. 110v, red door, with dialer.
SA-TRIM1 VS1 Flush mount trim, black
3
VS
SERIES
Analog Control
SUBMIT
Option Cards
Analog Control
VS Series
VS Series panels are supported by a complete line of modules and related equipment that
enhance performance and extend system capabilities. Option cards are easy to install and set
up. They simply plug directly into the control panel main circuit board or are connected to it
with a ribbon cable. After installation, terminals remain easily accessible for quick connection of
field wiring. The cabinet provides ample room for wire routing, keeping wiring neat and easy to
service at all times.
SA-232 RS-232
V-SLC2 Loop Expander Card interface
Class B wiring
SA-CLA
RZI16-2 Remote Zone Interface
-
Class A Module
Loop 1 SEC Data Line
+
- + +
Loop 1 PRI
+ - -
Loop Loop
Loop card device device
with VS4 control panels only. The loop expander card Loop 1 SEC
-
SA-CLA wiring
TB2 on main NAC1
+ + SA-CLA Class A Module
circuit board NAC1+
NAC2
+ + The SA-CLA card provides Class A capability for NAC and annuncia-
NAC2+ tor wiring. Its terminal block provides the wiring connection for NAC
return wiring. The card is required for annunciator Class A wiring even
+ though this wiring does not return to the SA-CLA card. The SA-CLA
is compatible with VS1 control panels only. VS4 panels are Class
+ A ready. The SA-CLA is installed directly to the control panel circuit
Class A card installed
board using its plastic standoffs and plug connection.
on main circuit board
SA-CLA VS1 Class A adapter module. Provides Class A capacity on NACs. Mounts in cabinet on main board.
4
VS
VS Series
SERIES
Analog Control
SUBMIT
Analog Control
VS Series
SA-ETH Ethernet Interface Card
The SA-ETH card provides a standard 10/100 Base-T Ethernet network connection
for connecting to an intranet, a local network, or the Internet. The card can be used
to upload and download panel configuration, history, and current status from the
VS-CU to the panel over the network.
Further, the SA-ETH can be used for central station monitoring service to transmit
system status changes (events) when connected to compatible Sur-Gard IP receivers.
The SA-ETH has been enhanced with the addition of the Sur-Gard FIBRO protocol,
and it can be configured in the configuration utility.
The Ethernet card is installed on the plastic assembly and connects to the main
Initiating
Devices
circuit board via a ribbon cable.
SA-ETH Ethernet Port, Slave, for Ethernet connection to local area networks. Mounts in cabinet on base plate.
Notification
Appliances
The RS-232 card is installed on the plastic assembly and connects to the main circuit
board via a ribbon cable.
SA-232 Serial Port (RS-232), for printers & computers, mounts in cabinet to base plate
SA-DACT Dialer
The SA-DACT provides communications between the control panel and the central station
Hazardous Location
over a telephone line system. It transmits system status changes (events) to a compat-
ible digital alarm communicator receiver over the public switched telephone network. The
dialer is capable of single, dual, or split reporting of events to two different account and
Devices
telephone numbers. The modem feature of the SA-DACT can also be used for uploading
and downloading panel configuration, history, and current status to a PC running the VS-CU.
The dialer phone lines connect to connectors on the dialer’s main circuit board. Phone line
1 connects to connector J4 and phone line 2 connects to connector J1.
SA-DACT Dual Line Dialer/Modem, supports Contact ID, mounts in cabinet on base plate
that provides connections for sixteen Class B Initiating Device Circuits and two Class B
& Relays
Supervised Output Circuits. The inputs and outputs can be configured individually for
several device types. It requires 18 consecutive addresses on the Signaling Line Circuit
(SLC). Addresses are assigned electronically. There are no address switches to set.
The RZI16-2 incorporates two 8-segment DIP switches that are used to select the Alarm or
Supervisory default device type for each of the 16 IDC circuits. The module also includes one 4-segment DIP
switch used to select the default Relay or NAC output device type. Device types other than the default are
accomplished through programming.
RZI16-2 Remote Zone Interface Module. 16 Class B IDCs, 2 Class B Output. Includes bracket.
5
VS
SERIES
Analog Control
SUBMIT
Option Cards
Analog Control
VS Series
SA-USB USB interface card for connection to printers and laptops running
configuration utility, mounts in cabinet to base plate
6
VS
VS Series
SERIES
Analog Control
SUBMIT
Power Supplies
Analog Control
VS Series
Remote Booster Power Supply
The Remote Booster Power Supply is a self-contained 24 Vdc power supply designed to aug-
ment fire alarm audible and visual power requirements as well as provide power for auxiliary,
access control and security applications. The booster contains all of the necessary circuits to
monitor and charge batteries, control and supervise four Class B or two Class A NAC circuits
and monitor two controlling inputs from external sources.
Simple switch selection provides a wide variety of operational configurations. Each remote
booster power supply is supplied with its own enclosure providing ample space for additional
interface modules and battery compartment.
When used withNAC
Genesis Notification appliances, the booster provides the ability to synchronize
Initiating
NAC Series Connection
Devices
NAC Sense Sense Up to ten boosters
strobes as well as horn signals. The booster flexibility allows synchronization with upstream
Circuit
can be connected
together
Booster Booster
Power Supply devices, Power
or, the booster may be used to synchronize downstream devices, as well as other
Supply
NAC
MIRBPS notification appliance circuits easily configure for either of two signaling rates: 3-3-3
Sense
temporal or continuous. This makes the MIRBPS ideal for applications requiring signaling
Parallel Connection
The number of boosters
that can be connected
Booster
Power Supply
rates not available
together is limited by wire
run length and available current
from the main panel. It also allows independent setup of a notification ap-
pliance circuit without interfering with the main panel and its initiating circuits. In addition to
the generated signal rates, the MIRBPS can also be configured to follow the signal rate of the
Parallel Connection
The number of boosters
main panel’s notification appliance circuit. This allows seamless expansion of existing NACs.
that can be connected
For comprehensive configuration and wiring details, refer to the MIRBPS Application Guide,
together is limited by wire
run length and available current
85001-0582.
Notification
Appliances
MIRBPS6A 6.5 Amp Booster Power Supply Data Sheet K85005-0125
MIRBPS6A/230 6.5 Amp Booster Power Supply (220V) Data Sheet K85005-0125
MIRBPS10A 10 Amp Booster Power Supply Data Sheet K85005-0125
MIRBPS10A/230 10 Amp Booster Power Supply (220V) Data Sheet K85005-0125
3-TAMP Tamper switch Data Sheet K85005-0125
Hazardous Location
TB1
Notification
The Auxiliary Power Supply (APS) is a self-contained 24 Vdc power
+
NAC1 appliance
circuit (NAC)
supply designed to augment fire alarm audible and visual power
+
NAC2
Notification
+
NAC3
requirements as well as provide auxiliary power for life safety and
appliance
circuit (NAC)
+
NAC4
Devices
200 mA AUX
security applications. The APS contains all of the necessary circuits
TB5
Sense 1 COM
IN
OUT
+
- to monitor and charge batteries, control and supervise four Class
NAC
B or two Class A NAC circuits and monitor two controlling inputs
To next signaling device,
IN
+
SUBMIT
Remote annunciation
Analog Control
VS Series
There are three R-Series annunciator models, plus an LED-based expander. Up to two expanders can be connected
to any annunciator. The expander includes 24 pairs of LEDs thatFACP
extend the capabilities of any of the annunciators.
Annunciator Annunciator
RS-485 CH1 (+) IN CH1 (+) IN
has 16 pairs of LEDs for zone annunciation. LCD models feature a large back-lit, four by twenty character per line,
CH1 – CH1 (+) OUT CH1 (+) OUT
CH2 + CH1 (–) OUT CH1 (–) OUT
R-Series annunciators and expanders are mounted on a standard 4-inch square electrical
LISTED 24 VDC
SUPPLY
CH2 (+) OUT
CH2 (–) OUT
box, using theCH2
included
(+) OUT
CH2 (–) OUT
mounting ring. They can also be surface mounted in locking steel enclosures.
24 VDC + Three different
24V (+) IN enclosures are 24V
available.
(+) IN
24 VDC – 24V (–) IN 24V (–) IN
GROUND GROUND
GROUND GROUND
LCDFACP
Annunciators Annunciator Annunciator
K-RLCD LCD text annunciator without common controls. English. Data Sheet K85005-0128
Annunciator First Expander Second Expander
RS-485 CH1 (+) IN CH1 (+) IN
OUT IN OUT IN OUT
K-RLCD-R
CH1 +
LCD text annunciator
CH1 (+) OUT
without common
CH1 (–) IN
controls. English. Red. V (–)
CH1 (+) OUT
CH1 (–) IN
V (–) Data
V (–) Sheet K85005-0128
V (–) V (–)
CH1 – V (+) V (+) V (+) V (+) V (+)
SERIES
Analog Control
SUBMIT
Analog Control
VS Series
Annunciator Enclosures
The RA Remote Annunciator Enclosures provide secure, surface mounted protec-
tion for annunciators and extenders. Each consists of a back plate, hinged cover,
and key lock. The enclosures are 16-gauge welded steel with a white, painted
RA-ENC1
finish. Each enclosure includes a security lock and two keys. The two- and three-
position enclosures have wiring channels for correct routing of interconnections.
