COMMENT
SN CLAUSE USACE COMMENTS CONTRACTOR’S COMPLIANCE
STATUS
The Submitted compliance statement indicated a lot of non compliant
1 33 11 00 statement, contractor to verify and comply as required by the contract Revised Compliance statement attached in Section-13 of this MAS. Complied
requirement.
All related fire submittals shall be reviewed and stamped by the Noted. Fire Related submittals are reviewed and stamped by the
2 33 11 00 Complied
Contractor’s Fire Protection Engineer. contractor’s Fire Protection Engineer.
TABLE OF CONTENTS
1. Company Profile
4. ISO certificates
15. Drawing(s)
16. Specification(s)
1.Company Profile
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
SUPPLIER PROFILE
WE’VE EARNED QATAR’S TRUST
MILESTONES
MAINTENANCE
SECURITY
TRADING
SERVICE
VASS VASS VASS VASS VASS
Contracting Maintenance Service Trading Security
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
MANUFACTURER
PROFILE
Viking Group, Inc.
Company Profile
EXECUTIVE SUMMARY
Founded in 1920, Viking Group, Inc. is an industry leading manufacturer and distributor of
fire sprinklers and related products for fixed fire protection systems. Viking offers total fire
suppression solutions by providing its manufactured products and related third party products
along with value-added services such as fabrication, pre-assembly, product training, and
technical assistance. Viking’s products, which include both water and non-water based fixed
fire suppression systems, are installed in commercial, industrial, storage, office, institutional,
and residential properties around the world.
Viking Group is comprised of five primary business units; Viking Corporation, Viking
SupplyNet, Viking SupplyNet International, Viking Fabrication Services, and Viking Plastics.
Viking Corporation manufactures fire sprinklers, fire system valves, and related devices.
Viking SupplyNet distributes Viking Corp. manufactured products and third party products to
over 3,000 fire sprinkler contractors in the United States and an additional 3,000 fire
contractors internationally in over 80 countries. Viking Fabrication Services provides
customized, pre-fabricated steel piping systems according to fire contractor specifications,
saving the contractor from having to source, cut, thread, weld, and package steel piping
systems in-house. Finally, Viking Plastics was formed in 2007 to manufacture CPVC plastic
sprinkler piping to capitalize on the growing residential sprinkler market and the associated
need for CPVC products.
Combined, the companies of The Viking Group provide customers with the following
advantages:
Quality: Our reputation for quality has been earned over decades by focusing on
continuous improvement in all elements of our business – from the products we
manufacture to the services we provide.
Breadth: The largest selection of fire protection products and services ensures single-
point solutions for any fire protection challenge.
Support: The companies of The Viking Group are dedicated exclusively to fire
protection. Knowledgeable and experienced customer service and technical support
is provided at every point in the project process.
Innovation: From valves that are easier to install and maintain, to automated
fabrication capabilities, Viking's product innovations have been developed by a
thorough understanding of the needs of our customers.
Viking Group’s primary goal is to enhance and support the efforts of the fire sprinkler
contractor. Viking’s commitment to quality, service, and innovation means fewer problems
and more cost-effective solutions for both the installers and end users of fire suppression
systems worldwide.
MISSION AND STRATEGY
Mission Statement
To design, manufacture and distribute fire protection products and services which meet or
exceed our customers' expectations, and safeguard people and property worldwide from the
devastating effects of fire.
Strategy Statement
Service the critical needs of the fire services sub-contractor and the building owner in the
construction markets of the world. This service takes the form of a set of high quality,
innovative products and services which enhance the contractor’s ability to profitably compete
and which provides the owner with lasting value.
Strategic Concepts
A focus on customer and market needs is consistent with the delivery of our Mission. It is the
Company’s ongoing responsibility to survey the market to determine what the independent
contractor needs to thrive in the future, and provide it.
These products and services must be of the finest quality available to the marketplace, and
the delivery of them must correspond to the highest service level available.
To achieve these key concepts, the company will seek to develop its people to reach their
highest level of competence, and maintain a strong capital structure in order to invest in new
opportunities as they become apparent.
Markets Served
The Company’s products are installed in the widest range of construction. The major
markets are identified as follows:
COMPANY HISTORY
The Viking Group traces its roots back to the 1880s when Emil Tyden, a
Swedish immigrant, developed an innovative railroad car seal in Chicago.
In the late 1890s, Tyden was introduced to a businessman in Michigan who
convinced him to move to Hastings and found the International Seal & Lock
Company to manufacture the patented seals. To produce his boxcar seal in
mass, Tyden went on to create one of the world's first automation systems
– fully a decade before Henry Ford mass-produced automobiles.
Around 1920, after a fire destroyed the factory at the International Seal and
Lock Company, Tyden resolved to enter the fire sprinkler business.
Through a mutual friend, Tyden was introduced to a St. Louis businessman
who claimed to have developed some designs for fire sprinklers and valves.
A short time later, after it was apparent that the business was in trouble,
Tyden bought 100% interest in The Viking Corporation and began
manufacturing fire sprinklers and valves in Hastings.
The rapid growth of the fire sprinkler market in the mid 1970s caused Viking to establish a
network of affiliates who could properly service the market with Viking products as well as
other components necessary for sprinkler installations. By the mid-to late-1980s, Viking
divested itself of all contracting and design interests and focused on the development,
manufacture, and distribution of fire sprinklers, valves, and devices.
By the early 1990s, Viking SupplyNet was established as the sole distributor of Viking
products, as well as related fire protection components. Viking SupplyNet International was
also developed to build a strong international presence. Worldwide, Viking SupplyNet is now
represented by over 50 wholly owned locations as well as a large network of independent
distributors.
In 2002, Viking Group, Inc. launched Viking Fabrication Services to offer contractors
complete fabrication services for steel pipe, the largest component for most sprinkler
systems. And, in 2007, Viking Group expanded again with the formation of Viking Plastics.
Viking Plastics manufactures high-quality CPVC plastic sprinkler pipe used in residential and
certain light hazard properties.
Today, the companies of the Viking Group provide independent fire sprinkler contractors with
integrated solutions for any fire protection challenge. Our commitment to quality, service, and
innovation means fewer problems and better, more cost-effective solutions for fire sprinkler
contractors.
COMPANY STRUCTURE
The Viking Group is a holding company with five major subsidiaries. Employees work for
either one of the subsidiaries or Viking Group itself. Viking Group employees provide
services to subsidiary companies, including Finance, Information Technology, Marketing,
Human Resources, Supply Chain, and Executive Leadership.
Viking
Group
Viking
Viking Viking
SupplyNet
Corporation SupplyNet
International
Viking
Viking
Fabrication
Plastics
Services
Viking Corporation
As the manufacturing entity of The Viking Group, Viking Corporation manufactures the fire
sprinklers, valves, and devices sold around the world. At its primary location in Hastings,
Michigan it also conducts research and development activities in an advanced hydraulics
laboratory and in two fire test buildings. This is essential for obtaining the product approvals
important to the industry, including Underwriter’s Laboratories, Factory Mutual Global, and a
host of international approvals.
Viking products are thoroughly tested, listed, and approved by the most recognized
independent laboratories in the world, including the following:
Viking has the finest reputation for product quality in the field. This stems from a deep
competency in manufacturing. Viking Corporation is believed to be more vertically integrated
than its competitors, possessing machining, stamping, assembly, soldering and testing
operations. The majority of its sales go through Viking SupplyNet distribution centers, with
the remainder through independent distributors.
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
2. License(s) of
Manufacturer
or Agent
Issue Date:
Page No: 1
*38572*
Issue Date: 26/02/2020
Partners
Page 1 of 2
CR No : 38572
ﺗﺸﻬﺪ ﻏﺮﻓﺔ ﺗﺠﺎﺭﺓ ﻭﺻﻨﺎﻋﺔ ﻗﻄﺮ ﺑﺄﻥ ﺍﻟﻤﻨﺸﺎﺓ ﺍﻟﻤﺬﻛﻮﺭﺓ ﺍﻋﻼﻩ ﺳﺠﻠﺖ ﻟﺪﻳﻨﺎ
Qatar Chamber certifies that the above mentioned establishment has been registered
Issue Date:
Page No: 1
Authority
Manager - Administrative
SALAH SULTAN M J AL-JABER 26663400955 QATAR
Authority (Passports)
Manager - Full and Absolute
OSAMA RIDA HADID 25699900054 CANADA
Authority
Manager - Administrative
SALAH SULTAN M J AL-JABER 26663400955 QATAR
Authority (Labor)
Manager - Full and Absolute
HEMAL PRADIP SALOT 27735614704 INDIA
Authority
Business Activities
Page 2 of 2
CR No : 38572
ﺗﺸﻬﺪ ﻏﺮﻓﺔ ﺗﺠﺎﺭﺓ ﻭﺻﻨﺎﻋﺔ ﻗﻄﺮ ﺑﺄﻥ ﺍﻟﻤﻨﺸﺎﺓ ﺍﻟﻤﺬﻛﻮﺭﺓ ﺍﻋﻼﻩ ﺳﺠﻠﺖ ﻟﺪﻳﻨﺎ
Qatar Chamber certifies that the above mentioned establishment has been registered
<Bar Code>
2020/03/04
Z[ $ [\ $
!
%&$'(&#(%" !
"#$"% !
%&%$(&'($; !
9:. ,-./ 0
1 2
3 45 6
7 ) *+
8/
#@;A% ) 6
7 <=8, >?.
,
D?* E
2 B,F B?C,
, *
8: B?C,
, 8I %AA#;"$'A&' DGH
@& L 4 J?, K8!
$ N? ( 4 EM J?, >?.
2 *8F 6
7 L3 P * E13G I "O L8,
!
>?. *? >=
R3- >
5 Q?83 K $&% >=
!"
