Harmonics According To IEC61000-3-12: Limit OK N/A (Rule) Limit Over N/A Limit OK N/A (Rule) Limit Over N/A
Harmonics According To IEC61000-3-12: Limit OK N/A (Rule) Limit Over N/A Limit OK N/A (Rule) Limit Over N/A
[Average] [Maximum]
Voltage(rms) : 401.88V Voltage(rms) : 402.78V
Current(rms) : 110.42A Current(rms) : 110.90A
Frequency : 49.98Hz Frequency : 50.03Hz
Power Factor : 0.86 Power Factor : 0.86
Sigma W Max : 76543.0W Sigma W Max : 76894.6W
THC : 2.82A THC : 2.94A
V THD : 1.32% V THD : 1.84%
A THD : 1.90% A THD : 2.34%
P THD : 0.02% P THD : 0.03%
80 80
60 60
40 40
20 20
0 0
2 5 10 13 THD PWHD 2 5 10 13 THD PWHD
[Order] [Order]
harmonics according to IEC61000-3-12
AnalysisDate(MeasureDate) : Tue Aug 21 14:38:57 2012(Tue Aug 21 14:27:55 2012)
Comment : First time usage of V5.01 software. Standard
applies for 16A < I < 75A. Real I: < 500 mA
Regulation : IEC61000-3-12
IEC61000-4-7 2002 PASS
MeasureTime : 150sec
Model : YOKOGAWA WT3000 Ssc : 112639
Power : ------- Min Rsce : 33
Impedance : -------
Wiring : 3V3A
Element : 2 Apply Limit : balanced 3-phase equipment under speciified.
Range : 300V/2A Situation1 : 1.01% (Pass)
Rating Voltage : 400V Term a : 53.92 - 357.53deg (Fail)
Iequ : 110.000A Term c(I5) : 1.12% (Pass)
Z Impedance : 0.1200ohm Term c(I7) : 0.29% (Pass)
I1 : 109.493A
Power Rsce : 17.4955
Max Rsce : 14.6755
[Average] [Maximum]
Voltage(rms) : 402.70V Voltage(rms) : 403.55V
Current(rms) : 109.52A Current(rms) : 109.91A
Frequency : 49.98Hz Frequency : 50.03Hz
Power Factor : 0.87 Power Factor : 0.87
Sigma W Max : 76543.0W Sigma W Max : 76894.6W
THC : 2.27A THC : 2.38A
V THD : 1.10% V THD : 1.58%
A THD : 1.19% A THD : 1.52%
P THD : 0.00% P THD : 0.01%
80 80
60 60
40 40
20 20
0 0
2 5 10 13 THD PWHD 2 5 10 13 THD PWHD
[Order] [Order]
harmonics according to IEC61000-3-12
AnalysisDate(MeasureDate) : Tue Aug 21 14:38:57 2012(Tue Aug 21 14:27:55 2012)
Comment : First time usage of V5.01 software. Standard
applies for 16A < I < 75A. Real I: < 500 mA
Regulation : IEC61000-3-12
IEC61000-4-7 2002 PASS
MeasureTime : 150sec
Model : YOKOGAWA WT3000 Ssc : 112639
Power : ------- Min Rsce : 33
Impedance : -------
Wiring : 3V3A
Element : 3 Apply Limit : balanced 3-phase equipment under speciified.
Range : 300V/2A Situation1 : 0.41% (Pass)
Rating Voltage : 400V Term a : 53.92 - 357.53deg (Fail)
Iequ : 110.000A Term c(I5) : 0.39% (Pass)
Z Impedance : 0.1200ohm Term c(I7) : 0.41% (Pass)
I1 : 109.305A
Power Rsce : 17.4955
Max Rsce : 14.7801
[Average] [Maximum]
Voltage(rms) : 403.59V Voltage(rms) : 404.54V
Current(rms) : 109.34A Current(rms) : 109.70A
Frequency : 49.98Hz Frequency : 50.03Hz
Power Factor : - 0.01 Power Factor : - 0.01
Sigma W Max : 76543.0W Sigma W Max : 76894.6W
THC : 2.51A THC : 2.67A
V THD : 1.14% V THD : 1.57%
A THD : 1.55% A THD : 2.06%
P THD : 0.10% P THD : 0.52%
80 80
60 60
40 40
20 20
0 0
2 5 10 13 THD PWHD 2 5 10 13 THD PWHD
[Order] [Order]