The enclosures attach to a standard 4-inch square or 3-gang electrical boxes, and
provide a mounting lip that takes the place of the integral mounting ring supplied
with the annunciators and expanders.
RA-ENC3
Initiating
Devices
RA-ENC2
Notification
Appliances
The FireWorks Graphical Annunciation Interface is a software platform that provides
end users with clear, concise, and coordinated site incident information. FireWorks also
supports optional text-based web clients to provide remote status updates. Five configu-
rable graphical viewports offer simultaneous insight into different aspects of an incident,
while the underlying software dynamically manages content in each viewport based on
real-time events and user interaction. Facility maps, embedded HTML viewer, and live
event flow from vital equipment all come together instantly within view of an operator fac-
ing events that require solid information and split-second timing.
FW-CGSVM FireWorks Graphics Software. Five viewport display. No common control. Data Sheet K85005-0068
Hazardous Location
FW-IPMON1000 IP Monitoring, 1000 connections. Requires FW-DARCOM. Data Sheet K85005-0068
FW-DARCOM For Communication to DACRs and/or IPMON1000. Data Sheet K85005-0068
approved power supply. Always ensure that National and Local approv- RS-485 NETWORK DATA RS-485 NETWORK DATA
als and requirements are met when selecting a graphic panel supplier. FROM PREVIOUS PANEL TO NEXT PANEL
9
VS
SERIES
Analog Control
SUBMIT
Accessories
Analog Control
VS Series
+ +
Circuit Pair 1 IN Circuit Pair 1 OUT
- -
16 15 14 13 3-2-1 12 11 10 9
JP1
The GFD module is designed to detect ground fault conditions on either
LED 1 LED 2 of two independent power or data circuits. Each circuit must be balanced
8 7 6 5 4 3 2 1 with respect to ground. The module will detect when the resistance be-
To earth ground
tween any of the monitored conductors and earth ground drops below 10
From UL/ULC listed 24 VDC+ + To next GFD
or EOLR [3] [4]
K Ohms. Two LEDs are provided to indicate the conductor with the ground
fire alarm panel [4] 24 VDC- -
From IDC or + condition. A normally energized Trouble/Ground Fault relay is provided with
previous GFD
NO/NC relay contacts for interfacing with monitoring systems.
-
CDR-3 Coder
The CDR-3 Coder is an auxiliary circuit option module that provides two audio outputs, March Time and PSNI, (Positive,
successive, non-interfering). Dry relay contacts are provided for PSNI code, march time and duration. For the PSNI code,
the RS-232C input provides communications, between VM Series’s RS-232 communications card and the CDR-3.
CDR-3 PSNI Coder Module Data Sheet K85003-02709
10
VS
SERIES
Analog Addressable Initiating Devices
Detector Bases p. 13
Duct Detectors p. 13
Input/Output Modules p. 14
KI-Series
Intelligent
Manual Pull Stations p. 20
Initiating Devices
Initiating
Devices
Kidde brand Intelligent addressable detectors are meticulously engineered Standard Features
to deliver high-performance features, superb reliability, and unbeatable
quality. With their highly stable design, these detectors resist air movement • Optical, CO, heat, and multisensor models available
caused by heating and air conditioning, making them reliable performers • Compatible standard, relay, isolator, and audible
ideally suited to modern building interiors. bases
The installation and maintenance advantages of Kidde brand Intel- • Electronic Addressing including mapping location
ligent addressable detectors add value throughout their service life. The
twist-and-lock design makes short work of installation and maintenance • Bases mount to standard North American two-
operations. A plastic breakout on the detector housing optionally prevents gang or 4" square electrical boxes
removal from the base except with a special tool. • Tamper-resistant feature
A bright, easy-to-see LED flashes red when the detector is in alarm, thus • Self diagnostic capability with on-board storage
eliminating much of the guesswork when responding to front-panel indications.
Notification
of results
Appliances
KI-Series Device loop • Optical detectors feature automatic rate compen-
sated sensitivity adjustment, as well as dirty sensor
VS Series control panels provide one device loop circuit that supports 125
warnings
detectors and 125 module addresses. V-SLC2 Loop Expander Cards
provide additional device loops on the VS4 control panel. The V-SLC2-1 • Manufactured to strict international ISO 9001
provides one loop with 250 additional addresses, and the V-SLC2-2 standards
provides two loops totalling an additional 500 device addresses.
Class B wiring
• Assembled using surface mount technology for RF
Circuit specifications resistance
Device loops One loop, expandable
- to four (VS4), Class A or B. • Conformally coated components resist dust and
Hazardous Location
EachLoop
loop1 SEC
support
+
up to 250 device
Data Line addresses
humidity
Com. line voltage Maximum 20 V peek-to-peek
- + +
Circuit current Loop 1 PRI 0.5 A max • Automatic detector test
+ - -
Devices
Circuit impedance 66Ω total, 0.5 µF, max
Loop Loop • Low Profile Design
Isolators Loop card 64 maximum device device
Class B wiring
Typical Wiring
Class A wiring
Class B Class A
- -
Loop 1 SEC Loop 1 SEC
Data Line
+ +
- + +- + +
Loop 1 PRI Loop 1 PRI
+ - -+ - -
Loop Loop Loop Loop
device Loopdevice
card device device
Loop card Data Line
Door Holders
Class Aheat
Kidde wiring
and smoke detectors comprehensive self-diagnostic capabil-
& Relays
ity. The KI-PD, KI-PCD, and KI-PHD optical detectors continuously adjust
their sensitivity- to compensate for changes in the environment such as the
Loop 1 SEC
presence of dirt, + smoke, temperature, and humidity. These detectors issue
a dirty sensor- warning when +they reach+ their preset limit.
Loop 1 PRI
+ - -
Loop Loop
Loop card device device
Data Line
11
VS
SERIES
Analog Addressable Initiating Devices
SUBMIT
KI-Series
Analog Control
VS Series
Intelligent
Detectors
12
VS
SERIES
Analog Addressable Initiating Devices
SUBMIT
Heat Detectors
Thanks to advanced thermistor technology, KI-Series heat detectors are ideal
for sensing fast, flaming fires and for applications where smoke detection is
inappropriate. They are particularly well-suited to areas such as kitchens and
shower rooms, where the ambient temperature is relatively constant, but
where steam and smoke are present. These heat detectors are capable of
performing comprehensive self-diagnostics and storing the results on board.
Initiating
Devices
The KI-HRD Rate-of-Rise Heat Detector provides a 15°F (8°C) per minute rate-of-rise
heat sensor for the detection of heat due to fire. The heat sensor monitors the tempera-
ture of the air and determines whether an alarm should be initiated.
Notification
Appliances
KI-HFD Fixed Temperature Heat Detector provides a 135°F (57°C) fixed-temperature
heat sensor for the detection of heat due to fire. The heat sensor monitors the tempera-
ture of the air and determines whether an alarm should be initiated.
KI-HFD Intelligent Addressable Fixed Temperature Heat Detector Data Sheet K85001-0647
Hazardous Location
Carbon Monoxide (CO) is the leading cause of accidental poisoning deaths in
America. Known as The Silent Killer, CO is odorless, tasteless, and colorless.
It claims nearly 500 lives, and results in more than 15,000 hospital visits
annually. CO detection has rapidly become a standard part of life safety
Devices
strategy. Monitored CO detection is mandated with increasing frequency in
all types of commercial applications, but particularly in occupancies such as
hotels, rooming houses, dormitories, day care facilities, schools, hospitals,
assisted living facilities, and nursing homes. In fact, more than half of the U.S.
population already lives in states requiring the installation of CO detectors in
some commercial occupancies.
13
VS
SERIES
Analog Addressable Initiating Devices
SUBMIT
KI-Series
Analog Control
VS Series
Bases
Detector mounting bases have wiring terminals that are accessible from the
room-side after mounting the base to the electrical box. The bases mount to
North American one-gang boxes and to 3½ inch or 4 inch octagon boxes, 1½
inches (38 mm) deep. They also mount to European BESA and one-gang boxes
with 60.3 mm fixing centers. The KI-SB4, KI-RB4, and KI-IB4 also mount to
North American 4 inch sq. electrical boxes. They include the GSA-TS4 Trim Skirt, Base with 4-inch
which is used to cover the “mounting ears” on the base. The KI-ABST mounts to trim skirt
Initiating
Devices
KI-SB KI-SB4 (c/w 4-inch trim skirt) Standard Detector Base Data Sheet K85001-0646
GSA-LED Remote alarm LED (use with standard base only) Data Sheet K85001-0646
KI-IB KI-IB4 (c/w 4-inch trim skirt) Isolator Detector Base Data Sheet K85001-0646
KI-RB KI-RB4 (c/w 4-inch trim skirt) Relay Detector Base Data Sheet K85001-0646
14
VS
SERIES
Analog Addressable Initiating Devices
SUBMIT
Sounder Bases for CO and fire detectors add audible out- From power supply 24 VDC (+)
24 VDC (-)
To next base 24 VDC (+)
24 VDC (-)
or previous base or EOL relay
put functions to KI-Series intelligent detectors. Audible From controller SLC in (+) To next device
SLC out (+)
SLC out (-)
part of a zone or system alarm with synchronized audible output. KI-ABLT is UL listed for sleep-
ing areas and other applications requiring 520 Hz low frequency audible tones. KI-ABDT and
KI-ABLT audible bases may be used with combination smoke/CO detectors when a GSA-T3T4
module is installed on the same data loop.
