GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

OWNER: CPWD
CONTRACTOR: ASHISH CONSTRUCTION
DETAILED ENGINEERING CONSULTANT: TASHAVI STRUCTURAL CONSULTANT
PROJECT: EXPORT INSPECTION AGENCY AT-AHMEDABAD

R2 ISSUED FOR REVIEW 23rd May 2022 ACP VKP VKP

R1 ISSUED FOR REVIEW 09th May 2022 ACP VKP VKP

R0 ISSUED FOR REVIEW 18th Feb. 2022 ACP VKP VKP

REV DESCRIPTION DATE PREPARED CHECKED APPROVED


GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

OWNER : CPWD
ENGINEERING CONSULTANT: TASHAVI CONSULTANTS
PROJECT: GLAZZING SUPPORTING STRUCTURE

CONTENT

DESCRIPTION PAGE NO

1. Preamble 2
2. Reference Documents/Drawings 2
3. Design parameters 2
4. Software Used 2
5. Outline of Structure 3
6. Loading on Structure 4
7. Primary Load Cases and Load Combination 5

ANNEXURE-A : STAAD INPUT FILE & OUTPUT FILE 6


ANNEXURE-B : DESIGN RESULTS & CHECK 9
ANNEXURE-C : STRUCTURAL GA DRAWING 22

1 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

1 Preamble

Structure for supporting the Glass Glazzing is Steel & Aluminum structure and
this Steel structure supporting on RCC existing column. The different type of
structure are analyzed in STAAD Pro. Software. Design of this structure is as per
Code and is considered suitable in STAAD Pro parameters. Members of the
structures are checked for various loads & combination of as stated in further
section.

2 Reference Documents/Drawings
Drawing provided by client

3 Design Parameters

 Yield strength of steel: 250 N/mm2


 Unit weight of steel: 7850 kg/m3
 Self weight multiplier: 1.0
 Connection Bolt: 8.8 grade (chemical bolt)
 Density of Glass 25 kN/m3

4 Software Used

 STAAD Pro
 MS excel

2 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

5 Outline of Structure

Y
X
Z Load 1

Fig 1 : STAAD model

Y
X
Z Load 1

Fig 2 : 3D model

3 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

Y
X
Z Load 2

Fig 3 : LOAD ON GLAZZING

6 Loading on Structure
 The Various types of load with different loading patterns are applied on
the structure as below.
6.1 Dead Load
 The dead load consists of self weight of the structures. Self weight of the
structure is considered as using self weight command in STAAD Pro
software.
 Glass combination = 6mm glass + 12mm air gap + 6mm glass.
Hence consider 12mm glass thickness
Weight of Glass = 25 x 12/1000 = 0.30 kN/m2
C/C support of Glass = 1.2m
Load on Glass supporting member = 0.30 x 1.2 = 0.36 kN/m

4 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

6.2 Wind load

WIND LOAD CALCULATION

Length of Trestle = 3.50 m


Width of Trestle = 0.00 m
Height of Trestle from Ground Level = 12.00 m
Basic Wind Speed Vb = 39.00 m/s
Probability Factor, Risk Coefficient k1 = 0.92
Terrain, Height & structure size factor k2 = 0.97
Topography factor k3 = 1.00
Importance factor for cyclonic Region k4 = 1.00
Design Wind Speed Vz = Vbk1k2k3k4
= 34.80 m/s
Wind Pressure pz = 0.6Vz2
= 726.77 N/m2
= 0.73 kN/m2
Wind Directionality Factor kd = 0.90
Area Averaging Factor ka = 0.80
Combination Factor kc = 1.00
Design wind pressure Pd1 = pzkdkakc
= 0.53 kN/m2
As per Requirement 1.5Pd1
Design wind pressure Pd = 0.79 kN/m2

Load apply in STAAD and width of member consider directly in STAAD.

