SUB-TOTAL 32,424.00
Table 2.20.3.3
Application of Demand Factor D.F. (%)
First 3000 VA 100.00% 10,000.00
From 3001 to 120,000 VA 35.00% 7,848.40
SUB-TOTAL 17,848.40 VA
SUB-TOTAL 20,820.00 VA
Art. 2.20.3.14
Application of Demand Factor D.F. (%) Qty. VA
If fewer than four units 100.00%
If four or more units 75.00% 8.00 15,615.00
SUB-TOTAL 15,615.00 VA
5. RANGES, OVENS, COOKTOPS & OTHER HOUSEHOLD COOKING APPLIANCES
OVER 1,750W OR 1-¾ kW; Art. 2.20.3.16
Description Rating (W) Qty. VA
a. Electric Range 2200.00 1.00 2,200.00
b. Range Igniter 200.00 1.00 200.00
b. Electric Range Hood 225.00 2.00 450.00
Table 2.20.3.16
Application of Demand Factor D.F. (%) Qty.
Column A (Less Than 3.5kW) 80.00% 1.00 1,760.00
SUB-TOTAL 2,210.00 VA
SUB-TOTAL 10,649.00 VA
SUB-TOTAL 690.00 VA