Initiating
KI-ABLT Low Frequency Sounder Base for KI-Series Detectors, 520 hz, T3/T4 Data Sheet K85001-0651
Devices
KI-ABDT Sounder Base for KI-Series Detectors, 3k hz, T3/T4 Data Sheet K85001-0651
KI-ABST Sounder Base for KI-Series Detectors, 3k hz, fire only Data Sheet K85001-0646
AB4G-SB Surface Box for Audible Base Data Sheet K85001-0646
Duct Housing
The SDH(R) series housings provide the ability to use Kidde intelligent detectors in duct
applications utilizing SD-Txx sampling tubes in lengths of 8” to 10ft.
KI-SDH Duct detector housing with standard base Date sheet K85001-0326
Notification
Appliances
KI-SDHR Duct detector housing with relay base Data sheet K85001-0326
sound patterns for carbon monoxide (CO) (TC4 per NFPA 720) and fire signals (TC3
per NFPA 72) for the KI-ABDT or KI-ABLT sounder bases. The control panel sends
synchronization and channel commands to the GSA-T3T4; the channel selection
determines the pattern. From previous device
SLC_IN +
To next device
SLC_OUT +
Hazardous Location
GSA-T3T4 Temporal Pattern Generator for KI-ABDT or KI-ABLT Sounder Bases Data Sheet K85001-0651
Devices
SuperDuct Duct Detectors
Less than two inches deep, SuperDuct Intelligent addressable smoke detectors are
ideal for installation in ductwork, where space is always at a premium. Offering the most
advanced and most reliable performance in its class, SuperDuct represents the perfect
balance of practical design and advanced technology.
SuperDuct detectors feature a unique design that speeds installation and simplifies
maintenance. Removable dust filters, conformally coated circuit boards, and optional
Door Holders
trouble-free service. When cleaning is required, the assemblies come apart easily and
snap back together in seconds.
SUBMIT
Addressable initiating
Analog Control
Input/Output
VS Series
boards.
The actual function of each module is determined by its installer-selected personality code. This is downloaded
to the module from the device controller during system configuration. Because they are intelligent devices, all deci-
sions are made at the module. This allows lower communication speed but very fast control panel response time
and less sensitivity to line noise and loop wiring properties. As a result, twisted or shielded wire is not required.
Plug-in UIO
Plug-in UIO modules mount to UIO motherboards. Two- and six-
module UIO motherboards are available, making them ideal for instal-
lations where more than one module is required. Motherboards can
RM
ALA
FIRE DULE
MO
16
VS
SERIES
Analog Addressable Initiating Devices
SUBMIT
Universal Class A/B Module
The Universal Class A/B Module is used to connect initiating, appliance, or two-wire smoke
GSA-UM
circuits in either Class A or Class B configurations. The plug-in version can also be used as a
Class A dry contact initiating device circuit. The actual function of this module is determined
by the “personality code” selected by the installer. Up to fifteen personalities are available. GSA-MAB
GSA-UM Universal Class A/B Module (Two-gang standard mount) Data Sheet K85001-0275
GSA-MAB Universal Class A/B UIO (Plug-in) Module Data Sheet K85001-0275
Initiating
Class B Input Module
Devices
The Class B Input Module is used to connect Class B normally-open Alarm, Supervisory, or
Monitor type dry contact initiating device circuits. The standard-mount version is available with
either one or two input connections. The plug-in version accepts two input connections. The
actual function of this module is determined by the “personality code” selected by the installer.
A total of four personalities are available. GSA-MCT2
GSA-CT1 Single Input Module (One-gang standard mount) Data Sheet K85001-0241
GSA-CT1HT Single Input High Temperature Module (One-gang standard mount) Data Sheet K85001-0241
GSA-CT2 Dual Input Module (One-gang standard mount) Data Sheet K85001-0241
GSA-MCT2 Dual Input UIO (Plug-in) Module Data Sheet K85001-0241
Notification
Appliances
Waterflow/Tamper Module
The GSA-WTM Waterflow/Tamper Module is a two circuit intelligent module. Circuit 1 is for Class
B normally-open waterflow alarm switches. When the input contact is closed for approximately 16
seconds, an “alarm” signal is sent to the loop controller. Circuit 2 is for Class B normally open dry
contact supervisory and tamper switches. When the input contact is closed, an “active” signal is sent GSA-WTM
to the loop controller. Conditions on both circuits are latched at the module.
GSA-WTM Waterflow/Tamper Module (One-gang standard mount) Data Sheet K85001-0297
Hazardous Location
Isolator Module
The GSA-IM2 Isolator Module is an intelligent device that allows part of the data loop to con-
Devices
tinue operating in the event of a short circuit. The module can be wired into a Class A data
loop at any point. A maximum of 64 isolator modules can be installed on one circuit. If a fault
occurs, the isolator cuts power to all devices beyond the isolator on the loop. Once activated,
the line fault isolator continuously checks the faulted side of the loop to determine if the short
still exists. When the fault is cleared, the module automatically restores the entire data loop GSA-IM2
to its normal condition.
GSA-IM2 Fault Isolator Module (Two-gang standard mount) Data Sheet K85001-0272
Monitor Module
Door Holders
The GSA-MM1 is a single-circuit intelligent module that includes a Class B normally-open dry
& Relays
contact. This is used for monitoring input from devices such as fans, dampers, and doors.
When the input contact is closed, an “active” signal is sent to the loop controller. The active
condition is not latched at the module. GSA-MM1
17
VS
SERIES
Analog Addressable Initiating Devices
SUBMIT
Signal Module
Analog Control
VS Series
The Signal Module is used to connect, upon command from the loop controller, supervised
Class B signal or telephone circuits to their respective power inputs. Models are available
with one or two power inputs. These may be either polarized 24 Vdc to operate audible
and visual signal appliances, or 25 and 70Vrms to operate audio evacuation speakers and
firefighter’s telephones. The actual function of this module is determined by the “personality
code” selected by the installer. A total of three personalities are available. GSA-MCC1/MCC2
GSA-CC1 Single Input Signal Module (Two-gang standard mount) Data Sheet K85001-0237
GSA-MCC1 Single Input Signal UIO (Plug-in) Module Data Sheet K85001-0237
GSA-CC2 Dual Input Signal Module (Two-gang standard mount) Data Sheet K85001-0237
GSA-MCC2 Dual Input Signal UIO (Plug-in) Module Data Sheet K85001-0237
Initiating
Devices
GSA-CR Control Relay Module (One-gang standard mount) Data Sheet K85001-0239
GSA-MCR Control Relay UIO (Plug-in) Module Data Sheet K85001-0239
GSA-CRH High Power Control Relay Module (One-gang standard mount) Data Sheet K85001-0644
the data loop. This module supports only one personality: no user configuration is required.
GSA-MCRR
GSA-CRR Polarity Reversal Relay Module (One-gang standard mount) Data Sheet K85001-0239
GSA-MCRR Polarity Reversal Relay UIO (Plug-in) Module Data Sheet K85001-0239
GSA-CC1S Synchronization Output Module (One-gang standard mount) Data Sheet K85001-0543
GSA-MCC1S Synchronization Output UIO (Plug-in) Module Data Sheet K85001-0543
Input/Output Module
The Input/Output Module is an intelligent device that provides
• Output with monitor input
• Input/programmable output
• Input/direct output
GSA-MMIO
GSA-IO Input/Output Module (One-gang standard mount) Data Sheet K85001-0533
GSA-MIO Input/Output UIO (Plug-in) Module Data Sheet K85001-0533
18
VS
SERIES
Analog Addressable Initiating Devices
SUBMIT
Individual Riser 1 Input to each SIGA-UIO module than one module. This significantly reduces wiring
requirements. UIO motherboards mount inside the
Initiating
MFC-A cabinet or other suitable UL-listed electrical enclosure.
Devices
GSA-UIO2R Universal Input/Output Module Board with Riser Inputs — 2 Module Positions Data Sheet K85001-0365
GSA-UIO6R Universal Input/Output Module Board with Riser Inputs — 6 Module Positions Data Sheet K85001-0365
GSA-UIO6 Universal Input/Output Module Board — 6 Module Positions Data Sheet K85001-0365
Abort
Releasing Module
First alarm output
Manual Release Form C 3 A @24 Vdc
24 Vdc in
Notification
Appliances
DS5 DS3
DS4
and offers a wide range of options that Pre-release CCT1 (pulsed 15/60)
ing module includes a built-in timer that inhibits the deluge function 2
3
2
3
Hazardous Location
mounts inside an MFC-A cabinet or other suitable UL-listed electrical enclosure. Each MFC-A will hold one GSA-REL.