7 Primary Load Cases and Load Combination


i. Primary Load cases :
LOAD 1 LOADTYPE Dead TITLE DL
LOAD 2 LOADTYPE WIND TITLE WL

ii. Load combinations :

AS PER STAAD MODEL

5 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

ANNEXURE – A : STAAD INPUT FILE & OUTPUT FILE

6 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

1. STAAD SPACE
INPUT FILE: Glazzing 1_R3.STD
2. START JOB INFORMATION
3. ENGINEER DATE 30-JAN-22
4. END JOB INFORMATION
5. INPUT WIDTH 79
6. UNIT METER KN
7. JOINT COORDINATES
8. 1 0 0 0; 2 3.5 0 0; 7 0 12 0; 8 3.5 12 0; 9 0.875 12 0; 10 1.75 12 0
9. 11 2.625 12 0; 12 0.875 0 0; 13 1.75 0 0; 14 2.625 0 0; 15 0 1.2 0
10. 16 3.5 1.2 0; 17 0.875 1.2 0; 18 1.75 1.2 0; 19 2.625 1.2 0; 20 0 2.4 0
11. 21 3.5 2.4 0; 22 0.875 2.4 0; 23 1.75 2.4 0; 24 2.625 2.4 0; 25 0 3.6 0
12. 26 3.5 3.6 0; 27 0.875 3.6 0; 28 1.75 3.6 0; 29 2.625 3.6 0; 30 0 4.8 0
13. 31 3.5 4.8 0; 32 0.875 4.8 0; 33 1.75 4.8 0; 34 2.625 4.8 0; 35 0 6 0
14. 36 3.5 6 0; 37 0.875 6 0; 38 1.75 6 0; 39 2.625 6 0; 40 0 7.2 0; 41 3.5 7.2 0
15. 42 0.875 7.2 0; 43 1.75 7.2 0; 44 2.625 7.2 0; 45 0 8.4 0; 46 3.5 8.4 0
16. 47 0.875 8.4 0; 48 1.75 8.4 0; 49 2.625 8.4 0; 50 0 9.6 0; 51 3.5 9.6 0
17. 52 0.875 9.6 0; 53 1.75 9.6 0; 54 2.625 9.6 0; 55 0 10.8 0; 56 3.5 10.8 0
18. 57 0.875 10.8 0; 58 1.75 10.8 0; 59 2.625 10.8 0
19. MEMBER INCIDENCES
20. 1 1 12; 4 7 9; 5 9 10; 6 10 11; 7 11 8; 8 7 55; 9 12 13; 10 9 57; 11 13 14
21. 12 10 58; 13 14 2; 14 11 59; 15 8 56; 16 15 1; 17 16 2; 18 17 12; 19 18 13
22. 20 19 14; 21 15 17; 22 17 18; 23 18 19; 24 19 16; 25 20 15; 26 21 16; 27 22 17
23. 28 23 18; 29 24 19; 30 20 22; 31 22 23; 32 23 24; 33 24 21; 34 25 20; 35 26 21
24. 36 27 22; 37 28 23; 38 29 24; 39 25 27; 40 27 28; 41 28 29; 42 29 26; 43 30 25
25. 44 31 26; 45 32 27; 46 33 28; 47 34 29; 48 30 32; 49 32 33; 50 33 34; 51 34 31
26. 52 35 30; 53 36 31; 54 37 32; 55 38 33; 56 39 34; 57 35 37; 58 37 38; 59 38 39
27. 60 39 36; 61 40 35; 62 41 36; 63 42 37; 64 43 38; 65 44 39; 66 40 42; 67 42 43
28. 68 43 44; 69 44 41; 70 45 40; 71 46 41; 72 47 42; 73 48 43; 74 49 44; 75 45 47
29. 76 47 48; 77 48 49; 78 49 46; 79 50 45; 80 51 46; 81 52 47; 82 53 48; 83 54 49
30. 84 50 52; 85 52 53; 86 53 54; 87 54 51; 88 55 50; 89 56 51; 90 57 52; 91 58 53
31. 92 59 54; 93 55 57; 94 57 58; 95 58 59; 96 59 56
32. DEFINE MATERIAL START
33. ISOTROPIC ALUMINUM
34. E 6.89476E+007
35. POISSON 0.33
36. DENSITY 26.6018
37. ALPHA 2.3E-005
38. DAMP 0.03
39. ISOTROPIC STEEL
40. E 2.05E+008
41. POISSON 0.3
42. DENSITY 76.8195
43. ALPHA 1.2E-005
44. DAMP 0.03
45. TYPE STEEL
46. STRENGTH FY 253200 FU 407800 RY 1.5 RT 1.2
47. END DEFINE MATERIAL
48. MEMBER PROPERTY INDIAN
49. 10 12 14 18 TO 24 27 TO 33 36 TO 38 45 TO 51 54 TO 60 63 TO 65 72 TO 78 81 -
50. 82 TO 87 90 TO 92 TABLE ST TUBE TH 0.0037 WT 0.131 DT 0.067
51. 4 TO 8 15 TO 17 25 26 34 35 43 44 52 53 61 62 70 71 79 80 88 -

