1(4) DATA SHEET

Input/Output Loop Unit


CS-IC22 WP
Part no. 5210061-00A

System: CFD5000

General description Local intelligence via an integrated


The CS-IC22 WP is an input and output unit for CPU
various integration of safety inputs/outputs. It has The integrated CPU makes it possible to make
been designed for use in harsh environments and decisions locally, like evaluation of the alarm
to comply with the standards for the industrial, condition.
maritime, offshore and rolling stock markets up to
Safety Integrity Level 2 (SIL 2). IDAxt protocol
The CS-IC22 WP has two inputs that can be The IDAxt protocol is an extension of Consilium’s
connected to external equipment with a dry relay communication protocol (IDA) and meets the
contact. The CS-IC22 WP supervises the cable to demands on data integrity, reliability and
the external equipment for cable break and short robustness required for use in SIL 1 and SIL 2
circuit, and the inputs can be configured as active safety functions and safety systems.
high or active low. The function of the inputs can
be configured to be: Periodic BIST
- a general input The Periodic Built-In Self-Test is a central
- a fault mechanism which the system uses to ensure long
- an alarm from a manual call point proof test intervals.
- an alarm from a smoke sensor Countermeasures (defences) have been
implemented in order to address the fault modes
- an alarm from a heat sensor
(threats) in the fire detection system. These
- an alarm from a flame sensor countermeasures are done in order to increase
- an alive signal (output) the confidence in the system.
The CS-IC22 WP can control and monitor The system has two types of Built-In Self-Tests
external devices, such as fire doors, fire dampers, (BIST). The first BIST is made continuously; for
sprinklers, hatches etc. The outputs on the instance when reading A/D values from hardware.
CS-IC22 WP can be configured to be activated This typically involves evaluation of the read value
when there is a fire, fault, disablement or input to determine if the hardware is broken; i.e. gives
condition locally on the loop-line. measurements outside an acceptable interval.
Features: The second BIST is the Periodic Built-In Self-Test
(Periodic BIST) which is made once every five
• Two dry relay contact outputs, used as safety minutes in order to verify the safety function by
relays for external control
testing communication paths and the end
• Two configurable I/O – they can either be ‘remote elements. All internal communication paths and all
indication’ outputs, alive signals or dry contact testable parts of the loop-units are included in the
inputs
Periodic BIST mechanism, to verify the whole path
• Handling of short circuits and cable breaks on the from detection to reporting (fire) status.
loop-line

The specifications described herein are subject to change without notice. Data sheet no. 5210061-00A_CS-IC22 WP_M_EN_2016_E

www.consilium.se
DATA SHEET 2(4)

The system creates a log with the results of the Functional Safety Data
Periodic BIST. This log can be extracted from the Type B
system with a USB memory stick.
HFT 0

Short Circuit Isolator (SCI) SFF 92 %

The built-in SCI isolates short circuits on the PFDavg 3.24 × 10-4
loop-line and also has a probe function for PFDavg is calculated for MTTR 8 h and proof test
evaluating a short circuit. The SCI ensures that the interval 1 year.
fire detection system does not lose contact with Suitable for use in SIL 1 and SIL 2 environments.
the loop units when there is one short circuit on
the loop-line. The probe function makes it
possible to reset the short circuit condition
Data for built-in Short Circuit
without restart of the loop-line. Isolator (SCI)
Ic max (Maximum Continuous 500 mA
Data current)
Operating voltage 22–38 VDC Is max (Maximum Switching current) 800 mA
Operating current: Current when short circuited < 1 mA
- Normal condition ≈0.1 mA (IL max)

- Alarm condition with ≈3 mA Open to Close voltage 22 ± 2 VDC


LED activated Open to Close, maximum load ≈1.2 kΩ
Sub-Loop (Remote Current limited: 5 mA expressed in ohms on the
indication, supervised non-energized side
dry-contact reading) Close to Open voltage 14 ± 2 VDC
Loop communication IDAxt
protocol Address switch
Relay contact output 30 VDC, max 1 A The loop units are identified by a physical address.
resestive load The address number is set on an 8 pole DIP
Operating temperature -40 °C to +70 °C switch located on the loop unit. (For settings use
Storage temperature -50 °C to +70 °C a pointed tool of suitable size.)
Relative humidity ≤ 95 % RH
non-condensing
Addressing method DIP switch
Ingress protection IP66/67
Cable gland M25 for cable ø 9–17mm
Material: Black polyamide
1 to 150 are valid addresses. The DIP switch value
Cable terminals 2.5 mm2 follows the binary system.
Material PC/ABS
Weight ≈530 g
Colour Transparent/RAL7035
Loop cable requirement See the Installation &
Commissioning manual
CE Conformity EN 54-17, EN 54-18
Certified according to
2531/yy
yy = year of production

The specifications described herein are subject to change without notice. Data sheet no. 5210061-00A_CS-IC22 WP_M_EN_2016_E

www.consilium.se
3(4) DATA SHEET

Location of DIP switches Configuration of Safe I/O and Safe


Relay
The CS-IC22 has:
• two configurable input/outputs, called Safe I/O
• two relay contact outputs, called Safe Relay
Table 1. The allowed configurations of Safe I/O
Safe I/O Active Monitored1) CS-IC22
High/Low
Alarm2) H/L X X3)
Input Fault H/L X X4)
General H/L X X
Alive
NA X
signal
Figure 1. Location of DIP switches and terminals on the Output Remote
PCB Indication NA
Address switch S101 (8 pole) for the loop (RIL)
address.
1) Monitored for cable break and short circuit.
Function switch S102 (4 pole) is factory set and
2) A Safe I/O configured as an Alarm input can be
will not be used for current operation modes. Do
assigned the alarm sub-types: ‘Smoke’, ‘Heat’,
not change ! ‘Flame’ and ‘MCP’.

Terminals 3) Only one alarm input per CS-IC22 is allowed.


4) Only one fault input per CS-IC22 is allowed.
Cable shield
Table 2. The allowed configurations of Safe Relay
1+ Loop Safe Relay Active Monitored CS-IC22
2- Loop/SCI High/Low
3+ Loop Fire H
4- Loop/SCI Fault L X
5+ Sub-loop 1, High Output Disable-
H
6- Sub-loop 1, Low ment

7+ Sub-loop 2, High General H/L X

8- Sub-loop 2, Low
11 C
12 NC Relay output 1
14 NO
21 C
22 NC Relay output 2
24 NO

The specifications described herein are subject to change without notice. Data sheet no. 5210061-00A_CS-IC22 WP_M_EN_2016_E

www.consilium.se
DATA SHEET 4(4)

Connection example

Figure 2. Terminals J101, J102 and J103


* External connection shown in normal not active state

NOTE!
If a shielded cable is used on the sub-loop it shall only be terminated at one end. If the shield is
terminated in the I/O unit it is connected to the shield terminal, this is only possible if the loop line is
shielded.

Seal the unused cable glands


NOTE!
Use the three included blanking plugs (spare part no. 5210214-00A) in order to seal any unused
cable glands.

Dimensions (mm)

* Holes for wall mounting (x4): Max screw thread Ø4. Max screw head Ø8

The specifications described herein are subject to change without notice. Data sheet no. 5210061-00A_CS-IC22 WP_M_EN_2016_E