Professional Documents
Culture Documents
Ap Savesenergy
Ap Savesenergy
NON-ELECTRICAL
A UTO- PURG ER (NEAP)
0 Low costand very simple
0 Typically usedfor a singlepurge point
0 Idealfor small systemsup to 100tons(350kW)
nominal capacity
0 Completelya nonelectricdesign
0 Especiallysuited for installation in hazardous
atmospheres
0 Fully automatic
0 Weldedpipe construction
0 Prepipedand assembled
(shownwith optional valve package) 0 Functionallytested
3
To calculate the approximate annual savings
that can be realized by installing an AUTO-PURGER,
use the formula at the left. Simply enter the values
and complete the computation. To determine the
condensing pressure of pure refrigerant, refer to a
pressure-temperature chart for the refrigerant used.
An ammonia pressure-temperatUrechart is on page 7.
To determine the excesspressure due to air, refer to
the explanation and examples on page 7.
US Customary
The conditions for this example are:
Refrigerant: ammonia
Suction temperature: OaF
Condensing temperature: 86°F
Excesspressure due to air (Pa): 17 psi
Pure refrigerant condensing pressure (Pd): 169.2psia
System capacity (C): 1500 tons
Energy consumption factor (H): .80
Hours of run-time per year (T): 6500hours
Electric rate per kilowatt-hour (M): .06 dollars
17 psi
x 1500tons x .80 x 6500 hours x $.06/kW-hr
169.2 psia
= $47,O20/year
Metric
The conditions for this example are:
Refrigerant: ammonia
Suction temperature: -30°C
Condensing temperature: 30°C
Excesspressure due to air (Pa): 1.2 bar
Pure refrigerant condensing pressure (Pd): 11.6bar
System capacity (C): 5300kW
Energy consumption factor (H): .32
Hours of run-time per year (T): 6000hours
Electric rate per kilowatt-hour (M): .08 dollars
1.2 bar
x 5300 kW x .32 x 6000 hours x $.08/kW-hr
11.6bar
Note: Thesefactors are calculated at 86~ and 30OC
= $84,212/year
condensing temperature.
5
Condensing pressure and
purger operation Q)
... Above I
~
AUTO-PURGERs
remove more air and over a In Pn~ssu "e
In
shorter period of time than other purging methods Q)
...
D..
or units to maintain the minimum possible con- C)
c
densingpressure.A refrigerationsystemwithout a ,
'In
c
purger or with an inadequatepurger may allow ~Q)
"'C
C
fluctuations in condensing pressure or may not be 0
able to maintain the minimum possiblecondensing '.u:
C1)
~
~ Above Desi~ri
(/)
Air can enter a system in a number of ways. For (/) Priessure
C1)
~
systems operating in a vacuum, leaky gaskets and C-
O')
shaft seals allow air into the system. Other common C
(/)
ways for air to enter are during repairs and service, C
C1)
when adding refrigerant to the system, and through "'0
C
the chemical breakdown of refrigerant. Also, lubri- 0
(,)
cating oils can breakdown under heat and high
Time ~.
pressure to create noncondensible gases.
Pressureprofiles for a system with an AUTO-PURGER
versus manual purging and the same system with an
AUTO-PURGER versus an inadequate purger.
Where does air collect?
Air collects at various locations on the high-
pressure side of the system. These locations are
typically the lowest gas velocity and coolest tem-
perature areas.High-pressure condensers, receivers,
and heat reclaim heat exchangers are all likely
locations where air will collect.
Air as an insulator
Air tends to act as insulation in refrigeration
systems.A layer of air forms a blanket on the walls
of the condensing surface, preventing refrigerant
from making contact with the lower-temperature
heat exchanger surface. This results in greatly
Air acts as an insulator between the refrigerant and the
reduced system efficiency. cooling surface,greatly reducing condensing efficiency.
6 . ..
How do I know how much air is
in the system?
180 psig The presence of air in a refrigeration system is
indicated by excessively high head pressure. This
may be indicated by a pressure gauge or by system
I compressors shutting down due to the high pres-
/
/
sure. The amount of air in a system can also be
measured by comparing the actual condensing
pressure to the condensing pressure of pure refrig-
erant at a given temperature. Refer to the following
Measuring the excesspressure in a refrigeration system. examples using ammonia as the refrigerant.