TIN: 000002732335583 000002732335583 ﺍﻟﺮﻗﻢ ﺍﻟﻀﺮﻳﺒﻲ
Taxpayer's Name: Vijay Arabia Fire & Security Systems ﺷﺮﻛﺔ ﻓﻴﺠﺎﻱ ﺍﻟﻌﺮﺑﻴﺔ ﻟﻠﺤﺮﻳﻖ ﻭﺍﻻﻧﻈﻤﺔ ﺍﻻﻣﻨﻴﺔ:ﺍﺳﻢ ﺍﻟﻤﻜﻠﻒ
Legal Form: Limited Liability Company ﺷﺮﻛﺔ ﺫﺍﺕ ﻣﺴﺆﻭﻟﻴﺔ ﻣﺤﺪﻭﺩﺓ:ﺍﻟﺸﻜﻞ ﺍﻟﻘﺎﻧﻮﻧﻲ
P.O. Box (28666) ﺏ. ﺹ- Fax (44461288) ﻓﺎﻛﺲ- Tel (44461444) ﺗﻠﻴﻔﻮﻥ
www.tasportal.mof.gov.qa ﺍﻟﻤﻮﻗﻊ ﺍﻻﻟﻜﺘﺮﻭﻧﻲ-taxpayer.services@gta.gov.qa ﺍﻟﺒﺮﻳﺪ ﺍﻻﻟﻜﺘﺮﻭﻧﻲ
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
3. Appointment
Letter of
Local Agent
September 25, 2020
Thisis to certify that company Vijay Arabia Fire and Security Systems W,LL, Post Box number
31145, Doha, qatar , is a VikingS.A's authorized non- exclusive distributor for fire - fighting
water-based products, foam based products and systems and forthe Viking's brand
"Fireking " line of hydrants, gate valves, check valves, butterfly valves PIF valves and strainers.
Sincerely,
g-
Divakaran
Manager
Viking Mi
4. ISO
Certificates
Awarded to
Quality Registrar Systems certify that the management system of the above
organization has been audited and found to be in compliance with the QRS
requirements for registration of the management system standard detailed
below:
Scope of work
EA 28
Certificate No: AQQ-10159
Originally Registered : 20 OCT 2015
Latest Issue: 15 SEP 2019
Valid up-to: 19 OCT 2020
ASCB(E
Accrediting
c~~~7~;.g
ISO 9001:2015
Quality Management Systems - Requirements
are certified by BRE Global Ltd. and are authorised to use the LPCB Certification Mark on stationery
and publications related to the products and/or services listed in the attached Appendix:
This certificate and appendix is maintained and held in force through regular surveillance activities.
This certificate and appendix remains the property of BRE Global Ltd. and is issued
subject to terms and conditions (for details visit www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR tag or contact us.
BRE Global Ltd, Watford, WD25 9XX
T: +44 (0)333 321 8811 E: enquiries@breglobal.com
LPCB is a Registered Trademark of the Building Research Establishment Ltd.
Company Scope
The Vikings Corportation Manufacture of fire sprinkers and related products for fire
11305 James Street sprinker systems.
Holland
Michigan 49424
USA
The Vikings Corportation Manufacture of fire sprinkers and related products for fire
4757 128th Avenue sprinker systems.
Holland
Michigan 49424
USA
This certificate and appendix is maintained and held in force through regular surveillance activities.
This certificate and appendix remains the property of BRE Global Ltd. and is issued
subject to terms and conditions (for details visit www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR tag or contact us.
BRE Global Ltd, Watford, WD25 9XX
T: +44 (0)333 321 8811 E: enquiries@breglobal.com
LPCB is a Registered Trademark of the Building Research Establishment Ltd.
5. Brochure with
Applicable
Materials
Post Indicator Valve - Flanged
PIF & PIF2
Control Valves
Technical Features
• Sizes available (Nominal) : 2”/DN50, 2½”/DN65,
3”/DN80, 4”/DN100, 5”/DN125, 6”/DN150,
8”/DN200, 10”/DN250 and 12”/DN300
• Working pressure : 21 bar (300 psi)
• Seat type : Resilient wedge
• Finish : Fusion bonded epoxy coated internal & external
• Connections : Flange diameter and thickness according
to ANSI B16.1 Class 125, EN1092-2 PN10 or EN1092-2
PN16
• Specifications : Design and dimensions conform to
AWWA C515
• Operation : For use with IPV or IPW indicator posts
• Remark : No post flange supplied with 2”, 2½” & 3”,
and size 2” is FM approved only and size 5” is UL listed
only * Image depicts 4”-14” sizes, 2”-3” not supplied
with Post Plate
Datasheet updates the datashet of 30-11-2015 (revised L dimension for 12” valve)
6” DN150 267 475 279 19.1 241.3 240 8-Ø22.2 8-Ø23 PIF-0600 54.2
8” DN200 292 585 343 22.2 298.5 295 8-Ø22.2 12-Ø23 8-Ø23 PIF-0800 PIF-0800PN10 PIF-0800PN16 86.1
10” DN250 330 656 406 23.8 362.0 355 350 12-Ø25.4 12-Ø28 12-Ø23 PIF-1000 PIF-1000PN10 PIF-1000PN16 117.2
12” DN300 356 751 483 25.4 431.8 410 400 12-Ø25.4 12-Ø28 12-Ø23 PIF-1200 PIF-1200PN10 PIF-1200PN16 180.0
* FM Approved only ** UL Listed only *** No post plate - flange supplied , UL Listed as PIF2, **** Valve flange drilling (size and location of bolt holes and pitch circle diameter) allows mating with the
following flange types :
ANSI = ANSI B16.1 Class 125 PN10 = DIN 2501, BS 4504, EN 1092 - PN10 PN16 = DIN 2501, BS 4504, EN 1092 - PN16
9 Square Operating Nut Ductile Iron ASTM A536 64-45-12 20 Wedge Nut Brass Hpb59-1
10 Bolt Carbon Steel Zinc Plated 21 Plug Bronze ASTM B584 C89833
11 Flat Washer Carbon Steel Zinc Plated
FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
Vertical Indicator Post
IPV
Indicator Posts
IPV - Vertical Indicator Post Physical Data
Dimensions (mm/inch) Weight
Reference
A B C D E F (kg)
IVP 1270 1006 759.5 292 190 305 98.7
FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
MVB composite Valve Box
Reliable
ReliableConnections
Connections
TM
TM
Product Features
• Bevelled edge Ductile Iron Adjustable • Easily cuts to required length with
Top available in 2 sizes – 12” (305mm) ordinary hand tools.
and 27” (686mm). • Impact-resistant, corrosion-proof polymer
• Tops are self-leveling and self-adjusting. lower section.
WATER
• Light weight – no special heavy
equipment required to install.
BEFORE Cover
WATER WATER
Top
Top Top
parts list
ID Part Name Material
1 T-Wrench* 2–7 Ft. (see Note 1) Cast Iron
2 MVB Extension Stem* 2–12 Ft. (see Note 1) Ductile Iron
3 Beveled Adjustable Top Ductile Iron
4 MVB Bottom Section Non-abrasive Polymer
5 Lid Cast Iron
6 Cover Cast Iron
www.viking-emea.com
FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
6. Certificate
Letter of Origin
E
PL
M
SA
Page 37
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
7. Manufacturer
Data Sheet
MATERIAL SCHEDULE‐ EXTERNAL VALVES & ABOVE GROUND HYDRANT
2 NRS Gate Valve with Valve Composite Box
NRS Gate Valve, EN1092‐2 PN16,
2.1 PIF Fireking by Viking USA
working pressure 21 Bar, Flanged
2.2 Valve Composite Box with T Wrench Custom Made VASS Qatar
3. Above ground Hydrant Valve with Instantaneous Coupling
Above ground Dry Barrel Fire Hydrant,
Fire King by
3.1 6” /DN150 Flanged with Instantaneous HYF3 USA
Viking
Coupling, Cap & Chain
NRS Gate Valve with Indicator Post Assembly
Post Indicator Valve - Flanged
PIF & PIF2
Control Valves
Technical Features
• Sizes available (Nominal) : 2”/DN50, 2½”/DN65,
3”/DN80, 4”/DN100, 5”/DN125, 6”/DN150,
8”/DN200, 10”/DN250 and 12”/DN300
• Working pressure : 21 bar (300 psi)
• Seat type : Resilient wedge
• Finish : Fusion bonded epoxy coated internal & external
• Connections : Flange diameter and thickness according
to ANSI B16.1 Class 125, EN1092-2 PN10 or EN1092-2
PN16
• Specifications : Design and dimensions conform to
AWWA C515
• Operation : For use with IPV or IPW indicator posts
• Remark : No post flange supplied with 2”, 2½” & 3”,
and size 2” is FM approved only and size 5” is UL listed
only * Image depicts 4”-14” sizes, 2”-3” not supplied
with Post Plate
Datasheet updates the datashet of 30-11-2015 (revised L dimension for 12” valve)
6” DN150 267 475 279 19.1 241.3 240 8-Ø22.2 8-Ø23 PIF-0600 54.2
8” DN200 292 585 343 22.2 298.5 295 8-Ø22.2 12-Ø23 8-Ø23 PIF-0800 PIF-0800PN10 PIF-0800PN16 86.1
10” DN250 330 656 406 23.8 362.0 355 350 12-Ø25.4 12-Ø28 12-Ø23 PIF-1000 PIF-1000PN10 PIF-1000PN16 117.2
12” DN300 356 751 483 25.4 431.8 410 400 12-Ø25.4 12-Ø28 12-Ø23 PIF-1200 PIF-1200PN10 PIF-1200PN16 180.0
* FM Approved only ** UL Listed only *** No post plate - flange supplied , UL Listed as PIF2, **** Valve flange drilling (size and location of bolt holes and pitch circle diameter) allows mating with the
following flange types :
ANSI = ANSI B16.1 Class 125 PN10 = DIN 2501, BS 4504, EN 1092 - PN10 PN16 = DIN 2501, BS 4504, EN 1092 - PN16
9 Square Operating Nut Ductile Iron ASTM A536 64-45-12 20 Wedge Nut Brass Hpb59-1
10 Bolt Carbon Steel Zinc Plated 21 Plug Bronze ASTM B584 C89833
11 Flat Washer Carbon Steel Zinc Plated
FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
Post Indicator Valve - Flanged
PIF & PIF2
Control Valves
Installation Inspection and Maintenance
1. Piping systems and valves should be 1. Valves should be inspected periodically and
thoroughly cleaned and free from ingress of should be cycled to prevent buildup of foreign
foreign materials. materials in the piping system and valve body.
