harmonics according to IEC61000-3-12

AnalysisDate(MeasureDate) : Tue Aug 21 14:55:40 2012(Tue Aug 21 14:54:33 2012)


Comment : First time usage of V5.01 software. Standard
applies for 16A < I < 75A. Real I: < 500 mA
Regulation : IEC61000-3-12
IEC61000-4-7 2002 PASS
MeasureTime : 150sec
Model : YOKOGAWA WT3000 Ssc : 197811
Power : ------- Min Rsce : 33
Impedance : -------
Wiring : 3V3A
Element : 1 Apply Limit : balanced 3-phase equipment under speciified.
Range : 300V/2A Situation1 : 4.12% (Pass)
Rating Voltage : 400V Term a : 3.21 - 359.58deg (Fail)
Iequ : 110.000A Term c(I5) : 4.10% (Pass)
Z Impedance : 0.1200ohm Term c(I7) : 1.95% (Pass)
I1 : 29.4391A
Power Rsce : 17.4955
Max Rsce : 30.2125

[Average] [Maximum]
Voltage(rms) : 404.91V Voltage(rms) : 405.40V
Current(rms) : 29.55A Current(rms) : 29.69A
Frequency : 50.00Hz Frequency : 50.10Hz
Power Factor : 0.86 Power Factor : 0.86
Sigma W Max : 20558.5W Sigma W Max : 20725.2W
THC : 2.46A THC : 2.71A
V THD : 1.42% V THD : 1.97%
A THD : 6.61% A THD : 8.67%
P THD : 0.08% P THD : 0.14%

Order Measure[%] Limit[%] Margin[%] Order Measure[%] Limit[%] Margin[%]


2 5.0032 8.0000 37.5 2 5.9376 12.0000 50.5
3 3.6087 ------- ------- 3 4.1211 ------- -------
4 0.4936 4.0000 87.7 4 0.7686 6.0000 87.2
5 3.7023 10.8900 66.0 5 4.1034 16.3350 74.9
6 0.6428 2.6667 75.9 6 0.8222 4.0000 79.4
7 1.4081 6.6000 78.7 7 1.9524 9.9000 80.3
8 0.3097 2.0000 84.5 8 0.4522 3.0000 84.9
9 1.5789 ------- ------- 9 1.7823 ------- -------
10 0.2748 1.6000 82.8 10 0.3458 2.4000 85.6
11 2.7297 3.1200 12.5 11 3.0198 4.6800 35.5
12 0.1643 1.3333 87.7 12 0.1951 2.0000 90.2
13 0.4925 2.3000 78.6 13 0.6023 3.4500 82.5
THD 8.3183 13.2000 37.0 THD 10.0655 19.8000 49.2
PWHD 11.1461 21.9100 49.1 PWHD 20.7310 32.8650 36.9

Limit Limit Over Limit Limit Over


OK N/A OK N/A
N/A (rule) N/A (rule)
100 100
In/I1 In/I1
[%] [%]

80 80

60 60

40 40

20 20

0 0
2 5 10 13 THD PWHD 2 5 10 13 THD PWHD
[Order] [Order]
harmonics according to IEC61000-3-12
AnalysisDate(MeasureDate) : Tue Aug 21 14:55:40 2012(Tue Aug 21 14:54:33 2012)
Comment : First time usage of V5.01 software. Standard
applies for 16A < I < 75A. Real I: < 500 mA
Regulation : IEC61000-3-12
IEC61000-4-7 2002 PASS
MeasureTime : 150sec
Model : YOKOGAWA WT3000 Ssc : 197811
Power : ------- Min Rsce : 33
Impedance : -------
Wiring : 3V3A
Element : 2 Apply Limit : balanced 3-phase equipment under speciified.
Range : 300V/2A Situation1 : 3.51% (Pass)
Rating Voltage : 400V Term a : 3.21 - 359.58deg (Fail)
Iequ : 110.000A Term c(I5) : 3.76% (Pass)
Z Impedance : 0.1200ohm Term c(I7) : 1.24% (Pass)
I1 : 29.3436A
Power Rsce : 17.4955
Max Rsce : 27.4163

[Average] [Maximum]
Voltage(rms) : 405.67V Voltage(rms) : 406.19V
Current(rms) : 29.42A Current(rms) : 29.62A
Frequency : 50.00Hz Frequency : 50.10Hz
Power Factor : 0.86 Power Factor : 0.86
Sigma W Max : 20558.5W Sigma W Max : 20725.2W
THC : 2.03A THC : 2.34A
V THD : 1.18% V THD : 1.64%
A THD : 4.71% A THD : 6.49%
P THD : 0.00% P THD : 0.03%

