Professional Documents
Culture Documents
Protective Device Coordination Enhancement For Motor Starting Programs
Protective Device Coordination Enhancement For Motor Starting Programs
I. INTRODUCTION
Tripped if
For the protection device of the line, Cooper Power Systems’
Not Tripped if
Edison-Pro microprocessor relay is chosen. The ground CT ratio
5) accumulator will be instantaneously stopped and reset to is set to 100:1 and IEC Curve A is used.
zero if the relay senses that branch current is less than The minimum single-line-to-ground fault at Bus 2 is 546 A.
at any point in time. Otherwise, if high current is still For the chosen relay, a tap setting of 5 is reasonable, resulting in
present, repeat Steps 2 through 5. a minimum pickup current, or , of 500 A. Fig. 1 also shows
the TCC curve of the relay in the above setting.
B. Nonideal Resetting Motor-starting simulation with the classic method [1] gives
the instantaneous starting current curve as shown in Fig. 5. The
Due to their mechanical nature, electromechanical relays are initial motor start current is close to 700 A, which is greater
reset to an initial status only when the average current drops than . So the time accumulator will start. In this simple case
below the pickup current, not just the instantaneous current. So, where an “across the line” start is used, the motor current curve
Step 5 of the previous algorithm must be changed to consider during startup has a nearly flat peak. So is more than 600
whether has dropped below . A. The exact value can be calculated using (1). From the TCC
Another variation from the ideal resetting is the way to cal- curve, associated with 600 A is slightly more than 1 s. The
culate at time peak current will sustain for about 3 s. Since , the
relay will trip during startup.
When relay misoperation is predicted, it is usually not an
(2) option to raise the relay pickup current, since the relay must
be able to trip when the minimum single-line-to-ground fault
where, as before, is the accumulator starting time, and occurs. Hence, different starting methods, such as reduced
is the branch current during startup. voltage starting for squirrel cage motors and the varying rotor
The branch current shown in Fig. 3 is an example of a non- external resistance method for wound rotor motors, can be used
ideal resetting potentially resulting in a nuisance trip operation. to reduce the average startup current. Choosing different motor
The current curve for two sequentially started motors makes types, such as a double-cage motor or changing the load torque
positive contributions to the average current during the intervals pattern, can also achieve the reduced starting current. Most of
and , while the interval has a negative con- the motor starting programs allow experimentation with the
tribution. It is possible that the cumulative effect of could different options to determine an acceptable solution.
result in a trip condition even though starting either motor inde-
pendently would not result in a trip. IV. CONCLUSION
A method for studying the effect of motor starting on distri-
III. EXAMPLE bution system protective devices is presented in this paper. Ac-
An example is used to demonstrate the simulation of motor- cording to a relay’s operating principle, this method compares
starting effects on protective devices. the accumulated energy during motor starting to the energy to
In Fig. 4, the source has equal positive–, negative-, and zero- trip a protective device based on its TCC curve to determine if
sequence impedance of . The line has a positive- the device will operate. Two different algorithms are used to
and negative-sequence impedance of and the zero- simulate ideal or nonideal resetting. The proposed protective
sequence impedance is . device coordination enhancement to motor-starting simulation
The motor is a 2.3-kV, 500-hp single-cage induction motor. programs is a useful tool to measure motor starting impact on
The stator and rotor circuit impedance is . system protective devices and help to avoid nuisance operations.
IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 1, JANUARY 2005 537
REFERENCES [3] S. E. Zocholl, “Motor analysis and thermal protection,” IEEE Trans.
Power Del., vol. 5, no. 3, pp. 1275–1280, Jul. 1990.
[1] S. M. Halpin, “An improved simulation algorithm for the determination
[4] A. N. Eliasen, “The protection of high-inertia drive motors during ab-
of motor starting transients,” in Proc. Ind. Applicat. Soc. Annu. Meeting, normal starting conditions,” IEEE Trans. Power App. Syst., vol. PAS-99,
Conf. Rec. IEEE, vol. 3, 1994, pp. 2256–2263.
no. 4, pp. 1483–1492, Jul./Aug. 1980.
[2] D. Osborn and R. Richins, “Voltage regulation system during large
motor starting and operation,” in Proc. Cement Industry Technical Conf.
Conference Rec. IEEE Ind. Applicat. Soc./PCA, 1999, pp. 109–119.