2. Visually inspect the valve seating and
ports for cleanliness immediately prior to
installation.
3. All valves should be independently supported
against movement and stress from the
connected piping system.
4. Ensure that the valve pressure rating is
compatible with service conditions.
5. Operate the valve at least once from the
open to closed position.
6. Gate valves are not suitable for throttling
applications.
7. Gate valves should be installed in the vertical
position on horizontal pipework and in the
horizontal position on vertical pipework.
8. See indicator post datashet for further
installation instructions.
Operation
Gate valves are manually operated multi-turn
valves and are opened by a handwheel or
other operating device, generally in a counter
Datasheet updates the datashet of 30-11-2015 (revised L dimension for 12” valve)
clockwise direction and then closed clockwise.
13-07-2016
FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
Vertical Indicator Post
IPV
Indicator Posts
IPV - Vertical Indicator Post Physical Data
Dimensions (mm/inch) Weight
Reference
A B C D E F (kg)
IVP 1270 1006 759.5 292 190 305 98.7
FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
Vertical Indicator Post
IPV
Indicator Posts
Installation of the Target Carrier Assembly. Locate the two
“Shut” Targets according to the size of the post
NOTE: Ensure that the post indicator valve is in indicator valve size (stem) turning distance.
the fully open position before installing the Vertical - If the post indicator valve is opened by turning
Indicator Post. the handwheel clockwise:
1.) Disassemble the Indicator Post Move the two “Shut” Targets to the very top of
Take off the Locking Wrench (11), loosen the two the Target Carrier Assembly (12, 13 & 14). Locate
Hex bolt (24) and Square Nut (23) and remove the the two “Open” Targets (16) according to the size
Top Section (20), operating nut assembly and the of the post indicator valve (stem) turning distance.
Square Stem (9) as well as the socket (3). Slide off 6.) Final Assembly and Test
the Body (10) from the Standpipe (8) by loosening Insert the Target Carrier Assembly (12, 13 &
the two Hex Bolts (6) and Hex Nuts (7), slide off the 14) back into the Top Section (20) by rotating
Standpipe (8) from the Base Flange (5). the Operating Nut (19) clockwise. Rotate the
2.) Install the Base Flange and Lower Operating Nut (19) until the “Open” Target (16) is
Standpipe centered in the window of the Body (10). Lower
Attach the Base Flange (5) together with the the Top Section (20) with the Target Carrier
Standpipe (8) to the Post Flange of the post Assembly (12, 13 & 14) onto the Body (10),
indicator valve using the four Hex nuts (1) and Hex carefully ensuring that the Stem (9) engages with
bolts (2). Fix the Standpipe (8) to the Base Flange the Operating Nut (19) at least 50mm (2 in) but
(5) using the Hex Bolt (6) and Hex Nut (7). not more than 120mm (4.5 in). Secure the Top
Section (20) to the Body (10) by tightening the
3.) Adjust the Ground Line Mark
hex bolt (24) and Square Nut (23). Close the post
Pull the Body (10) over the Standpipe (8) until the
indicator valve and check to make sure that the
Ground Line Mark on the Body (10) is the same
“Shut” Target is properly centered in the window
height as the ground level. Tighten the two Hex
of the Body (10) and adjust as necessary.
Nuts (6) and Hex Bolts (7).
4.) Adjust the Square Stem
Lower the Stem (9) into the Body (10) such that the
socket (3) fits over the operating nut of the post Maintenance
indicator valve.
Ensure that Stem (9) engages the Operating Nut Lubrication
(19) a minimum of 2” but no more than 4.5”. To Oil the bearing in the Top Section (20) at least once
check for correct engagement, the end of stem a year by adding several drops of oil in the hole
should be 2 to 4 inches below the top of the Body located on the top of the Operating Nut (19).
(10).
5.) Adjust the Targets
Remove the Target Carrier Assembly (12, 13 & 14)
from inside the Body (10) by rotating the Operating
Nut (19) counter-clockwise. The “Open” Target (16)
and “Shut” Target (16) are adjusted up and down
on the Target Carrier Assembly (12, 13 & 14) by
pulling the middle section of the Target (Open &
Shut) a small distance away from the Target Carrier
Datasheet Created
FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
NRS Gate Valve with Valve Composite Box
Post Indicator Valve - Flanged
PIF & PIF2
Control Valves
Technical Features
• Sizes available (Nominal) : 2”/DN50, 2½”/DN65,
3”/DN80, 4”/DN100, 5”/DN125, 6”/DN150,
8”/DN200, 10”/DN250 and 12”/DN300
• Working pressure : 21 bar (300 psi)
• Seat type : Resilient wedge
• Finish : Fusion bonded epoxy coated internal & external
• Connections : Flange diameter and thickness according
to ANSI B16.1 Class 125, EN1092-2 PN10 or EN1092-2
PN16
• Specifications : Design and dimensions conform to
AWWA C515
• Operation : For use with IPV or IPW indicator posts
• Remark : No post flange supplied with 2”, 2½” & 3”,
and size 2” is FM approved only and size 5” is UL listed
only * Image depicts 4”-14” sizes, 2”-3” not supplied
with Post Plate
Datasheet updates the datashet of 30-11-2015 (revised L dimension for 12” valve)
6” DN150 267 475 279 19.1 241.3 240 8-Ø22.2 8-Ø23 PIF-0600 54.2
8” DN200 292 585 343 22.2 298.5 295 8-Ø22.2 12-Ø23 8-Ø23 PIF-0800 PIF-0800PN10 PIF-0800PN16 86.1
10” DN250 330 656 406 23.8 362.0 355 350 12-Ø25.4 12-Ø28 12-Ø23 PIF-1000 PIF-1000PN10 PIF-1000PN16 117.2
12” DN300 356 751 483 25.4 431.8 410 400 12-Ø25.4 12-Ø28 12-Ø23 PIF-1200 PIF-1200PN10 PIF-1200PN16 180.0
* FM Approved only ** UL Listed only *** No post plate - flange supplied , UL Listed as PIF2, **** Valve flange drilling (size and location of bolt holes and pitch circle diameter) allows mating with the
following flange types :
ANSI = ANSI B16.1 Class 125 PN10 = DIN 2501, BS 4504, EN 1092 - PN10 PN16 = DIN 2501, BS 4504, EN 1092 - PN16
9 Square Operating Nut Ductile Iron ASTM A536 64-45-12 20 Wedge Nut Brass Hpb59-1
10 Bolt Carbon Steel Zinc Plated 21 Plug Bronze ASTM B584 C89833
11 Flat Washer Carbon Steel Zinc Plated
FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
Post Indicator Valve - Flanged
PIF & PIF2
Control Valves
Installation Inspection and Maintenance
1. Piping systems and valves should be 1. Valves should be inspected periodically and
thoroughly cleaned and free from ingress of should be cycled to prevent buildup of foreign
foreign materials. materials in the piping system and valve body.
2. Visually inspect the valve seating and
ports for cleanliness immediately prior to
installation.
3. All valves should be independently supported
against movement and stress from the
connected piping system.
4. Ensure that the valve pressure rating is
compatible with service conditions.
5. Operate the valve at least once from the
open to closed position.
6. Gate valves are not suitable for throttling
applications.
7. Gate valves should be installed in the vertical
position on horizontal pipework and in the
horizontal position on vertical pipework.
8. See indicator post datashet for further
installation instructions.
Operation
Gate valves are manually operated multi-turn
valves and are opened by a handwheel or
other operating device, generally in a counter
Datasheet updates the datashet of 30-11-2015 (revised L dimension for 12” valve)
clockwise direction and then closed clockwise.
13-07-2016
FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
MVB composite Valve Box
Reliable
ReliableConnections
Connections
TM
TM
Product Features
• Bevelled edge Ductile Iron Adjustable • Easily cuts to required length with
Top available in 2 sizes – 12” (305mm) ordinary hand tools.
and 27” (686mm). • Impact-resistant, corrosion-proof polymer
• Tops are self-leveling and self-adjusting. lower section.
WATER
• Light weight – no special heavy
equipment required to install.
BEFORE Cover
WATER WATER
Top
Top Top
parts list
ID Part Name Material
1 T-Wrench* 2–7 Ft. (see Note 1) Cast Iron
2 MVB Extension Stem* 2–12 Ft. (see Note 1) Ductile Iron
3 Beveled Adjustable Top Ductile Iron
4 MVB Bottom Section Non-abrasive Polymer
5 Lid Cast Iron
6 Cover Cast Iron
MVB
234133 8’ Extension Stem w/2” Operating Nut and 2” Socket
Bottom 234168 10’ Extension Stem w/2” Operating Nut and 2” Socket
Section
234184 12’ Extension Stem w/2” Operating Nut and 2” Socket
B NOTE: Stem Should be 1’ Shorter then Box
J
composite – with 12” Adjustable Top ®
B
corrosion resistance
• Finish: Red & black epoxy paint
Interior & exterior to AWWA C550
• Connections:
HYF2 & 5 - 4”/DN100 Flange PN16/ANSI
HYF3 & 4 - 6”/DN150 Flange PN16/ANSI
• Water Use: Non-potable water only
• Collision: Model HYF4 & HYF5 designed to maintain seal
should the hydrant suffer a collision
• 1 x Pumper Outlet:
HYF2 & 3 - 4” NH/Storz/BSRT
L
HYF4 & 5 - 4” UNE/AR/Storz
• 2 x Hose Outlet:
HYF2 & 3 - 2-1/2” NH/Storz/BS336
HYF4 & 5 - 2-1/2” UNE/DSP/Storz
• Approvals: LPCB
• Specification: EN14384
• Note: All hydrants include automatic drain to drain down
the barrel after closing the hydrant - this minimises the risk
A
of damage from freezing
www.viking-emea.com
FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
Fire Hydrant
HYF2-5 Dry Barrel Fire Hydrant
www.viking-emea.com
FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
Fire Hydrant
HYF2-5 Dry Barrel Fire Hydrant
Installation
1. Hydrants should be handled with care to avoid damage. It is recommended to keep hydrants closed until use.
2. If the hydrant is not to be used straight away then it is recommended to coat threads and other machined parts with
an anti-rust oil and the hydrant should be stored in a dry and ventilated area. For long-term storage, the hydrant
should be checked regularly.
