MATERIAL APPROVAL REQUEST

MAR Ref. No. 33 11 00-6.1 Rev. 01 Date: 25- Oct- 2020


Project: FALCON 5/F-15QA BEDDOWN PROJECT, AL UDEID AIR BASE, STATE OF QATAR
Employer: UNITED STATES ARMY CORPS OF ENGINEERS (USACE)
BAHADIR CONSTRUCTION ENGINEERING CONTRACTING & TRADING INC. CO
Contractor: AND IMPRESA COSTRUZIONI GIUSEPPE MALTAURO (ICM S.P.A) JOINT VENTURE
(BMJV)
Discipline: ☐ Civil ☐ Architectural ☐ Mechanical ☒ Others, specify: Fire Fighting System

Submitted as per Specification: ☒ Yes ☐ No Sample Provided: ☐ Yes ☒ No


External network NRS Gate Valve with Indicator Post & Valve composite box
Material Description:
and Above Ground Hydrant Valve
Type of Material: Fire External Valve & Above Ground Hydrant Valve
External Fire Water Network Underground Piping for Fire Fighting System in
Location of Use: (Facility Name)
Falcon 5/F-15qa Beddown Project, Al Udeid Air Base, State of Qatar
Project Specification 33 11 00 Para 2.1.2/ Kahraama General Specification
Specification:
Section-6/ QCS 2014 Section 23 Part 04 Para 4.5
Manufacturer: Fireking by Viking Corp
Standard: EN 1092-2
Agent/ Supplier: Vijay Arabia Fire & Security Systems WLL Qatar
Country of Origin: USA
ATTACHMENTS CHECKLIST:
1. Company Profile 11. Material Sample
2. License(s) of Manufacturer or Agent 12. Copies of previous Approvals
3. Appointment Letter of Local Agent 13. Compliance Statement with Project Specification
4. ISO Certificates 14. Contractual Non-Compliance – only if applicable
5. Brochure with applicable Materials 15. Drawing(s)
6. Certificate letter of Origin 16. Specification(s)
7. Manufacturer Data Sheet 17. Design Calculation
8. Material Safety Data Sheet 18. Bill of Quantities
9. Manufacturer’s Test Certificates 19. International Standards
10. Warranty Certificate

BMJV DOCUMENT AUTHORITY


Role Name Signature Date
Prepared by: Procurement Manager Ahmad El Essaili
Reviewed & Miroslav Kolev
CQC System Manager
Approved by: Tsanev
Approved by: Project Manager Oliver Kleebach

• Note: For approval and review, please use USACE comment sheet

Doc. No: BMJV-QUA-F02 Rev. No: 00 Rev. Date: 10-Sep-2020 Page 1 of 1


MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

REV00 USACE Comment & Reply


DOCUMENT OBSERVATION AND COMMENT SHEET

OCS Ref. No.: BMJV-MEP-OCS-20-00036 Rev. 00 Date: 21-10-2020


Project: Falcon 5/F-15QA Beddown Project Contract: W912ER20C0010 Contractor: BMJV
Document Ref.: 33 11 00- 6 Rev. 01 Document Title: Fire External Valves, Valves Boxes and Above Ground Fire Hydrants

COMMENT
SN CLAUSE USACE COMMENTS CONTRACTOR’S COMPLIANCE
STATUS
The Submitted compliance statement indicated a lot of non compliant
1 33 11 00 statement, contractor to verify and comply as required by the contract Revised Compliance statement attached in Section-13 of this MAS. Complied
requirement.
All related fire submittals shall be reviewed and stamped by the Noted. Fire Related submittals are reviewed and stamped by the
2 33 11 00 Complied
Contractor’s Fire Protection Engineer. contractor’s Fire Protection Engineer.

Reviewer Position Name Signature Date


Sr. Materials Engineer Khushboo Kumar
BMJV Procurement Manager Ahmad El Essaili
CQC System Manager Mutie Baidas

Doc. No.: BMJV-DC-F08 Rev. No.: 00 Rev. Date: 29-Aug-2020 Page 1 of 1


MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

REV01 MAS for External Valves,


Valve Box and Fire Hydrant
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

TABLE OF CONTENTS

1. Company Profile

2. License(s) of Manufacturer or Agent

3. Appointment Letter of Local Agent

4. ISO certificates

5. Brochure with applicable materials

6. Certificate letter of origin

7. Manufacturer Data Sheet

8. Material Safety Data Sheet

9. Manufacturer’s Test Certificates

10. Warranty Certificate

11. Material Sample

12. Copies of previous approvals

13. Compliance Statement with Project Specification

14. Contractual non-compliance – only if applicable

15. Drawing(s)

16. Specification(s)

17. Design Calculation

18. Bill of Quantities

19. International Standards


MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

1.Company Profile
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

SUPPLIER PROFILE
WE’VE EARNED QATAR’S TRUST
MILESTONES

Fast QCDD approval Maintaining Safeguarding


with GAP Analysis for Latest technology in
Security Systems for the OVER 30 MILLION
Fire Protection & Detection Fire Protection & Detection
WORLD’S LARGEST MIDDLE EAST’S PASSENGERS systems for
BIGGEST MEDICAL Systems for
GTL PLANT at the world’s premier 109 BUILDINGS
INSTITUTION 15,354,000 sq.ft.
International Airport

Sidra Medical and Malls / Hotels / High-rises Hamad


Shell GTL Plant Research Center Corporate Offices / Factories International Airport Hamad Port Project
Protecting Qatar’s Matching stringent QCDD Fire Detection & Protection
PREMIER requirements for the Systems ensuring
Safeguarding the future
Fire systems for
PETROLEUM WORLD’S FIRST NON-STOP POWER QATAR’S PREMIER
TO OVER 500,000 of Qatar at 7 SCHOOLS RAIL PROJECT
COMPANY Sustainable Downtown
Regeneration Project HOMES

Qatar Petroleum - Mshreib Mesaieed


Ras Laffan Pump Room Downtown Project Power Plant Ashghal Schools QATAR RAIL Stations
With competence,
experience and passion
comes excellence…
VASS Solutions
VASS - Vijay Arabia Fire & Security Systems WLL – is Qatar’s fastest growing
integrated Fire & Security Specialist company. With its zeal to perform • Fire Detection Systems – Addressable
and prove, and the 57-years of experience of the Vijay Group, its parent Detection Systems with Voice
company in India, VASS has become Qatar’s preferred choice within a
Evacuation and Fire Fighters
span of just 10 years!
Telephone, Graphic User Interface
Along with its genetic advantage, being a joint venture between the with Networked Panels
Vijay Group and Al Jaber Group has given it a strong foundation in Qatar.
The Al Jaber Group is one of Qatar’s premier business conglomerates with • Fire Protection Systems – Hydrant,
80 companies that encompass Engineering, Infrastructure Development,
Sprinkler, Foam, Gas Suppression,
Oil & Gas and Petrochemical industry, Water & Electricity, Building Products,
and more. Fire Extinguishers, Pre-action &
Deluge Systems
Today, VASS, with a professional strength of over 400 trained and experienced
personnel, specializes in turnkey industrial and commercial projects and offers • Passive Fire Protection – Fire Sealants,
a comprehensive array of Fire Detection, Fire Protection and Security Systems
with services that include conceptualizing, design, supply, installation, testing,
Fire Paint and Fire Doors
commissioning and maintenance.
• Security Systems – Access Control,
From the world-class Hamad International Airport, the multi-billion dollar CCTV, Intruder Alarm & AV Systems
Sidra Medical and Research Center, Qatar’s largest power plant at Messaied,
the Hamad Sea Port, to the world’s largest GTL Plant, VASS has successfully
executed the biggest, most complex and most prestigious projects.
Achievements which stem from across-the-scale competencies, services
and products delivered by its specialized Divisions.
VASS DivisionsCONTRACTING

MAINTENANCE

SECURITY
TRADING
SERVICE
VASS VASS VASS VASS VASS
Contracting Maintenance Service Trading Security
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

MANUFACTURER
PROFILE
Viking Group, Inc.
Company Profile
EXECUTIVE SUMMARY

Founded in 1920, Viking Group, Inc. is an industry leading manufacturer and distributor of
fire sprinklers and related products for fixed fire protection systems. Viking offers total fire
suppression solutions by providing its manufactured products and related third party products
along with value-added services such as fabrication, pre-assembly, product training, and
technical assistance. Viking’s products, which include both water and non-water based fixed
fire suppression systems, are installed in commercial, industrial, storage, office, institutional,
and residential properties around the world.

Viking Group is comprised of five primary business units; Viking Corporation, Viking
SupplyNet, Viking SupplyNet International, Viking Fabrication Services, and Viking Plastics.
Viking Corporation manufactures fire sprinklers, fire system valves, and related devices.
Viking SupplyNet distributes Viking Corp. manufactured products and third party products to
over 3,000 fire sprinkler contractors in the United States and an additional 3,000 fire
contractors internationally in over 80 countries. Viking Fabrication Services provides
customized, pre-fabricated steel piping systems according to fire contractor specifications,
saving the contractor from having to source, cut, thread, weld, and package steel piping
systems in-house. Finally, Viking Plastics was formed in 2007 to manufacture CPVC plastic
sprinkler piping to capitalize on the growing residential sprinkler market and the associated
need for CPVC products.

Combined, the companies of The Viking Group provide customers with the following
advantages:

Quality: Our reputation for quality has been earned over decades by focusing on
continuous improvement in all elements of our business – from the products we
manufacture to the services we provide.

Breadth: The largest selection of fire protection products and services ensures single-
point solutions for any fire protection challenge.

Support: The companies of The Viking Group are dedicated exclusively to fire
protection. Knowledgeable and experienced customer service and technical support
is provided at every point in the project process.

Innovation: From valves that are easier to install and maintain, to automated
fabrication capabilities, Viking's product innovations have been developed by a
thorough understanding of the needs of our customers.

Availability: With over 50 locations worldwide, and a host of independent distribution


partners, Viking’s products and services are available when and where our customers
need them.

Viking Group’s primary goal is to enhance and support the efforts of the fire sprinkler
contractor. Viking’s commitment to quality, service, and innovation means fewer problems
and more cost-effective solutions for both the installers and end users of fire suppression
systems worldwide.
MISSION AND STRATEGY

Mission Statement

To design, manufacture and distribute fire protection products and services which meet or
exceed our customers' expectations, and safeguard people and property worldwide from the
devastating effects of fire.

Strategy Statement

Service the critical needs of the fire services sub-contractor and the building owner in the
construction markets of the world. This service takes the form of a set of high quality,
innovative products and services which enhance the contractor’s ability to profitably compete
and which provides the owner with lasting value.

Strategic Concepts

A focus on customer and market needs is consistent with the delivery of our Mission. It is the
Company’s ongoing responsibility to survey the market to determine what the independent
contractor needs to thrive in the future, and provide it.

Development of innovative products and services is the cornerstone of the Company’s


competitive advantage. Viking Group will continuously examine new product ideas
generated by anyone, be they customers, the company itself, or other interested parties.

These products and services must be of the finest quality available to the marketplace, and
the delivery of them must correspond to the highest service level available.

To achieve these key concepts, the company will seek to develop its people to reach their
highest level of competence, and maintain a strong capital structure in order to invest in new
opportunities as they become apparent.

Markets Served

The Company’s products are installed in the widest range of construction. The major
markets are identified as follows:

Commercial: Offices, hotels, retail, hospitals, nursing homes, schools, restaurants,


assembly areas, etc.
Industrial/Storage: Factories, warehouses, etc.
Residential: Apartments, condominiums, townhomes, single-family homes,
hotels, dormitories, etc.
Special Hazards: Aircraft hangers, chemical plants, oil refineries/platforms, power
generation and transmission, machinery spaces, etc.
Damage Sensitive: Libraries, museums, computer/data centers, command centers,
telecommunications equipment, etc.
Each of these segments uses somewhat different products in the Viking portfolio. Generally
the higher the value of the property protected, the higher the level of system sophistication.
Ironically the most important systems from a life-safety perspective (residential) incorporate
the simplest, least expense products. Promotional efforts differ by market in order to target
each segment.

COMPANY HISTORY

The Viking Group traces its roots back to the 1880s when Emil Tyden, a
Swedish immigrant, developed an innovative railroad car seal in Chicago.
In the late 1890s, Tyden was introduced to a businessman in Michigan who
convinced him to move to Hastings and found the International Seal & Lock
Company to manufacture the patented seals. To produce his boxcar seal in
mass, Tyden went on to create one of the world's first automation systems
– fully a decade before Henry Ford mass-produced automobiles.

Around 1920, after a fire destroyed the factory at the International Seal and
Lock Company, Tyden resolved to enter the fire sprinkler business.
Through a mutual friend, Tyden was introduced to a St. Louis businessman
who claimed to have developed some designs for fire sprinklers and valves.
A short time later, after it was apparent that the business was in trouble,
Tyden bought 100% interest in The Viking Corporation and began
manufacturing fire sprinklers and valves in Hastings.

Tyden continued to expand the company by partnering with talented


“sprinklermen” around the United States and, in a very short time,
developed a sizable number of highly qualified Viking sprinkler contractors.
Viking maintained this contractor orientation until the mid 1960s.

The rapid growth of the fire sprinkler market in the mid 1970s caused Viking to establish a
network of affiliates who could properly service the market with Viking products as well as
other components necessary for sprinkler installations. By the mid-to late-1980s, Viking
divested itself of all contracting and design interests and focused on the development,
manufacture, and distribution of fire sprinklers, valves, and devices.

By the early 1990s, Viking SupplyNet was established as the sole distributor of Viking
products, as well as related fire protection components. Viking SupplyNet International was
also developed to build a strong international presence. Worldwide, Viking SupplyNet is now
represented by over 50 wholly owned locations as well as a large network of independent
distributors.

In 2002, Viking Group, Inc. launched Viking Fabrication Services to offer contractors
complete fabrication services for steel pipe, the largest component for most sprinkler
systems. And, in 2007, Viking Group expanded again with the formation of Viking Plastics.
Viking Plastics manufactures high-quality CPVC plastic sprinkler pipe used in residential and
certain light hazard properties.

Today, the companies of the Viking Group provide independent fire sprinkler contractors with
integrated solutions for any fire protection challenge. Our commitment to quality, service, and
innovation means fewer problems and better, more cost-effective solutions for fire sprinkler
contractors.
COMPANY STRUCTURE

The Viking Group is a holding company with five major subsidiaries. Employees work for
either one of the subsidiaries or Viking Group itself. Viking Group employees provide
services to subsidiary companies, including Finance, Information Technology, Marketing,
Human Resources, Supply Chain, and Executive Leadership.

Viking
Group

Viking
Viking Viking
SupplyNet
Corporation SupplyNet
International

Viking
Viking
Fabrication
Plastics
Services

Viking Corporation

As the manufacturing entity of The Viking Group, Viking Corporation manufactures the fire
sprinklers, valves, and devices sold around the world. At its primary location in Hastings,
Michigan it also conducts research and development activities in an advanced hydraulics
laboratory and in two fire test buildings. This is essential for obtaining the product approvals
important to the industry, including Underwriter’s Laboratories, Factory Mutual Global, and a
host of international approvals.

Viking products are thoroughly tested, listed, and approved by the most recognized
independent laboratories in the world, including the following:

Viking has the finest reputation for product quality in the field. This stems from a deep
competency in manufacturing. Viking Corporation is believed to be more vertically integrated
than its competitors, possessing machining, stamping, assembly, soldering and testing
operations. The majority of its sales go through Viking SupplyNet distribution centers, with
the remainder through independent distributors.
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

2. License(s) of
Manufacturer
or Agent
Issue Date:
Page No: 1

Commercial Registration Data

*38572*
Issue Date: 26/02/2020

Commercial Reg. No.: 38572 Tax Reg. No.: 000002732335583


Trade Name: VIJAY ARABIA FIRE AND Trade Type:
SECURITY SYSTEMS
COMPANY
Creation Date: 20/03/2008 Expiry Date: 17/03/2021
Legal Form: W.L.L Capital: 200000
Commercial Reg. Status: Active Firm Nationality: QATAR
No. of Branches: 0
Contact Information

Mail Box: Contacts Numbers: +974


Email:

Partners

Name Document No CR No Nationality Percentage Status


OSAMA RIDA HADID 25699900054 CANADA 9% Active
AL-JABER CAPITAL 59121 QATAR 51% Active
vijay security systems private limited INDIA 40% Active

Managers (Authorized Signatories)

Name Document No CR No Nationality Designation


(Authority)
Manager - Full and Absolute
PRADIP RATILAL SALOT 25135604599 INDIA
Authority
Manager - Full and Absolute
HISHAM OSAMA RIDA HADID 28884000022 CANADA
Authority
NISHIT PRADIP SALOT 1109046‫ﺯﺩ‬ INDIA Manager - Full and Absolute

Page 1 of 2
CR No : 38572

‫ﺗﺸﻬﺪ ﻏﺮﻓﺔ ﺗﺠﺎﺭﺓ ﻭﺻﻨﺎﻋﺔ ﻗﻄﺮ ﺑﺄﻥ ﺍﻟﻤﻨﺸﺎﺓ ﺍﻟﻤﺬﻛﻮﺭﺓ ﺍﻋﻼﻩ ﺳﺠﻠﺖ ﻟﺪﻳﻨﺎ‬
Qatar Chamber certifies that the above mentioned establishment has been registered
Issue Date:
Page No: 1

Commercial Registration Data

Authority
Manager - Administrative
SALAH SULTAN M J AL-JABER 26663400955 QATAR
Authority (Passports)
Manager - Full and Absolute
OSAMA RIDA HADID 25699900054 CANADA
Authority
Manager - Administrative
SALAH SULTAN M J AL-JABER 26663400955 QATAR
Authority (Labor)
Manager - Full and Absolute
HEMAL PRADIP SALOT 27735614704 INDIA
Authority

Business Activities

Activity Name Activity Code Activity Name Activity Code


Trading in the security equipments 2002906 Installation of security and safety 2000885
Trading in fire warning and safety 2004338 equipment and devices
devices Trading in fire warning and safety 2004339
equipments

Page 2 of 2
CR No : 38572

‫ﺗﺸﻬﺪ ﻏﺮﻓﺔ ﺗﺠﺎﺭﺓ ﻭﺻﻨﺎﻋﺔ ﻗﻄﺮ ﺑﺄﻥ ﺍﻟﻤﻨﺸﺎﺓ ﺍﻟﻤﺬﻛﻮﺭﺓ ﺍﻋﻼﻩ ﺳﺠﻠﺖ ﻟﺪﻳﻨﺎ‬
Qatar Chamber certifies that the above mentioned establishment has been registered
<Bar Code>
2020/03/04  
Z[ $ [\ $  

 ! 