Metric US Customary
Temperature at the Temperature at the
outlet of the condenser: 32°C outlet of the condenser: 89°F
Pressure at the Pressure at the
outlet of the condenser: 12.8bar or 13.8bar absolute outlet of the condenser: 180 psig or 194.7psia
Pressure of pure ammonia at 32°C: 12.3 bar absolute Pressure of pure ammonia at 89°P: 177.7psia
Excesspressure: 13.8bar - 12.3bar = 1.5 bar Excesspressure: 194.7psia -177.7 psia = 17 psi
Saturation pressure-temperature charts for pure ammonia (no air). *absolute pressure
7
It is difficult to determine where air will collect
in a system. There are typically several likely collec-
tion points. Multiple factors influence where air will
collect. The number of condensers and receivers,
condenser piping design, and component arrange-
ment and operation all affect the location of air.
Multipoint purging.
Why not just open all purge points at the same To AUTO-PURGER
time?If this is done,air is removedfrom only one of (lower pressure)
the points. Eventhough the pressuredifference ~
effectively removed from throughout the entire When multiple purge points are open simultaneously, air
refrigeration system. is purgedfrom only the point with the highest pressure.
8
Gas velocity is too high at the
inlet to allow air to collect \
Purge points should be installed at the most
Inlet likely locations where air will collect. In general,
these points are at the lowest-temperature, lowest-
velocity areas of high-pressure receivers, condens-
lAir ers, and other high-pressure components.
Purge point location for an evaporative condenser. Evaporative condensers should be purged from
the top of the outlet header of each circuit. Manu-
facturers often provide a connection at this location
for a purge point. A trap should be installed in the
condenser drain leg. This creates a liquid seal to
trap air at the outlet of the condenser and prevent it
from migrating to the receivers.
9
AUTO-PURGER AP
Shown at the right is an AUTO-PURGER AP
installed in a typical large industrial refrigeration
system. The piping arrangement shown is typical
high-side piping for two dual-circuit condensers
and a receiver.
10
NON-ELECTRICAL
AUTO-PURGER (NEAP)
Shown at the right is a Non-Electrical
Selecting an AUTO-PURGER
Severalfactorsareinvolved in selectingthe
a System size? correctAUTO-PURGERfor an application.First, the
a Suction above or in a vacuum? systemsizeneedsto be considered.In general,for a
Above vacuum (nominal capacity): systemwith a high potential for air entry,suchas
a AUTO-PURGER AP one with suctionin a vacuum or frequently opened
1500 tons (5300 kW) for repairs,the purger capacitymust be derated.For
a AUTO-PURGER APM example,the AUTO-PURGERAP is suitedfor sys-
200 tons (700 k W) ternsup to 1500tons (5300kW) with suction above
a Non-Electrical AUTO-PURGER vacuum.For systemswith suction in a vacuum,the
100 tons (350 kW) NEAP AP is suited for systemsup to 750tons (2600kW).
In a vacuum (nominal capacity):
a AUTO-PURGER AP In addition, the total number of purge points
750 tons (2600k W) must be considered.TheAUTO-PURGERAP is
a AUTO-PURGER APM suited for up to 24 purge points, the APM for up to
100 tons (350 kW) four purge poirits, and the NEAP is typically used
a Non-Electrical AUTO-PURGER to purge a singlepoint.
75 tons (265 k W) NEAP If nonelectric control is required, such as for
0 Number of purge points? hazardous atmospheres, the model NEAP should be
installed. The simple, nonelectric design of the
0 Electronic or nonelectric control?
NEAP also makes it ideal for installation in geo-
0 Hazardous atmosphere installation? graphically-remote locations.
11
All AUTO-PURGERs are designed for use with tioning system on the foul gas and liquid lines. The
ammonia refrigerant. In addition, Model APF is a filter-dryer system removes water from the refriger-
variation of the AUTO-PURGER AP designed ant beforeit entersthe purger.This preventsfreeze-
specifically for use with halocarbon refrigerants. up at the expansion device, but also supplements
The APF comes complete with a filter-dryer condi- the water removal of the system's main filter-dryers.
T' CORPORATION
6827 High Grove Boulevard
Burr Ridge, It 60521USA
Phone: 630-325-1565
Toll-free (US and Canada): 800-426-7368
Fax: 630-325-1572
E-mail: info@hantech.com
Web site: www.hantech.com