GSA-REL Intelligent addressable releasing module Data Sheet K85001-0531
Devices
RELA-ABT Abort station Data Sheet K85001-0531
RELA-SRV-1 Service disconnect station Data Sheet K85001-0531
276A-REL Manual releasing station (single-action) Data Sheet K85001-0531
278A-REL Manual releasing station (double-action) Data Sheet K85001-0531
RELA-EOL Polarized end-of-line relay Data Sheet K85001-0531
Related Equipment
MFC-A Multi-function Cabinet (for UIO and Releasing modules)
27193-11 Surface Mount Box - Red, One-gang
Door Holders
19
VS
SERIES
Analog Addressable Initiating Devices
SUBMIT
Addressable initiating
Analog Control
VS Series
TB2
GSA-M270 series manual pull stations are made from Red LED
(Alarm/Active)
4 3 2 1
Green LED
(Normal)
or Previous Device
GSA-M270 One Stage Fire Alarm Station, English Markings Data Sheet K85001-0279
GSA-M270P Two Stage (Pre-signal) Fire Alarm Station, English Markings Data Sheet K85001-0279
276-K2 GA Key — for pre-signal station Data Sheet K85001-0279
270-GLR 20 Break-rods — for GSA-M270 series Data Sheet K85001-0279
276B-RSB Surface Mount Box, Red — for GSA-M270 series Data Sheet K85001-0279
REAR VIEW
8 7
red LEXAN. To initiate an alarm, first lift the upper door, TB1
GSA-M278 Double Action (One Stage) Fire Alarm Station, English Markings Data Sheet K85001-0279
276B-RSB Surface Mount Box, Red — for GSA-M278 series Data Sheet K85001-0279
276-GLR 20 Break-rods — for GSA-M278 series Data Sheet K85001-0279
Stopper II
This unique device helps prevent false alarms without restricting legitimate ones. It consists of a tamper-
proof clear LEXAN polycarbonate shield and frame that fits easily over manual pull stations. When lifted,
it sounds a piercing warning horn.
STI-1100 (Flush) STI-1130 (Surface) Stopper II with Horn Data Sheet K85001-0491
STI-1200 (Flush) STI-1230 (Surface) Stopper II without Horn Data Sheet K85001-0491
STI-3100 (2" Spacer) STI-3004 (Conduit Insert) Spacers Data Sheet K85001-0491
STI-3002 (Gasket) STI-3003 (Conduit Gasket) Weatherproofing Data Sheet K85001-0491
20
VS
SERIES
Notification Appliances
Notification
Outdoor Speakers & Strobes p. 29
Audible Signals p. 31
Appliances
Harsh Environment Signals p. 34
Accessories p. 35
Notification
Appliances
Class B with separate strobe and horn circuits
combination horn-strobes, when used
with the innovative Signal Master Module,
support independent horn control over
a single pair of wires and precision
Notification Appliance Circuit
synchronization that exceeds UL Class A with combination horn-strobe circuit
requirements. This reduces wiring time while
meeting the requirements of even the most
demanding application.
Hazardous Location
Device Wiring, Speaker-strobes Device Wiring, Horn-strobes
Devices
To listed fire alarm control panel
(supervised amplifier signal circuit
– 25.2 or 70.7V rms) + +
To listed fire alarm control panel
(supervised signal circuit
– 20-24 Vdc) + +
SPKR
C
S+
S-
On a common circuit, strobes flash once per second (1 The following control panels, power supplies, and modules
fps) within 10 milliseconds over a two-hour time period. A provide synchronization sources that enable Genesis strobe
synchronization source is required to comply with UL 1971 devices to comply with UL 1971 synchronization standards:
synchronization standards. Temporal setting (private mode only): GSA-CC1S, GSA-MCC1S, SIGA-CC2A, GSA-MCC2A,
synchronized to temporal output on the same circuit. Genesis MG1M-RM, MIRBPS6A, MIRBPS10A, APS6A, APS10A, VM
LED strobes are synchronized, backwards compatible, and can Series, VS1, VS4, VM, FX Series Intelligent and Conventional
be used in the same field of view as Genesis Xenon strobes. control panels.
21
VS
SERIES
Notification Appliances
SUBMIT
Genesis Visual
Analog Control
VS Series
Horn-Strobes, p. 23
while speakers and ceiling models with clean modern lines
blend inconspicuously with their surroundings.
Signaling on-demand
LED Wall Strobes, Horns, Though designed for discretion, Genesis signals are also
Horn-Strobes p. 24
engineered to command attention. Wall-penetrating high
dB output and patented strobe technology immerse the
protected area with levels of light and sound that simply
can’t be ignored – all in exchange for the lowest current
Notification
Appliances
Application flexibility
Whether you’re designing for a new landmark structure,
Low Frequency Horns and or simply retrofitting a local strip mall, competitively-
Horn-Strobes, p. 28
priced Genesis signals bring value, good looks, and
installation flexibility to every application. Contact Kidde
today to learn how your signal solutions can be the
model of discretion.
Outdoor Horns, Horn-Strobes,
p. 29
22
VS
SERIES
Notification Appliances
SUBMIT
Genesis strobes offer 15 to 75 candela output, which is selectable with a conveniently located switch on the
side of the device. The current is only 24mA VDC and 32mA VFWR for all light output settings. The candela output setting
remains clearly visible even after final installation, yet it stays locked in place to prevent unauthorized tampering.
(Data Sheet K85001-0667)
White housing White housing Red housing Red housing
no marking with “FIRE” no marking with “FIRE”
EG1VWN EG1VWF EG1VRN EG1VRF
Genesis Horns reach output levels as high as 92 dB and feature a unique multiple-frequency tone that results in
excellent wall penetration and an unmistakable warning of danger. Horns may be configured for either constant or temporal
3 output and high or low dB output with a conveniently located switch under the cover. No more cutting jumpers. Horns
operate at 13mA VDC and 15mA VFWR on Low dB output and 23mA VDC and 29mA VFWR on High dB output.
Notification
(Data Sheet K85001-0667)
Appliances
White housing White housing Red housing Red housing
no marking with “FIRE” no marking with “FIRE”
EG1AWN EG1AWF EG1ARN EG1ARF
Genesis Horn-strobes provide a low-profile design with horn output reaching as high as 92 dBA and as low as 80 dBA
and have strobes that offer 15 to 75 candela output. Both the horn and strobe can be field configured with a switch,
which is conveniently located on the side of the device. The candela output setting remains clearly visible even after final
installation, yet it stays locked in place to prevent unauthorized tampering. Horns may be configured for either constant or
temporal 3 output and high or low dB output. Horn-Strobes operate at 35mA VDC and 43mA VFWR on Low dB output
and 45mA VDC and 55mA VFWR on High dB output for all light output settings. (Data Sheet E85001-0667)
Hazardous Location
White housing White housing Red housing Red housing
no marking with “FIRE” no marking with “FIRE”
Devices
EG1AVWN EG1AVWF EG1AVRN EG1AVRF
Trim plates for wall horns, horn-strobes, and strobes are ideal for covering openings left behind during retrofits.
White plate Red plate Trim Plates
no marking no marking
EG1TW EG1TR Trim plate for 2-gang or 4" boxes
Replacement covers are available for all models. When ordering add -CVR to the model number.
R = Red R = Red
W = White W = White
Cover
EG1AVRF Housing Marking
N = None
EG1AVRF-CVR Designation
23
VS
SERIES
Notification Appliances
SUBMIT
& Horn-Strobes
Genesis LED EG4 Series horns and LED strobes feature a sleek, low-profile design
and energy-efficient technology that makes them less expensive to install and
operate by reducing overhead. High-performance LEDs and patented electronics
allow for more devices per loop and fewer booster power supplies. Genesis
LED EG4 devices mount to the required GP10 room side wiring plate for
installation.The GP10 mounting plate is included with the EG4 device for
convenient pre-installing and pre-wiring.
Initiating
Devices
Genesis strobes offer 15 to 110 candela output, which is selectable with a conveniently located switch on the side
of the device. The current is only 28mA VDC and 36mA VFWR for all light output settings. The candela output setting
remains clearly visible even after final installation, yet it stays locked in place to prevent unauthorized tampering.
(Data Sheet K85001-0668)
White housing White housing Red housing Red housing
no marking with “FIRE” no marking with “FIRE”
EG4VWN EG4VWF EG4VRN EG4VRF
Genesis Horns reach output levels as high as 92 dB and feature a unique multiple-frequency tone that results in
excellent wall penetration and an unmistakable warning of danger. Horns may be configured for either constant or temporal
3 output and high or low dB output with a conveniently located switch under the cover. No more cutting jumpers. Horns
operate at 18mA VDC and 22mA VFWR on Low dB output and 28mA VDC and 38mA VFWR on High dB output.