3. Before installation of hydrants, the connection should be free from dirt or other matter.
4. The positioning of the hydrant should be in accordance with local requirements. Ideally the pumper should face the
street and all connections should be away from any obstruction to connecting hoses.
5. The inlet elbow should be placed on a solid surface and if possible brace the side opposite the incoming flow to
reduce reaction stresses.
6. The underground parts of the hydrant should be surrounded with coarse gravel for support and drainage.
7. After the hydrant has been installed and tested, it is recommended to fully flush the hydrant before closing for
service. Before replacing the nozzle caps, it is recommended to check for correct drainage of the hydrant on closing
of the valve. This can be achieved by placing a hand over the nozzle opening, a suction should be felt.
Operation
1. Unscrew the nozzle caps and connect hoses.
2. Open the hydrant using the hydrant key (included) to the fully open position by turning the valve nut in an
anti-clockwise direction – do not force the hydrant to open further past the fully open position. Note that the
hydrant valve is not intended to control the flow, it should be used in either the fully open or fully closed position.
To control flow, a pressure/flow control valve should be fitted to the nozzle outlets on the hydrant.
3. To close, turn the valve nut in a clockwise direction – again, do not over tighten.
Maintenance
1. Carry out a visual inspection for signs of significant corrosion which may impair performance.
2. Where possible, carry out leak tests by opening one of the nozzle caps slightly and then opening the hydrant valve.
Once the air has escaped tighten the hose cap and check for leaks.
3. Close hydrant and remove one nozzle cap so that the drainage can be checked.
4. Flush the hydrant.
5. Clean and lubricate all nozzle threads.
6. Clean the exterior of the hydrant and repaint if required.
www.viking-emea.com
FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
8. Material Safety
Data Sheet
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
NOT APPLICABLE
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
9. Manufacturer’s
Test
Certificates
LPCB® www.redbooklive.com
Products Standards
'Viking Corp' Fireking Pillar Fire Hydrants EN 14384:2005
1refe1 to attacheci .:ippend1x for de ;ills P a re I ydranh
Th is cert1fic,1te and af)pend1x s mcl nta1 1ed a 1d held 11° for e throuoih I egu ar sc1rve,lla1 re ac.: v tte'> Jnd
sc1bJeLt to tl 1 e cor'espond11g l\tJ -1001 Cert1+1c,He he 11g 1"'a11ta1red
bre
,.i. (.,
2020-09-30 ﺗﺎﺭﻳﺦ ﺍﻟﻄﺒﺎﻋﺔ : ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴــــﺔ
AM 8:07 ﻭﻗـﺖ ﺍﻟﻄﺒﺎﻋﺔ : ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ
PAC20010201 ﺭﻗــﻢ ﺍﻟﻄﻠـﺐ : ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ
ﺑﻴﺎﻧﺎﺕ ﺍﻟﻤﻨﺸﺄﺓ
ﺗﻔﺎﺻﻴﻞ ﺍﻟﺸﻬﺎﺩﺓ
ﺗﻢ ﻣﺮﺍﺟﻌﺔ ﺍﻟﻄﻠﺐ ﺍﻟﻤﻘﺪﻡ ﻭﺍﺗﻀﺢ ﺑﺄﻧﻪ ﻻ ﻣﺎﻧﻊ ﻣﻦ ﺍﻋﺘﻤﺎﺩ ﺍﻟﻤﻨﺘﺞ /ﺍﻟﻤﻨﺘﺠﺎﺕ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻰ ﺍﻟﻤﺮﻓﻖ ﺑﻨﺎﺀ ﻋﻠﻰ ﺍﻋﺘﻤﺎﺩﻩ ﻣﻦ ﻗﺒﻞ ﺍﻟﻬﻴﺌﻪ
ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﺭ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ.
ﻣﻼﺣﻈﺎﺕ
.1ﻳﺠﺐ ﻋﻠﻰ ﺍﻟﺸﺮﻛﻪ ﺍﻻﻟﺘﺰﺍﻡ ﻭﺍﻟﻌﻤﻞ ﺑﻤﺎ ﺟﺎﺀ ﻓﻲ ﺍﺷﺘﺮﺍﻃﺎﺕ ﻗﺴﻢ ﺃﻧﻈﻤﺔ ﺍﻟﺴﻼﻣﻪ ﺍﻟﺘﻲ ﺗﻢ ﺍﻻﻃﻼﻉ ﻭﺍﻟﻤﻮﺍﻓﻘﺔ ﻋﻠﻴﻬﺎ ﻣﻦ ﺧﻼﻝ ﺍﻟﻤﻮﻗﻊ.
.2ﻳﺠﺐ ﺍﻥ ﻳﻘﻮﻡ ﺑﺘﺮﻛﻴﺐ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ ﻣﻦ ﻗﺒﻞ ﻣﻬﻨﺪﺳﻴﻦ ﻭﻓﻨﻴﻴﻦ ﻣﻌﺘﻤﺪﻳﻦ ﻣﻦ ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ.
.3ﻳﺠﺐ ﺍﻥ ﻳﺤﻤﻞ ﺍﻟﻤﻨﺘﺞ ﺍﻟﻌﻼﻣﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ ﻟﻠﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻌﺘﻤﺪﺓ ﻭﺍﻟﻤﻮﺿﺤﻪ ﻓﻲ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ .
ﻉ/
Page 1 of 2
ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ
DATE : 2020-09-30 : ﺍﻟﺘﺎﺭﻳـــــــﺦ
ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ
PERMIT # PAC20010201 : ﺭﻗﻢ ﺍﻟﻄﻠﺐ
ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ
RECOMMENDATIONS ﺍﻟﺘﻮﺻﻴﺎﺕ
MUST BE FITTED WITH BS 336 HOSE ADAPTOR.
Certificate No 096w to EN 14384:2005.
This product approval shall comply with the Design, Inspection, Installation, Testing and Maintenance requirements of
NFPA 24 (and/or other related NFPA Codes / Standards), other acceptable International Codes / Standards, Local
Regulations and/or Manufacturer's Published Instructions subject to the technical review and approval of the Authority
Having Jurisdiction (Qatar Civil Defence).
/ﻉ
Page 2 of 2
HMRZ.EX15003
Gate Valves
Page Bottom
Gate Valves
Rated
End Pressure,
Pattern Model Size, in. Configuration psig
OS&Y OSF2 2, 2.5, 3, 4, 5, 6, 8, 10, 12, 14, 16, 18, 20, 24 F by F (ANSI Flange) 250
NRS PIF3 2.5, 3, 4, 5, 6, 8, 10, 12, 14, 16, 18, 20, 24 F by F (ANSI Flange) 250
NRS PIF4 2.5, 3, 4, 5, 6, 8, 10, 12, 14, 16, 18, 20, 24 F by F (BS Flange) 232
OS&Y OSF3 2, 2.5, 3, 4, 5, 6, 8, 10, 12, 14, 16, 18, 20, 24 F by F (BS Flange) 232
NRS NRFL3 2.5, 3, 4, 5, 6, 8, 10, 12, 14, 16, 18, 20, 24 F by F (BS Flange) 232
NRS NRFL2 2.5, 3, 4, 5, 6, 8, 10, 12, 14, 16, 18, 20, 24 F by F (ANSI Flange) 250
© 2018 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under
UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up Service.
Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading
manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission
from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format:
"© 2018 UL LLC".
h ps://database.ul.com/cgi‐bin/XYV/template/LISEXT/1FRAME/show... 03/09/2018, 16:25
Inside Screw Gate Valves
Inside screw gate valves are used underground with indicator posts attached or as roadway box valves (curb box installation). FM
Approved valves are available with a variety of end connections as indicated in the listings.
Valves having Ring-Tite, Fluid-Tite or Tyton-Joint connections should be anchored in place during installation. Unless otherwise noted
in the listing, these valves have 175 psi (1205 kPa) rated working pressure.
Model PIF, PIG Resilient Seated Gate Valves. 2 through 12 in. NPS. Valves have a rated working pressure of 300 psi (2070 kPa).
Available with the following end connections.
Product Specification
Valve Size
Model No End Connection
in (mm)
Flange x Flange
PIF 2, 2 1/2, 3, 4, 6, 8, 10, 12 (50, 65, 80, 100, 150, 200, 250, 300)
(ANSI, BS, EN, JIS)
Groove x Groove
PIG 2, 2 1/2, 3, 4, 6, 8, 10, 12 (50, 65, 80, 100, 150, 200, 250, 300)
(AWWA C606)
ﺑﻴﺎﻧﺎﺕ ﺍﻟﻤﻨﺸﺄﺓ
ﺗﻔﺎﺻﻴﻞ ﺍﻟﺸﻬﺎﺩﺓ
ﺗﻢ ﻣﺮﺍﺟﻌﺔ ﺍﻟﻄﻠﺐ ﺍﻟﻤﻘﺪﻡ ﻭﺍﺗﻀﺢ ﺑﺄﻧﻪ ﻻ ﻣﺎﻧﻊ ﻣﻦ ﺍﻋﺘﻤﺎﺩ ﺍﻟﻤﻨﺘﺞ /ﺍﻟﻤﻨﺘﺠﺎﺕ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻰ ﺍﻟﻤﺮﻓﻖ ﺑﻨﺎﺀ ﻋﻠﻰ ﺍﻋﺘﻤﺎﺩﻩ ﻣﻦ
ﻗﺒﻞ ﺍﻟﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﺭ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ.