%&$'(&#(%" !     "#$"% !  
%&%$(&'($; !  9:.  ,-./ 0 1  2 3 4 5 6 7 ) *+
 8/
#@;A% )   6 7  <=8, >?.
 ,

 
  
D?* E 2 B, F B?C, , *
8: B?C, ,  8I %AA#;"$'A&' DGH 
       
@&  L 4 J?, K 8!
$ N? (  4 EM J?, >?.
2 *8F 6 7  L3 P * E1 3G I "O L8,
 !  >?.  *? >=
R3- > 5  Q?83 K  $&%  >= 
   !"

S=8 * S=8  S=8 * S=8 


X 8/ U:I/ Y5  %&&%O&" T R/ U:I D3 E 6  %&&&@@;
V./ 9W/ U:I  %&&'##@ T V./ 9W/ D3  %&&'##O
T


     
TIN: 000002732335583 000002732335583 ‫ﺍﻟﺮﻗﻢ ﺍﻟﻀﺮﻳﺒﻲ‬

Taxpayer's Name: Vijay Arabia Fire & Security Systems ‫ ﺷﺮﻛﺔ ﻓﻴﺠﺎﻱ ﺍﻟﻌﺮﺑﻴﺔ ﻟﻠﺤﺮﻳﻖ ﻭﺍﻻﻧﻈﻤﺔ ﺍﻻﻣﻨﻴﺔ‬:‫ﺍﺳﻢ ﺍﻟﻤﻜﻠﻒ‬

Address, P.O.Box: 31146 Doha ‫ ﺍﻟﺪﻭﺣﺔ‬31146 :‫ﺏ‬.‫ ﺹ‬،‫ﺍﻟﻌﻨﻮﺍﻥ‬

CR No: 38572 38572 :‫ﺭﻗﻢ ﺍﻟﺴﺠﻞ ﺍﻟﺘﺠﺎﺭﻱ‬.

Legal Form: Limited Liability Company ‫ ﺷﺮﻛﺔ ﺫﺍﺕ ﻣﺴﺆﻭﻟﻴﺔ ﻣﺤﺪﻭﺩﺓ‬:‫ﺍﻟﺸﻜﻞ ﺍﻟﻘﺎﻧﻮﻧﻲ‬

Number of Branches: 0 0 :‫ﻋﺪﺩ ﺍﻟﻔﺮﻭﻉ‬

Activity Commencing Date: 20/03/2008 2008/03/20 :‫ﺗﺎﺭﻳﺦ ﺑﺪﺀ ﺍﻟﻨﺸﺎﻁ‬

Issuing Date: 18/03/2020 2020/03/18 :‫ﺗﺎﺭﻳﺦ ﺍﻹﺻﺪﺍﺭ‬

Expiry Date: 17/03/2021 2021/03/17 :‫ﺗﺎﺭﻳﺦ ﺍﻹﻧﺘﻬﺎﺀ‬

‫ﻣﺪﻳﺮ ﺇﺩﺍﺭﺓ ﺧﺪﻣﺎﺕ ﺍﻟﻤﻜﻠﻔﻴﻦ‬


03489278407684
Taxpayer Services Department

P.O. Box (28666) ‫ﺏ‬.‫ ﺹ‬- Fax (44461288)‫ ﻓﺎﻛﺲ‬- Tel (44461444) ‫ﺗﻠﻴﻔﻮﻥ‬
www.tasportal.mof.gov.qa ‫ ﺍﻟﻤﻮﻗﻊ ﺍﻻﻟﻜﺘﺮﻭﻧﻲ‬-taxpayer.services@gta.gov.qa ‫ﺍﻟﺒﺮﻳﺪ ﺍﻻﻟﻜﺘﺮﻭﻧﻲ‬
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

3. Appointment
Letter of
Local Agent
September 25, 2020

TO WHOM IT MAY CONCERN

Subiect: Distribution Letter

Thisis to certify that company Vijay Arabia Fire and Security Systems W,LL, Post Box number
31145, Doha, qatar , is a VikingS.A's authorized non- exclusive distributor for fire - fighting
water-based products, foam based products and systems and forthe Viking's brand
"Fireking " line of hydrants, gate valves, check valves, butterfly valves PIF valves and strainers.

This distribution letter is valid until 30/09/2021.

Sincerely,

g-
Divakaran

Manager

Viking Mi

Viking Arabia FZE


LOB 19 Office # 2506lPost Box No. 17531
JebelAliFree Zone ] DubailUnited Arab Emirates
T: +971 4 889s 561 I F: +971 4 8895 562
vikingdubai@viking.orp.com
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

4. ISO
Certificates
Awarded to

VIJAY ARABIA FIRE & SECURITY SYSTEMS


W.L.l
at
P.0.BOX NO : 31146, DOHA, QATAR

Quality Registrar Systems certify that the management system of the above
organization has been audited and found to be in compliance with the QRS
requirements for registration of the management system standard detailed
below:

ISO 9001 :2015


Quality Management Systems

Scope of work

DESIGN, SUPPLY, INSTALLATION, TESTING, COMMISSIONING AND SERVICES


OF FIRE SAFETY & SECURITY SYSTEM, ALLIED EQUIPMENTS AND RELATED
SPARE PARTS

EA 28
Certificate No: AQQ-10159
Originally Registered : 20 OCT 2015
Latest Issue: 15 SEP 2019
Valid up-to: 19 OCT 2020

Quality Registrar Systems

ASCB(E
Accrediting
c~~~7~;.g

QATAR OFFICE ADDRESS:


ASCB (EUROPE) Ltd P.O.BOX NO: 6 150
6, Ferris Place, Bournemouth, DOHA. QATAR
Dorest, BH8 OAU. UK TEL : +974-4466-4 134
www.asb.co.uk FAX : +974-4466-3960

WORLD WIDE CERTIFICATION


This is an accred ited certificate authorized for issue by Accreditation Service for Certifying Bodies (Europe) Limited who have assessed ORS as a Certifying
Body for compliance with ISO 17021:2015 'Conformity Assessment - Requirements for bodies providing audit and certification of management systems.
This certificate is only valid when confirmed by the register listed in the quality registrar system ( qrsyst.com)
Certificate of Management
System Registration
Certificate Number: 096 Issue: 13

The Viking Corporation

having complied with the requirements of:

ISO 9001:2015
Quality Management Systems - Requirements

are certified by BRE Global Ltd. and are authorised to use the LPCB Certification Mark on stationery
and publications related to the products and/or services listed in the attached Appendix:

The Viking Corporation Scope:


210 Hastings Industrial Park Road Manufacture of fire sprinklers, fire protection
Hastings valves and related products for fire sprinker
Michigan 49058 systems.
USA

This certificate and appendix is maintained and held in force through regular surveillance activities.

Phil Clare 03 September 2018 02 September 2021 06 March 1992


Signed for BRE Global Ltd. BGM Assessment Services Date of this Issue Expiry Date Date of First Issue

This certificate and appendix remains the property of BRE Global Ltd. and is issued
subject to terms and conditions (for details visit www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR tag or contact us.
BRE Global Ltd, Watford, WD25 9XX
T: +44 (0)333 321 8811 E: enquiries@breglobal.com
LPCB is a Registered Trademark of the Building Research Establishment Ltd.

BF040A Rev 11.1 Page 1 of 2 © BRE Global Ltd, 2018


Appendix to Certificate Number: 096 Issue: 13

Company Scope
The Vikings Corportation Manufacture of fire sprinkers and related products for fire
11305 James Street sprinker systems.
Holland
Michigan 49424
USA
The Vikings Corportation Manufacture of fire sprinkers and related products for fire
4757 128th Avenue sprinker systems.
Holland
Michigan 49424
USA

This certificate and appendix is maintained and held in force through regular surveillance activities.

Phil Clare 3 September 2018 2 September 2021 6 March 1992


Signed for BRE Global Ltd. BGM Assessment Services Date of this issue Expiry date Date of first issue

This certificate and appendix remains the property of BRE Global Ltd. and is issued
subject to terms and conditions (for details visit www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR tag or contact us.
BRE Global Ltd, Watford, WD25 9XX
T: +44 (0)333 321 8811 E: enquiries@breglobal.com
LPCB is a Registered Trademark of the Building Research Establishment Ltd.

BF040A Rev 11.1 Page 2 of 2 © BRE Global Ltd, 2018


MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

5. Brochure with
Applicable
Materials
Post Indicator Valve - Flanged
PIF & PIF2

Control Valves
Technical Features
• Sizes available (Nominal) : 2”/DN50, 2½”/DN65,
3”/DN80, 4”/DN100, 5”/DN125, 6”/DN150,
8”/DN200, 10”/DN250 and 12”/DN300
• Working pressure : 21 bar (300 psi)
• Seat type : Resilient wedge
• Finish : Fusion bonded epoxy coated internal & external
• Connections : Flange diameter and thickness according
to ANSI B16.1 Class 125, EN1092-2 PN10 or EN1092-2
PN16
• Specifications : Design and dimensions conform to
AWWA C515
• Operation : For use with IPV or IPW indicator posts
• Remark : No post flange supplied with 2”, 2½” & 3”,
and size 2” is FM approved only and size 5” is UL listed
only * Image depicts 4”-14” sizes, 2”-3” not supplied
with Post Plate

Post Indicator Valve - Flanged - PIF & PIF2 Physical Data


Nominal Pipe
Dimensions (mm) Reference****
Size Weight
D1 n-ØL (kg)
inch Metric L H D C ANSI PN10 PN16
ANSI PN16 PN10 ANSI PN16 PN10
2”* DN50*** 178 278 152 16.0 120.7 125 4-Ø19.1 PIF-0200 PIF-0200PN 12.9
2½” DN65*** 190 300 178 17.5 139.7 145 4-Ø19.1 PIF-0250 PIF-0250PN 15.9
3” DN80*** 203 321 191 19.1 152.4 160 4-Ø19.1 8-Ø19.1 PIF-0300 PIF-0300PN 20.9
4” DN100 229 395 229 19.1 190.5 180 8-Ø19.1 8-Ø19.1 PIF-0400 PIF-0400PN 35.7
5”** DN125 254 432 254 19.1 215.9 210 8-Ø22.2 8-Ø19.1 PIF-0500 PIF-0500PN 44.6

Datasheet updates the datashet of 30-11-2015 (revised L dimension for 12” valve)
6” DN150 267 475 279 19.1 241.3 240 8-Ø22.2 8-Ø23 PIF-0600 54.2
8” DN200 292 585 343 22.2 298.5 295 8-Ø22.2 12-Ø23 8-Ø23 PIF-0800 PIF-0800PN10 PIF-0800PN16 86.1
10” DN250 330 656 406 23.8 362.0 355 350 12-Ø25.4 12-Ø28 12-Ø23 PIF-1000 PIF-1000PN10 PIF-1000PN16 117.2
12” DN300 356 751 483 25.4 431.8 410 400 12-Ø25.4 12-Ø28 12-Ø23 PIF-1200 PIF-1200PN10 PIF-1200PN16 180.0
* FM Approved only ** UL Listed only *** No post plate - flange supplied , UL Listed as PIF2, **** Valve flange drilling (size and location of bolt holes and pitch circle diameter) allows mating with the
following flange types :
ANSI = ANSI B16.1 Class 125 PN10 = DIN 2501, BS 4504, EN 1092 - PN10 PN16 = DIN 2501, BS 4504, EN 1092 - PN16

Post Indicator Valve - Flanged - PIF & PIF2 Materials List


Item Description Material ASTM Specifications Item Description Material ASTM Specifications
1 Valve Body Ductile Iron ASTM A536 64-45-12 12 Bolt Carbon Steel Zinc Plated
2 Wedge Disc Ductile Iron ASTM A536 64-45-12 & EPDM 13 Flat Washer Carbon Steel Zinc Plated
3 Stem Stainless Steel AISI 431 14 Ring Wiper EPDM Commercial
4 Bonnet Gasket EPDM Commercial 15 O-Ring NBR Commercial
5 Bonnet Ductile Iron ASTM A536 64-45-12 16 Axis Guide Brass Hpb59-1
6 O-Ring NBR Commercial 17 Washer Brass Hpb59-1
7 Gland Ductile Iron ASTM A536 64-45-12 18 O-Ring NBR Commercial
8 Post Flange Ductile Iron ASTM A536 64-45-12 19 Bolt Carbon Steel Zinc Plated
13-07-2016

9 Square Operating Nut Ductile Iron ASTM A536 64-45-12 20 Wedge Nut Brass Hpb59-1
10 Bolt Carbon Steel Zinc Plated 21 Plug Bronze ASTM B584 C89833
11 Flat Washer Carbon Steel Zinc Plated

Worldwide Fire Protection www.viking-emea.com

FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
Vertical Indicator Post
IPV

Indicator Posts
IPV - Vertical Indicator Post Physical Data
Dimensions (mm/inch) Weight
Reference
A B C D E F (kg)
IVP 1270 1006 759.5 292 190 305 98.7

IPV - Vertical Indicator Post Trench Depth


Trench Depth according to Valve Size
Reference Unit DN100/4” DN150/6” DN200/8” DN250/10” DN300/12”
Min. Max Min. Max Min. Max Min. Max Min. Max
IVP mm 958 1808 1073 1923 1200 2050 1314 2164 1448 2298

IPV - Vertical Indicator Post Specifications


• Indicator of “Open” and “Shut” positions
• Used to operate a buried or hidden post indicator valve
• 850 mm adjustment range
• Wrench handle fits over a “U” bracket on the barrel, this can
be fixed with a padlock to secure the operating wrench to the
barrel
• Internally and externally coated in red epoxy RAL3000
• 2.5 m long stem bar is supplied

IPV Materials List


Part Weight
Item Part Material Specification
Number (kg.)
1 Hex Nut Carbon Steel Zinc Plated - -
2 Hex Bolt Carbon Steel Zinc Plated - -
3 Socket Ductile Iron A536, 65-45-12 IPV-SOCK 2.42
4 Cotter Pin Stainless Steel AISI 304 IPV-COTT 0.02
5 Base Flange Cast Iron ASTM A126 Class B IPV-BF 14.52
6 Hex Bolt Carbon Steel Zinc Plated - -
7 Hex Nut Carbon Steel Zinc Plated - -
8 Standpipe Carbon Steel ASTM A53 - -
9 Stem 1" Square Carbon Steel AISI 1045 IPV-STEM 12.18
10 Body Cast Iron ASTM A126 Class B
11 Locking Wrench Ductile Iron A536, 65-45-12 IPV-WREN 3.56
12 Target Carrier Nut Stainless Steel AISI 304 - -
13 Hex Bolt Carbon Steel Zinc Plated - -
14 Hex Nut Carbon Steel Zinc Plated - -
15 Hex Bolt Carbon Steel Zinc Plated - -
Target - Open IPV-OPEN 0.07
16 Cast Aluminum
Target - Shut IPV-SHUT 0.07
17 Window Class Plexiglass IPV-WIN 0.03
18 Window Gasket PTFE IPV-WG 0.01
19 Operating Nut Stainless Steel AISI 304 - -
Datasheet Created

20 Top Section Cast Iron ASTM A126 Class B - -


21 Snap Ring AISI 1066 - -
22 Plug Malleable Iron Galvanized - -
23 Square Nut Carbon Steel Zinc Plated - -
24 Hex Bolt Carbon Steel Zinc Plated - -
09-03-2015

25 Hex Bolt Carbon Steel Zinc Plated - -


26 Hex Nut Carbon Steel Zinc Plated - -

Worldwide Fire Protection www.viking-emea.com

FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
MVB composite Valve Box
Reliable
ReliableConnections
Connections
TM
TM

Product Features
• Bevelled edge Ductile Iron Adjustable • Easily cuts to required length with
Top available in 2 sizes – 12” (305mm) ordinary hand tools.
and 27” (686mm). • Impact-resistant, corrosion-proof polymer
• Tops are self-leveling and self-adjusting. lower section.
WATER
• Light weight – no special heavy
equipment required to install.

The advanTage of using The adjusTable valve box Top –


valve box moves wiTh any surface movemenT.

BEFORE Cover

WATER WATER

Top

Cover AFTER Cover

Top Top

parts list
ID Part Name Material
1 T-Wrench* 2–7 Ft. (see Note 1) Cast Iron
2 MVB Extension Stem* 2–12 Ft. (see Note 1) Ductile Iron
3 Beveled Adjustable Top Ductile Iron
4 MVB Bottom Section Non-abrasive Polymer
5 Lid Cast Iron
6 Cover Cast Iron

Vijay Arabia Fire & Security Systems W.L.L.