7 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

52. 89 TABLE ST TUBE TH 0.003 WT 0.131 DT 0.0385


53. MEMBER PROPERTY TATASTRUCTURA
54. 1 9 11 13 39 TO 42 66 TO 69 93 TO 96 TABLE ST 72X72X3.2SHS
55. CONSTANTS
56. MATERIAL ALUMINUM MEMB 4 TO 8 10 12 14 TO 38 43 TO 65 70 TO 92
57. MATERIAL STEEL MEMB 1 9 11 13 39 TO 42 66 TO 69 93 TO 96
58. SUPPORTS
59. 1 2 25 26 40 41 55 56 PINNED
60. DEFINE WIND LOAD
61. TYPE 1 WIND 1
62. INT 0.79 HEIG 20
63. EXP 1 JOINT 1 2 7 TO 59
64. LOAD 1 LOADTYPE DEAD TITLE DL
65. SELFWEIGHT Y -1
66. MEMBER LOAD
67. 1 4 TO 7 9 11 13 21 TO 24 30 TO 33 39 TO 42 48 TO 51 57 TO 60 66 TO 69 75 -
68. 76 TO 78 84 TO 87 93 TO 96 UNI GY -0.36
69. LOAD 2 LOADTYPE WIND TITLE WL
70. WIND LOAD Z 1 TYPE 1
71. LOAD COMB 101 1.2(DL+WL)
72. 1 1.2 2 1.2
73. LOAD COMB 201 DL+WL
74. 1 0.8 2 0.8
75. PERFORM ANALYSIS PRINT STATICS CHECK

8 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

ANNEXURE – B : DESIGN RESULTS AND CHECK

9 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

STAAD.PRO CODE CHECKING - IS-800 2007(LSD)


*****************************************************

|----------------------------------------------------------------------------------|
| Member Number: 1 |
| Member Section: ST 72X72X3.2SHS (TATA STRUCTURA SECTIONS) |
| Status: PASS Ratio: 0.502 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 4 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.213 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 5 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.213 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 6 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.213 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 7 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.213 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 8 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.292 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 9 |
| Member Section: ST 72X72X3.2SHS (TATA STRUCTURA SECTIONS) |
| Status: PASS Ratio: 0.314 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 10 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 11 |
| Member Section: ST 72X72X3.2SHS (TATA STRUCTURA SECTIONS) |
| Status: PASS Ratio: 0.314 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 12 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.00 |

10 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

| Critical Condition: Slenderness |


|----------------------------------------------------------------------------------|
| Member Number: 13 |
| Member Section: ST 72X72X3.2SHS (TATA STRUCTURA SECTIONS) |
| Status: PASS Ratio: 0.502 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 14 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 15 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.292 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 16 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.292 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 17 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.292 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 18 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.80 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 19 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.107 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 20 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.80 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 21 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.125 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 22 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.125 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|

11 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

| Member Number: 23 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.125 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 24 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.125 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 25 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.292 Critical Load Case: 101 Location: 0.80 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 26 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.292 Critical Load Case: 101 Location: 0.80 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 27 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.107 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 28 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.107 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 29 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.107 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 30 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.087 Critical Load Case: 101 Location: 0.87 |
| Critical Condition: Minor Axis Bending (Sec. 8) |
|----------------------------------------------------------------------------------|
| Member Number: 31 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.132 Critical Load Case: 101 Location: 0.87 |
| Critical Condition: Minor Axis Bending (Sec. 8) |
|----------------------------------------------------------------------------------|
| Member Number: 32 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.132 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Minor Axis Bending (Sec. 8) |
|----------------------------------------------------------------------------------|
| Member Number: 33 |
| Member Section: ST TUB E (INDIAN SECTIONS) |