Notification
Appliances
Genesis Horn-strobes provide a low-profile design with horn output reaching as high as 92 dBA and as low as 80 dBA
and have strobes that offer 15 to 110 candela output. Both the horn and strobe can be field configured with a switch,
which is conveniently located on the side of the device. The candela output setting remains clearly visible even after final
installation, yet it stays locked in place to prevent unauthorized tampering. Horns may be configured for either constant or
temporal 3 output and high or low dB output. Horn-Strobes operate at 40mA VDC and 48mA VFWR on Low dB output
and 50mA VDC and 60mA VFWR on High dB output for all light output settings. (Data Sheet K85001-0668)
White housing White housing Red housing Red housing
no marking with “FIRE” no marking with “FIRE”
EG4AVWN EG4AVWF EG4AVRN EG4AVRF
Accessories including required room side wiring plate and trim plates ideal for openings left behind during retrofits.
White plate Red plate Room Side Wiring Plate
no marking no marking (Included)
EG4TW EG4TR
Replacement covers are available for all models. When ordering add -CVR to the model number.
24
VS
SERIES
Notification Appliances
SUBMIT
Genesis strobes offer 15 to 115 candela output, which is selectable with a conveniently located switch on the
side of the device. The current is only 35mA VDC and 45mA VFWR for all light output settings. The candela output
setting remains clearly visible even after final installation, yet it stays locked in place to prevent unauthorized tampering.
(Data Sheet K85001-1021)
White housing White housing Red housing Red housing
no marking with “FIRE” no marking with “FIRE”
EGCVWN EGCVWF EGCVRN EGCVRF
Genesis Horns reach output levels as high as 92 dB and feature a unique multiple-frequency tone that results in excellent
wall penetration and an unmistakable warning of danger. Horns may be configured for either constant or temporal 3 output
and high or low dB output with a conveniently located switch under the cover. No more cutting jumpers. Horns operate at
20mA VDC and 25mA VFWR on Low dB output and 30mA VDC and 40mA VFWR on High dB output.
Notification
Appliances
(Data Sheet K85001-1021)
White housing Red housing
with “FIRE” with “FIRE”
EGCAWF EGCARF
Genesis Horn-strobes provide a low-profile design with horn output reaching as high as 92 dBA and as low as 80 dBA and
have strobes that offer 15 to 115 candela output. Both the horn and strobe can be field configured with a switch, which is
conveniently located on the side of the device. The candela output setting remains clearly visible even after final installation,
yet it stays locked in place to prevent unauthorized tampering. Horns may be configured for either constant or temporal 3
output and high or low dB output. Horn-Strobes operate at 50mA VDC and 60mA VFWR on Low dB output and 60mA VDC
Hazardous Location
and 75mA VFWR on High dB output for all light output settings. (Data Sheet K85001-1021)
White housing White housing Red housing Red housing
no marking with “FIRE” with “FIRE” with “FIRE”
Devices
EGCAVWN EGCAVWF EGCAVRN EGCAVRF
Accessories including required room side wiring plate and trim plates ideal for openings left behind during retrofits.
White plate Red plate Room Side Wiring Plate
(Included)
EGCTW EGCTR
Replacement covers are available for all models. When ordering add -CVR to the model number.
Model Number Syntax, Appliances Model Number Syntax, Replacement Covers
Genesis LED Series Genesis LED Series
EGC = Wall-mount appliances EGC = Wall-mount appliances
Door Holders
W = White W = White
Cover
EGCAVRF Housing Marking
N = None
EGCAVRF-CVR Designation
Note: GC devices
F = FIRE are designed for Cover Marking
ceiling applications N = None
Functions but are UL listed to Functions F = FIRE
A = Horn only be wall or ceiling A = Horn only
V = Strobe only mounted. V = Strobe only
AV = Horn-Strobe AV = Horn-Strobe
25
VS
SERIES
Notification Appliances
SUBMIT
& Speaker-Strobes
Genesis LED EG4S Series speakers and speaker-strobes combine high
performance output with a sleek low profile design and energy-efficient
technology that makes them less expensive to install and operate. High
performance LEDs require fewer power supplies, backup power, and batteries. These new appliances are designed
with energy-efficiency, and life safety in mind. Understanding the content of the message is as important as knowing
there is an emergency.
Intelligibility is measured in Speech Transmission Index and anything above .76 is considered excellent. G4S Series speakers
Initiating
deliver audio with an STI of .81 ensuring the message is clear. They also meet NFPA and UL 520Hz requirements for sleeping
Devices
areas making them ideal for new construction or retrofits. Genesis LED appliances mount to the required GRSW room side
wiring plate for installation. The GRSW mounting plate is included with the EG4S for convenient pre-installing and pre-wiring.
Genesis Speakers feature selectable wattage taps that are visible after installation. Speakers are also capable of both 25V
and 70V and voltage in a single model with a field selectable switch. Speakers meet NFPA and UL 520Hz requirements for
sleeping areas and have an STI rating of .81 ensuring speakers deliver a clear, highly intelligible message.
(Data Sheet K85001-1026)
White housing White housing Red housing Red housing White housing
no marking with “FIRE” no marking with “FIRE” with “ALERT”
EG4SWN EG4SWF EG4SRN EG4SRF EG4SWA
Notification
Appliances
Genesis Speaker-strobes feature selectable wattage taps, and allow for both wattage and light output levels to be
configured in the field. Both settings remain clearly visible — even after final installation. Speakers are also capable of
both 25V and 70V and voltage in a single model with a field selectable switch. Speakers meet NFPA and UL 520Hz
requirements for sleeping areas and have an STI rating of .81 ensuring speakers deliver a clear, highly intelligible message.
Speaker-strobes feature field-selectable 15, 30,75, or 110 cd light output and have a constant current draw for all light
output settings of 28mA for VDC and 36mA for VFWR. (Data Sheet K85001-1026)
White housing White housing Red housing Red housing White housing
no marking with “FIRE” no marking with “FIRE” with “ALERT”
EG4SVWN EG4SVWF EG4SVRN EG4SVRF EG4SVWA
Accessories including required room side wiring plate and trim plates ideal for openings left behind during retrofits.
White plate Red plate Room Side Wiring Plate
no marking no marking (Included)
EG4TW EG4TR
Replacement covers are available for all models. When ordering add -CVR to the model number.
Model Number Syntax, Appliances Model Number Syntax, Replacement Covers
Genesis Series Genesis Series
EG4S = Wall-mount speakers EG4S = Wall-mount speakers
Housing Color Housing Color
R = Red R = Red
W = White W = White
Cover
EG4SVRF Housing Marking
N = None
EG4SVRF-CVR Designation
26
VS
SERIES
Notification Appliances
SUBMIT
Genesis Speakers feature selectable wattage taps that are visible after installation. Speakers are also capable of both 25V
and 70V and voltage in a single model with a field selectable switch. Speakers meet NFPA and UL 520Hz requirements for
sleeping areas and have an STI rating of .81 ensuring speakers deliver a clear, highly intelligible message.
(Data Sheet K85001-1025)
White housing White housing Red housing Red housing White housing
no marking with “FIRE” no marking with “FIRE” with “ALERT”
EGCSWN EGCSWF EGCSRN EGCSRF EGCSWA
Genesis Speaker-strobes feature selectable wattage taps, and allow for both wattage and light output levels to be
Notification
Appliances
configured in the field. Both settings remain clearly visible — even after final installation. Speakers are also capable of
both 25V and 70V and voltage in a single model with a field selectable switch. Speakers meet NFPA and UL 520Hz
requirements for sleeping areas and have an STI rating of .81 ensuring speakers deliver a clear, highly intelligible message.
Speaker-strobes feature field-selectable 15, 30,75, or 115 cd light output and have a constant current draw for all light
output settings of 35mA for VDC and 45mA for VFWR. (Data Sheet K85001-1025)
White housing White housing Red housing Red housing White housing
no marking with “FIRE” no marking with “FIRE” with “ALERT”
EGCSVWN EGCSVWF EGCSVRN EGCSVRF EGCSWA
Accessories including required room side wiring plate and trim plates ideal for openings left behind during retrofits.
Hazardous Location
White plate Red plate Room Side Wiring Plate
no marking no marking (Included)
Devices
EGCTW EGCTR
Replacement covers are available for all models. When ordering add -CVR to the model number.
Model Number Syntax, Appliances Model Number Syntax, Replacement Covers
Genesis Series Genesis Series
EGCS = Ceiling mount appliances EGCS = Ceiling mount appliances
Housing Color Housing Color
R = Red R = Red
W = White W = White
Cover
EGCSVRF Housing Marking
N = None
EGCSVRF-CVR Designation
Note: GC devices
F = FIRE are designed for Cover Marking
A = ALERT*
Door Holders
27
VS
SERIES
Notification Appliances
SUBMIT
UL
compliant
signals for
G4LF Series notification appliances provide the benefits of Genesis life safety
signals with output suitable for sleeping areas and other applications requiring
low frequency audible tones. These high-performance appliances generate a
crisp 520 Hz tone in the standard 3-3 temporal pattern. An optional setting
configures the appliance for continuous audible output — a critical feature for
notification appliance circuits that are coded with a CDR-3 coder module. All
G4LF appliances feature field-configurable high and low dB output settings.