P.O.Box: 31146, C.R.No.38572, Doha Qatar
Tel. No. : (+974) 40190900 Fax No: (974) 44364993
Email : info@vijayarabia.com Web : www.vijayarabia.com
Fire Hydrant
HYF2-5 Dry Barrel Fire Hydrant

Fire Hydrants & Equipment


Fire Hydrant - HYF2, HYF3, HYF4 & HYF5 Parts

HYF2 & 3 HYF4 & 5


No. Description No. Description
1 Operating handle 1 Operating handle
2 Operating nut 2 Operating nut

TD3.2.3.1/23052018-04022019/en | Update: Pumper and hose outlet information


3 Cover 3 Cover
4 Cover bolt 4 Cover bolt
5 Upper barrel 5 Bushing
6 Upper stem 6 Connecting stem
7 Claw bolts 7 Upper barrel
8 O-ring 8 Upper stem
9 Claw 9 Stem coupling
10 Nut 10 Pedestal
11 Lower stem assembly 11 Bolts
12 Lower barrel 12 Lower stem
13 Bottom bolts 13 Spring seat
14 Automatic drain assembly 14 Spring
15 90° bend 15 Lower barrel
16 O-ring 16 Bottom boltgaskt & nut
17 Cover sheet 17 Automatic drain assembly
18 O-ring 18 Seal
19 Stem coupling 19 Seal seat
20 Stem coupling bolt 20 Bend (90° or 180° typa)
21 Stem coupling nut

www.viking-emea.com

FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

6. Certificate
Letter of Origin
E
PL
M
SA

Page 37
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

7. Manufacturer
Data Sheet
MATERIAL SCHEDULE‐ EXTERNAL VALVES & ABOVE GROUND HYDRANT 

S.No. Material Description  Model  Make  COO 


1  NRS Gate Valve with Indicator Post Assembly 
NRS Gate Valve, EN1092‐2 PN16, 
1.1  PIF  Fireking by Viking  USA 
Working pressure 21 Bar, Flanged 
1.2  Indicator Post Vertical  IPV  Fireking by Viking  USA 

2  NRS Gate Valve with Valve Composite Box 
NRS Gate Valve, EN1092‐2 PN16, 
2.1  PIF  Fireking by Viking  USA 
working pressure 21 Bar, Flanged 
2.2  Valve Composite Box with T Wrench  Custom Made  VASS  Qatar 

3.  Above ground Hydrant Valve with Instantaneous Coupling 
Above ground Dry Barrel Fire Hydrant, 
Fire King by 
3.1  6” /DN150 Flanged with Instantaneous  HYF3  USA 
Viking 
Coupling, Cap & Chain 
NRS Gate Valve with Indicator Post Assembly
Post Indicator Valve - Flanged
PIF & PIF2

Control Valves
Technical Features
• Sizes available (Nominal) : 2”/DN50, 2½”/DN65,
3”/DN80, 4”/DN100, 5”/DN125, 6”/DN150,
8”/DN200, 10”/DN250 and 12”/DN300
• Working pressure : 21 bar (300 psi)
• Seat type : Resilient wedge
• Finish : Fusion bonded epoxy coated internal & external
• Connections : Flange diameter and thickness according
to ANSI B16.1 Class 125, EN1092-2 PN10 or EN1092-2
PN16
• Specifications : Design and dimensions conform to
AWWA C515
• Operation : For use with IPV or IPW indicator posts
• Remark : No post flange supplied with 2”, 2½” & 3”,
and size 2” is FM approved only and size 5” is UL listed
only * Image depicts 4”-14” sizes, 2”-3” not supplied
with Post Plate

Post Indicator Valve - Flanged - PIF & PIF2 Physical Data


Nominal Pipe
Dimensions (mm) Reference****
Size Weight
D1 n-ØL (kg)
inch Metric L H D C ANSI PN10 PN16
ANSI PN16 PN10 ANSI PN16 PN10
2”* DN50*** 178 278 152 16.0 120.7 125 4-Ø19.1 PIF-0200 PIF-0200PN 12.9
2½” DN65*** 190 300 178 17.5 139.7 145 4-Ø19.1 PIF-0250 PIF-0250PN 15.9
3” DN80*** 203 321 191 19.1 152.4 160 4-Ø19.1 8-Ø19.1 PIF-0300 PIF-0300PN 20.9
4” DN100 229 395 229 19.1 190.5 180 8-Ø19.1 8-Ø19.1 PIF-0400 PIF-0400PN 35.7
5”** DN125 254 432 254 19.1 215.9 210 8-Ø22.2 8-Ø19.1 PIF-0500 PIF-0500PN 44.6

Datasheet updates the datashet of 30-11-2015 (revised L dimension for 12” valve)
6” DN150 267 475 279 19.1 241.3 240 8-Ø22.2 8-Ø23 PIF-0600 54.2
8” DN200 292 585 343 22.2 298.5 295 8-Ø22.2 12-Ø23 8-Ø23 PIF-0800 PIF-0800PN10 PIF-0800PN16 86.1
10” DN250 330 656 406 23.8 362.0 355 350 12-Ø25.4 12-Ø28 12-Ø23 PIF-1000 PIF-1000PN10 PIF-1000PN16 117.2
12” DN300 356 751 483 25.4 431.8 410 400 12-Ø25.4 12-Ø28 12-Ø23 PIF-1200 PIF-1200PN10 PIF-1200PN16 180.0
* FM Approved only ** UL Listed only *** No post plate - flange supplied , UL Listed as PIF2, **** Valve flange drilling (size and location of bolt holes and pitch circle diameter) allows mating with the
following flange types :
ANSI = ANSI B16.1 Class 125 PN10 = DIN 2501, BS 4504, EN 1092 - PN10 PN16 = DIN 2501, BS 4504, EN 1092 - PN16

Post Indicator Valve - Flanged - PIF & PIF2 Materials List


Item Description Material ASTM Specifications Item Description Material ASTM Specifications
1 Valve Body Ductile Iron ASTM A536 64-45-12 12 Bolt Carbon Steel Zinc Plated
2 Wedge Disc Ductile Iron ASTM A536 64-45-12 & EPDM 13 Flat Washer Carbon Steel Zinc Plated
3 Stem Stainless Steel AISI 431 14 Ring Wiper EPDM Commercial
4 Bonnet Gasket EPDM Commercial 15 O-Ring NBR Commercial
5 Bonnet Ductile Iron ASTM A536 64-45-12 16 Axis Guide Brass Hpb59-1
6 O-Ring NBR Commercial 17 Washer Brass Hpb59-1
7 Gland Ductile Iron ASTM A536 64-45-12 18 O-Ring NBR Commercial
8 Post Flange Ductile Iron ASTM A536 64-45-12 19 Bolt Carbon Steel Zinc Plated
13-07-2016

9 Square Operating Nut Ductile Iron ASTM A536 64-45-12 20 Wedge Nut Brass Hpb59-1
10 Bolt Carbon Steel Zinc Plated 21 Plug Bronze ASTM B584 C89833
11 Flat Washer Carbon Steel Zinc Plated

Worldwide Fire Protection www.viking-emea.com

FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
Post Indicator Valve - Flanged
PIF & PIF2

Control Valves
Installation Inspection and Maintenance
1. Piping systems and valves should be 1. Valves should be inspected periodically and
thoroughly cleaned and free from ingress of should be cycled to prevent buildup of foreign
foreign materials. materials in the piping system and valve body.
2. Visually inspect the valve seating and
ports for cleanliness immediately prior to
installation.
3. All valves should be independently supported
against movement and stress from the
connected piping system.
4. Ensure that the valve pressure rating is
compatible with service conditions.
5. Operate the valve at least once from the
open to closed position.
6. Gate valves are not suitable for throttling
applications.
7. Gate valves should be installed in the vertical
position on horizontal pipework and in the
horizontal position on vertical pipework.
8. See indicator post datashet for further
installation instructions.

Operation
Gate valves are manually operated multi-turn
valves and are opened by a handwheel or
other operating device, generally in a counter

Datasheet updates the datashet of 30-11-2015 (revised L dimension for 12” valve)
clockwise direction and then closed clockwise.

13-07-2016

Worldwide Fire Protection www.viking-emea.com

FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
Vertical Indicator Post
IPV

Indicator Posts
IPV - Vertical Indicator Post Physical Data
Dimensions (mm/inch) Weight
Reference
A B C D E F (kg)
IVP 1270 1006 759.5 292 190 305 98.7

IPV - Vertical Indicator Post Trench Depth


Trench Depth according to Valve Size
Reference Unit DN100/4” DN150/6” DN200/8” DN250/10” DN300/12”
Min. Max Min. Max Min. Max Min. Max Min. Max
IVP mm 958 1808 1073 1923 1200 2050 1314 2164 1448 2298

IPV - Vertical Indicator Post Specifications


• Indicator of “Open” and “Shut” positions
• Used to operate a buried or hidden post indicator valve
• 850 mm adjustment range
• Wrench handle fits over a “U” bracket on the barrel, this can
be fixed with a padlock to secure the operating wrench to the
barrel
• Internally and externally coated in red epoxy RAL3000
• 2.5 m long stem bar is supplied

IPV Materials List


Part Weight
Item Part Material Specification
Number (kg.)
1 Hex Nut Carbon Steel Zinc Plated - -
2 Hex Bolt Carbon Steel Zinc Plated - -
3 Socket Ductile Iron A536, 65-45-12 IPV-SOCK 2.42
4 Cotter Pin Stainless Steel AISI 304 IPV-COTT 0.02
5 Base Flange Cast Iron ASTM A126 Class B IPV-BF 14.52
6 Hex Bolt Carbon Steel Zinc Plated - -
7 Hex Nut Carbon Steel Zinc Plated - -
8 Standpipe Carbon Steel ASTM A53 - -
9 Stem 1" Square Carbon Steel AISI 1045 IPV-STEM 12.18
10 Body Cast Iron ASTM A126 Class B
11 Locking Wrench Ductile Iron A536, 65-45-12 IPV-WREN 3.56
12 Target Carrier Nut Stainless Steel AISI 304 - -
13 Hex Bolt Carbon Steel Zinc Plated - -
14 Hex Nut Carbon Steel Zinc Plated - -
15 Hex Bolt Carbon Steel Zinc Plated - -
Target - Open IPV-OPEN 0.07
16 Cast Aluminum
Target - Shut IPV-SHUT 0.07
17 Window Class Plexiglass IPV-WIN 0.03
18 Window Gasket PTFE IPV-WG 0.01
19 Operating Nut Stainless Steel AISI 304 - -
Datasheet Created

20 Top Section Cast Iron ASTM A126 Class B - -


21 Snap Ring AISI 1066 - -
22 Plug Malleable Iron Galvanized - -
23 Square Nut Carbon Steel Zinc Plated - -
24 Hex Bolt Carbon Steel Zinc Plated - -
09-03-2015

25 Hex Bolt Carbon Steel Zinc Plated - -


26 Hex Nut Carbon Steel Zinc Plated - -

Worldwide Fire Protection www.viking-emea.com

FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
Vertical Indicator Post
IPV

Indicator Posts
Installation of the Target Carrier Assembly. Locate the two
“Shut” Targets according to the size of the post
NOTE: Ensure that the post indicator valve is in indicator valve size (stem) turning distance.
the fully open position before installing the Vertical - If the post indicator valve is opened by turning
Indicator Post. the handwheel clockwise:
1.) Disassemble the Indicator Post Move the two “Shut” Targets to the very top of
Take off the Locking Wrench (11), loosen the two the Target Carrier Assembly (12, 13 & 14). Locate
Hex bolt (24) and Square Nut (23) and remove the the two “Open” Targets (16) according to the size
Top Section (20), operating nut assembly and the of the post indicator valve (stem) turning distance.
Square Stem (9) as well as the socket (3). Slide off 6.) Final Assembly and Test
the Body (10) from the Standpipe (8) by loosening Insert the Target Carrier Assembly (12, 13 &
the two Hex Bolts (6) and Hex Nuts (7), slide off the 14) back into the Top Section (20) by rotating
Standpipe (8) from the Base Flange (5). the Operating Nut (19) clockwise. Rotate the
2.) Install the Base Flange and Lower Operating Nut (19) until the “Open” Target (16) is
Standpipe centered in the window of the Body (10). Lower
Attach the Base Flange (5) together with the the Top Section (20) with the Target Carrier
Standpipe (8) to the Post Flange of the post Assembly (12, 13 & 14) onto the Body (10),
indicator valve using the four Hex nuts (1) and Hex carefully ensuring that the Stem (9) engages with
bolts (2). Fix the Standpipe (8) to the Base Flange the Operating Nut (19) at least 50mm (2 in) but
(5) using the Hex Bolt (6) and Hex Nut (7). not more than 120mm (4.5 in). Secure the Top
Section (20) to the Body (10) by tightening the
3.) Adjust the Ground Line Mark
hex bolt (24) and Square Nut (23). Close the post
Pull the Body (10) over the Standpipe (8) until the
indicator valve and check to make sure that the
Ground Line Mark on the Body (10) is the same
“Shut” Target is properly centered in the window
height as the ground level. Tighten the two Hex
of the Body (10) and adjust as necessary.
Nuts (6) and Hex Bolts (7).
4.) Adjust the Square Stem
Lower the Stem (9) into the Body (10) such that the
socket (3) fits over the operating nut of the post Maintenance
indicator valve.
Ensure that Stem (9) engages the Operating Nut Lubrication
(19) a minimum of 2” but no more than 4.5”. To Oil the bearing in the Top Section (20) at least once
check for correct engagement, the end of stem a year by adding several drops of oil in the hole
should be 2 to 4 inches below the top of the Body located on the top of the Operating Nut (19).
(10).
5.) Adjust the Targets
Remove the Target Carrier Assembly (12, 13 & 14)
from inside the Body (10) by rotating the Operating
Nut (19) counter-clockwise. The “Open” Target (16)
and “Shut” Target (16) are adjusted up and down
on the Target Carrier Assembly (12, 13 & 14) by
pulling the middle section of the Target (Open &
Shut) a small distance away from the Target Carrier
Datasheet Created

Assembly (12, 13 & 14) and sliding the Target (Open


& Shut) up or down as desired.
- If the post indicator valve is opened by turning the
handwheel counter clockwise:
09-03-2015

Move the two Open Targets (16) to the very top

Worldwide Fire Protection www.viking-emea.com

FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
NRS Gate Valve with Valve Composite Box
Post Indicator Valve - Flanged
PIF & PIF2

Control Valves
Technical Features
• Sizes available (Nominal) : 2”/DN50, 2½”/DN65,
3”/DN80, 4”/DN100, 5”/DN125, 6”/DN150,
8”/DN200, 10”/DN250 and 12”/DN300
• Working pressure : 21 bar (300 psi)
• Seat type : Resilient wedge
• Finish : Fusion bonded epoxy coated internal & external
• Connections : Flange diameter and thickness according
to ANSI B16.1 Class 125, EN1092-2 PN10 or EN1092-2
PN16
• Specifications : Design and dimensions conform to
AWWA C515
• Operation : For use with IPV or IPW indicator posts
• Remark : No post flange supplied with 2”, 2½” & 3”,
and size 2” is FM approved only and size 5” is UL listed
only * Image depicts 4”-14” sizes, 2”-3” not supplied
with Post Plate

Post Indicator Valve - Flanged - PIF & PIF2 Physical Data


Nominal Pipe
Dimensions (mm) Reference****
Size Weight
D1 n-ØL (kg)
inch Metric L H D C ANSI PN10 PN16
ANSI PN16 PN10 ANSI PN16 PN10
2”* DN50*** 178 278 152 16.0 120.7 125 4-Ø19.1 PIF-0200 PIF-0200PN 12.9
2½” DN65*** 190 300 178 17.5 139.7 145 4-Ø19.1 PIF-0250 PIF-0250PN 15.9
3” DN80*** 203 321 191 19.1 152.4 160 4-Ø19.1 8-Ø19.1 PIF-0300 PIF-0300PN 20.9
4” DN100 229 395 229 19.1 190.5 180 8-Ø19.1 8-Ø19.1 PIF-0400 PIF-0400PN 35.7
5”** DN125 254 432 254 19.1 215.9 210 8-Ø22.2 8-Ø19.1 PIF-0500 PIF-0500PN 44.6

Datasheet updates the datashet of 30-11-2015 (revised L dimension for 12” valve)
6” DN150 267 475 279 19.1 241.3 240 8-Ø22.2 8-Ø23 PIF-0600 54.2
8” DN200 292 585 343 22.2 298.5 295 8-Ø22.2 12-Ø23 8-Ø23 PIF-0800 PIF-0800PN10 PIF-0800PN16 86.1
10” DN250 330 656 406 23.8 362.0 355 350 12-Ø25.4 12-Ø28 12-Ø23 PIF-1000 PIF-1000PN10 PIF-1000PN16 117.2
12” DN300 356 751 483 25.4 431.8 410 400 12-Ø25.4 12-Ø28 12-Ø23 PIF-1200 PIF-1200PN10 PIF-1200PN16 180.0
* FM Approved only ** UL Listed only *** No post plate - flange supplied , UL Listed as PIF2, **** Valve flange drilling (size and location of bolt holes and pitch circle diameter) allows mating with the
following flange types :
ANSI = ANSI B16.1 Class 125 PN10 = DIN 2501, BS 4504, EN 1092 - PN10 PN16 = DIN 2501, BS 4504, EN 1092 - PN16

Post Indicator Valve - Flanged - PIF & PIF2 Materials List


Item Description Material ASTM Specifications Item Description Material ASTM Specifications
1 Valve Body Ductile Iron ASTM A536 64-45-12 12 Bolt Carbon Steel Zinc Plated
2 Wedge Disc Ductile Iron ASTM A536 64-45-12 & EPDM 13 Flat Washer Carbon Steel Zinc Plated
3 Stem Stainless Steel AISI 431 14 Ring Wiper EPDM Commercial
4 Bonnet Gasket EPDM Commercial 15 O-Ring NBR Commercial
5 Bonnet Ductile Iron ASTM A536 64-45-12 16 Axis Guide Brass Hpb59-1
6 O-Ring NBR Commercial 17 Washer Brass Hpb59-1
7 Gland Ductile Iron ASTM A536 64-45-12 18 O-Ring NBR Commercial
8 Post Flange Ductile Iron ASTM A536 64-45-12 19 Bolt Carbon Steel Zinc Plated
13-07-2016

9 Square Operating Nut Ductile Iron ASTM A536 64-45-12 20 Wedge Nut Brass Hpb59-1
10 Bolt Carbon Steel Zinc Plated 21 Plug Bronze ASTM B584 C89833
11 Flat Washer Carbon Steel Zinc Plated

Worldwide Fire Protection www.viking-emea.com

FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
Post Indicator Valve - Flanged
PIF & PIF2

Control Valves
Installation Inspection and Maintenance
1. Piping systems and valves should be 1. Valves should be inspected periodically and
thoroughly cleaned and free from ingress of should be cycled to prevent buildup of foreign
foreign materials. materials in the piping system and valve body.
2. Visually inspect the valve seating and
ports for cleanliness immediately prior to
installation.
3. All valves should be independently supported
against movement and stress from the
connected piping system.
4. Ensure that the valve pressure rating is
compatible with service conditions.
5. Operate the valve at least once from the
open to closed position.
6. Gate valves are not suitable for throttling
applications.
7. Gate valves should be installed in the vertical
position on horizontal pipework and in the
horizontal position on vertical pipework.
8. See indicator post datashet for further
installation instructions.

Operation
Gate valves are manually operated multi-turn
valves and are opened by a handwheel or
other operating device, generally in a counter

Datasheet updates the datashet of 30-11-2015 (revised L dimension for 12” valve)
clockwise direction and then closed clockwise.

13-07-2016

Worldwide Fire Protection www.viking-emea.com

FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
MVB composite Valve Box
Reliable
ReliableConnections
Connections
TM
TM

Product Features
• Bevelled edge Ductile Iron Adjustable • Easily cuts to required length with
Top available in 2 sizes – 12” (305mm) ordinary hand tools.
and 27” (686mm). • Impact-resistant, corrosion-proof polymer
• Tops are self-leveling and self-adjusting. lower section.
WATER
• Light weight – no special heavy
equipment required to install.

The advanTage of using The adjusTable valve box Top –


valve box moves wiTh any surface movemenT.

BEFORE Cover

WATER WATER

Top

Cover AFTER Cover

Top Top

parts list
ID Part Name Material
1 T-Wrench* 2–7 Ft. (see Note 1) Cast Iron
2 MVB Extension Stem* 2–12 Ft. (see Note 1) Ductile Iron
3 Beveled Adjustable Top Ductile Iron
4 MVB Bottom Section Non-abrasive Polymer
5 Lid Cast Iron
6 Cover Cast Iron

Vijay Arabia Fire & Security Systems W.L.L.