Order Measure[%] Limit[%] Margin[%] Order Measure[%] Limit[%] Margin[%]


2 4.9570 8.0000 38.0 2 4.2058 12.0000 65.0
3 1.9295 ------- ------- 3 3.5111 ------- -------
4 0.4425 4.0000 88.9 4 0.4586 6.0000 92.4
5 1.1742 10.8900 89.2 5 3.7591 16.3350 77.0
6 0.7173 2.6667 73.1 6 0.5899 4.0000 85.3
7 1.7762 6.6000 73.1 7 1.2374 9.9000 87.5
8 0.6091 2.0000 69.5 8 0.2529 3.0000 91.6
9 1.3846 ------- ------- 9 1.5609 ------- -------
10 0.3141 1.6000 80.4 10 0.2745 2.4000 88.6
11 2.3383 3.1200 25.1 11 2.8078 4.6800 40.0
12 0.1597 1.3333 88.0 12 0.1555 2.0000 92.2
13 0.3656 2.3000 84.1 13 0.4831 3.4500 86.0
THD 6.8777 13.2000 47.9 THD 7.8186 19.8000 60.5
PWHD 12.7181 21.9100 42.0 PWHD 10.3805 32.8650 68.4

Limit Limit Over Limit Limit Over


OK N/A OK N/A
N/A (rule) N/A (rule)
100 100
In/I1 In/I1
[%] [%]

80 80

60 60

40 40

20 20

0 0
2 5 10 13 THD PWHD 2 5 10 13 THD PWHD
[Order] [Order]
harmonics according to IEC61000-3-12
AnalysisDate(MeasureDate) : Tue Aug 21 14:55:40 2012(Tue Aug 21 14:54:33 2012)
Comment : First time usage of V5.01 software. Standard
applies for 16A < I < 75A. Real I: < 500 mA
Regulation : IEC61000-3-12
IEC61000-4-7 2002 PASS
MeasureTime : 150sec
Model : YOKOGAWA WT3000 Ssc : 197811
Power : ------- Min Rsce : 33
Impedance : -------
Wiring : 3V3A
Element : 3 Apply Limit : balanced 3-phase equipment under speciified.
Range : 300V/2A Situation1 : 1.99% (Pass)
Rating Voltage : 400V Term a : 3.21 - 359.58deg (Fail)
Iequ : 110.000A Term c(I5) : 0.87% (Pass)
Z Impedance : 0.1200ohm Term c(I7) : 1.71% (Pass)
I1 : 29.0292A
Power Rsce : 17.4955
Max Rsce : 25.9560

[Average] [Maximum]
Voltage(rms) : 405.79V Voltage(rms) : 406.34V
Current(rms) : 29.13A Current(rms) : 29.45A
Frequency : 50.00Hz Frequency : 50.10Hz
Power Factor : 0.01 Power Factor : 0.02
Sigma W Max : 20558.5W Sigma W Max : 20725.2W
THC : 2.35A THC : 2.63A
V THD : 1.25% V THD : 1.72%
A THD : 6.23% A THD : 8.33%
P THD : 0.88% P THD : 4.38%

Order Measure[%] Limit[%] Margin[%] Order Measure[%] Limit[%] Margin[%]


2 5.0405 8.0000 37.0 2 4.1617 12.0000 65.3
3 2.8974 ------- ------- 3 1.9939 ------- -------
4 0.6267 4.0000 84.3 4 0.4084 6.0000 93.2
5 4.2435 10.8900 61.0 5 0.8727 16.3350 94.7
6 0.4440 2.6667 83.4 6 0.6933 4.0000 82.7
7 1.3468 6.6000 79.6 7 1.7083 9.9000 82.7
8 0.6194 2.0000 69.0 8 0.5467 3.0000 81.8
9 0.3625 ------- ------- 9 1.4601 ------- -------
10 0.3033 1.6000 81.0 10 0.2949 2.4000 87.7
11 2.1338 3.1200 31.6 11 2.3740 4.6800 49.3
12 0.1533 1.3333 88.5 12 0.1612 2.0000 91.9
13 0.4125 2.3000 82.1 13 0.3591 3.4500 89.6
THD 8.0661 13.2000 38.9 THD 6.2647 19.8000 68.4
PWHD 12.4484 21.9100 43.2 PWHD 12.1174 32.8650 63.1

Limit Limit Over Limit Limit Over


OK N/A OK N/A
N/A (rule) N/A (rule)
100 100
In/I1 In/I1
[%] [%]

80 80

60 60

40 40

20 20

0 0
2 5 10 13 THD PWHD 2 5 10 13 THD PWHD