Horn-Strobe models feature field-selectable 15, 30, 75 or 110 cd output settings.
Initiating
Devices
G4LFWN-HVM Horn-Strobe, 520 Hz, White Housing, No Marking, 15/30/75/110 cd Data Sheet K85001-0639
G4LFWF-HVM Horn-Strobe, 520 Hz, White Housing, FIRE Marking, 15/30/75/110 cd Data Sheet K85001-0639
G4LFRN-HVM Horn-Strobe, 520 Hz, Red Housing, No Marking, 15/30/75/110 cd Data Sheet K85001-0639
G4LFRF-HVM Horn-Strobe, 520 Hz, Red Housing, FIRE Marking, 15/30/75/110 cd Data Sheet K85001-0639
G4LFWN-H Horn, 520 Hz, White Housing, No Marking Data Sheet K85001-0639
G4LFWF-H Horn, 520 Hz, White Housing, FIRE Marking Data Sheet K85001-0639
G4LFRN-H Horn, 520 Hz, Red Housing, No Marking Data Sheet K85001-0639
G4LFRF-H Horn, 520 Hz, Red Housing, FIRE Marking Data Sheet K85001-0639
Notification
Appliances
28
VS
SERIES
Notification Appliances
SUBMIT
Field Configuration
Genesis WG4 strobes feature four selectable light output settings. Cd Signal In — Signal Out —
selections are changed by removing the cover and simply sliding the Signal In + Signal Out +
switches to the desired setting, which remains visible through a small
window on the front of the device after the cover is replaced. Gen-
esis Horn-strobes may also be configured for high or low dB output
and temporal flash. This battery-saving feature is intended for private
mode signaling only.
Notification
—/+ designations indicate the signal polarity
Appliances
required to activate the device.
Light Output
Standard Candela Horn-strobes High Candela Horn-strobes
Strobe Switch Position Strobe Switch Position
Standard/rating Standard/rating
Hazardous Location
D C B A D C B A
UL 1971 Indoor 15 cd 29 cd 70 cd 87 cd UL 1971 Indoor 102cd 123cd 147cd 161cd
UL 1638 Outdoor @ -35°C 6 cd 12 cd 28 cd 35 cd UL 1638 Outdoor @ -35°C 41cd 50 cd 60 cd 65 cd
CAN/ULC-S526 Outdoor @ -40°C 1 cd 3 cd 8 cd 10 cd CAN/ULC-S526 Outdoor @ -40°C 11 cd 14 cd 17 cd 18 cd
Devices
White housing White housing Red housing Red housing Outdoor Fire Alarm Appliances
no marking with “FIRE” no marking with “FIRE”
WG4WN-H WG4WF-H WG4RN-H WG4RF-H Horn Only
WG4WN-HVMC WG4WF-HVMC WG4RN-HVMC WG4RF-HVMC Horn-Strobe, standard cd output
WG4WN-HVMHC WG4WF-HVMHC WG4RN-HVMHC WG4RF-HVMHC Horn Only, high cd output
WG4WTS (white) WG4RTS (red) Surface Skirt for Genesis WG4 Appliances
74347U (white) 449 (red) Surface mount box, outdoor rated
WG4GSKT Genesis WG4 Full Body Mounting Gasket for Smooth Surfaces
29
VS
SERIES
Notification Appliances
SUBMIT
and Speaker-Strobes
Genesis WG4 Series speakers and speaker-strobes are among the most
versatile emergency signals of their kind. Rated for indoor or outdoor use,
they are suitable for a wide range of wet and harsh environments with a
listed operating temperature range of as low as -31°F to as high as
151°F (-35°C to 66°C).
Refer to Data Sheet K85001-0626 -- Genesis Outdoor Speakers and Strobes for details.
Initiating
Devices
intended for private mode signaling only. To set the S2: JP1: Strobe temporal
Candela mode selection
device for temporal flash, snip the jumper at JP1.
WG4RF-S WG4RF-SVMC WG4WF-S WG4WF-SVMC WG4RN-S WG4RN-SVMC WG4WN-S WG4WN-SVMC WG4WN-SVMA WG4WA-SVMA WG4WA-SVMC
White housing White housing Red housing Red housing Fire Alarm Speakers
no marking with “FIRE” no marking with “FIRE”
WG4WN-S WG4WF-S WG4RN-S WG4RF-S 25/70 V Speaker
WG4WN-SVMC WG4WF-SVMC WG4RN-SVMC WG4RF-SVMC 25/70 V Speaker-strobe (15/29/70/87 cd)
WG4WF-SVMHC WG4RN-SVMHC WG4RF-SVMHC 25/70 V Speaker-strobe (102/123/147/161 cd)
Genesis mass notification speakers and speaker-strobes bring the same high-performance fire alarm features and
unobtrusive design to mass notification applications. Available with amber lenses and optional “ALERT” lettering, they are
ideal for applications that require differentiation between fire alarm and mass notification alerts.
White housing White housing Mass Notification Speakers
no marking “ALERT” — white housing, no “Running Man” icon
WG4WN-SVMA WG4WA-SVMA 25/70 V Speaker-strobe, amber lens (13/25/5962 cd output)
WG4WN-SVMHA WG4WA-SVMHA 25/70 V Speaker-strobe, amber lens (84/101/125/130 cd output)
WG4WA-SVMC 25/70 V Speaker-strobe, clear lens (15/29/70/87 cd output)
WG4WN-SVMHC WG4WA-SVMHC 25/70 V Speaker-strobe, clear lens (102/123/147/161 cd output)
WG4WA-S 25/70 V Speaker
Trim skirts
WG4WTS (white) WG4RTS (red) Surface Skirt for Genesis WG4 appliance family.
30
VS
SERIES
Notification Appliances
SUBMIT
Multiple Tone Signal
The 5530MD-24AW is a weatherproof heavy-duty industrial, tone-selectable, signaling device
capable of producing volume-controlled, high-decibel tones. It uses a microprocessor circuit
to create 27 distinctive tones. A single tone may be selected by setting a miniature dip switch
within the unit.
5530MD-24AW 27-Tone Selectable Signal — 24Vdc Data Sheet K85001-0415
Notification
Appliances
Multi-purpose Loudspeaker
The HPSA15 loudspeaker is a high-efficiency double re-entrant loudspeaker that operates within a
nominal frequency response range of 400-14,000 Hz, and provides audible output of 120 dB (peak
at one meter) at the rated power level. It includes a versatile, three-way, 25/70.7 V line transformer
that meets a variety of distributed system needs. The transformer is adjustable by means of a con-
venient seven-position, watts/impedance selection switch.
HPSA15R2570 15-watt loudspeaker, red Data Sheet K85001-0591
HPSA15G2570 15-watt loudspeaker, gray Data Sheet K85001-0591
Hazardous Location
Medium Power Speaker Arrays
Devices
Mass Notification
The Kidde HyperSpike® Series TCPA-10 is intended for indoor and
outdoor audio signaling and notification. Its best-in-class acoustic cover-
age allows for fewer units to be installed in large indoor and outdoor areas,
lowering installation and long-term maintenance costs, while also improving
intelligibility and aesthetics..
90215A-801-04-L Gray UL 1480 listed C1D2 certified TCPA-10 Distributed Data Sheet K85001-0669
Audio Speaker with 5 selectable power taps that run
off of 25V, 70V and 100 VRMS audio systems
90215A-801-05-L Red UL 1480 listed C1D2 certified TCPA-10 Distributed Data Sheet K85001-0669
Audio Speaker with 5 selectable power taps that run
off of 25V, 70V and 100 VRMS audio systems
90215A-801-06-L White UL 1480 listed C1D2 certified TCPA-10 Distributed Data Sheet K85001-0669
Audio Speaker with 5 selectable power taps that run
off of 25V, 70V and 100 VRMS audio systems
31
VS
SERIES
Notification Appliances
SUBMIT
Kidde brand Hyperspike Series Medium Power loudspeakers employ exclusive HyperSpike technology to deliver
lightweight and acoustically sophisticated solutions for large indoor and smaller outdoor mass notification installations.
Analog Control
VS Series
MN-HSMT25P5N 250-Watt Medium Power Speaker Array, tan housing. Data Sheet K85001-0652
MN-HSMG25P5N 250-Watt Medium Power Speaker Array, gray housing. Data Sheet K85001-0652
Initiating
Devices
MN-HSMR25P5N 250-Watt Medium Power Speaker Array, red housing. Data Sheet K85001-0652
powerful tones never before possible within reverberant environments. The beam forming
capability of the LineWave loudspeaker allows even coverage across the listening plane while
to come focusing the acoustic pattern away from surfaces that cause unwanted reflections. This
technology is essential for achieving optimum levels of speech intelligibility within reverberant
spaces. The result is clear and intelligible direct sound that ensures critical messages are
heard and understood.