P.O.Box: 31146, C.R.No.38572, Doha Qatar
Tel. No. : (+974) 40190900 Fax No: (974) 44364993
Email : info@vijayarabia.com Web : www.vijayarabia.com
E
ØF Dimensions – inches (mm)
ØG
C D E ØF ØG ØH J
D 31/2 (89) 11/2 (38) 65/8 (168) 55/8 (140) 5 (127) 93/16 (233) 93/4 (248)
C
Lid A – Ductile Iron Adjustable Top ®
Lid
A Part No. Length Wt.– Lbs (Kg) Part No. Wt.– Lbs (Kg)
Adjustable Top
AJBV-4D 12” (305mm) 22 (10) AJBV-4C Water 11.0 (5.0)
AJBV-4D-27 27” (686mm) 33 (15)

MVB Extention Stems* (sold separately)


Part No. Size/Description
MVB 234079 2’ Extension Stem w/2” Operating Nut and 2” Socket
Extension Stem 234095 4’ Extension Stem w/2” Operating Nut and 2” Socket
(sold separately)
WATER 234117 6’ Extension Stem w/2” Operating Nut and 2” Socket

MVB
234133 8’ Extension Stem w/2” Operating Nut and 2” Socket
Bottom 234168 10’ Extension Stem w/2” Operating Nut and 2” Socket
Section
234184 12’ Extension Stem w/2” Operating Nut and 2” Socket
B NOTE: Stem Should be 1’ Shorter then Box

T-Wrench* – with 2” Socket


Part No. Description Wt.– Lbs (Kg)
020A24610 2’ T-Wrench w/2” Socket 11 (5)
T-Wrench 030A24610 3’ T-Wrench w/2” Socket 13 (6)
040A24610 4’ T-Wrench w/2” Socket 15 (7)
050A24610 5’ T-Wrench w/2” Socket 17 (8)
060A24610 6’ T-Wrench w/2” Socket 19 (9)
070A24610 7’ T-Wrench w/2” Socket 22 (10)

J
composite – with 12” Adjustable Top ®

Part No. Length of B Max. Extension Wt.– Lbs (Kg)


MVB030C 3’ (0.91m) 3’6” (1.1m) 39.2 (17.8)
MVB050C 5’ (1.6m) 5’6” (1.7m) 41.8 (19.0)
ØH
MVB070C 7’ (2.2m) 7’6” (2.3m) 44.4 (20.2)
B* – MVB Bottom Section WATER Cover MVB090C 9’ (2.8m) 9’6” (2.9m) 47.0 (21.4)
MVB110C 11’ (3.3m) 11’6” (3.5m) 49.6 (22.6)
Part No. Length Wt.– Lbs (Kg) MVB130C 13’ (3.9m) 13’6” (4.1m) 52.2 (23.8)
MVB030 3’ (0.91m) 6.2 (2.8)
MVB050 5’ (1.6m) 8.8 (4.0) composite – with 27” Adjustable Top ®

MVB070 7’ (2.2m) 11.4 (5.2)


MVB090 9’ (2.8m) 14.0 (6.4) Part No. Length of B Max. Extension Wt.– Lbs (Kg)
MVB110 11’ (3.3m) 16.6 (7.6) MVB030C-27 3’ (0.91m) 4’6” (1.4m) 50.2 (22.8)
MVB130 13’ (3.9m) 19.2 (8.8) MVB050C-27 5’ (1.6m) 6’6” (1.9m) 52.8 (24.0)
MVB070C-27 7’ (2.2m) 8’6” (2.5m) 55.4 (25.2)
MVB090C-27 9’ (2.8m) 10’6” (3.2m) 58.1 (26.4)
MVB110C-27 11’ (3.3m) 12’6” (3.8m) 60.6 (27.6)
MVB130C-27 13’ (3.9m) 14’6” (4.4m) 63.2 (28.8)
*Other lengths/sizes available on request.
Vijay Arabia Fire & Security Systems W.L.L.
P.O.Box: 31146, C.R.No.38572, Doha Qatar
Tel. No. : (+974) 40190900 Fax No: (974) 44364993
Email : info@vijayarabia.com Web : www.vijayarabia.com
Above ground Hydrant Valve with Instantaneous Coupling
Fire Hydrant
HYF2-5 Dry Barrel Fire Hydrant

Fire Hydrants & Equipment


Technical features
• Pressure data:
Working pressure: 17.2 bar (250 psi)
• Shell Material: Ductile Iron
• Stem: Brass (HYF4/5) or Steel (HYF2/3) for improved

B
corrosion resistance
• Finish: Red & black epoxy paint
Interior & exterior to AWWA C550
• Connections:
HYF2 & 5 - 4”/DN100 Flange PN16/ANSI
HYF3 & 4 - 6”/DN150 Flange PN16/ANSI
• Water Use: Non-potable water only
• Collision: Model HYF4 & HYF5 designed to maintain seal
should the hydrant suffer a collision
• 1 x Pumper Outlet:
HYF2 & 3 - 4” NH/Storz/BSRT

L
HYF4 & 5 - 4” UNE/AR/Storz
• 2 x Hose Outlet:
HYF2 & 3 - 2-1/2” NH/Storz/BS336
HYF4 & 5 - 2-1/2” UNE/DSP/Storz
• Approvals: LPCB
• Specification: EN14384
• Note: All hydrants include automatic drain to drain down
the barrel after closing the hydrant - this minimises the risk

A
of damage from freezing

Note: Diagram only representative for dimensional purposes

Fire Hydrant - HYF2-5 Part Numbers & Dimensions


Dimensions (mm) MOT* MST** Closing Opening Drain Retained
Model Connection Kv
A B L (Nm) (Nm) Direction Turns time (min) Water (ml)
680

TD3.2.3.1/23052018-04022019/en | Update: Pumper and hose outlet information


HYF2 DN100 PN16 306 494 1080 105 ≤125 ≥250 Clockwise 16 ≤10 ≤150
1325
480
680
HYF3 DN150 PN16 305 569 1080 184 ≤125 ≥250 Clockwise 15 ≤10 ≤200
1380
1580
300
563
HYF4 DN150 PN16 321 565 223 ≤125 ≥250 Clockwise 11 ≤10 ≤150
680
0
300
453
HYF5 DN100 PN16 321 565 112 ≤125 ≥250 Clockwise 11 ≤10 ≤150
680
0
* Maximum Operating Torque | ** Minimum Strength Torque

www.viking-emea.com

FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
Fire Hydrant
HYF2-5 Dry Barrel Fire Hydrant

Fire Hydrants & Equipment


Fire Hydrant - HYF2, HYF3, HYF4 & HYF5 Parts

HYF2 & 3 HYF4 & 5


No. Description No. Description
1 Operating handle 1 Operating handle
2 Operating nut 2 Operating nut

TD3.2.3.1/23052018-04022019/en | Update: Pumper and hose outlet information


3 Cover 3 Cover
4 Cover bolt 4 Cover bolt
5 Upper barrel 5 Bushing
6 Upper stem 6 Connecting stem
7 Claw bolts 7 Upper barrel
8 O-ring 8 Upper stem
9 Claw 9 Stem coupling
10 Nut 10 Pedestal
11 Lower stem assembly 11 Bolts
12 Lower barrel 12 Lower stem
13 Bottom bolts 13 Spring seat
14 Automatic drain assembly 14 Spring
15 90° bend 15 Lower barrel
16 O-ring 16 Bottom boltgaskt & nut
17 Cover sheet 17 Automatic drain assembly
18 O-ring 18 Seal
19 Stem coupling 19 Seal seat
20 Stem coupling bolt 20 Bend (90° or 180° typa)
21 Stem coupling nut

www.viking-emea.com

FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
Fire Hydrant
HYF2-5 Dry Barrel Fire Hydrant

Fire Hydrants & Equipment


Fire Hydrant - HYF2-5 Installation, operation & maintenance

Installation
1. Hydrants should be handled with care to avoid damage. It is recommended to keep hydrants closed until use.
2. If the hydrant is not to be used straight away then it is recommended to coat threads and other machined parts with
an anti-rust oil and the hydrant should be stored in a dry and ventilated area. For long-term storage, the hydrant
should be checked regularly.
3. Before installation of hydrants, the connection should be free from dirt or other matter.
4. The positioning of the hydrant should be in accordance with local requirements. Ideally the pumper should face the
street and all connections should be away from any obstruction to connecting hoses.
5. The inlet elbow should be placed on a solid surface and if possible brace the side opposite the incoming flow to
reduce reaction stresses.
6. The underground parts of the hydrant should be surrounded with coarse gravel for support and drainage.
7. After the hydrant has been installed and tested, it is recommended to fully flush the hydrant before closing for
service. Before replacing the nozzle caps, it is recommended to check for correct drainage of the hydrant on closing
of the valve. This can be achieved by placing a hand over the nozzle opening, a suction should be felt.

Operation
1. Unscrew the nozzle caps and connect hoses.
2. Open the hydrant using the hydrant key (included) to the fully open position by turning the valve nut in an
anti-clockwise direction – do not force the hydrant to open further past the fully open position. Note that the
hydrant valve is not intended to control the flow, it should be used in either the fully open or fully closed position.
To control flow, a pressure/flow control valve should be fitted to the nozzle outlets on the hydrant.
3. To close, turn the valve nut in a clockwise direction – again, do not over tighten.

Maintenance
1. Carry out a visual inspection for signs of significant corrosion which may impair performance.
2. Where possible, carry out leak tests by opening one of the nozzle caps slightly and then opening the hydrant valve.
Once the air has escaped tighten the hose cap and check for leaks.
3. Close hydrant and remove one nozzle cap so that the drainage can be checked.
4. Flush the hydrant.
5. Clean and lubricate all nozzle threads.
6. Clean the exterior of the hydrant and repaint if required.

TD3.2.3.1/23052018-04022019/en | Update: Pumper and hose outlet information

www.viking-emea.com

FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

8. Material Safety
Data Sheet
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

NOT APPLICABLE
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

9. Manufacturer’s
Test
Certificates
LPCB® www.redbooklive.com

Products Standards
'Viking Corp' Fireking Pillar Fire Hydrants EN 14384:2005
1refe1 to attacheci .:ippend1x for de ;ills P a re I ydranh

Th is cert1fic,1te and af)pend1x s mcl nta1 1ed a 1d held 11° for e throuoih I egu ar sc1rve,lla1 re ac.: v tte'> Jnd
sc1bJeLt to tl 1 e cor'espond11g l\tJ -1001 Cert1+1c,He he 11g 1"'a11ta1red

'>Jr ,1 11 c.. 01we 15 Jal'UilY 2Ll18 1J 'lf U,1ry 2 8


Ve '_ ,.... E- f ,s ,. ) tr • s•

bre
,.i. (.,
‫‪2020-09-30‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻟﻄﺒﺎﻋﺔ ‪:‬‬ ‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴــــﺔ‬
‫‪AM 8:07‬‬ ‫ﻭﻗـﺖ ﺍﻟﻄﺒﺎﻋﺔ ‪:‬‬ ‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬
‫‪PAC20010201‬‬ ‫ﺭﻗــﻢ ﺍﻟﻄﻠـﺐ ‪:‬‬ ‫ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺷﻬــــــﺎﺩﺓ ﻋﺪﻡ ﻣﻤﺎﻧﻌﺔ‬

‫‪ :‬ﺍﻋﺘﻤﺎﺩ ﻣﻨﺘﺞ‬ ‫ﻧﻮﻉ ﺍﻟﺸﻬﺎﺩﺓ‬

‫ﺑﻴﺎﻧﺎﺕ ﺍﻟﻤﻨﺸﺄﺓ‬

‫‪ :‬ﺷﺮﻛﻪ ﻓﻴﺠﺎﻯ ﺍﻟﻌﺮﺑﻴﻪ ﻟﻠﺤﺮﻳﻖ ﻭﺍﻻﻧﻈﻤﻪ ﺍﻻﻣﻨﻴﻪ‬ ‫ﺍﻹﺳﻢ ﺍﻟﺘﺠﺎﺭﻱ‬


‫‪63162 :‬‬ ‫ﺭﻗﻢ ﺍﻟﺮﺧﺼﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ‬ ‫‪38572 :‬‬ ‫ﺭﻗﻢ ﺍﻟﺴﺠﻞ ﺍﻟﺘﺠﺎﺭﻱ‬
‫‪:‬‬ ‫ﺭﻗﻢ ﺍﻟﻬﺎﺗﻒ‬ ‫‪12-6790-00 :‬‬ ‫ﺭﻗﻢ ﻗﻴﺪ ﺍﻟﻤﻨﺸﺄﺓ‬
‫‪:‬‬ ‫ﺍﻟﺒﺮﻳﺪ ﺍﻹﻟﻜﺘﺮﻭﻧﻲ‬
‫‪Fire Fighting Systems :‬‬ ‫ﺍﻟﺘﺼﻨﻴﻒ‬
‫‪Fire Hydrants /Monitor :‬‬ ‫ﺇﺳﻢ ﺍﻟﻤﻨﺘﺞ‬

‫ﺗﻔﺎﺻﻴﻞ ﺍﻟﺸﻬﺎﺩﺓ‬

‫ﺗﻢ ﻣﺮﺍﺟﻌﺔ ﺍﻟﻄﻠﺐ ﺍﻟﻤﻘﺪﻡ ﻭﺍﺗﻀﺢ ﺑﺄﻧﻪ ﻻ ﻣﺎﻧﻊ ﻣﻦ ﺍﻋﺘﻤﺎﺩ ﺍﻟﻤﻨﺘﺞ ‪/‬ﺍﻟﻤﻨﺘﺠﺎﺕ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻰ ﺍﻟﻤﺮﻓﻖ ﺑﻨﺎﺀ ﻋﻠﻰ ﺍﻋﺘﻤﺎﺩﻩ ﻣﻦ ﻗﺒﻞ ﺍﻟﻬﻴﺌﻪ‬
‫ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﺭ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ‪.‬‬

‫ﻣﻼﺣﻈﺎﺕ‬

‫‪ .1‬ﻳﺠﺐ ﻋﻠﻰ ﺍﻟﺸﺮﻛﻪ ﺍﻻﻟﺘﺰﺍﻡ ﻭﺍﻟﻌﻤﻞ ﺑﻤﺎ ﺟﺎﺀ ﻓﻲ ﺍﺷﺘﺮﺍﻃﺎﺕ ﻗﺴﻢ ﺃﻧﻈﻤﺔ ﺍﻟﺴﻼﻣﻪ ﺍﻟﺘﻲ ﺗﻢ ﺍﻻﻃﻼﻉ ﻭﺍﻟﻤﻮﺍﻓﻘﺔ ﻋﻠﻴﻬﺎ ﻣﻦ ﺧﻼﻝ ﺍﻟﻤﻮﻗﻊ‪.‬‬
‫‪ .2‬ﻳﺠﺐ ﺍﻥ ﻳﻘﻮﻡ ﺑﺘﺮﻛﻴﺐ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ ﻣﻦ ﻗﺒﻞ ﻣﻬﻨﺪﺳﻴﻦ ﻭﻓﻨﻴﻴﻦ ﻣﻌﺘﻤﺪﻳﻦ ﻣﻦ ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‪.‬‬
‫‪ .3‬ﻳﺠﺐ ﺍﻥ ﻳﺤﻤﻞ ﺍﻟﻤﻨﺘﺞ ﺍﻟﻌﻼﻣﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ ﻟﻠﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻌﺘﻤﺪﺓ ﻭﺍﻟﻤﻮﺿﺤﻪ ﻓﻲ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ ‪.‬‬

‫‪2022-09-29‬‬ ‫‪:‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻹﻧﺘﻬﺎﺀ‬ ‫‪2020-09-29‬‬ ‫‪:‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻻﻋﺘﻤﺎﺩ‬

‫ﻉ‪/‬‬

‫ﻣﺪﻳﺮ ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬

‫‪Page 1 of 2‬‬
‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
DATE : 2020-09-30 : ‫ﺍﻟﺘﺎﺭﻳـــــــﺦ‬
‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬
PERMIT # PAC20010201 : ‫ﺭﻗﻢ ﺍﻟﻄﻠﺐ‬
‫ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

TECHNICAL REPORT ‫ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ‬


PRODUCT Fire Hydrants /Monitor ‫ﻣﻨﺘﺞ‬
PRODUCT APPLICATION Fire Fighting Systems ‫ﺗﺼﻨﻴﻒ ﺍﻟﻤﻌﺪﺓ‬
APPLICANT / P.O BOX ‫ﺷﺮﻛﻪ ﻓﻴﺠﺎﻯ ﺍﻟﻌﺮﺑﻴﻪ ﻟﻠﺤﺮﻳﻖ ﻭﺍﻻﻧﻈﻤﻪ ﺍﻻﻣﻨﻴﻪ‬ ‫ﻣﻘﺪﻡ ﺍﻟﻄﻠﺐ‬
MANUFACTURER / LOCATION VIKING CORP. / USA ‫ ﺑﻠﺪ ﺍﻟﺼﻨﻊ‬/ ‫ﺍﻟﺸﺮﻛﺔ ﺍﻟﻤﺼﻨﻌﺔ‬
‫ﺍﻟﻮﺻﻒ‬ ‫ﺍﻟﻤﻮﺩﻳﻞ‬
Viking Corp Fireking Pillar Fire Hydrants, 6 inch (DN 150) inlet size, 2 X 2.5 inch BSP (65mm)
HYF3
hose outlet, 1 x 4 inch BSP (100mm) pumper connection.
Viking Corp Fireking Pillar Fire Hydrants, 6 inch (DN 150) inlet size, 2 X 2.5 inch BSP (65mm)
HYF4
hose outlet, 1 x 4 inch BSP (100mm) pumper connection.
3RD PARTY CERTIFICATE / LOSS PREVENTION ‫ﺷﻬﺎﺩﺓ ﺍﻟﻤﺨﺘﺒﺮﺍﺕ ﺍﻟﻤﺴﺎﻧﺪﺓ‬
APPROVAL 096w CERTIFICATION BOARD
(LPCB-BRE) ( ‫)ﻣﻦ ﻫﻴﺌﺎﺕ ﻣﻌﺘﻤﺪﺓ‬

RECOMMENDATIONS ‫ﺍﻟﺘﻮﺻﻴﺎﺕ‬
MUST BE FITTED WITH BS 336 HOSE ADAPTOR.
Certificate No 096w to EN 14384:2005.

This product approval shall comply with the Design, Inspection, Installation, Testing and Maintenance requirements of
NFPA 24 (and/or other related NFPA Codes / Standards), other acceptable International Codes / Standards, Local
Regulations and/or Manufacturer's Published Instructions subject to the technical review and approval of the Authority
Having Jurisdiction (Qatar Civil Defence).