12 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

| Status: PASS Ratio: 0.087 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Minor Axis Bending (Sec. 8) |
|----------------------------------------------------------------------------------|
| Member Number: 34 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.290 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Sec. 9.3.1.3 |
|----------------------------------------------------------------------------------|
| Member Number: 35 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.290 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Sec. 9.3.1.3 |
|----------------------------------------------------------------------------------|
| Member Number: 36 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.107 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 37 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.107 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 38 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.107 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 39 |
| Member Section: ST 72X72X3.2SHS (TATA STRUCTURA SECTIONS) |
| Status: PASS Ratio: 0.314 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 40 |
| Member Section: ST 72X72X3.2SHS (TATA STRUCTURA SECTIONS) |
| Status: PASS Ratio: 0.502 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 41 |
| Member Section: ST 72X72X3.2SHS (TATA STRUCTURA SECTIONS) |
| Status: PASS Ratio: 0.502 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 42 |
| Member Section: ST 72X72X3.2SHS (TATA STRUCTURA SECTIONS) |
| Status: PASS Ratio: 0.314 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 43 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.292 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |

13 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

|----------------------------------------------------------------------------------|
| Member Number: 44 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.292 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 45 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 46 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.107 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 47 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 48 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.129 Critical Load Case: 101 Location: 0.87 |
| Critical Condition: Sec. 9.3.2.2 (Y) |
|----------------------------------------------------------------------------------|
| Member Number: 49 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.150 Critical Load Case: 101 Location: 0.87 |
| Critical Condition: Sec. 9.3.2.2 (Y) |
|----------------------------------------------------------------------------------|
| Member Number: 50 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.150 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 (Y) |
|----------------------------------------------------------------------------------|
| Member Number: 51 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.129 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 (Y) |
|----------------------------------------------------------------------------------|
| Member Number: 52 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.292 Critical Load Case: 101 Location: 0.60 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 53 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.292 Critical Load Case: 101 Location: 0.60 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 54 |

14 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

| Member Section: ST TUB E (INDIAN SECTIONS) |


| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 55 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.20 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 56 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 57 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.092 Critical Load Case: 101 Location: 0.87 |
| Critical Condition: Minor Axis Bending (Sec. 8) |
|----------------------------------------------------------------------------------|
| Member Number: 58 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.144 Critical Load Case: 101 Location: 0.87 |
| Critical Condition: Minor Axis Bending (Sec. 8) |
|----------------------------------------------------------------------------------|
| Member Number: 59 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.144 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Minor Axis Bending (Sec. 8) |
|----------------------------------------------------------------------------------|
| Member Number: 60 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.092 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Minor Axis Bending (Sec. 8) |
|----------------------------------------------------------------------------------|
| Member Number: 61 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.262 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Sec. 9.3.1.3 |
|----------------------------------------------------------------------------------|
| Member Number: 62 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.262 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Sec. 9.3.1.3 |
|----------------------------------------------------------------------------------|
| Member Number: 63 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 64 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.00 |

15 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

| Critical Condition: Slenderness |


|----------------------------------------------------------------------------------|
| Member Number: 65 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 66 |
| Member Section: ST 72X72X3.2SHS (TATA STRUCTURA SECTIONS) |
| Status: PASS Ratio: 0.502 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 67 |
| Member Section: ST 72X72X3.2SHS (TATA STRUCTURA SECTIONS) |
| Status: PASS Ratio: 0.314 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 68 |
| Member Section: ST 72X72X3.2SHS (TATA STRUCTURA SECTIONS) |
| Status: PASS Ratio: 0.314 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 69 |
| Member Section: ST 72X72X3.2SHS (TATA STRUCTURA SECTIONS) |
| Status: PASS Ratio: 0.502 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 70 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.292 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 71 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.292 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 72 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 73 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 74 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|

16 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

| Member Number: 75 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.125 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 76 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.140 Critical Load Case: 101 Location: 0.87 |
| Critical Condition: Sec. 9.3.2.2 (Y) |
|----------------------------------------------------------------------------------|
| Member Number: 77 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.140 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Sec. 9.3.2.2 (Y) |
|----------------------------------------------------------------------------------|
| Member Number: 78 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.125 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 79 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.292 Critical Load Case: 101 Location: 0.60 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 80 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.292 Critical Load Case: 101 Location: 0.60 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 81 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 82 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 83 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 84 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.083 Critical Load Case: 101 Location: 0.87 |
| Critical Condition: Minor Axis Bending (Sec. 8) |
|----------------------------------------------------------------------------------|
| Member Number: 85 |
| Member Section: ST TUB E (INDIAN SECTIONS) |

17 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

| Status: PASS Ratio: 0.132 Critical Load Case: 101 Location: 0.87 |
| Critical Condition: Minor Axis Bending (Sec. 8) |
| Member Number: 86 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.132 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Minor Axis Bending (Sec. 8) |
| Member Number: 87 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.083 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Minor Axis Bending (Sec. 8) |
|----------------------------------------------------------------------------------|
| Member Number: 88 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.221 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Sec. 9.3.1.3 |
| Member Number: 89 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.221 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Sec. 9.3.1.3 |
| Member Number: 90 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 91 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
| Member Number: 92 |
| Member Section: ST TUB E (INDIAN SECTIONS) |
| Status: PASS Ratio: 0.172 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|
| Member Number: 93 |
| Member Section: ST 72X72X3.2SHS (TATA STRUCTURA SECTIONS) |
| Status: PASS Ratio: 0.314 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
| Member Number: 94 |
| Member Section: ST 72X72X3.2SHS (TATA STRUCTURA SECTIONS) |
| Status: PASS Ratio: 0.502 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
| Member Number: 95 |
| Member Section: ST 72X72X3.2SHS (TATA STRUCTURA SECTIONS) |
| Status: PASS Ratio: 0.502 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
| Member Number: 96 |
| Member Section: ST 72X72X3.2SHS (TATA STRUCTURA SECTIONS) |
| Status: PASS Ratio: 0.314 Critical Load Case: 101 Location: 0.00 |
| Critical Condition: Slenderness |
|----------------------------------------------------------------------------------|

18 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

Members unity Check:

Actual Limiting
BEAM Property Ratio Ratio check
1 72X72X3.2SHS 0.502 0.8 OK
4 TUBE 0.213 0.8 OK
5 TUBE 0.213 0.8 OK
6 TUBE 0.213 0.8 OK
7 TUBE 0.213 0.8 OK
8 TUBE 0.292 0.8 OK
9 72X72X3.2SHS 0.314 0.8 OK
10 TUBE 0.172 0.8 OK
11 72X72X3.2SHS 0.314 0.8 OK
12 TUBE 0.172 0.8 OK
13 72X72X3.2SHS 0.502 0.8 OK
14 TUBE 0.172 0.8 OK
15 TUBE 0.292 0.8 OK
16 TUBE 0.292 0.8 OK
17 TUBE 0.292 0.8 OK
18 TUBE 0.172 0.8 OK
19 TUBE 0.107 0.8 OK
20 TUBE 0.172 0.8 OK
21 TUBE 0.125 0.8 OK
22 TUBE 0.125 0.8 OK
23 TUBE 0.125 0.8 OK
24 TUBE 0.125 0.8 OK
25 TUBE 0.292 0.8 OK
26 TUBE 0.292 0.8 OK
27 TUBE 0.107 0.8 OK
28 TUBE 0.107 0.8 OK
29 TUBE 0.107 0.8 OK
30 TUBE 0.087 0.8 OK
31 TUBE 0.132 0.8 OK
32 TUBE 0.132 0.8 OK
33 TUBE 0.087 0.8 OK
34 TUBE 0.29 0.8 OK
35 TUBE 0.29 0.8 OK
36 TUBE 0.107 0.8 OK
37 TUBE 0.107 0.8 OK
38 TUBE 0.107 0.8 OK