90243A-801-01-L LineWave line array speaker 2 Black Data sheet K85001-0659
90243A-802-01-L LineWave line array speaker 4 Black Data sheet K85001-0659
90243A-803-01-L LineWave line array speaker 8 Black Data sheet K85001-0659
90243A-804-01-L LineWave line array speaker 16 Black Data sheet K85001-0659
90243A-801-05-L LineWave line array speaker 2 Red Data sheet K85001-0659
90243A-802-05-L LineWave line array speaker 4 Red Data sheet K85001-0659
90243A-803-05-L LineWave line array speaker 8 Red Data sheet K85001-0659
90243A-804-05-L LineWave line array speaker 16 Red Data sheet K85001-0659
90243A-801-06-L LineWave line array speaker 2 White Data sheet K85001-0659
90243A-802-06-L LineWave line array speaker 4 White Data sheet K85001-0659
90243A-803-06-L LineWave line array speaker 8 White Data sheet K85001-0659
90243A-804-06-L LineWave line array speaker 16 White Data sheet K85001-0659
90243A-801-07-L LineWave line array speaker 2 Gray Data sheet K85001-0659
90243A-802-07-L LineWave line array speaker 4 Gray Data sheet K85001-0659
90243A-803-07-L LineWave line array speaker 8 Gray Data sheet K85001-0659
90243A-804-07-L LineWave line array speaker 16 Gray Data sheet K85001-0659
72581B-801 LineWave line array speaker pole mount kit Data sheet K85001-0659
72575B-801-L LineWave 25V/70V/100V Transformer 2/4 speaker Data sheet K85001-0659
72542B-801-L LineWave 25V/70V/100V Transformer 8 speaker Data sheet K85001-0659
72542B-802-L LineWave 25V/70V/100V Transformer 16 speaker Data sheet K85001-0659
32
Notification Hazardous Location Door Holders
Appliances Devices & Relays
SUBMIT
33
Notification Appliances
SERIES
VS
VS
SERIES
Notification Appliances
SUBMIT
North American
2-gang electrical box
VS Series
Mounting Plate
Signals Housing
Surface Box (optional)
All Enhanced Integrity devices are UL 1971 listed for both wall and First Device
ceiling orientation. Enhanced Integrity strobes meet the latest UL1971 - Horn/Strobe Horn/Strobe
To Fire Alarm
H+ H+
34
VS
SERIES
Notification Appliances
SUBMIT
Accessories
Bell/Strobe Plate
The bell/strobe plate is ideal for renovation and retrofit projects, and new construction.
It is equipped with a self-synchronizing strobe and is designed to allow on-site mount-
ing of the 439 series Vibrating Bell, providing instant conversion to Bell/Strobe audible/
visual signal appliances. The strobe is designed for 20 to 24Vdc operation and must
be connected to signal circuits which output a constant (not pulsed) voltage. A diode
is used to allow full signal circuit supervision.
403-5A-R (15 cd) 403-7A-R (15/75 cd) 403-3A-R (30 cd) 403-8A-R (110 cd) Data Sheet K85001-0441
Notification
Appliances
Integrity strobes are shipped with wall mount style “FIRE” lens markings. Where ceiling mount, other languages or dif-
ferent lens markings are required, optional LKW and LKC series Lens Marking Kits are available. Lens marking sleeves
snap right over the strobe lens providing a quick, easy, change.
LKW-1R (Wall orientation) “FIRE” (Red)
LKW-1 (Wall orientation) LKC-1 (Ceiling orientation) “FIRE”
LKW-2 (Wall orientation) LKC-2 (Ceiling orientation) “FEU”
LKW-3 (Wall orientation) LKC-3 (Ceiling orientation) “FIRE/FEU”
LKW-4 (Wall orientation) LKC-4 (Ceiling orientation) “SMOKE”
Hazardous Location
LKW-5 (Wall orientation) LKC-5 (Ceiling orientation) “HALON”
LKW-6 (Wall orientation) LKC-6 (Ceiling orientation) “CO2”
Devices
LKW-7 (Wall orientation) LKC-7 (Ceiling orientation) “EMERGENCY”
LKW-8 (Wall orientation) LKC-8 (Ceiling orientation) “ALARM”
LKW-9 (Wall orientation) LKC-9 (Ceiling orientation) “FUEGO”
LKW-10 (Wall orientation) LKC-10 (Ceiling orientation) “ALERT”
Mounting Accessories
960A-4SF Flush Box, Indoor G4RB Speaker Surface Box, Red, Indoor
757A-SB Surface Box, Red, Indoor G4B Speaker Surface Box, White, Indoor
757A-SBW Surface Box, White, Indoor G4ERB G4 Dual-strobe Format Surface box, Red
G4EWB G4 Dual-strobe Format Surface box, White
Integrity Re-entrant speakers, Speaker/strobes
960A-4SF Flush Box, Indoor Horn/siren Combination
757A-SB Surface Box, Red, Indoor 349 Weatherproof Backbox
Genesis G4B Speaker
757A-SBW Surface Box, White, Indoor
Fire Alarm Bells and CS-405 Series Surface Box
757A-WB Weatherproof Box, Red, Surface
757A-WBW Weatherproof Box, White, Surface 449 Weatherproof Backbox
35
VS
SERIES
Notification Appliances
SUBMIT
Audio Notification System
Analog Control
VS Series
See Data Sheet K85001-0587 for complete specifications and ordering information.
8 TB2
Appliances
P3 P4
Panels include DMR, Power Supply & Battery Charger, Standard Message, Microphone, and Cabinet.
LED 5
LED 4
ANS25MDG2 (Grey Cabinet) ANS25MDG2 (Red Cabinet) P5 25 Watt Audio Notification Panel.
ANS50MDG2 (Grey Cabinet) ANS50MDG2 (Red Cabinet) S1
50 Watt Audio Notification Panel.
P9 P8
ANS100MDG2 (Grey Cabinet) ANS100MDG2 (Red Cabinet) SN1 SN2
100 Watt Audio Notification Panel.
36
VS
SERIES
Hazardous Location Devices
SUBMIT
Initiating Devices p. 38
Hazardous
Notification Appliances p. 39
Location Devices
Kidde hazardous location devices provide reliable life safety protection and emergency signaling in areas where
atmospheres could become harsh or explosive. All hazardous location devices are UL rated under the full range of
classifications set out in the National Electrical Code.
The following classification definitions are an interpretive summary based on the 1996 edition of the National Elec-
trical Code (NEC, NFPA 70). Refer to the latest editions of NFPA 497M, NFPA 70 and the UL Hazardous Location
Equipment Directory for current and more detailed information. For more information on NEMA classifications, refer
to NEMA Standards Publication No. 250.
Classes Divisions
The Location Classes are broken down by the NFPA into
Class I - Hazardous Gases. Class I locations are areas in which flam- Divisions 1 and 2, defining different levels of risk. In general,
mable gases or vapors are or may be present in the air in quantities the risk of there being a hazardous presence of flammable/
sufficient to produce explosive or ignitable mixtures. combustible/ignitable materials is higher for Division 1 than
Typical Class I Hazardous Areas for Division 2. The specifics differ between the three classes
• Spray painting and finishing areas (I, II and III). Equipment suitable for Division 1 is also suitable
• Utility gas plants for Division 2 locations.
• Petroleum refining production plants
• Petroleum dispensing locations
• Dry cleaning facilities
Groups
Class I and II locations are divided by the NFPA into Group
• Dip tanks containing combustibles or flammable liquids
designations identifying specific gases, vapors and dusts by
• Plant facilities extracting solvents
characteristic similarities that relate to specific equipment
• Inhalation anesthetics areas
construction requirements. Class III locations are not divided
• Process facilities manufacturing pyroxylin type plastics
into separate group designations.
Class II - Hazardous Dusts. Class II locations represent areas that are
hazardous due to the presence of combustible dust. Class I Groups
Group A. Atmospheres containing acetylene.
Hazardous Location
Typical Class II Hazardous Areas
• Flour mills Group B. Atmospheres containing hydrogen, fuel and
• Feed mills combustible process gases containing more than 30 percent
• Grain elevators and grain handling facilities hydrogen by volume, or gases or vapors of equivalent hazard
• Aluminum manufacturing and storage areas such as butadiene, ethylene oxide, propylene oxide, and
Devices
• Magnesium manufacturing and storage areas acrolein.
• Coal preparation and handling facilities
• Starch manufacturing and storage areas Group C. Atmospheres such as ethyl ether, ethylene, or
• Confectionery plants other gases or vapors of equivalent hazard.
• Pulverizer sugar and cocoa manufacturing, and storage plants
Group D. Atmospheres containing acetone, ammonia,
• Spice grinding and storage plants
benzene, butane, cyclopropane, ethanol, gasoline, hexane,
Class III - Hazardous Fibers. Class III locations have easily ignitable methanol, methane, natural gas, naphtha (petroleum), pro-
fibers or flyings present, but not likely to be suspended in air in quantities pane, or gases or vapors of equivalent hazard.
sufficient to produce ignitable mixtures in the atmosphere.