ﻣﻼﺣﻈﺎﺕ :
.1ﻳﺠﺐ ﻋﻠﻰ ﺍﻟﺸﺮﻛﻪ ﺍﻻﻟﺘﺰﺍﻡ ﻭﺍﻟﻌﻤﻞ ﺑﻤﺎ ﺟﺎﺀ ﻓﻲ ﺍﺷﺘﺮﺍﻃﺎﺕ ﻗﺴﻢ ﺃﻧﻈﻤﺔ ﺍﻟﺴﻼﻣﻪ ﺍﻟﺘﻲ ﺗﻢ ﺍﻻﻃﻼﻉ ﻭﺍﻟﻤﻮﺍﻓﻘﺔ ﻋﻠﻴﻬﺎ ﻣﻦ ﺧﻼﻝ ﺍﻟﻤﻮﻗﻊ .
.2ﻳﺠﺐ ﺍﻥ ﻳﻘﻮﻡ ﺑﺘﺮﻛﻴﺐ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ ﻣﻦ ﻗﺒﻞ ﻣﻬﻨﺪﺳﻴﻦ ﻭﻓﻨﻴﻴﻦ ﻣﻌﺘﻤﺪﻳﻦ ﻣﻦ ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ.
.3ﻳﺠﺐ ﺍﻥ ﻳﺤﻤﻞ ﺍﻟﻤﻨﺘﺞ ﺍﻟﻌﻼﻣﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ ﻟﻠﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻌﺘﻤﺪﺓ ﻭﺍﻟﻤﻮﺿﺤﻪ ﻓﻲ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ .
ﻉ/
Page 1 of 2
ﺑﺴﻢ ﺍﻟﻠﻪ ﺍﻟﺮﺣﻤﻦ ﺍﻟﺮﺣﻴﻢ
ﺍﻟﻮﺻﻒ ﺍﻟﻤﻮﺩﻳﻞ
Inside Screw Gate Valves, resilient seated, 2, 2 1/2, 3, 4, 6, 8, 10, 12 inch sizes, Flange x
PIF
Flange end configuration, 300 PSI rated working pressure.
RECOMMENDATIONS ﺍﻟﺘﻮﺻﻴﺎﺕ
NOTES/STANDARD:
FM APPROVED
FM CLASS 1130.
/ﻉ
Page 2 of 2
9/27/2020 HCBZ.EX15462 - Indicator Posts, Gate Valve | UL Product iQ
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading
manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission
from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following
format: "© 2020 UL LLC"
https://iq.ulprospector.com/en/profile?e=44906 1/1
2020-09-29 ﺗﺎﺭﻳﺦ ﺍﻟﻄﺒﺎﻋﺔ : ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴــــﺔ
AM 8:42 ﻭﻗـﺖ ﺍﻟﻄﺒﺎﻋﺔ : ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ
PAC20010121 ﺭﻗــﻢ ﺍﻟﻄﻠـﺐ : ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ
ﺑﻴﺎﻧﺎﺕ ﺍﻟﻤﻨﺸﺄﺓ
ﺗﻔﺎﺻﻴﻞ ﺍﻟﺸﻬﺎﺩﺓ
ﺗﻢ ﻣﺮﺍﺟﻌﺔ ﺍﻟﻄﻠﺐ ﺍﻟﻤﻘﺪﻡ ﻭﺍﺗﻀﺢ ﺑﺄﻧﻪ ﻻ ﻣﺎﻧﻊ ﻣﻦ ﺍﻋﺘﻤﺎﺩ ﺍﻟﻤﻨﺘﺞ /ﺍﻟﻤﻨﺘﺠﺎﺕ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻰ ﺍﻟﻤﺮﻓﻖ ﺑﻨﺎﺀ ﻋﻠﻰ ﺍﻋﺘﻤﺎﺩﻩ ﻣﻦ ﻗﺒﻞ ﺍﻟﻬﻴﺌﻪ
ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﺭ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ.
ﻣﻼﺣﻈﺎﺕ
.1ﻳﺠﺐ ﻋﻠﻰ ﺍﻟﺸﺮﻛﻪ ﺍﻻﻟﺘﺰﺍﻡ ﻭﺍﻟﻌﻤﻞ ﺑﻤﺎ ﺟﺎﺀ ﻓﻲ ﺍﺷﺘﺮﺍﻃﺎﺕ ﻗﺴﻢ ﺃﻧﻈﻤﺔ ﺍﻟﺴﻼﻣﻪ ﺍﻟﺘﻲ ﺗﻢ ﺍﻻﻃﻼﻉ ﻭﺍﻟﻤﻮﺍﻓﻘﺔ ﻋﻠﻴﻬﺎ ﻣﻦ ﺧﻼﻝ ﺍﻟﻤﻮﻗﻊ.
.2ﻳﺠﺐ ﺍﻥ ﻳﻘﻮﻡ ﺑﺘﺮﻛﻴﺐ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ ﻣﻦ ﻗﺒﻞ ﻣﻬﻨﺪﺳﻴﻦ ﻭﻓﻨﻴﻴﻦ ﻣﻌﺘﻤﺪﻳﻦ ﻣﻦ ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ.
.3ﻳﺠﺐ ﺍﻥ ﻳﺤﻤﻞ ﺍﻟﻤﻨﺘﺞ ﺍﻟﻌﻼﻣﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ ﻟﻠﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻌﺘﻤﺪﺓ ﻭﺍﻟﻤﻮﺿﺤﻪ ﻓﻲ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ .
ﻉ/
Page 1 of 2
ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ
DATE : 2020-09-29 : ﺍﻟﺘﺎﺭﻳـــــــﺦ
ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ
PERMIT # PAC20010121 : ﺭﻗﻢ ﺍﻟﻄﻠﺐ
ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ
Indicator Posts, Gate Valves, Underground types, adjustable length, for valve sizes 4-12 in. IPV
Indicator Posts, Gate Valves, Wall types, for valve sizes 4-12 in. IPW
3RD PARTY CERTIFICATE /
Underwriters Laboratories ﺷﻬﺎﺩﺓ ﺍﻟﻤﺨﺘﺒﺮﺍﺕ ﺍﻟﻤﺴﺎﻧﺪﺓ
APPROVAL HCBZ.EX15462
(UL) ( )ﻣﻦ ﻫﻴﺌﺎﺕ ﻣﻌﺘﻤﺪﺓ
RECOMMENDATIONS ﺍﻟﺘﻮﺻﻴﺎﺕ
Intended for use in operating gate valves of the inside-screw pattern and for indicating the position of the gates in the
valves.
INVESTIGATED TO STANDARD UL 789.
TRADEMARK AND/OR TRADENAME: FIREKING
This product approval shall comply with the Design, Inspection, Installation, Testing and Maintenance requirements of
NFPA 11,13,14,24 (and/or other related NFPA Codes / Standards), other acceptable International Codes / Standards,
Local Regulations and/or Manufacturer's Published Instructions subject to the technical review and approval of the
Authority Having Jurisdiction (Qatar Civil Defence).
/ﻉ
Page 2 of 2
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
10. Warranty
Certificate
Vijay Arabia Fire & Security Systems
WARRANTY CERTIFICATE
There are no warranties, express or implied, made by Vijay Arabia on New Equipment, except a
warranty against defects in material and workmanship set out below:
1. Vijay Arabia Warrants the following product supplied against sub contract agreement XXXXXXXX
Dated XX‐XXX‐XXXX shall be free from defects in materials and workmanship.
Project: Falcon 5/ F-15QA Beddown Project
Client: US Army Corps of Engineers
Main Contractor: BMJV
System: External Valves & Fire Hydrant 33 11 00
2. Vijay Arabia Obligation and liability under this warranty is limited to rectification or replacement
of any part/s found defective under normal use and service, within 400 Days (Warranty Period)
from handling over date XX‐XXX‐XXXX.
3. This Warranty Certificate must be presented to obtain services pursuant to the warranties set
forth herein.
4. This Warranty does not cover sets repaired by workshops not authorised by Vijay Arabia.
5. This Warranty is in lieu of all other warranties, express or implied, including any implied
warranty of merchantability or fitness for a particular purpose and the obligation and liability of
Vijay Arabia under this warranty shall not include any transportation, any other charges, liability
for direct, indirect or consequential damages and delay resulting from the defect or any other
obligations or liability on the part of Vijay Arabia, and Vijay Arabia neither assumes not
authorizes any other person to assume for if any other liability in connection with such
equipment. Any improper use or application of the product or the substitution of any parts not
approved by Vijay Arabia shall void this warranty. Failure to provide regular maintenance in
accordance with safety regulations shall likewise void this warranty. This Warranty covers only
the products listed in paragraph 1 & above.
6. Service Policy.
This Warranty is void in case of full payment of the above mentioned project is not received.
VIJAY ARABIA
Al Difaf Street, 38 Al Sadd, P.O.Box: 31146, Doha Qatar | Tel. No.: (+974) 44365529/ 44982275 | Fax No: (974) 44364993,
Email: info@vijayarabia.com, Web: www.vijayarabia.com
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
11. Material
Sample
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
NOT APPLICABLE
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
12. Copies of
Previous
Approvals
TRANSMITTAL OF SHOP DRAWINGS, EQUIPMENT DATA, MATERIAL SAMPLES, OR DATE TRANSMITTAL NO.