/‫ﻉ‬

‫ﻣﺪﻳﺮ ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬

Page 2 of 2
HMRZ.EX15003
Gate Valves

Page Bottom

Gate Valves

See General Information for Gate Valves

VIKING CORP EX15003


210 INDUSTRIAL PARK DR
HASTINGS, MI 49058-9706 USA

Rated
End Pressure,
Pattern Model Size, in. Configuration psig

NRS PIF 4, 5, 6, 8, 10, 12 F by F (ANSI Flange) 300

NRS PIG 4, 6, 8, 10, 12 G by G 300

OS&Y OSG 2, 2.5, 3, 4, 5, 6, 8, 10, 12 G by G 300

OS&Y OSF 2, 2.5, 3, 4, 5, 6, 8, 10, 12 F by F 300

OS&Y OSF2 2, 2.5, 3, 4, 5, 6, 8, 10, 12, 14, 16, 18, 20, 24 F by F (ANSI Flange) 250

NRS PIF3 2.5, 3, 4, 5, 6, 8, 10, 12, 14, 16, 18, 20, 24 F by F (ANSI Flange) 250

NRS PIF4 2.5, 3, 4, 5, 6, 8, 10, 12, 14, 16, 18, 20, 24 F by F (BS Flange) 232

OS&Y OSF3 2, 2.5, 3, 4, 5, 6, 8, 10, 12, 14, 16, 18, 20, 24 F by F (BS Flange) 232

NRS NRFL1 2.5, 3, 4, 5, 6, 8, 10, 12 F by F (ANSI Flange) 300

NRS NRFL3 2.5, 3, 4, 5, 6, 8, 10, 12, 14, 16, 18, 20, 24 F by F (BS Flange) 232

NRS PIF5 4, 5, 6, 8, 10, 12 F by F (BS Flange) 233

NRS NRFL2 2.5, 3, 4, 5, 6, 8, 10, 12, 14, 16, 18, 20, 24 F by F (ANSI Flange) 250

NRS NRGL1 2.5, 3, 4, 5, 6, 8, 10, 12 G by G 300

OS&Y OSF-1 2.5,3,4,5,6,8,10,12 Flange & Flange 300

NRS NRFL-4 2.5,3,4,5,6,8,10,12 Flange & Flange 300

Trademark and/or Tradename:

Last Updated on 2018-06-11

Questions? Print this page Terms of Use Page Top

© 2018 UL LLC

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under
UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up Service.
Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading
manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission
from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format:
"© 2018 UL LLC".

h ps://database.ul.com/cgi‐bin/XYV/template/LISEXT/1FRAME/show... 03/09/2018, 16:25
Inside Screw Gate Valves
Inside screw gate valves are used underground with indicator posts attached or as roadway box valves (curb box installation). FM
Approved valves are available with a variety of end connections as indicated in the listings.
Valves having Ring-Tite, Fluid-Tite or Tyton-Joint connections should be anchored in place during installation. Unless otherwise noted
in the listing, these valves have 175 psi (1205 kPa) rated working pressure.

Models PIF, PIG

Model PIF, PIG Resilient Seated Gate Valves. 2 through 12 in. NPS. Valves have a rated working pressure of 300 psi (2070 kPa).
Available with the following end connections.

Product Specification

Valve Size
Model No End Connection
in (mm)
Flange x Flange
PIF 2, 2 1/2, 3, 4, 6, 8, 10, 12 (50, 65, 80, 100, 150, 200, 250, 300)
(ANSI, BS, EN, JIS)
Groove x Groove
PIG 2, 2 1/2, 3, 4, 6, 8, 10, 12 (50, 65, 80, 100, 150, 200, 250, 300)
(AWWA C606)

Company Name: The Viking Corporation


Company Address: 5150 Beltway Dr SE, Caledonia, Michigan 49316, USA
Company Website: http://vikingcorp.com
New/Updated Product Listing: No
Listing Country: United States of America
Certification Type: FM Approved
Class of Work: 1130-OS&Y and NRS Gate Valves

© 2007-2020 FM Approvals. All rights reserved. Page 1 of 1


‫ﺗﺎﺭﻳﺦ ﺍﻟﻄﺒﺎﻋﺔ ‪2019-03-19 :‬‬ ‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴــــﺔ‬
‫ﻭﻗـﺖ ﺍﻟﻄﺒﺎﻋﺔ ‪ :‬ص ‪8:56‬‬ ‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﻪ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬
‫ﺭﻗــﻢ ﺍﻟﻄﻠـﺐ ‪PAC19003375 :‬‬ ‫ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺷﻬــــــﺎﺩﺓ ﻋﺪﻡ ﻣﻤﺎﻧﻌﺔ‬


‫ﺍﻋﺘﻤﺎﺩ ﻣﻨﺘﺞ‬ ‫ﻧﻮﻉ ﺍﻟﺸﻬﺎﺩﺓ ‪:‬‬

‫ﺑﻴﺎﻧﺎﺕ ﺍﻟﻤﻨﺸﺄﺓ‬

‫ﺷﺮﻛﻪ ﻓﻴﺠﺎﻯ ﺍﻟﻌﺮﺑﻴﻪ ﻟﻠﺤﺮﻳﻖ ﻭﺍﻻﻧﻈﻤﻪ ﺍﻻﻣﻨﻴﻪ‬ ‫ﺍﻻﺳﻢ ﺍﻟﺘﺠﺎﺭﻱ‪:‬‬


‫‪63162‬‬ ‫ﺭﻗﻢ ﺍﻟﺮﺧﺼﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ‪:‬‬ ‫‪38572‬‬ ‫ﺭﻗﻢ ﺍﻟﺴﺠﻞ ﺍﻟﺘﺠﺎﺭﻱ‪:‬‬
‫ﺭﻗﻢ ﺍﻟﻬﺎﺗﻒ‪:‬‬ ‫‪12-6790-00‬‬ ‫ﺭﻗﻢ ﻗﻴﺪ ﺍﻟﻤﻨﺸﺄﺓ‪:‬‬
‫ﺍﻟﺒﺮﻳﺪ ﺍﻹﻟﻜﺘﺮﻭﻧﻲ‪:‬‬
‫‪Fire Fighting systems‬‬ ‫ﺍﻟﺘﺼﻨﻴﻒ ‪:‬‬
‫)‪Valves (OS&Y,Butterfly,Globe,Check,Gate Relief Valves etc‬‬ ‫ﺇﺳﻢ ﺍﻟﻤﻨﺘﺞ ‪:‬‬

‫ﺗﻔﺎﺻﻴﻞ ﺍﻟﺸﻬﺎﺩﺓ‬

‫ﺗﻢ ﻣﺮﺍﺟﻌﺔ ﺍﻟﻄﻠﺐ ﺍﻟﻤﻘﺪﻡ ﻭﺍﺗﻀﺢ ﺑﺄﻧﻪ ﻻ ﻣﺎﻧﻊ ﻣﻦ ﺍﻋﺘﻤﺎﺩ ﺍﻟﻤﻨﺘﺞ ‪/‬ﺍﻟﻤﻨﺘﺠﺎﺕ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻰ ﺍﻟﻤﺮﻓﻖ ﺑﻨﺎﺀ ﻋﻠﻰ ﺍﻋﺘﻤﺎﺩﻩ ﻣﻦ‬
‫ﻗﺒﻞ ﺍﻟﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﺭ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ‪.‬‬

‫ﻣﻼﺣﻈﺎﺕ ‪:‬‬

‫‪ .1‬ﻳﺠﺐ ﻋﻠﻰ ﺍﻟﺸﺮﻛﻪ ﺍﻻﻟﺘﺰﺍﻡ ﻭﺍﻟﻌﻤﻞ ﺑﻤﺎ ﺟﺎﺀ ﻓﻲ ﺍﺷﺘﺮﺍﻃﺎﺕ ﻗﺴﻢ ﺃﻧﻈﻤﺔ ﺍﻟﺴﻼﻣﻪ ﺍﻟﺘﻲ ﺗﻢ ﺍﻻﻃﻼﻉ ﻭﺍﻟﻤﻮﺍﻓﻘﺔ ﻋﻠﻴﻬﺎ ﻣﻦ ﺧﻼﻝ ﺍﻟﻤﻮﻗﻊ ‪.‬‬
‫‪ .2‬ﻳﺠﺐ ﺍﻥ ﻳﻘﻮﻡ ﺑﺘﺮﻛﻴﺐ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ ﻣﻦ ﻗﺒﻞ ﻣﻬﻨﺪﺳﻴﻦ ﻭﻓﻨﻴﻴﻦ ﻣﻌﺘﻤﺪﻳﻦ ﻣﻦ ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‪.‬‬
‫‪ .3‬ﻳﺠﺐ ﺍﻥ ﻳﺤﻤﻞ ﺍﻟﻤﻨﺘﺞ ﺍﻟﻌﻼﻣﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ ﻟﻠﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻌﺘﻤﺪﺓ ﻭﺍﻟﻤﻮﺿﺤﻪ ﻓﻲ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ ‪.‬‬

‫‪18/03/2021‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻹﻧﺘﻬﺎﺀ ‪:‬‬ ‫‪19/03/2019‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻻﻋﺘﻤﺎﺩ ‪:‬‬

‫ﻉ‪/‬‬

‫ﻣﺪﻳﺮ ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗـﺎﻳـــــﺔ‬


‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬

‫‪Page 1 of 2‬‬
‫ﺑﺴﻢ ﺍﻟﻠﻪ ﺍﻟﺮﺣﻤﻦ ﺍﻟﺮﺣﻴﻢ‬

DATE : 2019-03-19 : ‫ﺍﻟﺘﺎﺭﻳـــــــﺦ‬ ‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬


PERMIT PAC19003375 : ‫ﺭﻗﻢ ﺍﻟﻄﻠﺐ‬ ‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬
‫ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

TECHNICAL REPORT ‫ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ‬

PRODUCT : Valves (OS&Y,Butterfly,Globe,Check,Gate Relief : ‫ﺍﻟﻤﻨﺘﺞ‬


Valves etc)
PRODUCT APPLICATION : Fire Fighting systems : ‫ﺗﺼﻨﻴﻒ ﺍﻟﻤﻌﺪﺓ‬
APPLICANT / P.O .Box ‫ﺷﺮﻛﻪ ﻓﻴﺠﺎﻯ ﺍﻟﻌﺮﺑﻴﻪ ﻟﻠﺤﺮﻳﻖ ﻭﺍﻻﻧﻈﻤﻪ ﺍﻻﻣﻨﻴﻪ‬ : ‫ﻣﻘﺪﻡ ﺍﻟﻄﻠﺐ‬
MANUFACTURER /
VIKING CORP. / USA :‫ ﺑﻠﺪ ﺍﻟﺼﻨﻊ‬/ ‫ﺍﻟﺸﺮﻛﺔ ﺍﻟﻤﺼﻨﻌﺔ‬
LOCATION :

‫ﺍﻟﻮﺻﻒ‬ ‫ﺍﻟﻤﻮﺩﻳﻞ‬
Inside Screw Gate Valves, resilient seated, 2, 2 1/2, 3, 4, 6, 8, 10, 12 inch sizes, Flange x
PIF
Flange end configuration, 300 PSI rated working pressure.

3RD PARTY ‫ﺷﻬﺎﺩﺓ ﺍﻟﻤﺨﺘﺒﺮﺍﺕ ﺍﻟﻤﺴﺎﻧﺪﺓ‬


CERTIFICATE / - Factory Mutual - Factory Mutual
APPROVAL : (FM) (FM) : ( ‫)ﻣﻦ ﻫﻴﺌﺎﺕ ﻣﻌﺘﻤﺪﺓ‬

RECOMMENDATIONS ‫ﺍﻟﺘﻮﺻﻴﺎﺕ‬
NOTES/STANDARD:

FM APPROVED
FM CLASS 1130.

/‫ﻉ‬

‫ﻣﺪﻳﺮ ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗـﺎﻳـــــﺔ‬


‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬

Page 2 of 2
9/27/2020 HCBZ.EX15462 - Indicator Posts, Gate Valve | UL Product iQ

HCBZ.EX15462 - Indicator Posts, Gate Valve

Indicator Posts, Gate Valve


See General Information for Indicator Posts, Gate Valve

VIKING CORP EX15462


210 INDUSTRIAL PARK DR
HASTINGS, MI 49058-9706 USA
Underground types, adjustable length, for valve sizes 4-12 in., Model(s) IPV

Wall types, for valve sizes 4-12 in., Model(s) IPW

Trademark and/or Tradename:

Last Updated on 2018-01-17

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading
manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission
from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following
format: "© 2020 UL LLC"

https://iq.ulprospector.com/en/profile?e=44906 1/1
‫‪2020-09-29‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻟﻄﺒﺎﻋﺔ ‪:‬‬ ‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴــــﺔ‬
‫‪AM 8:42‬‬ ‫ﻭﻗـﺖ ﺍﻟﻄﺒﺎﻋﺔ ‪:‬‬ ‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬
‫‪PAC20010121‬‬ ‫ﺭﻗــﻢ ﺍﻟﻄﻠـﺐ ‪:‬‬ ‫ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺷﻬــــــﺎﺩﺓ ﻋﺪﻡ ﻣﻤﺎﻧﻌﺔ‬

‫‪ :‬ﺍﻋﺘﻤﺎﺩ ﻣﻨﺘﺞ‬ ‫ﻧﻮﻉ ﺍﻟﺸﻬﺎﺩﺓ‬

‫ﺑﻴﺎﻧﺎﺕ ﺍﻟﻤﻨﺸﺄﺓ‬

‫‪ :‬ﺷﺮﻛﻪ ﻓﻴﺠﺎﻯ ﺍﻟﻌﺮﺑﻴﻪ ﻟﻠﺤﺮﻳﻖ ﻭﺍﻻﻧﻈﻤﻪ ﺍﻻﻣﻨﻴﻪ‬ ‫ﺍﻹﺳﻢ ﺍﻟﺘﺠﺎﺭﻱ‬


‫‪63162 :‬‬ ‫ﺭﻗﻢ ﺍﻟﺮﺧﺼﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ‬ ‫‪38572 :‬‬ ‫ﺭﻗﻢ ﺍﻟﺴﺠﻞ ﺍﻟﺘﺠﺎﺭﻱ‬
‫‪:‬‬ ‫ﺭﻗﻢ ﺍﻟﻬﺎﺗﻒ‬ ‫‪12-6790-00 :‬‬ ‫ﺭﻗﻢ ﻗﻴﺪ ﺍﻟﻤﻨﺸﺄﺓ‬
‫‪:‬‬ ‫ﺍﻟﺒﺮﻳﺪ ﺍﻹﻟﻜﺘﺮﻭﻧﻲ‬
‫‪Fire Fighting Systems :‬‬ ‫ﺍﻟﺘﺼﻨﻴﻒ‬
‫‪Valves (OS&Y,Butterfly,Globe,Check,Gate Relief Valves etc) :‬‬ ‫ﺇﺳﻢ ﺍﻟﻤﻨﺘﺞ‬

‫ﺗﻔﺎﺻﻴﻞ ﺍﻟﺸﻬﺎﺩﺓ‬

‫ﺗﻢ ﻣﺮﺍﺟﻌﺔ ﺍﻟﻄﻠﺐ ﺍﻟﻤﻘﺪﻡ ﻭﺍﺗﻀﺢ ﺑﺄﻧﻪ ﻻ ﻣﺎﻧﻊ ﻣﻦ ﺍﻋﺘﻤﺎﺩ ﺍﻟﻤﻨﺘﺞ ‪/‬ﺍﻟﻤﻨﺘﺠﺎﺕ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻰ ﺍﻟﻤﺮﻓﻖ ﺑﻨﺎﺀ ﻋﻠﻰ ﺍﻋﺘﻤﺎﺩﻩ ﻣﻦ ﻗﺒﻞ ﺍﻟﻬﻴﺌﻪ‬
‫ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﺭ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ‪.‬‬

‫ﻣﻼﺣﻈﺎﺕ‬

‫‪ .1‬ﻳﺠﺐ ﻋﻠﻰ ﺍﻟﺸﺮﻛﻪ ﺍﻻﻟﺘﺰﺍﻡ ﻭﺍﻟﻌﻤﻞ ﺑﻤﺎ ﺟﺎﺀ ﻓﻲ ﺍﺷﺘﺮﺍﻃﺎﺕ ﻗﺴﻢ ﺃﻧﻈﻤﺔ ﺍﻟﺴﻼﻣﻪ ﺍﻟﺘﻲ ﺗﻢ ﺍﻻﻃﻼﻉ ﻭﺍﻟﻤﻮﺍﻓﻘﺔ ﻋﻠﻴﻬﺎ ﻣﻦ ﺧﻼﻝ ﺍﻟﻤﻮﻗﻊ‪.‬‬
‫‪ .2‬ﻳﺠﺐ ﺍﻥ ﻳﻘﻮﻡ ﺑﺘﺮﻛﻴﺐ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ ﻣﻦ ﻗﺒﻞ ﻣﻬﻨﺪﺳﻴﻦ ﻭﻓﻨﻴﻴﻦ ﻣﻌﺘﻤﺪﻳﻦ ﻣﻦ ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‪.‬‬
‫‪ .3‬ﻳﺠﺐ ﺍﻥ ﻳﺤﻤﻞ ﺍﻟﻤﻨﺘﺞ ﺍﻟﻌﻼﻣﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ ﻟﻠﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻌﺘﻤﺪﺓ ﻭﺍﻟﻤﻮﺿﺤﻪ ﻓﻲ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ ‪.‬‬

‫‪2022-09-29‬‬ ‫‪:‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻹﻧﺘﻬﺎﺀ‬ ‫‪2020-09-29‬‬ ‫‪:‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻻﻋﺘﻤﺎﺩ‬

‫ﻉ‪/‬‬

‫ﻣﺪﻳﺮ ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬

‫‪Page 1 of 2‬‬
‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬
DATE : 2020-09-29 : ‫ﺍﻟﺘﺎﺭﻳـــــــﺦ‬
‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬
PERMIT # PAC20010121 : ‫ﺭﻗﻢ ﺍﻟﻄﻠﺐ‬
‫ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

TECHNICAL REPORT ‫ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ‬


PRODUCT Valves (OS&Y,Butterfly,Globe,Check,Gate Relief Valves etc) ‫ﻣﻨﺘﺞ‬
PRODUCT APPLICATION Fire Fighting Systems ‫ﺗﺼﻨﻴﻒ ﺍﻟﻤﻌﺪﺓ‬
APPLICANT / P.O BOX ‫ﺷﺮﻛﻪ ﻓﻴﺠﺎﻯ ﺍﻟﻌﺮﺑﻴﻪ ﻟﻠﺤﺮﻳﻖ ﻭﺍﻻﻧﻈﻤﻪ ﺍﻻﻣﻨﻴﻪ‬ ‫ﻣﻘﺪﻡ ﺍﻟﻄﻠﺐ‬
MANUFACTURER / LOCATION VIKING CORP / USA ‫ ﺑﻠﺪ ﺍﻟﺼﻨﻊ‬/ ‫ﺍﻟﺸﺮﻛﺔ ﺍﻟﻤﺼﻨﻌﺔ‬
‫ﺍﻟﻮﺻﻒ‬ ‫ﺍﻟﻤﻮﺩﻳﻞ‬

Indicator Posts, Gate Valves, Underground types, adjustable length, for valve sizes 4-12 in. IPV

Indicator Posts, Gate Valves, Wall types, for valve sizes 4-12 in. IPW
3RD PARTY CERTIFICATE /
Underwriters Laboratories ‫ﺷﻬﺎﺩﺓ ﺍﻟﻤﺨﺘﺒﺮﺍﺕ ﺍﻟﻤﺴﺎﻧﺪﺓ‬
APPROVAL HCBZ.EX15462
(UL) ( ‫)ﻣﻦ ﻫﻴﺌﺎﺕ ﻣﻌﺘﻤﺪﺓ‬

RECOMMENDATIONS ‫ﺍﻟﺘﻮﺻﻴﺎﺕ‬
Intended for use in operating gate valves of the inside-screw pattern and for indicating the position of the gates in the
valves.
INVESTIGATED TO STANDARD UL 789.
TRADEMARK AND/OR TRADENAME: FIREKING

This product approval shall comply with the Design, Inspection, Installation, Testing and Maintenance requirements of
NFPA 11,13,14,24 (and/or other related NFPA Codes / Standards), other acceptable International Codes / Standards,
Local Regulations and/or Manufacturer's Published Instructions subject to the technical review and approval of the
Authority Having Jurisdiction (Qatar Civil Defence).