Class II Groups
Typical Class III Hazardous Areas
Group E. Atmospheres containing combustible metal dusts,
• Textile mills
including aluminum, magnesium, and their commercial
• Woodworking plants*
alloys, or other combustible dusts whose particle size, abra-
Door Holders
• Furniture manufacturers*
siveness and conductivity present similar hazards in the use
• Cotton gins
& Relays
of electrical equipment.
• Cotton seed milling plants
• Flax plants Group F. Atmospheres containing combustible carbona-
• Carpet manufacturers ceous dusts, including carbon black, charcoal, coal, or dusts
that have been sensitized by other materials so that they
* Except if wood flour (dust), which is Class II Group G, is present
present an explosion hazard.
37
VS
SERIES
Hazardous Location Devices
SUBMIT
Initiating Devices
Analog Control
VS Series
302-AW-135 All-weather Heat Detector - Vertical Mounting FM & UL, 135 °F (57.2 °C) Data Sheet: K85001-0589
302-AW-194 All-weather Heat Detector - Vertical Mounting FM & UL, 194°F (90 °C) Data Sheet: K85001-0589
Notification
Appliances
302-ET-135 All-weather Heat Detector - Vertical, Box Mount (½" NPT), FM & UL, 135 °F (57.2 °C) Data Sheet: K85001-0589
302-ET-194 All-weather Heat Detector - Vertical, Box Mount (½" NPT), FM & UL, 194°F (90 °C) Data Sheet: K85001-0589
302-EPM-135 Heat Detector - Explosionproof Mounting UL (Not FM approved), 135 °F (57.2 °C) Data Sheet: K85001-0589
302-EPM-194 Heat Detector - Explosionproof Mounting UL (not FM approved), 194°F (90 °C) Data Sheet: K85001-0589
AP-P Adaptor plate for mounting 302 and 302-AW to any 3" box or 4" octagon outlet box Data Sheet: K85001-0589
JALX11 Explosion proof outlet body with cover - Killark Data Sheet: K85001-0589
Hazardous Location
MPSR Series explosionproof/weatherproof manual pull stations are noncoded fire alarm sta-
tions solidly constructed of die-cast material. They are rated for Class I Group B (hydrogen)
C & D, Class II Groups E. F, G, Class III environments, and are rated NEMA 4X for outdoor use.
Key and screw reset models feature terminal connections and come complete with backbox.
Hex Screw Reset Cat 45 Key Reset Manual Stations Data Sheet: K85001-0588
MPSR1-DHTWX-GE MPSR1-D45WX-GE Explosionproof Single-action, SPST with backbox.
MPSR1-SHTW-GE MPSR1-S45W-GE Weatherproof Single-action, SPST with bac box.
MPSR1-DHTW-GE MPSR1-D45W-GE Weatherproof Single-action, DPDT with backbox.
MPSR2-SHTW-GE MPSR2-S45W-GE Weatherproof Double-action, SPST with backbox.
MPSR2-DHTW-GE MPSR2-D45W-GE Weatherproof Double-action, DPDT with backbox.
MPSR2-SHTW-GE-NYW MPSR2-S45W-GE-NYW Weatherproof Double-action, SPST with backbox, NYC white stripe.
For French markings add -F to the suffix of the model number. For bilinguial French/English markings add -B to the suffix of the model number.
38
VS
SERIES
Hazardous Location Devices
SUBMIT
Notification Appliances
Hazardous Location Strobes
• Class I, II, or III locations
116DEGEX-FJ hazardous location strobes are life safety signaling appliances designed for installation in
hazardous environments. State-of-the-art technology provide for high visual output and low maintenance.
The 116DEGEX-FJ has negligible in-rush current. When pendant, wall or ceiling mounted, the 116DEGEX-
FJ meets or exceeds the requirements of UL 1971 Signaling Appliance for the Hearing Impaired.
116DEGEX-FJ Explosionproof Strobe, Diode Polarized Data Sheet K85001-0624
116EX-B Wall bracket mounting elbow (required for wall mount applications) Data Sheet K85001-0624
116EX-C Ceiling/wall mounting module (required for wall mount applications) Data Sheet K85001-0624
116EX-P Pendant mounting module - 3/4” (19 mm) NPT Data Sheet K85001-0624
116-GRD Lens Guard Data Sheet K85001-0624
Hazardous Location
430D series of hazardous location bells are diode-polarized, heavy duty fire bells for use in life safety applications
where a diode supervised signal is required. They can be mounted to any solid surface using two 3/8 inch (10 mm)
bolts and the supplied mounting brackets or to a rigid conduit. The integral explosion-proof housing is mechanically
terminated to accept a standard 3/4 inch -14 National Pipe Taper (NPT) nipple.
Devices
439DEX-6AW (6”) 439DEX-8AW (8”) 439DEX-10AW (10”) Bell – 24 Vdc, Red Data Sheet K85001-0399
439DEX-6AW-R (6”) 439DEX-8AW-R (8”) 439DEX-10AW-R (10”) Bell – 24 Vdc, Grey Data Sheet K85001-0399
for the electrical connection to the life safety system notification appliance circuit.
& Relays
888D-N5 (120 Vac) 74339U (24 Vdc) Horn – 120 Vac Data Sheet K85001-0397
39
VS
SERIES
Notification Appliances
SUBMIT
Analog Control
VS Series
Door Holders
Electromagnetic Door Holders
Electromagnetic door holders keep doors open until signaled by the fire
alarm system, a heat detector, a smoke detector, or an electrical switch.
Door holders should be installed wherever doors may be effectively used to
confine smoke and fire, or where the release of a self-closing door from a
remote location is required. Fail-safe operation is an inherent feature of these
door holders. If power fails, doors are released automatically, but may be
24 Vac 60 Hz opened or closed manually at any time. All units are free of moving parts,
Initiating
Devices
24 Vdc are self-contained, and require no maintenance. Door holders have a holding
120 Vac 60 Hz force of approximately 15-25 Lbf (66-111N).
1501-AQN5 (Single Door) 1502-AQN5 (Double Door) Floor Mounted Data Sheet K85001-0421
1504-AQN5 (Long Catch Plate) 1505-AQN5 (Short Catch Plate) Flush Wall Mounted Data Sheet K85001-0421
1508-AQN5 (Surface) 1505-AQN9 (Completely flush) Wall Mounted Data Sheet K85001-0421
1500-1 (1.5” Extension) 1500-2 (2.5” Extension) Catch Plate Data Sheet K85001-0421
1500-7 (5.25 to 7.5” Extension) 1500-12 (7.5 to 12” Extension) Catch Plate Data Sheet K85001-0421
CS2595-5 (short) CS2598-5 (long) Replacement Armature Data Sheet K85001-0421
Notification
Appliances
Relays
Four-Voltage SPDT/DPDT Control Relays
MR Series multi-voltage control relays are ideal for applications where local contacts are
required for system status, remote contacts, or for control of electrical loads and general
purpose switching. They are suitable for use with HVAC temperature control, fire alarm, se-
curity, energy management, and lighting control systems. Relays provide 10-Amp contacts,
Hazardous Location
which may be operated by one of four input control voltages. Each relay position contains
a red LED that indicates the relay coil is energized. Relays may be snapped apart from a
standard four-module assembly and used independently.
Devices
MR101/T (with mounting hardware) MR101/C (in metal enclosure) Single SPDT relay Data Sheet K85300-02762
MR104/T (with mounting hardware) MR104/C (in metal enclosure) 4-position SPDT relay Data Sheet K85300-02762
MR201/T (with mounting hardware) MR201/C (in metal enclosure) Single DPDT relay Data Sheet K85300-02762
MR204/T (with mounting hardware) MR204/C (in metal enclosure) 4-position DPDT relay Data Sheet K85300-02762
MR199X13 (relay only) MR199X13/C (in metal enclosure) Power Relay — 24 VDC Data Sheet K85300-02766
MR199X14 (relay only) MR199X14/C (in metal enclosure) Power Relay — 120 VDC Data Sheet K85300-02766
40
VS
SERIES
Notification Appliances
SUBMIT
SPDT Relays
Single-pull/double-throw relays are ideal for applications where local or remote con-
tacts are required for control of electrical loads. They are suitable for use with HVAC,
temperature control, fire alarm, security, energy management, and lighting control
systems. Each relay position contains a high-intensity LED which, when illuminated,
indicates the relay coil is energized. Individual relay circuits may be snapped apart
from standard four- or eight-position modules, and are also available in a single-circuit
configuration. The common power to each relay position is bussed on the printed
wiring board, which permits power to be connected only once per multi-position
module.
PAM1 relays provide 10-Amp Form C contacts. The relay may be energized by one of three
input voltages: 24Vac, 24Vdc, or 115Vac. The PAM1 may be mounted with double-sided
adhesive tape, a self-tapping screw, or loosely placed in a backbox.
41
Value, efficiency, and a legacy
of fire protection innovation
When building owners and designers do business with Kidde, their
investment is underwritten by a 100-year history of dedication to the
fire alarm industry. That’s why today architects and engineers agree
that when it comes to protecting people and property, Kidde life safety
systems remain the technology of choice.