MANUFACTURER'S CERTIFICATES OF COMPLIANCE
8/28/2018 33 11 00-9
For use of this form, see ER 415-1-0; the proponent agency is CECW-CE
SECTION I - REQUEST FOR APPROVAL OF THE FOLLOWING ITEMS (This section will be initiated by the contractor)
TO: Qatar Program Management Office FROM: Al Seal Contracting and Trading Company CONTRACT NO. THIS IS A:
Building Palm Tower B Majis A L Taawon W912ER18C0005
Street NEW TRANSMITTAL
Doha 3657
Qatar
SPECIFICATION SEC. NO. (Cover only one section with each transmittal) PROJECT TITLE AND LOCATION 01 THIS TRANSMITTAL IS FOR: (Check one)
33 11 00-WATER DISTRIBUTION Shield 5 Program, State of Qatar Site 5, Qatar FIO GA DA CR DA/CR DA/GA S
External Valves for Potable Water & Sewer Water Network - Vijay Arabia
I certify that the above submitted items have been reviewed in detail and
are correct and in the strict conformance with the contract drawings and
specifications except as otherwise stated.
ENG FORM 4025-R, JUL 2015 Page 1 of 1 REPLACES EDITION OF MAR 2012, WHICH IS OBSOLETE
TRANSMITTAL OF SHOP DRAWINGS, EQUIPMENT DATA, MATERIAL SAMPLES, OR DATE TRANSMITTAL NO.
MANUFACTURER'S CERTIFICATES OF COMPLIANCE
8/4/2018 33 11 00-5
For use of this form, see ER 415-1-0; the proponent agency is CECW-CE
SECTION I - REQUEST FOR APPROVAL OF THE FOLLOWING ITEMS (This section will be initiated by the contractor)
TO: Qatar Program Management Office FROM: Al Seal Contracting and Trading Company CONTRACT NO. THIS IS A:
Building Palm Tower B Majis A L Taawon W912ER18C0003
Street NEW TRANSMITTAL
Doha 3657
Qatar
SPECIFICATION SEC. NO. (Cover only one section with each transmittal) PROJECT TITLE AND LOCATION 01 THIS TRANSMITTAL IS FOR: (Check one)
33 11 00-WATER DISTRIBUTION Shield 5 Program, State of Qatar Site 3, Qatar FIO GA DA CR DA/CR DA/GA S
* 1 (One) Hard Copy + 2 (Two) Soft Copies to USACE Qatar Area Office.
I certify that the above submitted items have been reviewed in detail and
are correct and in the strict conformance with the contract drawings and
specifications except as otherwise stated.
ENG FORM 4025-R, JUL 2015 Page 1 of 1 REPLACES EDITION OF MAR 2012, WHICH IS OBSOLETE
DATE TRANSMITTAL NO.
TRANSMITTAL OF SHOP DRAWINGS, EQUIPMENT DATA
MATERIAL SAMPLES, OR MANUFACTURER'S 9/10/2018 33 11 00-5
CERTIFICATES OF COMPLIANCE
PROJECT TITLE Shield 5 Program, State of Qatar Site 3 CONTRACT NO. PAGE
W912ER18C0003 Page 1 of 1
LOCATION Qatar
SECTION I - REQUEST FOR APPROVAL OF THE FOLLOWING ITEMS (This section will be initiated by the contractor)
TO: Qatar Program Management Office FROM: Al Seal Contracting and Trading Company CONTRACT NO. THIS IS A:
Building Palm Tower B Majis A L Taawon W912ER18C0005
Street NEW TRANSMITTAL
Doha 3657
Qatar
SPECIFICATION SEC. NO. (Cover only one section with each transmittal) PROJECT TITLE AND LOCATION 01 THIS TRANSMITTAL IS FOR: (Check one)
33 11 00-WATER DISTRIBUTION Shield 5 Program, State of Qatar Site 5, Qatar FIO GA DA CR DA/CR DA/GA S
I certify that the above submitted items have been reviewed in detail and
are correct and in the strict conformance with the contract drawings and
specifications except as otherwise stated.
ENG FORM 4025-R, JUL 2015 Page 1 of 1 REPLACES EDITION OF MAR 2012, WHICH IS OBSOLETE
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
13. Compliance
Statement
with Project
Specification
VIJAY ARABIA
Fire and Security Systems
·r·r·� ��1 ;w;..;�1.,� ��1 �� as�
Dear Sir,
We Vijay Arabia Fire & Security Systems WLL, Qatar, whose registered office is at Ahmed Bin Hanbal Street,
Villa No: 59, D- Ring Road, P.O.Box: 31146, Doha, Qatar., would thank you for opportunity to work with you as
Fire Fighting & Fire Alarm Subcontractor to provide the scope of Design, Supply, Installation, Testing &
Commissioning of External Valves & Above Ground Hydrant- Fire Water External Network under specification
reference 33 11 00, for the above-referenced Project.
We thank you.
With Compliments,
C.R.No. 38572
i P. 0. Box 3 I 146, Doha, Qatar
T :+974 4019 2900 l 4436AS29 [_4498_2275 __ ---·· ____ . ------------·
: ----
I Doc. Ro;:-+&ll1Wl��l929 _ Rev. No.: 00 1, Rev. Date: 03-Sep-2020
,i --·--------------
Pag� of 4_
e-mail: info@vijayarabia.com www.vijayarabia.com
SUPPLIER/ SUBCONTRACTOR COMPLIANCE STATEMENT
Specification Compliance
Manufacturer Specification
S/n Description of Material (If Ref. (project
Requirements Compliance Compliant
Applicable) spec./ Test Results
for Testing Testing Ref.
Kahraama
Specification)
Project Specification Reference- 33 11 00 WATER UTILITY DISTRIBUTION PIPING
PART 2 PRODUCTS
2.1 MATERIALS
2.1.2 Valves
Proposed NRS
Gate valves shall comply with the relevant Gate valve is for Refer Section-7
provisions of (KAHRAMAA) Chapter 4: Fire Water for Technical
Section-6 Gate Valve. All sluice valves shall be 33 11 00 Para application for Datasheet and
manufactured and tested in accordance with 2.1.2.2.1
EN1092-2 which it is FM Section-9 for
Yes
BS 5163 Type ‘B’/ BS EN 1171 and their approved as per FM & QCDD
amendments. EN1092-2 PN16 certificate.
and QCDD
approved.
Composite Valve
Box with wall
thickness of 6mm,.
The Valve box lid
is with minimum
Provide cast iron valve boxes with a minimum
15mm and 91T
wall thickness of 6 mm. The valve box cover is
load capacity. The
to have a minimum thickness of 15 mm and be 33 11 00 Para
minimum Inner Yes
90,700 kg proof load tested. The minimum 2.1.1.1.2 c
Diameter of the
diameter and extension of the shaft of the box
Shaft will be
is to be 155 mm and 990 mm, respectively.
150mm and
Extension of the
shaft will be
minimum of
990mm.
2.1.3 Fire Hydrants And Hose Houses
Kahramaa
Specification
6.1.3 Gear box shall be of: N/A
Chapter 4,
Section 6
Kahramaa Gear box is not
Specification applicable for NRS
I Standard ratio - 1.1-10.1 ( as specified) N/A
Chapter 4, Gate Valves.
Section 6 Proposed Valve is
Kahramaa NRS Gate valve
Specification with IPV or
I Torque ranges - 400-40,000 Nm. N/A
Chapter 4, Composite valve
Section 6 box assembly.
Kahramaa
Specification
I Thrust range - 4,000-250,000 daN N/A
Chapter 4,
Section 6
6.1.4 All sluice valve and gear box shall be Kahramaa
Sluice Valves are
suitable for use with water temperature up to Specification
suitable to used to Yes
50° C and in climate and soil conditions Chapter 4,
50 deg C
encountered in the State of Qatar. Section 6
Kahramaa
6.1.5 All sluice valves shall be of the resilient Specification
Yes
seat type. Chapter 4,
Section 6
6.1.6 All component parts of the valve body i.e. Kahramaa
bonnet and stem seal housing shall be bolted Specification
Yes
together, where setscrews are used, the socket Chapter 4,
shall be provided with a PVC cap. Section 6
Kahramaa
6.1.7 All sluice valves shall be designed for Specification
Yes
clockwise closing and be marked accordingly. Chapter 4,
Section 6
Kahramaa
Specification
6.2 TESTING Yes
Chapter 4,
Section 6
Kahramaa
6.2.1 The sluice valve shall be tested as per Specification
Yes
BS 5163 as follows: Chapter 4,
Section 6
Kahramaa
Specification
Hydraulic test for body - 24 Bar Yes
Chapter 4,
Section 6
Kahramaa
Specification
Hydraulic test for seat - 17.6 Bar Yes
Chapter 4,
Section 6
A factory test certificate shall be issued for Kahramaa Material Test
each valve giving its serial numbers. This Specification certificate will be
Yes
certificate shall be submitted to KAHRAMAA at Chapter 4, provided with the
the time of supply if requested by the engineer. Section 6 delivered valves.
Kahramaa
Specification
6.3 HAND-WHEEL N/A
Chapter 4,
Section 6
Handwheel is not
applicable for the
6.3.1 Sluice valves shall be supplied with cast External Fire
Kahramaa
iron hand wheels marked "Open" and "Closed" network valves.
Specification
with arrow in appropriate directions. The The Valve spindle N/A
Chapter 4,
design shall be such that it can be removed if is operated by IPV
Section 6
necessary. and Composite
valve box with T-
Wrench.
Kahramaa
Specification
6.4 MARKING Yes
Chapter 4,
Section 6
Kahramaa
6.4.1 All valves shall have clearly marked m
Specification
the casting of the body the following Yes
Chapter 4,
information:
Section 6
A. Size of valve in mm.
B. Pressure rating in Bars. Kahramaa
C. Manufacturer's name and/or logo. Specification
Yes
D. Material type (GGG40/GGG50/SG) Chapter 4,
E. Manufacturing Standards Number. Section 6
F. Year of manufacture.
6.4.2 All valves shall have individual
identification strip which shall be marked by Kahramaa
engraving or embossing on a metal strip, the Specification
Yes
name of manufacturer, individual serial Chapter 4,
number, tender number and Year of Section 6
manufacturing.