/‫ﻉ‬

‫ﻣﺪﻳﺮ ﺍﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺓ ﻟﻟﺩﻓﺎﻉ ﺍﻟﻣﺩﻧﻲ‬

Page 2 of 2
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

10. Warranty
Certificate
Vijay Arabia Fire & Security Systems

WARRANTY CERTIFICATE
There are no warranties, express or implied, made by Vijay Arabia on New Equipment, except a 
warranty against defects in material and workmanship set out below: 

1. Vijay Arabia Warrants the following product supplied against sub contract agreement XXXXXXXX
Dated XX‐XXX‐XXXX shall be free from defects in materials and workmanship.
Project: Falcon 5/ F-15QA Beddown Project
Client: US Army Corps of Engineers
Main Contractor: BMJV
System: External Valves & Fire Hydrant 33 11 00

2. Vijay Arabia Obligation and liability under this warranty is limited to rectification or replacement
of any part/s found defective under normal use and service, within 400 Days (Warranty Period)
from handling over date XX‐XXX‐XXXX.

3. This Warranty Certificate must be presented to obtain services pursuant to the warranties set
forth herein.

4. This Warranty does not cover sets repaired by workshops not authorised by Vijay Arabia.

5. This Warranty is in lieu of all other warranties, express or implied, including any implied
warranty of merchantability or fitness for a particular purpose and the obligation and liability of
Vijay Arabia under this warranty shall not include any transportation, any other charges, liability
for direct, indirect or consequential damages and delay resulting from the defect or any other
obligations or liability on the part of Vijay Arabia, and Vijay Arabia neither assumes not
authorizes any other person to assume for if any other liability in connection with such
equipment. Any improper use or application of the product or the substitution of any parts not
approved by Vijay Arabia shall void this warranty. Failure to provide regular maintenance in
accordance with safety regulations shall likewise void this warranty. This Warranty covers only
the products listed in paragraph 1 & above.

6. Service Policy.

This Warranty is void in case of full payment of the above mentioned project is not received.

VIJAY ARABIA 

Al Difaf Street, 38 Al Sadd, P.O.Box: 31146, Doha Qatar | Tel. No.: (+974) 44365529/ 44982275 | Fax No: (974) 44364993,      
Email: info@vijayarabia.com, Web: www.vijayarabia.com 
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

11. Material
Sample
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

NOT APPLICABLE
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

12. Copies of
Previous
Approvals
TRANSMITTAL OF SHOP DRAWINGS, EQUIPMENT DATA, MATERIAL SAMPLES, OR DATE TRANSMITTAL NO.
MANUFACTURER'S CERTIFICATES OF COMPLIANCE
8/28/2018 33 11 00-9
For use of this form, see ER 415-1-0; the proponent agency is CECW-CE

SECTION I - REQUEST FOR APPROVAL OF THE FOLLOWING ITEMS (This section will be initiated by the contractor)
TO: Qatar Program Management Office FROM: Al Seal Contracting and Trading Company CONTRACT NO. THIS IS A:
Building Palm Tower B Majis A L Taawon W912ER18C0005
Street NEW TRANSMITTAL
Doha 3657
Qatar
SPECIFICATION SEC. NO. (Cover only one section with each transmittal) PROJECT TITLE AND LOCATION 01 THIS TRANSMITTAL IS FOR: (Check one)
33 11 00-WATER DISTRIBUTION Shield 5 Program, State of Qatar Site 5, Qatar FIO GA DA CR DA/CR DA/GA S

ITEM NO. CONTRACT REFERENCE FOR VARIATION FOR CE USE


DESCRIPTION OF SUBMITTAL ITEM SUBMITTAL TYPE CODE NO. OF
(See Note DOCUMENT CONTRACTOR (See CODE
(Type size, model number/etc) (See Note 8) COPIES
3) USE Instruction No. (Note 9)
SPEC. PARA DRAWING
6)
b. c. d. NO. SHEET NO.
a. g. h. i.
e. f.
25 External Valves 03 - PRODUCT DATA 4 2.1.2 A No A
Remarks from Contractor
* One (1) Hard Copy + One (1) Soft Copy to USACE Qatar Site Office

External Valves for Potable Water & Sewer Water Network - Vijay Arabia

I certify that the above submitted items have been reviewed in detail and
are correct and in the strict conformance with the contract drawings and
specifications except as otherwise stated.

NAME AND SIGNATURE OF CONTRACTOR


SECTION II - APPROVAL ACTION
ENCLOSURES RETURNED (List by item No.) NAME, TITLE AND SIGNATURE OF APPROVING AUTHORITY DATE

ENG FORM 4025-R, JUL 2015 Page 1 of 1 REPLACES EDITION OF MAR 2012, WHICH IS OBSOLETE
TRANSMITTAL OF SHOP DRAWINGS, EQUIPMENT DATA, MATERIAL SAMPLES, OR DATE TRANSMITTAL NO.
MANUFACTURER'S CERTIFICATES OF COMPLIANCE
8/4/2018 33 11 00-5
For use of this form, see ER 415-1-0; the proponent agency is CECW-CE

SECTION I - REQUEST FOR APPROVAL OF THE FOLLOWING ITEMS (This section will be initiated by the contractor)
TO: Qatar Program Management Office FROM: Al Seal Contracting and Trading Company CONTRACT NO. THIS IS A:
Building Palm Tower B Majis A L Taawon W912ER18C0003
Street NEW TRANSMITTAL
Doha 3657
Qatar
SPECIFICATION SEC. NO. (Cover only one section with each transmittal) PROJECT TITLE AND LOCATION 01 THIS TRANSMITTAL IS FOR: (Check one)
33 11 00-WATER DISTRIBUTION Shield 5 Program, State of Qatar Site 3, Qatar FIO GA DA CR DA/CR DA/GA S

ITEM NO. CONTRACT REFERENCE FOR VARIATION FOR CE USE


DESCRIPTION OF SUBMITTAL ITEM SUBMITTAL TYPE CODE NO. OF
(See Note DOCUMENT CONTRACTOR (See CODE
(Type size, model number/etc) (See Note 8) COPIES
3) USE Instruction No. (Note 9)
SPEC. PARA DRAWING
6)
b. c. d. NO. SHEET NO.
a. g. h. i.
e. f.
22 External Valves - Fire Water Network 03 - PRODUCT DATA 1 2.1.2 A No A
Remarks from Contractor
Manufacturer : Viking Group
Supplier : VASS

* 1 (One) Hard Copy + 2 (Two) Soft Copies to USACE Qatar Area Office.

I certify that the above submitted items have been reviewed in detail and
are correct and in the strict conformance with the contract drawings and
specifications except as otherwise stated.

NAME AND SIGNATURE OF CONTRACTOR


SECTION II - APPROVAL ACTION
ENCLOSURES RETURNED (List by item No.) NAME, TITLE AND SIGNATURE OF APPROVING AUTHORITY DATE

ENG FORM 4025-R, JUL 2015 Page 1 of 1 REPLACES EDITION OF MAR 2012, WHICH IS OBSOLETE
DATE TRANSMITTAL NO.
TRANSMITTAL OF SHOP DRAWINGS, EQUIPMENT DATA
MATERIAL SAMPLES, OR MANUFACTURER'S 9/10/2018 33 11 00-5
CERTIFICATES OF COMPLIANCE
PROJECT TITLE Shield 5 Program, State of Qatar Site 3 CONTRACT NO. PAGE
W912ER18C0003 Page 1 of 1
LOCATION Qatar

Item Description Variation QA Code

22 External Valves - Fire Water Network No A


SECTION III - GOVERNMENT REVIEW REMARKS
No remarks

Attachment to ENG FORM 4025-R Page 1 of 1


TRANSMITTAL OF SHOP DRAWINGS, EQUIPMENT DATA, MATERIAL SAMPLES, OR DATE TRANSMITTAL NO.
MANUFACTURER'S CERTIFICATES OF COMPLIANCE
10/22/2018 33 11 00-11
For use of this form, see ER 415-1-0; the proponent agency is CECW-CE

SECTION I - REQUEST FOR APPROVAL OF THE FOLLOWING ITEMS (This section will be initiated by the contractor)
TO: Qatar Program Management Office FROM: Al Seal Contracting and Trading Company CONTRACT NO. THIS IS A:
Building Palm Tower B Majis A L Taawon W912ER18C0005
Street NEW TRANSMITTAL
Doha 3657
Qatar
SPECIFICATION SEC. NO. (Cover only one section with each transmittal) PROJECT TITLE AND LOCATION 01 THIS TRANSMITTAL IS FOR: (Check one)
33 11 00-WATER DISTRIBUTION Shield 5 Program, State of Qatar Site 5, Qatar FIO GA DA CR DA/CR DA/GA S

ITEM NO. CONTRACT REFERENCE FOR VARIATION FOR CE USE


DESCRIPTION OF SUBMITTAL ITEM SUBMITTAL TYPE CODE NO. OF
(See Note DOCUMENT CONTRACTOR (See CODE
(Type size, model number/etc) (See Note 8) COPIES
3) USE Instruction No. (Note 9)
SPEC. PARA DRAWING
6)
b. c. d. NO. SHEET NO.
a. g. h. i.
e. f.
27 External Valves for Fire Water Network 03 - PRODUCT DATA 4 2.1.2 A No A
Remarks from Contractor
* One (1) Hard Copy + One (1) Soft Copy to USACE Qatar Site Office

This submittal is a revision of 33 11 00-6.

I certify that the above submitted items have been reviewed in detail and
are correct and in the strict conformance with the contract drawings and
specifications except as otherwise stated.

NAME AND SIGNATURE OF CONTRACTOR


SECTION II - APPROVAL ACTION
ENCLOSURES RETURNED (List by item No.) NAME, TITLE AND SIGNATURE OF APPROVING AUTHORITY DATE

ENG FORM 4025-R, JUL 2015 Page 1 of 1 REPLACES EDITION OF MAR 2012, WHICH IS OBSOLETE
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

13. Compliance
Statement
with Project
Specification
VIJAY ARABIA
Fire and Security Systems
·r·r·� ��1 ;w;..;�1.,� ��1 �� as�

Ref: VASS-BMJV-0005 Date: 27-Sep-2020

CONTRACTOR: Bahadir Construction Engineering Contracting & Trading Inc. Co and


lmpresa Costruzioni Giuseppe Maltauro (ICM S.p.A.) Joint Venture (BMJV)

For the attention Mr. Oliver Kleebach - Project Manager

Project Name Falcon 5/F-15QA Beddown Project


Contract No. W912ER20C0010
Employer United States Army Corps of Engineers (USACE)
Subject Compliance Statement

Dear Sir,

We Vijay Arabia Fire & Security Systems WLL, Qatar, whose registered office is at Ahmed Bin Hanbal Street,
Villa No: 59, D- Ring Road, P.O.Box: 31146, Doha, Qatar., would thank you for opportunity to work with you as
Fire Fighting & Fire Alarm Subcontractor to provide the scope of Design, Supply, Installation, Testing &
Commissioning of External Valves & Above Ground Hydrant- Fire Water External Network under specification
reference 33 11 00, for the above-referenced Project.

We hereby guarantee and confirm that:


• We will supply the materials throughout the period of the project as per compliance statement
attached

We thank you.

With Compliments,

Role: Construction Manager

C.R.No. 38572
i P. 0. Box 3 I 146, Doha, Qatar
T :+974 4019 2900 l 4436AS29 [_4498_2275 __ ---·· ____ . ------------·
: ----
I Doc. Ro;:-+&ll1Wl��l929 _ Rev. No.: 00 1, Rev. Date: 03-Sep-2020
,i --·--------------
Pag� of 4_
e-mail: info@vijayarabia.com www.vijayarabia.com
SUPPLIER/ SUBCONTRACTOR COMPLIANCE STATEMENT

Ref. No.: VASS-Sep-0009 Rev. 1 Date: 25/10/2020


Project: Falcon 5/F-15QA Beddown Project
Vijay Arabia Fire & Security Systems WLL, Qatar (VASS)
Subcontractor:

Specification Compliance
Manufacturer Specification
S/n Description of Material (If Ref. (project
Requirements Compliance Compliant
Applicable) spec./ Test Results
for Testing Testing Ref.
Kahraama
Specification)
Project Specification Reference- 33 11 00 WATER UTILITY DISTRIBUTION PIPING
PART 2 PRODUCTS
2.1 MATERIALS
2.1.2 Valves

2.1.2.1 Gate Valves


Proposed NRS
Resiliant Gate
Gate Valves shall comply with the relevant Valve Model PIF
provisions of (KAHRAMAA) Chapter 4: are in accordance Refer Section-7
Section-6 Gate Valve. All sluice valves shall be with EN1092-2 for Technical
manufactured and tested in accordance with 33 11 00 Para PN16 for which FM Datasheet and
EN1092-2 Yes
BS 5163 Type ‘B’/ BS EN 1171 and their 2.1.2.1 certified and Section-9 for
amendments. Provide all valves from one QCDD Approved. FM & QCDD
manufacturer. Provide FM/UL listed gate Design & certificate.
valves on fire water lines per NFPA 24. dimension
according to
AWWA C515.
2.1.2.2 Water Service Valves
2.1.2.2.1 Gate Valves

Proposed NRS
Gate valves shall comply with the relevant Gate valve is for Refer Section-7
provisions of (KAHRAMAA) Chapter 4: Fire Water for Technical
Section-6 Gate Valve. All sluice valves shall be 33 11 00 Para application for Datasheet and
manufactured and tested in accordance with 2.1.2.2.1
EN1092-2 which it is FM Section-9 for
Yes
BS 5163 Type ‘B’/ BS EN 1171 and their approved as per FM & QCDD
amendments. EN1092-2 PN16 certificate.
and QCDD
approved.

2.1.2.3 Valve Boxes


Valve box is
applicable for
Isolating PIF valve
without Indicator
Post. Composite
box for valve is
Provide a valve box for each gate valve on
with Body of Non-
buried piping. Construct adjustable valve boxes
abrasive Polymer
manufactured from cast iron of a size Refer Section-7
33 11 00 Para with Impact-
compatible for the valve on which it is used. for Technical Yes
2.1.2.3 resistant,
Coat the cast-iron box with a heavy coat of Datasheet.
corrosion-proof for
bituminous paint. Provide a round head. Cast
which bituminous
the word "WATER" on the lid.
coating is not
applicable. Lid &
Cover is of Cast
Iron, and lid will be
provided with
“Water”.
2.1.2.3.1 Valve Boxes Outside the Airfield
Composite Valve
Box is with
minimum wall
thickness of 5mm,
Cover, lid and T-
Wrench of Cast
Provide cast iron valve boxes with a minimum
Iron material.
cover and wall thickness of 5 mm and Refer Section-7
33 11 00 Para Adjustable top,
conforming to ASTM A48/A48M, Class 35B. for Technical Yes
2.1.1.1.2 b Bottom Shaft and
The minimum diameter of the shaft of the box Datasheet.
Extension stem
is 135 mm.
are of Ductile Iron
Material which will
be buried and
Ductile Iron is
more superior than
Cast Iron.
2.1.2.3.2 Valve Boxes Inside the Airfield

Doc. No.: BMJV-QUA-F21 Rev. No.: 00 Rev. Date: 07-Sep-2020 Page 2 of 7


SUPPLIER/ SUBCONTRACTOR COMPLIANCE STATEMENT

Composite Valve
Box with wall
thickness of 6mm,.
The Valve box lid
is with minimum
Provide cast iron valve boxes with a minimum
15mm and 91T
wall thickness of 6 mm. The valve box cover is
load capacity. The
to have a minimum thickness of 15 mm and be 33 11 00 Para
minimum Inner Yes
90,700 kg proof load tested. The minimum 2.1.1.1.2 c
Diameter of the
diameter and extension of the shaft of the box
Shaft will be
is to be 155 mm and 990 mm, respectively.
150mm and
Extension of the
shaft will be
minimum of
990mm.
2.1.3 Fire Hydrants And Hose Houses

2.1.3.1 Fire Hydrants


Provide fire hydrants where indicated. Proposed Above
Fire hydrants shall comply with the relevant Ground Dry Barrel
provisions of (QCD) Qatar Fire Safety type Fire Hydrant
Standards; Fire Hydrant Design Criteria; QNS Model HYF3,
No. FH 01. Hydrants shall be of the PN16 with DN150 Yes
aboveground double pillar (PN 16) type with a Flanged. Each
150 mm nominal diameter barrel. Each hydrant Hydrant has two
shall have at least two (2) outlets. Outlets shall Hose outlet 65mm
be 65 mm nominal diameter. dia.
2.1.3.1.1 Valve Boxes
Provide a valve box for each valve on piping,
Isolating Gate
except where indicator post is shown. Valve
Valve composite
box shafts, supports and backfill shall be
box will be Yes
constructed as described in section 2.1.2.3 of
provided where
this specification and as shown on the
ever applicable.
drawings.
Kahramaa Specification Chapter 4: Section-6 Gate Valve
6.1 General
Kahramaa
These clauses shall be read in continuation Specification
Yes
of Section 1 of this specification. Chapter 4,
Section 6
Proposed NRS
Gate Valve is in
Refer Section-7
Kahramaa accordance with
6.1.1 All sluice valves shall be manufactured for Datasheet &
Specification EN1092-2 PN16,
and tested in accordance with BS-5163 Type EN1092-2 Section-9 for Yes
Chapter 4, FM & QCDD
'B'/ BSEN 1171 and their amendments. FM & QCDD
Section 6 Approved. Design
Certificates.
accordance with
AWWA C515
Kahramaa
Specification
6.1.2 All sluice valves shall be: - Yes
Chapter 4,
Section 6
Proposed NRS
Refer Section-7
Kahramaa Gate Valve is in
for Datasheet &
A. Double flanged drilled according to BSEN Specification accordance with
Section-9 for Yes
1092-2 PN16. Chapter 4, EN1092-2 PN16,
FM & QCDD
Section 6 FM & QCDD
Certificates.
Approved.
Proposed NRS
Gate Valve is in
accordance with Refer Section-7
Kahramaa
EN1092-2 PN16, for Datasheet &
B. Face -to-face dimensions according to Specification
FM & QCDD Section-9 for Yes
BSEN 558-1; Series 3 and 14. Chapter 4,
Approved. Design FM & QCDD
Section 6
and dimensions Certificates.
conform to
AWWA C515
Kahramaa
Refer Section-7
D. Designed for use with nominal pressure of Specification Working pressure
for Product Yes
l6 Bar. Chapter 4, of 21 Bar (300Psi)
Catalogue.
Section 6
Kahramaa
Non rising & Refer Section-7
E. with inside screw, solid wedge and shall be Specification
Resiliant wedge for Product Yes
of non-rising stem type. Chapter 4,
type. Catalogue.
Section 6
Valves either with
indicator post or
Kahramaa with composite box
Refer Section-7
F. Operated by the use of a removable key Specification in which using T
for Product Yes
through a valve cap. Chapter 4, wrench valves
Catalogue.
Section 6 shall be operated
as per design shop
drawings.
Kahramaa
Specification
G. Suitable for use in a closed end test. Yes
Chapter 4,
Section 6