19 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

39 72X72X3.2SHS 0.314 0.8 OK


40 72X72X3.2SHS 0.502 0.8 OK
41 72X72X3.2SHS 0.502 0.8 OK
42 72X72X3.2SHS 0.314 0.8 OK
43 TUBE 0.292 0.8 OK
44 TUBE 0.292 0.8 OK
45 TUBE 0.172 0.8 OK
46 TUBE 0.107 0.8 OK
47 TUBE 0.172 0.8 OK
48 TUBE 0.129 0.8 OK
49 TUBE 0.15 0.8 OK
50 TUBE 0.15 0.8 OK
51 TUBE 0.129 0.8 OK
52 TUBE 0.292 0.8 OK
53 TUBE 0.292 0.8 OK
54 TUBE 0.172 0.8 OK
55 TUBE 0.172 0.8 OK
56 TUBE 0.172 0.8 OK
57 TUBE 0.092 0.8 OK
58 TUBE 0.144 0.8 OK
59 TUBE 0.144 0.8 OK
60 TUBE 0.092 0.8 OK
61 TUBE 0.262 0.8 OK
62 TUBE 0.262 0.8 OK
63 TUBE 0.172 0.8 OK
64 TUBE 0.172 0.8 OK
65 TUBE 0.172 0.8 OK
66 72X72X3.2SHS 0.502 0.8 OK
67 72X72X3.2SHS 0.314 0.8 OK
68 72X72X3.2SHS 0.314 0.8 OK
69 72X72X3.2SHS 0.502 0.8 OK
70 TUBE 0.292 0.8 OK
71 TUBE 0.292 0.8 OK
72 TUBE 0.172 0.8 OK
73 TUBE 0.172 0.8 OK
74 TUBE 0.172 0.8 OK
75 TUBE 0.125 0.8 OK
76 TUBE 0.14 0.8 OK
77 TUBE 0.14 0.8 OK
78 TUBE 0.125 0.8 OK

20 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

79 TUBE 0.292 0.8 OK


80 TUBE 0.292 0.8 OK
81 TUBE 0.172 0.8 OK
82 TUBE 0.172 0.8 OK
83 TUBE 0.172 0.8 OK
84 TUBE 0.083 0.8 OK
85 TUBE 0.132 0.8 OK
86 TUBE 0.132 0.8 OK
87 TUBE 0.083 0.8 OK
88 TUBE 0.221 0.8 OK
89 TUBE 0.221 0.8 OK
90 TUBE 0.172 0.8 OK
91 TUBE 0.172 0.8 OK
92 TUBE 0.172 0.8 OK
93 72X72X3.2SHS 0.314 0.8 OK
94 72X72X3.2SHS 0.502 0.8 OK
95 72X72X3.2SHS 0.502 0.8 OK
96 72X72X3.2SHS 0.314 0.8 OK

21 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

Deflection Check:

1.411 mm
6.137 mm
8.121 mm
1.411 6.137
mm mm
6.602 mm
9.109 mm
6.602 mm
2.977 mm
7.529 mm
9.450 mm
2.977 mm mm
7.529
2.811 mm
7.577 mm
9.579 mm
2.811 7.577
mm mm
7.010 mm
9.637 mm
7.010 mm
2.274 mm
7.246 mm
9.338 mm
7.246 mm
2.274 mm
2.188 mm
7.335 mm
9.497 mm
7.335 mm
2.188 mm
7.377 mm
10.135 mm
7.377 mm
3.673 mm
8.262 mm
10.185 mm
3.673 8.262
mm mm
4.463 mm
7.885 mm
9.342 mm
7.885 mm
4.463 mm
5.217 mm
7.265 mm
5.217 mm

Deflection check in “Z” direction:

Difference of Deflection in Vertical node = 10.135 – 9.497 = 0.638mm


Difference of Deflection in Horizontal node = 10.135 – 7.377 = 2.758mm

22 of 23
GLAZZING SUPPORTING STRUCTURE

Doc No : 22012401 Date : 23/05/2022

Doc. Title SUPPORTING STRUCTURE DESIGN FOR GLAZZING Rev : 2

ANNEXURE – C : STRUCTURAL GA DRAWING

23 of 23