6.4.3 The metal strip shall be of minimum size
Kahramaa Manufactured
of 100mm x 30mm and shall be fixed securely
Specification standard
and permanently at appropriate location by Yes
Chapter 4, identification will
industrial type cold welded glue and shall not
Section 6 be provided.
be screwed or riveted. The glue shall be of
Doc. No.: BMJV-QUA-F21 Rev. No.: 00 Rev. Date: 07-Sep-2020 Page 4 of 7
SUPPLIER/ SUBCONTRACTOR COMPLIANCE STATEMENT
Kahramaa
6.8 MATERIAL COATING & INTERNAL Specification
Yes
COMPONENTS Chapter 4,
Section 6
Valve body are
Kahramaa
6.8.1 The entire body of valves shall be coated both internally &
Specification
both internally and externally with either of the Externally Fusion Yes
Chapter 4,
following: bonded epoxy
Section 6
coated.
Coating thickness
will be of 300
Kahramaa microns for Valve
300 micron Fusion bonded epoxy (Polymeric Specification body with both
Yes
anticorrosion) coating as per WIS No. 4-52-01. Chapter 4, internally &
Section 6 Externally Fusion
bonded epoxy
coated
Coating thickness
will be of 300
Kahramaa microns for Valve
300 micron Electrostatic ally applied epoxy Specification body with both
Yes
coating Chapter 4, internally &
Section 6 Externally Fusion
bonded epoxy
coated
Coating thickness
will be of 300
Kahramaa microns for Valve
Specification body with both
300 micron Fluidized bed epoxy coating Yes
Chapter 4, internally &
Section 6 Externally Fusion
bonded epoxy
coated
QCS 2014 Section 23 Part 04: Fire Fighting System
4.5.1 General
Fire Hydrant will be
1 Fire hydrants shall be installed in locations as
QCS 2014 installed as per
stated in the Project Documentation unless
Section 23 Part approved Shop Yes
otherwise directed by the Civil Defence
04 Para 4.5 drawing and QCD
Department.
standards.
Above ground Fire
Hydrant Model
2 A certificate shall be obtained from the QCS 2014 HYF3 is approved Refer Section-9
manufacturer stating that the fire hydrants to Section 23 Part by QCDD. For for QCDD Yes
be supplied are suitable for use in Qatar. 04 Para 4.5 which QCDD Certificates.
certificate
provided.
Fire hydrants will
QCS 2014
3 Fire hydrants shall be installed in accordance be installed as per
Section 23 Part
with the manufacturer’s instructions. manufacturer’s
04 Para 4.5
instructions.
4.5.2 High Pressure Dry Barrel Hydrant Yes
1 High pressure dry barrel hydrants shall come
Proposed Dry
complete with removable/replaceable nozzles
QCS 2014 Barrel Above
and hydrant seat, top stop nut, easily repaired Refer Section-7
Section 23 Part Ground Fire Yes
traffic section, nozzle section with 360° for Datasheet.
04 Para 4.5.2 Hydrant Model
rotation, main valve opening and bronze drain
HYF3.
plug.
Proposed Model
2 Working pressure of the hydrant shall be 14
QCS 2014 HYF3 is having
bar and the testing pressure shall be 28 bar Refer Section-7
Section 23 Part ASTM A536 working pressure Yes
unless otherwise stated in the Project for Datasheet.
04 Para 4.5.2 of 17.2 Bar
Documentation or agreed with the Engineer.
(250Psi).
The Dry Barrel
Hydran Valve is
complying to local
QCD connection
requirement with
inbuilt
Instantaneous
coupling
Refer Section-7
connection for
QCS 2014 for Datasheet &
3 The hydrant shall comply with ASNI/AWWA which Model HYF3
Section 23 Part AWWA C502 Section-9 for Yes
C502 and shall be UL listed and FM approved. is LPCB apporved
04 Para 4.5.2 LPCB & QCDD
& QCDD
Certificate.
approved. UL/FM
hydrant valves
avaialble only with
threaded outlet
connection which
is not matching to
local QCD
requirements.
QCS 2014
4 Materials for the hydrants shall be as follows: Section 23 Part Yes
04 Para 4.5.2
Body, Nozzle
(a)nozzle section, barrels, stand pipe flanges,
QCS 2014 Section, barrels, Refer Section-7
breakable flange, base, main valve flange,
Section 23 Part ASTM A536 Operating nut and for Technical Yes
weather-shield operating nut and bonnet all
04 Para 4.5.2 bonnet are Ductile Datasheet.
shall be ductile iron
Iron
QCS 2014
(b)main valve disc shall be ductile iron core
Section 23 Part Yes
and fully encapsulated in EPDM rubber
04 Para 4.5.2
QCS 2014 Refer Section-7
Caps will be Cast
(c)caps shall be cast iron Section 23 Part for Product Yes
Iron
04 Para 4.5.2 Catalogue.
Proposed Fire
Hydrant finsih is
QCS 2014 with Red and Black Refer Section-7
(d)coating above ground shall be fusion
Section 23 Part Epoxy painted for Product Yes
bonded epoxy inside and out
04 Para 4.5.2 to interior and Catalogue.
exterior to AWWA
C550.
Coating below
QCS 2014 Refer Section-7
(e)coating below ground shall be bitumen or ground will be
Section 23 Part for Product Yes
fusion bonded epoxy black epoxy paint
04 Para 4.5.2 Catalogue.
for the hydrant
Screw stem
bushing is of
(f)nozzles, valve seat ring, drain ring, drain QCS 2014 Refer Section-7
Stainless Steel and
bushings and plugs, stem nut, stem bushing Section 23 Part for Product Yes
Screw nut seat,
and thrust nut shall be bronze 04 Para 4.5.2 Catalogue.
lock nut seat are of
Aluminum Bronze.
Bolt, nut and Cap
Chain will be of
QCS 2014 Refer Section-7
(g)stop nut, cap chain, bolts and nuts shall be Stainless steel
Section 23 Part for Product Yes
zinc plated steel material, which is
04 Para 4.5.2 Catalogue.
more superior than
Zinc plated Steel.
Connecting rod
(h)stem rod coupling, standpipe lock rings, QCS 2014 sleeve, Screw Refer Section-7
nozzle lock screw, lock plate, lock plate screw Section 23 Part Stem bushing and for Product Yes
and spider bolt shall be stainless steel 04 Para 4.5.2 bolt is of stainless Catalogue.
steel,
Barrel and Cap
QCS 2014 Refer Section-7
(i)barrel gaskets and cap gaskets shall be gaskets will be of
Section 23 Part for Product Yes
nitrile rubber. NBR (Nitrile
04 Para 4.5.2 Catalogue.
rubbber) material.
5 Each hydrant shall be clearly marked, either
QCS 2014
integrally with the stated components or on a
Section 23 Part Yes
plate of durable material securely fixed to that
04 Para 4.5.2
component, as follows:
QCS 2014
(a)the number of the standard to which the
Section 23 Part Yes
hydrant conforms and the date of the standard
04 Para 4.5.2
QCS 2014
(b)the manufacturer‟s name or trade mark Section 23 Part Yes
04 Para 4.5.2
Role: QC Engineer
Signature:
14. Contractual
Non-
Compliance
(only if applicable)
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
NOT APPLICABLE
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
15. Drawings
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
NOT APPLICABLE
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
16.Specification(s)
F-15QA BEDDOWN 60593057
1.3 SUBMITTALS
Connections; G
Valves; G
Valve Boxes; G
SECTION 33 11 00 Page 3
Solicitation No. W912ER-20-R-0001
F-15QA BEDDOWN 60593057
Fire Hydrants; G
Pipe Restraint; G
Tapping Sleeves; G
Corporation Stops; G
Backflow Preventer; G
Disinfection Procedures; G
Bacteriological Samples; G
Leakage Test
Hydrostatic Test
SD-07 Certificates
Lining
Valves
Fire Hydrants
Backflow Certificate
SECTION 33 11 00 Page 4
Solicitation No. W912ER-20-R-0001
F-15QA BEDDOWN 60593057
Provide push-on joints or mechanical joints for pipe and fittings unless
otherwise indicated.. Provide flanged joints for above ground
applications, unless otherwise noted.
a. Push-On Joints: Shape of pipe ends and fitting ends, gaskets, and
lubricant for joint assembly as recommended in (KAHRAMAA) Chapter 4:
Appendix A: GENERAL SPECIFICATION FOR MAIN LAYING MATERIALS FOR
WATERWORKS, SECTION 2.0 Ductile Iron Pipes and Fittings.
2.1.2 Valves
Gate Valves shall comply with the relevant provisions of (KAHRAMAA) Chapter
4: Section-6 Gate Valve. All sluice valves shall be manufactured and
tested in accordance with BS 5163 Type ‘B’/ BS EN 1171 and their
amendments. Provide all valves from one manufacturer. Provide FM/UL
listed gate valves on fire water lines per NFPA 24.
SECTION 33 11 00 Page 6
Solicitation No. W912ER-20-R-0001
F-15QA BEDDOWN 60593057
Gate valves shall comply with the relevant provisions of (KAHRAMAA) Chapter
4: Section-6 Gate Valve. All sluice valves shall be manufactured and
tested in accordance with BS 5163 Type ‘B’/ BS EN 1171 and their amendments.
Provide a valve box for each gate valve on buried piping. Construct
adjustable valve boxes manufactured from cast iron of a size compatible for
the valve on which it is used. Coat the cast-iron box with a heavy coat of
bituminous paint. Provide a round head. Cast the word "WATER" on the lid.
Provide cast iron valve boxes with a minimum cover and wall thickness of 5
mm and conforming to ASTM A48/A48M, Class 35B. The minimum diameter of the
shaft of the box is 135 mm.