Doc. No.: BMJV-QUA-F21 Rev. No.: 00 Rev. Date: 07-Sep-2020 Page 3 of 7


SUPPLIER/ SUBCONTRACTOR COMPLIANCE STATEMENT

Kahramaa
Specification
6.1.3 Gear box shall be of: N/A
Chapter 4,
Section 6
Kahramaa Gear box is not
Specification applicable for NRS
I Standard ratio - 1.1-10.1 ( as specified) N/A
Chapter 4, Gate Valves.
Section 6 Proposed Valve is
Kahramaa NRS Gate valve
Specification with IPV or
I Torque ranges - 400-40,000 Nm. N/A
Chapter 4, Composite valve
Section 6 box assembly.
Kahramaa
Specification
I Thrust range - 4,000-250,000 daN N/A
Chapter 4,
Section 6
6.1.4 All sluice valve and gear box shall be Kahramaa
Sluice Valves are
suitable for use with water temperature up to Specification
suitable to used to Yes
50° C and in climate and soil conditions Chapter 4,
50 deg C
encountered in the State of Qatar. Section 6
Kahramaa
6.1.5 All sluice valves shall be of the resilient Specification
Yes
seat type. Chapter 4,
Section 6
6.1.6 All component parts of the valve body i.e. Kahramaa
bonnet and stem seal housing shall be bolted Specification
Yes
together, where setscrews are used, the socket Chapter 4,
shall be provided with a PVC cap. Section 6
Kahramaa
6.1.7 All sluice valves shall be designed for Specification
Yes
clockwise closing and be marked accordingly. Chapter 4,
Section 6
Kahramaa
Specification
6.2 TESTING Yes
Chapter 4,
Section 6
Kahramaa
6.2.1 The sluice valve shall be tested as per Specification
Yes
BS 5163 as follows: Chapter 4,
Section 6
Kahramaa
Specification
Hydraulic test for body - 24 Bar Yes
Chapter 4,
Section 6
Kahramaa
Specification
Hydraulic test for seat - 17.6 Bar Yes
Chapter 4,
Section 6
A factory test certificate shall be issued for Kahramaa Material Test
each valve giving its serial numbers. This Specification certificate will be
Yes
certificate shall be submitted to KAHRAMAA at Chapter 4, provided with the
the time of supply if requested by the engineer. Section 6 delivered valves.
Kahramaa
Specification
6.3 HAND-WHEEL N/A
Chapter 4,
Section 6
Handwheel is not
applicable for the
6.3.1 Sluice valves shall be supplied with cast External Fire
Kahramaa
iron hand wheels marked "Open" and "Closed" network valves.
Specification
with arrow in appropriate directions. The The Valve spindle N/A
Chapter 4,
design shall be such that it can be removed if is operated by IPV
Section 6
necessary. and Composite
valve box with T-
Wrench.
Kahramaa
Specification
6.4 MARKING Yes
Chapter 4,
Section 6
Kahramaa
6.4.1 All valves shall have clearly marked m
Specification
the casting of the body the following Yes
Chapter 4,
information:
Section 6
A. Size of valve in mm.
B. Pressure rating in Bars. Kahramaa
C. Manufacturer's name and/or logo. Specification
Yes
D. Material type (GGG40/GGG50/SG) Chapter 4,
E. Manufacturing Standards Number. Section 6
F. Year of manufacture.
6.4.2 All valves shall have individual
identification strip which shall be marked by Kahramaa
engraving or embossing on a metal strip, the Specification
Yes
name of manufacturer, individual serial Chapter 4,
number, tender number and Year of Section 6
manufacturing.
6.4.3 The metal strip shall be of minimum size
Kahramaa Manufactured
of 100mm x 30mm and shall be fixed securely
Specification standard
and permanently at appropriate location by Yes
Chapter 4, identification will
industrial type cold welded glue and shall not
Section 6 be provided.
be screwed or riveted. The glue shall be of
Doc. No.: BMJV-QUA-F21 Rev. No.: 00 Rev. Date: 07-Sep-2020 Page 4 of 7
SUPPLIER/ SUBCONTRACTOR COMPLIANCE STATEMENT

industrial grade with a melting point higher than


80 ° C.
Kahramaa
6.5 MATERIALS Specification
Yes
For valve Chapter 4,
Section 6
Kahramaa
6.5.1 The valve body, bonnet, gland, yoke and External NRS Gate
Specification
wedge body shall be manufactured of Ductile Valves are of Yes
Chapter 4,
Iron as per one of the following standards: Ductile Iron Body.
Section 6
NRS Gate Valve
proposed is Ductile
iron body as per
Kahramaa Spec 6.5.1. And
II DIN 1693 GGG-50/40 Refer Section-7
Specification material standard
II BS EN 1563:1997 grade EN-GJS-500-7 ASTM A 536 for Product Yes
Chapter 4, is ASTM A 536 64
II ISO 500-7, ISO 400-15 Catalogue
Section 6 - 45-12 for which
Valve is UL listed,
FM approved &
QCDD approved
Refer Section-7
6.5.2 The stem shall be manufactured of acid Kahramaa Stem is of AISI for Product
resistance stainless steel 316L/BS 970 Gr 431 Specification 431. Valve is FM Catalogue.
AISI 431 Yes
S29 with the threaded portion being formed by Chapter 4, approved & QCDD Section-9 for
rolling process. Section 6 approved. FM & QCDD
approval.
Kahramaa
6.5.3 Stem nuts shall be gunmetal to BS 1400 Specification
Yes
LG2 or BS 2874 CZ132. Chapter 4,
Section 6
Proposed NRS
Gate Valve is
Kahramaa
6.5.4 Dimensions and materials shall conform EN1092-2 PN16, Refer Section-7
Specification
to those detailed in BS 5163, as applicable for Design and for Product Yes
Chapter 4,
Type "B", and BS EN 1171. dimension Catalogue.
Section 6
conforms to
AWWA C515.
Kahramaa
Refer Section-7
6.5.5 The wedge body/core shall be Specification Wedge Disc of
for Product Yes
manufactured from ductile iron. Chapter 4, Ductile Iron.
Catalogue.
Section 6
6.5.6 The wedge shall be completely Wedge disc is of
vulcanized by EPDM and coupled to the valve Ductile iron
Kahramaa
stem by gunmetal or dezincification resistance material, Bonnet Refer Section-7
Specification
brass nut slide into the specifically designed Gasket & Ring for Product Yes
Chapter 4,
slot hole in wedge or rigidly fastened into the Wiper is of EPDM Catalogue.
Section 6
wedge body by forging before rubber and O-Rings of
vulcanization. NBR.
6.5.7 Rubber material shall be of "EPDM EDK- Kahramaa
70 and the minimum thickness shall be 1.5 Specification
Yes
mm, and all sealing surfaces not less than 4.0 Chapter 4,
mm. Section 6
Gear box is not
applicable for NRS
Kahramaa Gate Valves.
Specification Proposed Valve is
6.5.8 Gear box N/A
Chapter 4, NRS Gate valve
Section 6 with IPV or
Composite valve
box assembly.
Kahramaa
Specification
6.6 FLANGES Yes
Chapter 4,
Section 6
Kahramaa
6.6.1 All sluice valve flanges shall be drilled to Proposed Valves
Specification
suite ductile iron flanges as detailed in BS EN are BS EN 1092-2, Yes
Chapter 4,
1092-2, PN-16 rating. PN-16 Rating.
Section 6
Kahramaa
Specification
6.7 SLUICE VALVE STEM SEALS Yes
Chapter 4,
Section 6
6.7.1 Sluice valves up to and including 300 mm
0 shall have 'O' ring seals which are to
Kahramaa
comprise of seal, wiper rings and lip seal.
Specification
There shall be a minimum of two wiper rings or Yes
Chapter 4,
one wiper ring and one lip seal in addition to
Section 6
the seal rings and shall be made of synthetic
rubber material.
6.7.2 Sluice valves above 300mm may have Kahramaa
either 'O' ring seals, or stuffing boxes fitted with Specification
Yes
an approved 'Teflon' or graphite based packing Chapter 4,
material. Section 6
Kahramaa
6.7.3 The stem sealing shall be maintenance Specification
Yes
free. Chapter 4,
Section 6
Kahramaa
6.7.4 There shall not be any direct contact with Specification
Yes
spindle and bonnet to avoid cold welding. Chapter 4,
Section 6
Doc. No.: BMJV-QUA-F21 Rev. No.: 00 Rev. Date: 07-Sep-2020 Page 5 of 7
SUPPLIER/ SUBCONTRACTOR COMPLIANCE STATEMENT

Kahramaa
6.8 MATERIAL COATING & INTERNAL Specification
Yes
COMPONENTS Chapter 4,
Section 6
Valve body are
Kahramaa
6.8.1 The entire body of valves shall be coated both internally &
Specification
both internally and externally with either of the Externally Fusion Yes
Chapter 4,
following: bonded epoxy
Section 6
coated.
Coating thickness
will be of 300
Kahramaa microns for Valve
300 micron Fusion bonded epoxy (Polymeric Specification body with both
Yes
anticorrosion) coating as per WIS No. 4-52-01. Chapter 4, internally &
Section 6 Externally Fusion
bonded epoxy
coated
Coating thickness
will be of 300
Kahramaa microns for Valve
300 micron Electrostatic ally applied epoxy Specification body with both
Yes
coating Chapter 4, internally &
Section 6 Externally Fusion
bonded epoxy
coated
Coating thickness
will be of 300
Kahramaa microns for Valve
Specification body with both
300 micron Fluidized bed epoxy coating Yes
Chapter 4, internally &
Section 6 Externally Fusion
bonded epoxy
coated
QCS 2014 Section 23 Part 04: Fire Fighting System

4.5 FIRE HYDRANTS Yes

4.5.1 General
Fire Hydrant will be
1 Fire hydrants shall be installed in locations as
QCS 2014 installed as per
stated in the Project Documentation unless
Section 23 Part approved Shop Yes
otherwise directed by the Civil Defence
04 Para 4.5 drawing and QCD
Department.
standards.
Above ground Fire
Hydrant Model
2 A certificate shall be obtained from the QCS 2014 HYF3 is approved Refer Section-9
manufacturer stating that the fire hydrants to Section 23 Part by QCDD. For for QCDD Yes
be supplied are suitable for use in Qatar. 04 Para 4.5 which QCDD Certificates.
certificate
provided.
Fire hydrants will
QCS 2014
3 Fire hydrants shall be installed in accordance be installed as per
Section 23 Part
with the manufacturer’s instructions. manufacturer’s
04 Para 4.5
instructions.
4.5.2 High Pressure Dry Barrel Hydrant Yes
1 High pressure dry barrel hydrants shall come
Proposed Dry
complete with removable/replaceable nozzles
QCS 2014 Barrel Above
and hydrant seat, top stop nut, easily repaired Refer Section-7
Section 23 Part Ground Fire Yes
traffic section, nozzle section with 360° for Datasheet.
04 Para 4.5.2 Hydrant Model
rotation, main valve opening and bronze drain
HYF3.
plug.
Proposed Model
2 Working pressure of the hydrant shall be 14
QCS 2014 HYF3 is having
bar and the testing pressure shall be 28 bar Refer Section-7
Section 23 Part ASTM A536 working pressure Yes
unless otherwise stated in the Project for Datasheet.
04 Para 4.5.2 of 17.2 Bar
Documentation or agreed with the Engineer.
(250Psi).
The Dry Barrel
Hydran Valve is
complying to local
QCD connection
requirement with
inbuilt
Instantaneous
coupling
Refer Section-7
connection for
QCS 2014 for Datasheet &
3 The hydrant shall comply with ASNI/AWWA which Model HYF3
Section 23 Part AWWA C502 Section-9 for Yes
C502 and shall be UL listed and FM approved. is LPCB apporved
04 Para 4.5.2 LPCB & QCDD
& QCDD
Certificate.
approved. UL/FM
hydrant valves
avaialble only with
threaded outlet
connection which
is not matching to
local QCD
requirements.

Doc. No.: BMJV-QUA-F21 Rev. No.: 00 Rev. Date: 07-Sep-2020 Page 6 of 7


SUPPLIER/ SUBCONTRACTOR COMPLIANCE STATEMENT

QCS 2014
4 Materials for the hydrants shall be as follows: Section 23 Part Yes
04 Para 4.5.2
Body, Nozzle
(a)nozzle section, barrels, stand pipe flanges,
QCS 2014 Section, barrels, Refer Section-7
breakable flange, base, main valve flange,
Section 23 Part ASTM A536 Operating nut and for Technical Yes
weather-shield operating nut and bonnet all
04 Para 4.5.2 bonnet are Ductile Datasheet.
shall be ductile iron
Iron
QCS 2014
(b)main valve disc shall be ductile iron core
Section 23 Part Yes
and fully encapsulated in EPDM rubber
04 Para 4.5.2
QCS 2014 Refer Section-7
Caps will be Cast
(c)caps shall be cast iron Section 23 Part for Product Yes
Iron
04 Para 4.5.2 Catalogue.
Proposed Fire
Hydrant finsih is
QCS 2014 with Red and Black Refer Section-7
(d)coating above ground shall be fusion
Section 23 Part Epoxy painted for Product Yes
bonded epoxy inside and out
04 Para 4.5.2 to interior and Catalogue.
exterior to AWWA
C550.
Coating below
QCS 2014 Refer Section-7
(e)coating below ground shall be bitumen or ground will be
Section 23 Part for Product Yes
fusion bonded epoxy black epoxy paint
04 Para 4.5.2 Catalogue.
for the hydrant
Screw stem
bushing is of
(f)nozzles, valve seat ring, drain ring, drain QCS 2014 Refer Section-7
Stainless Steel and
bushings and plugs, stem nut, stem bushing Section 23 Part for Product Yes
Screw nut seat,
and thrust nut shall be bronze 04 Para 4.5.2 Catalogue.
lock nut seat are of
Aluminum Bronze.
Bolt, nut and Cap
Chain will be of
QCS 2014 Refer Section-7
(g)stop nut, cap chain, bolts and nuts shall be Stainless steel
Section 23 Part for Product Yes
zinc plated steel material, which is
04 Para 4.5.2 Catalogue.
more superior than
Zinc plated Steel.
Connecting rod
(h)stem rod coupling, standpipe lock rings, QCS 2014 sleeve, Screw Refer Section-7
nozzle lock screw, lock plate, lock plate screw Section 23 Part Stem bushing and for Product Yes
and spider bolt shall be stainless steel 04 Para 4.5.2 bolt is of stainless Catalogue.
steel,
Barrel and Cap
QCS 2014 Refer Section-7
(i)barrel gaskets and cap gaskets shall be gaskets will be of
Section 23 Part for Product Yes
nitrile rubber. NBR (Nitrile
04 Para 4.5.2 Catalogue.
rubbber) material.
5 Each hydrant shall be clearly marked, either
QCS 2014
integrally with the stated components or on a
Section 23 Part Yes
plate of durable material securely fixed to that
04 Para 4.5.2
component, as follows:
QCS 2014
(a)the number of the standard to which the
Section 23 Part Yes
hydrant conforms and the date of the standard
04 Para 4.5.2

QCS 2014
(b)the manufacturer‟s name or trade mark Section 23 Part Yes
04 Para 4.5.2

(c)the identification number (the reference QCS 2014


used by the manufacturer allowingidentification Section 23 Part Yes
for the supply of spares, etc). 04 Para 4.5.2

Prepared and Approved by:

Role: QC Engineer

Name: Ashwin Bhaskar

Signature:

Doc. No.: BMJV-QUA-F21 Rev. No.: 00 Rev. Date: 07-Sep-2020 Page 7 of 7


MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

14. Contractual
Non-
Compliance
(only if applicable)
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

NOT APPLICABLE
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

15. Drawings
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

NOT APPLICABLE
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

16.Specification(s)
F-15QA BEDDOWN 60593057

NSF/ANSI 61 (2017) Drinking Water System Components -


Health Effects

STATE OF QATAR (SOQ)

KAHRAMAA (2016) CS-CSI-P1/C1 - Electricity Wiring


Code Low Voltage Electricity & Water
Installations Regulations

QCS 2014 Qatar Construction Specifications 2014

1.2 DESIGN REQUIREMENTS

1.2.1 Water Distribution Mains

Provide cement-lined ductile iron water distribution mains. Provide water


main accessories, gate valves and check valves as specified and where
indicated.

1.2.2 Water Service Lines

Provide water service lines from water distribution main to building


service at the points indicated. Water service lines shall copper tubing
unless otherwise noted. Provide water service line appurtenances as
specified and where indicated.

1.2.3 Fire Water Mains and Service Lines

Provide cement-lined ductile iron fire distribution mains. Provide fire


service lines from fire distribution main to building fire service at
points indicated or as directed by the Contracting Officer's Representative
and QEADF Representative. Fire service lines shall be cement-lined
ductile-iron pipe. Provide fire distribution main and fire service line
appurtenances and valves as specified and where indicated. All piping
within valve chambers shall be flanged ductile iron pipe only.

1.3 SUBMITTALS

Government approval is required for submittals with a "G" designation;


submittals not having a "G" designation are for information only. When
used, a designation following the "G" designation identifies the office
that will review the submittal for the Government. Submit the following in
accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-01 Preconstruction Submittals

Connections; G

SD-03 Product Data

Pipe, Fittings, Joints and Couplings; G

Ball And Socket Joint; G

Valves; G

Valve Boxes; G

SECTION 33 11 00 Page 3
Solicitation No. W912ER-20-R-0001
F-15QA BEDDOWN 60593057

Fire Hydrants; G

Pipe Restraint; G

Tapping Sleeves; G

Corporation Stops; G

Backflow Preventer; G

Precast Concrete Thrust Blocks; G

Disinfection Procedures; G

Submit manufacturer's standard drawings or catalog cuts, except


submit both drawings and cuts for push-on and rubber-gasketed
bell-and-spigot joints. Include information concerning gaskets
with submittal for joints and couplings.

SD-06 Test Reports

Backflow Preventer Tests; G

Bacteriological Samples; G

Test results from commercial laboratory verifying disinfection.

Leakage Test

Hydrostatic Test

SD-07 Certificates

Pipe, Fittings, Joints and Couplings

Shop-Applied Lining and Coating

Lining

Lining for Fittings

Valves

Fire Hydrants

Backflow Certificate

SD-08 Manufacturer's Instructions

Delivery, storage, and handling

Ductile Iron Piping

Copper Pipe For Service Lines

Provide documentation confirming that the international


standards used by the manufacturer meet the specified standards
indicated in the contract documents.

SECTION 33 11 00 Page 4
Solicitation No. W912ER-20-R-0001
F-15QA BEDDOWN 60593057

2.1.1.1 Ductile-Iron Piping

2.1.1.1.1 Pipe and Fittings

Pipe shall conform to the relevant provisions of (KAHRAMAA) Chapter 4:


Appendix A: GENERAL SPECIFICATION FOR MAIN LAYING MATERIALS FOR WATERWORKS,
SECTION 2.0 Ductile Iron Pipes and Fittings, Pressure Class 40. Fittings
with push-on joint ends are to meet the same requirements as fittings with
mechanical-joint ends, except for the factory modified bell design.
Provide fittings with pressure ratings equivalent to that of the pipe.
Provide compatible pipe ends and fittings for the specified joints.
Provide internal lining and external coating of piping and fittings in
accordance with the relevant provisions of (KAHRAMAA) Chapter 4: Appendix
A: GENERAL SPECIFICATION FOR MAIN LAYING MATERIALS FOR WATERWORKS, SECTION
2.0 Ductile Iron Pipes and Fittings.

2.1.1.1.2 Joints and Jointing Material

Provide push-on joints or mechanical joints for pipe and fittings unless
otherwise indicated.. Provide flanged joints for above ground
applications, unless otherwise noted.

a. Push-On Joints: Shape of pipe ends and fitting ends, gaskets, and
lubricant for joint assembly as recommended in (KAHRAMAA) Chapter 4:
Appendix A: GENERAL SPECIFICATION FOR MAIN LAYING MATERIALS FOR
WATERWORKS, SECTION 2.0 Ductile Iron Pipes and Fittings.

b. Mechanical Joints: Dimensional and material requirements for pipe


ends, glands, bolts and nuts, and gaskets as recommended in (KAHRAMAA)
Chapter 4: Appendix A: GENERAL SPECIFICATION FOR MAIN LAYING MATERIALS
FOR WATERWORKS, SECTION 2.0 Ductile Iron Pipes and Fittings.

c. Flanged Joints: Bolts, nuts, and gaskets for flanged connections as


recommended in (KAHRAMAA) Chapter 4: Appendix A: GENERAL SPECIFICATION
FOR MAIN LAYING MATERIALS FOR WATERWORKS, SECTION 2.0 Ductile Iron
Pipes and Fittings.

d. Sleeve-Type Mechanical Coupled Joints: As specified in the paragraph


SLEEVE-TYPE MECHANICAL COUPLINGS.

2.1.1.2 Copper Pipe For Service Lines

2.1.1.2.1 Copper Tubing and Associated Fittings

Provide copper tubing and fittings in accordance with(KAHRAMAA) Chapter 4:


Appendix A: GENERAL SPECIFICATION FOR MAIN LAYING MATERIALS FOR WATERWORKS,
SECTION 12.0 Copper Tubes, and SECTION 13.0 Copper Fittings, Ferrules,
Stopcocks & Poly Adapters.

2.1.2 Valves

2.1.2.1 Gate Valves

Gate Valves shall comply with the relevant provisions of (KAHRAMAA) Chapter
4: Section-6 Gate Valve. All sluice valves shall be manufactured and
tested in accordance with BS 5163 Type ‘B’/ BS EN 1171 and their
amendments. Provide all valves from one manufacturer. Provide FM/UL
listed gate valves on fire water lines per NFPA 24.

SECTION 33 11 00 Page 6
Solicitation No. W912ER-20-R-0001
F-15QA BEDDOWN 60593057

2.1.2.2 Water Service Valves

2.1.2.2.1 Gate Valves

Gate valves shall comply with the relevant provisions of (KAHRAMAA) Chapter
4: Section-6 Gate Valve. All sluice valves shall be manufactured and
tested in accordance with BS 5163 Type ‘B’/ BS EN 1171 and their amendments.

2.1.2.3 Valve Boxes

Provide a valve box for each gate valve on buried piping. Construct
adjustable valve boxes manufactured from cast iron of a size compatible for
the valve on which it is used. Coat the cast-iron box with a heavy coat of
bituminous paint. Provide a round head. Cast the word "WATER" on the lid.

2.1.2.3.1 Valve Boxes Outside the Airfield

Provide cast iron valve boxes with a minimum cover and wall thickness of 5
mm and conforming to ASTM A48/A48M, Class 35B. The minimum diameter of the
shaft of the box is 135 mm.

2.1.2.3.2 Valve Boxes Inside the Airfield

Provide cast iron valve boxes with a minimum wall thickness of 6 mm. The
valve box cover is to have a minimum thickness of 15 mm and be 90,700 kg
proof load tested. The minimum diameter and extension of the shaft of the
box is to be 155 mm and 990 mm, respectively.

2.1.3 Fire Hydrants And Hose Houses

2.1.3.1 Fire Hydrants

Provide fire hydrants where indicated.

Fire hydrants shall comply with the relevant provisions of (QCD) Qatar Fire
Safety Standards; Fire Hydrant Design Criteria; QNS No. FH 01. Hydrants
shall be of the aboveground double pillar (PN 16) type with a 150 mm
nominal diameter barrel. Each hydrant shall have at least two (2)
outlets. Outlets shall be 65 mm nominal diameter.

2.1.3.1.1 Valve Boxes

Provide a valve box for each valve on piping, except where indicator post
is shown. Valve box shafts, supports and backfill shall be constructed as
described in section 2.1.2.3 of this specification and as shown on the
drawings.

2.1.3.2 Manhole Frames and Covers

Heavy duty ductile iron manhole frames and covers shall comply with
BS EN 124, Class D400 with precast concrete ring.

2.1.4 GRP Ladder

GRP ladders shall comply with the relevant provisions of (KAHRAMAA) Section
08: Part 7.2.1 GRP.

SECTION 33 11 00 Page 7
Solicitation No. W912ER-20-R-0001
Section - 6
Gate valves
6.1 GENERAL

These clauses shall be read in continuation of Section 1 of this specification.

6.1.1 All sluice valves shall be manufactured and tested in accordance with BS-5163 Type
'B'/ BSEN 1171 and their amendments.

6.1.2 All sluice valves shall be: -


A. Double flanged drilled according to BSEN 1092-2 PN16.
B. Face -to-face dimensions according to BSEN 558-1; Series 3 and 14.
C. Designed for use with nominal pressure of l6 Bar.
D. with inside screw, solid wedge and shall be of non-rising stem type.
E. Operated by the use of a removable key through a valve cap.
F. Suitable for use in a closed end test.

6 .1.3 Gear box shall be of:


• Standard ratio l.1-10.1 (as specified)
• Torque ranges 400-40,000 Nm.
• Thrust range 4,000-250,000 daN

6.1.4 All sluice valve and gear box shall be suitable for use with water temperature up to
50 ° C and in climate and soil conditions encountered in the State of Qatar.

6.1.5 All sluice valves shall be of the resilient seat type.

6.1.6 All component parts of the valve body i.e. bonnet and stem seal housing shall be
bolted together, where setscrews are used, the socket shall be provided with a PVC
cap.

6.1.7 All sluice valves shall be designed for clockwise closing and be marked accordingly.

6.2 TESTING

6.2.1 The sluice valve shall be tested as per BS 5163 as follows:


• Hydraulic test for body - 24 Bar
• Hydraulic test for seat - 17.6 Bar

A factory test certificate shall be issued for each valve giving its serial numbers. This certificate
shall be submitted to KAHRAMAA at the time of supply if requested by the engineer.

6.3 HAND-WHEEL

6.3.1 Sluice valves shall be supplied with cast iron hand wheels marked "Open" and
"Closed" with arrow in appropriate directions. The design shall be such that it can be
removed if necessary.

General Specification of Main laying Materials for Water Works 6-22


6.4 MARKING

6.4. l All valves shall have clearly marked m the casting of the body the following
information;
A. Size of valve in mm.
B. Pressure rating in Bars.
C. Manufacturer's name and/or logo.
D. Material type (GGG40/GGG50/SG)
E. Manufacturing Standards Number.
F. Year of manufacture.

6.4.2 All valves shall have individual identification strip which shall be marked by
engraving or embossing on a metal strip, the name of manufacturer, individual serial
number, tender number and Year of manufacturing.

6.4.3 The metal strip shall be of minimum size of 100mm x 30mm and shall be fixed
securely and permanently at appropriate location by industrial type cold welded glue
and shall not be screwed or riveted. The glue shall be of industrial grade with a
melting point higher than 80 ° C.

6.5 MATERIALS
For valve

6.5.1 The valve body, bonnet, gland, yoke and wedge body shall be manufactured of
Ductile Iron as per one of the following standards
II
DIN 1693 GGG-50/40
II
BS EN 1563:1997 grade EN-GJS-500-7
II
ISO 500-7, ISO 400-15

6.5.2 The stem shall be manufactured of acid resistance stainless steel 316L/BS 970 Gr 431
S29 with the threaded portion being formed by rolling process.

6.5.3 Stem nuts shall be gunmetal to BS 1400 LG2 or BS 2874 CZ132.

6.5.4 Dimensions and materials shall conform to those detailed in BS 5163, as applicable
for Type "B", and BS EN 1171.

6.5.5 The wedge body/core shall be manufactured from ductile iron.

6.5.6 The wedge shall be completely vulcanized by EPDM and coupled to the valve stem
by gunmetal or dezincification resistance brass nut slide into the specifically designed
slot hole in wedge or rigidly fastened into the wedge body by forging before rubber
vulcanization.

6.5.7 Rubber material shall be of "EPDM EDK-70 and the minimum thickness shall be
1.5 mm, and all sealing surfaces not less than 4.0 mm.

Gear box

6.5.8 Gear box shall be of following materials: -


II
Body & body cover Ductile Iron GGG 50/40, SG
II
Bevel gear-shaft Steel / Carbon steel
II
Gear SG Iron, BS EN 1563 Grade 700-2

General Specification of Main laying Materials for Water Works 6-23


Valve

GGG 50 or AISI 1045


1111
Bearing Steel
1111
Plate & base plate Carbon steel
1111
Stem nut Aluminum Bronze/ Steel/ DZR Brass

6.5.9 Fasteners shall be as per Section 1, Clause 1.6 of this specification.

6.6 FLANGES

6.6.1 All sluice valve flanges shall be drilled to suite ductile iron flanges as detailed in BS
EN 1092-2, PN-16 rating.

6.7 SLUICE VAL VE STEM SEALS

6.7.1 Sluice valves up to and including 300 mm 0 shall have 'O' ring seals which are to
comprise of seal, wiper rings and lip seal. There shall be a minimum of two wiper
rings or one wiper ring and one lip seal in addition to the seal rings and shall be made
of synthetic rubber material.

6.7.2 Sluice valves above 300mm may have either 'O' ring seals, or stuffing boxes fitted
with an approved 'Teflon' or graphite based packing material.

6.7.3 The stem sealing shall be maintenance free.

6.7.4 There shall not be any direct contact with spindle and bonnet to avoid cold welding.

6.8 MATERIAL COATING & INTERNAL COMPONENTS

6.8.1 The entire body of valves shall be coated both internally and externally with either of
the following:
II 300 micron Fusion bonded epoxy (Polymeric anticorrosion) coating as per WIS No.
4-52-01.
II 300 micron Electrostatic ally applied epoxy coating.
II 300 micron Fluidized bed epoxy coating.

General Specification of Main laying Materials for Water Works 6-24


QCS 2014 Section 23: Fire Fighting and Fire Alarm Systems Page 9
Part 04: Fire Fighting System

8 The hose shall terminate in a shut-off nozzle which shall give the following control settings:

(a) shut
(b) spray (sheet or conical) and/or jet.

9 Rotary operated nozzles shall be marked to show the direction of closing and opening.
Lever operated nozzles shall be marked to show the setting for:

(a) shut
(b) (spray and/or jet.

10 A manual inlet stop valve shall be fitted to the hose system. The valve shall be screw down
or other slow-opening type. The inlet and outlet of the valve shall form an angle of not less
than 90 and not more than 135

11 Hose assemblies shall be designed for the following pressures unless otherwise stated in the
project documentation or agreed with the Engineer:

(a) maximum working pressure shall be 12 bar


(b) test pressure shall be 24 bar
(c) minimum burst pressure shall be 42 bar

12 Testing, performance and materials of hose systems with lay-flat hose shall comply with the
relevant provisions of BS EN 671-2.

4.5 FIRE HYDRANTS


4.5.1 General

1 Fire hydrants shall be installed in locations as stated in the Project Documentation unless
otherwise directed by the Civil Defence Department.

2 A certificate shall be obtained from the manufacturer stating that the fire hydrants to be
supplied are suitable for use in Qatar.

3 Fire hydrants shall be installed in accordance with the manufacturer‟s instructions.

4.5.2 High Pressure Dry Barrel Hydrant

1 High pressure dry barrel hydrants shall come complete with removable/replaceable nozzles
and hydrant seat, top stop nut, easily repaired traffic section, nozzle section with 360°
rotation, main valve opening and bronze drain plug.

2 Working pressure of the hydrant shall be 14 bar and the testing pressure shall be 28 bar
unless otherwise stated in the Project Documentation or agreed with the Engineer.

3 The hydrant shall comply with ASNI/AWWA C502 and shall be UL listed and FM approved.

4 Materials for the hydrants shall be as follows:

(a) nozzle section, barrels, stand pipe flanges, breakable flange, base, main valve flange,
weather-shield operating nut and bonnet all shall be ductile iron
(b) main valve disc shall be ductile iron core and fully encapsulated in EPDM rubber
(c) caps shall be cast iron
(d) coating above ground shall be fusion bonded epoxy inside and out
(e) coating below ground shall be bitumen or fusion bonded epoxy
QCS 2014 Section 23: Fire Fighting and Fire Alarm Systems Page 10
Part 04: Fire Fighting System

(f) nozzles, valve seat ring, drain ring, drain bushings and plugs, stem nut, stem bushing
and thrust nut shall be bronze
(g) stop nut, cap chain, bolts and nuts shall be zinc plated steel
(h) stem rod coupling, standpipe lock rings, nozzle lock screw, lock plate, lock plate screw
and spider bolt shall be stainless steel
(i) barrel gaskets and cap gaskets shall be nitrile rubber.

5 Each hydrant shall be clearly marked, either integrally with the stated components or on a
plate of durable material securely fixed to that component, as follows:

(a) the number of the standard to which the hydrant conforms and the date of the
standard
(b) the manufacturer‟s name or trade mark
(c) the identification number (the reference used by the manufacturer allowing
identification for the supply of spares, etc).

4.5.3 Underground Fire Hydrants and Surface Box Frames and Covers

1 Underground fire hydrants and surface box frames and covers shall generally comply with
the requirements of BS 750.

2 Underground fire hydrants with wedge gate type or screw down type valves shall be suitable
for a maximum working pressure of 16 bar.

3 Fire hydrants shall be of the wedge gate type or screw-down type.

4 The wedge gate valve shall comply with the requirements of BS 5163 for PN 16 valves. The
associated duck foot bends shall be grey cast iron (CI) to BS EN 1561 Grade 250 or
spheroidal graphite cast iron (SG) to BS EN 1563.

5 Materials and testing of underground fire hydraulic shall be to BS 750. Provision shall be
made for a certificate to be made available which certifies that the hydrant has complied with
all testing requirements of BS 750.

6 Each screw-down type hydrant and each duck foot bend on a wedge gate type hydrant shall
be provided with a drain boss on the outlet side. It shall be located at the lowest practicable
point.

7 The hydrants shall have screwed outlets. The screwed outlet shall be provided with a cap to
cover the outlet thread. It shall be securely attached to the hydrant by a chain or other
flexible device.

8 When fitted with a standard round thread outlet, the hydrant shall deliver not less than 2000
litres/minute at a constant pressure of 1.7 bar at the inlet to the hydrant.

9 The hydrant operating spindle shall be provided with a cast iron cap complying with the
requirements of BS 5163. The cap shall be securely fixed to the spindle so that it remains
fixed in position during normal use.

10 Each hydrant valve, duckfoot bend and outlet shall be clearly marked, either integrally with
the stated components or on a plate of durable material securely fixed to that component, as
follows:

(a) on wedge gate type hydrant valves:


(i) in addition to the marking requirements of BS 5163, the direction of valve
opening on the gland or upper part of the hydrant.
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

17. Design
Calculation
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

NOT APPLICABLE
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

18. Bill of
Quantities
BILL OF QUANTITIES‐ External Valves & Above Ground Hydrant
S.No. Material Description Size (mm) Qty Unit Remarks
1 NRS Gate valve with Indicator Post (PIV)

1.1 NRS Gate valve with Indicator Post (PIV) 300ᴓ  dia. 2 No's

1.2 NRS Gate valve with Indicator Post (PIV) 200ᴓ dia. 1 No's

1.3 NRS Gate valve with Indicator Post (PIV) 150ᴓ dia. 10 No's

2 NRS Gate Valve with Valve Composite Box

2.1 NRS Gate Valve with Valve Composite Box 300ᴓ  dia. 34 No's

2.2 NRS Gate Valve with Valve Composite Box 200ᴓ dia. 15 No's

2.3 NRS Gate Valve with Valve Composite Box 150ᴓ dia. 22 No's

3 Above Ground Dry Barrel Hydrant 

150ᴓ dia. ‐ dry barrel fire hydrant, 6" flanged inlet, two 2‐1/2" 
3.1 hose connections, one 4" pumper connection, AWWA C502,  150ᴓ dia. 105 No's
LPCB certified @ 250 psi

* Note‐ This BOQ is of tendative quantity, which may vary with final design & Shop drawing submissions. 
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

19. International
Standards
MATERIAL SUBMITTAL FOR EXTERNAL NETWORK &
HYDRANT VALVES

EN 1902-2, ASTM A536