1(4) DATA SHEET

Input Loop Unit


CS-IC10 WP
Part no. 5210060-00A

System: CFD5000

General description IDAxt protocol


The CS-IC10 WP is an input unit for various The IDAxt protocol is an extension of Consilium’s
integration of safety inputs. It has been designed communication protocol (IDA) and meets the
for use in harsh environments and to comply with demands on data integrity, reliability and
the standards for the industrial, maritime, offshore robustness required for use in SIL 1 and SIL 2
and rolling stock markets up to Safety Integrity safety functions and safety systems.
Level 2 (SIL 2).
The CS-IC10 WP has one input that can be Periodic BIST
connected to external equipment with a dry relay The Periodic Built-In Self-Test is a central
contact. The CS-IC10 WP supervises the cable to mechanism which the system uses to ensure long
the external equipment for cable break and short proof test intervals.
circuit, and the input can be configured as active Countermeasures (defences) have been
high or active low. The function of the input can implemented in order to address the fault modes
be configured to be: (threats) in the fire detection system. These
- a general input countermeasures are done in order to increase
the confidence in the system.
- a fault
- an alarm from a manual call point The system has two types of Built-In Self-Tests
(BIST). The first BIST is made continuously; for
- an alarm from a smoke sensor
instance when reading A/D values from hardware.
- an alarm from a heat sensor This typically involves evaluation of the read value
- an alarm from a flame sensor to determine if the hardware is broken; i.e. gives
- an alive signal (output) measurements outside an acceptable interval.
The second BIST is the Periodic Built-In Self-Test
Features:
(Periodic BIST) which is made once every five
• One supervised input for a dry relay contact minutes in order to verify the safety function by
• Communication with the loop-line testing communication paths and the end
elements. All internal communication paths and all
• Handling of short circuits and cable breaks on the
loop-line testable parts of the loop-units are included in the
Periodic BIST mechanism, to verify the whole path
from detection to reporting (fire) status.
Local intelligence via an integrated The system creates a log with the results of the
CPU Periodic BIST. This log can be extracted from the
The integrated CPU makes it possible to make system with a USB memory stick.
decisions locally, like evaluation of the alarm
condition. Short Circuit Isolator (SCI)
The built-in SCI isolates short circuits on the
loop-line and also has a probe function for

The specifications described herein are subject to change without notice. Data sheet no. 5210060-00A_CS-IC10 WP_M_EN_2016_E

www.consilium.se
DATA SHEET 2(4)

evaluating a short circuit. The SCI ensures that the Data for built-in Short Circuit
fire detection system does not lose contact with
the loop units when there is one short circuit on Isolator (SCI)
the loop-line. The probe function makes it Ic max (Maximum Continuous 500 mA
possible to reset the short circuit condition current)
without restart of the loop-line. Is max (Maximum Switching current) 800 mA
Current when short circuited < 1 mA
Data (IL max)
Operating voltage 22–38 VDC Open to Close voltage 22 ± 2 VDC
Operating current: Open to Close, maximum load ≈1.2 kΩ
- Normal condition ≈0.1 mA expressed in ohms on the
non-energized side
- Alarm condition with ≈3 mA
LED activated Close to Open voltage 14 ± 2 VDC
Sub-Loop (Remote Current limited: 5 mA
indication, supervised Configuration of Safe I/O
dry-contact reading)
The CS-IC10 has one configurable input/output,
Loop communication IDAxt called Safe I/O.
protocol
Table 1. The allowed configurations of Safe I/O
Operating temperature -40 °C to +70 °C
Safe I/O Active Monitored1) CS-IC10
Storage temperature -50 °C to +70 °C
High/Low
Relative humidity ≤ 95 % RH
non-condensing Alarm2) H/L X X
Input Fault H/L X X
Addressing method DIP switch
Ingress protection IP66/67 General H/L X X

Cable gland M25 for cable ø 9–17mm Alive


NA X
Material: Black polyamide signal
Output Remote
Cable terminals 2.5 mm2
Indication NA
Material PC/ABS (RIL)
Weight ≈160 g
1) Monitored for cable break and short circuit.
Colour Transparent/RAL7035
2) A Safe I/O configured as an Alarm input can be
Loop cable requirement See the Installation & assigned the alarm sub-types: ‘Smoke’, ‘Heat’,
Commissioning manual ‘Flame’ and ‘MCP’.
CE Conformity EN 54-17, EN 54-18
Certified according to Address switch
2531/yy
The loop units are identified by a physical address.
yy = year of production
The address number is set on an 8 pole DIP
switch located on the loop unit. (For settings use
a pointed tool of suitable size.)

Functional Safety Data


Type B
HFT 0
1 to 150 are valid addresses. The DIP switch value
SFF 93 % follows the binary system.
PFDavg 2.61 × 10-4
PFDavg is calculated for MTTR 8 h and proof test
interval 1 year.
Suitable for use in SIL 1 and SIL 2 environments.

The specifications described herein are subject to change without notice. Data sheet no. 5210060-00A_CS-IC10 WP_M_EN_2016_E

www.consilium.se
3(4) DATA SHEET

Location of DIP switches

Figure 1. Location of DIP switches and terminals on the


PCB
Address switch S101 (8 pole) for the loop
address.
Function switch S102 (5 pole) is factory set to
ID0. Do not change!
For terminal no. see section Connection.

Connection

Figure 2. Terminals J101 and J102


* External connection shown in normal not active
state

NOTE!
If a shielded cable is used on the sub-loop
it shall only be terminated at one end. If
the shield is terminated in the I/O unit it is
connected to the shield terminal, this is
only possible if the loop line is shielded.

The specifications described herein are subject to change without notice. Data sheet no. 5210060-00A_CS-IC10 WP_M_EN_2016_E

www.consilium.se
DATA SHEET 4(4)

Dimensions (mm)

* Holes for wall mounting (x4): Max screw thread Ø4. Max screw head Ø8

The specifications described herein are subject to change without notice. Data sheet no. 5210060-00A_CS-IC10 WP_M_EN_2016_E

www.consilium.se