Provide cast iron valve boxes with a minimum wall thickness of 6 mm. The
valve box cover is to have a minimum thickness of 15 mm and be 90,700 kg
proof load tested. The minimum diameter and extension of the shaft of the
box is to be 155 mm and 990 mm, respectively.
Fire hydrants shall comply with the relevant provisions of (QCD) Qatar Fire
Safety Standards; Fire Hydrant Design Criteria; QNS No. FH 01. Hydrants
shall be of the aboveground double pillar (PN 16) type with a 150 mm
nominal diameter barrel. Each hydrant shall have at least two (2)
outlets. Outlets shall be 65 mm nominal diameter.
Provide a valve box for each valve on piping, except where indicator post
is shown. Valve box shafts, supports and backfill shall be constructed as
described in section 2.1.2.3 of this specification and as shown on the
drawings.
Heavy duty ductile iron manhole frames and covers shall comply with
BS EN 124, Class D400 with precast concrete ring.
GRP ladders shall comply with the relevant provisions of (KAHRAMAA) Section
08: Part 7.2.1 GRP.
SECTION 33 11 00 Page 7
Solicitation No. W912ER-20-R-0001
Section - 6
Gate valves
6.1 GENERAL
6.1.1 All sluice valves shall be manufactured and tested in accordance with BS-5163 Type
'B'/ BSEN 1171 and their amendments.
6.1.4 All sluice valve and gear box shall be suitable for use with water temperature up to
50 ° C and in climate and soil conditions encountered in the State of Qatar.
6.1.6 All component parts of the valve body i.e. bonnet and stem seal housing shall be
bolted together, where setscrews are used, the socket shall be provided with a PVC
cap.
6.1.7 All sluice valves shall be designed for clockwise closing and be marked accordingly.
6.2 TESTING
A factory test certificate shall be issued for each valve giving its serial numbers. This certificate
shall be submitted to KAHRAMAA at the time of supply if requested by the engineer.
6.3 HAND-WHEEL
6.3.1 Sluice valves shall be supplied with cast iron hand wheels marked "Open" and
"Closed" with arrow in appropriate directions. The design shall be such that it can be
removed if necessary.
6.4. l All valves shall have clearly marked m the casting of the body the following
information;
A. Size of valve in mm.
B. Pressure rating in Bars.
C. Manufacturer's name and/or logo.
D. Material type (GGG40/GGG50/SG)
E. Manufacturing Standards Number.
F. Year of manufacture.
6.4.2 All valves shall have individual identification strip which shall be marked by
engraving or embossing on a metal strip, the name of manufacturer, individual serial
number, tender number and Year of manufacturing.
6.4.3 The metal strip shall be of minimum size of 100mm x 30mm and shall be fixed
securely and permanently at appropriate location by industrial type cold welded glue
and shall not be screwed or riveted. The glue shall be of industrial grade with a
melting point higher than 80 ° C.
6.5 MATERIALS
For valve
6.5.1 The valve body, bonnet, gland, yoke and wedge body shall be manufactured of
Ductile Iron as per one of the following standards
II
DIN 1693 GGG-50/40
II
BS EN 1563:1997 grade EN-GJS-500-7
II
ISO 500-7, ISO 400-15
6.5.2 The stem shall be manufactured of acid resistance stainless steel 316L/BS 970 Gr 431
S29 with the threaded portion being formed by rolling process.
6.5.4 Dimensions and materials shall conform to those detailed in BS 5163, as applicable
for Type "B", and BS EN 1171.
6.5.6 The wedge shall be completely vulcanized by EPDM and coupled to the valve stem
by gunmetal or dezincification resistance brass nut slide into the specifically designed
slot hole in wedge or rigidly fastened into the wedge body by forging before rubber
vulcanization.
6.5.7 Rubber material shall be of "EPDM EDK-70 and the minimum thickness shall be
1.5 mm, and all sealing surfaces not less than 4.0 mm.
Gear box
6.6 FLANGES
6.6.1 All sluice valve flanges shall be drilled to suite ductile iron flanges as detailed in BS
EN 1092-2, PN-16 rating.
6.7.1 Sluice valves up to and including 300 mm 0 shall have 'O' ring seals which are to
comprise of seal, wiper rings and lip seal. There shall be a minimum of two wiper
rings or one wiper ring and one lip seal in addition to the seal rings and shall be made
of synthetic rubber material.
6.7.2 Sluice valves above 300mm may have either 'O' ring seals, or stuffing boxes fitted
with an approved 'Teflon' or graphite based packing material.
6.7.4 There shall not be any direct contact with spindle and bonnet to avoid cold welding.
6.8.1 The entire body of valves shall be coated both internally and externally with either of
the following:
II 300 micron Fusion bonded epoxy (Polymeric anticorrosion) coating as per WIS No.
4-52-01.
II 300 micron Electrostatic ally applied epoxy coating.
II 300 micron Fluidized bed epoxy coating.
8 The hose shall terminate in a shut-off nozzle which shall give the following control settings:
(a) shut
(b) spray (sheet or conical) and/or jet.
9 Rotary operated nozzles shall be marked to show the direction of closing and opening.
Lever operated nozzles shall be marked to show the setting for:
(a) shut
(b) (spray and/or jet.
10 A manual inlet stop valve shall be fitted to the hose system. The valve shall be screw down
or other slow-opening type. The inlet and outlet of the valve shall form an angle of not less
than 90 and not more than 135
11 Hose assemblies shall be designed for the following pressures unless otherwise stated in the
project documentation or agreed with the Engineer:
12 Testing, performance and materials of hose systems with lay-flat hose shall comply with the
relevant provisions of BS EN 671-2.
1 Fire hydrants shall be installed in locations as stated in the Project Documentation unless
otherwise directed by the Civil Defence Department.
2 A certificate shall be obtained from the manufacturer stating that the fire hydrants to be
supplied are suitable for use in Qatar.
1 High pressure dry barrel hydrants shall come complete with removable/replaceable nozzles
and hydrant seat, top stop nut, easily repaired traffic section, nozzle section with 360°
rotation, main valve opening and bronze drain plug.
2 Working pressure of the hydrant shall be 14 bar and the testing pressure shall be 28 bar
unless otherwise stated in the Project Documentation or agreed with the Engineer.
3 The hydrant shall comply with ASNI/AWWA C502 and shall be UL listed and FM approved.
(a) nozzle section, barrels, stand pipe flanges, breakable flange, base, main valve flange,
weather-shield operating nut and bonnet all shall be ductile iron
(b) main valve disc shall be ductile iron core and fully encapsulated in EPDM rubber
(c) caps shall be cast iron
(d) coating above ground shall be fusion bonded epoxy inside and out
(e) coating below ground shall be bitumen or fusion bonded epoxy
QCS 2014 Section 23: Fire Fighting and Fire Alarm Systems Page 10
Part 04: Fire Fighting System
(f) nozzles, valve seat ring, drain ring, drain bushings and plugs, stem nut, stem bushing
and thrust nut shall be bronze
(g) stop nut, cap chain, bolts and nuts shall be zinc plated steel
(h) stem rod coupling, standpipe lock rings, nozzle lock screw, lock plate, lock plate screw
and spider bolt shall be stainless steel
(i) barrel gaskets and cap gaskets shall be nitrile rubber.
5 Each hydrant shall be clearly marked, either integrally with the stated components or on a
plate of durable material securely fixed to that component, as follows:
(a) the number of the standard to which the hydrant conforms and the date of the
standard
(b) the manufacturer‟s name or trade mark
(c) the identification number (the reference used by the manufacturer allowing
identification for the supply of spares, etc).
4.5.3 Underground Fire Hydrants and Surface Box Frames and Covers
1 Underground fire hydrants and surface box frames and covers shall generally comply with
the requirements of BS 750.
2 Underground fire hydrants with wedge gate type or screw down type valves shall be suitable
for a maximum working pressure of 16 bar.
4 The wedge gate valve shall comply with the requirements of BS 5163 for PN 16 valves. The
associated duck foot bends shall be grey cast iron (CI) to BS EN 1561 Grade 250 or
spheroidal graphite cast iron (SG) to BS EN 1563.
5 Materials and testing of underground fire hydraulic shall be to BS 750. Provision shall be
made for a certificate to be made available which certifies that the hydrant has complied with
all testing requirements of BS 750.
6 Each screw-down type hydrant and each duck foot bend on a wedge gate type hydrant shall
be provided with a drain boss on the outlet side. It shall be located at the lowest practicable
point.
7 The hydrants shall have screwed outlets. The screwed outlet shall be provided with a cap to
cover the outlet thread. It shall be securely attached to the hydrant by a chain or other
flexible device.
8 When fitted with a standard round thread outlet, the hydrant shall deliver not less than 2000
litres/minute at a constant pressure of 1.7 bar at the inlet to the hydrant.
9 The hydrant operating spindle shall be provided with a cast iron cap complying with the
requirements of BS 5163. The cap shall be securely fixed to the spindle so that it remains
fixed in position during normal use.
10 Each hydrant valve, duckfoot bend and outlet shall be clearly marked, either integrally with
the stated components or on a plate of durable material securely fixed to that component, as
follows:
17. Design
Calculation
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
NOT APPLICABLE
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
18. Bill of
Quantities
BILL OF QUANTITIES‐ External Valves & Above Ground Hydrant
S.No. Material Description Size (mm) Qty Unit Remarks
1 NRS Gate valve with Indicator Post (PIV)
2 NRS Gate Valve with Valve Composite Box
3 Above Ground Dry Barrel Hydrant
150ᴓ dia. ‐ dry barrel fire hydrant, 6" flanged inlet, two 2‐1/2"
3.1 hose connections, one 4" pumper connection, AWWA C502, 150ᴓ dia. 105 No's
LPCB certified @ 250 psi
* Note‐ This BOQ is of tendative quantity, which may vary with final design & Shop drawing submissions.
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES
19. International
Standards
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES