Professional Documents
Culture Documents
Ingersoll Rand System Automation Operator's Manual X8I: More Than Air. Answers
Ingersoll Rand System Automation Operator's Manual X8I: More Than Air. Answers
System Automation
X8I
Operator’s Manual
RS485 NETWORK.......................................................................11
INDICATORS................................................................................23
SECTION 8 — COMMISSIONING................................26
PHYSICAL CHECKS....................................................................26
WARNING : Risk of High Pressure • The X8I must only be operated at the supply voltage
! and frequency for which it is designed.
• When main power is switched on, lethal voltages are
WARNING : Consult Manual present in the electrical circuits and extreme caution
must be exercised whenever it is necessary to carry
out any work on the unit.
• Before installing or operating the X8I, take time to
carefully read all the instructions contained in this • Do not open access panels or touch electrical
manual, all compressor manuals, and all manuals of components while voltage is applied unless it is
any other peripheral devices that may be installed or necessary for measurements, tests or adjustments.
connected to the unit. Such work should be carried out only by a qualified
electrician equipped with the correct tools and
• Electricity and compressed air have the potential to wearing appropriate protection against electrical
cause severe personal injury or property damage. hazards.
• The operator should use common sense and good • All air compressors and/or other equipment
working practices while operating and maintaining connected to the unit should have a warning sign
this system. All applicable codes should be strictly attached stating ‘THIS UNIT MAY START WITHOUT
adhered to. WARNING’ next to the display panel.
• Maintenance must be performed by adequately • If an air compressor and/or other equipment
qualified personnel that are equipped with the connected to the unit is to be started remotely,
proper tools. attach warning signs to the equipment stating ‘THIS
INSTALLATION UNIT CAN BE STARTED REMOTELY’ in a prominent
location, one on the outside of the equipment, the
• Installation work must only be carried out by a other inside the equipment control compartment.
competent person under qualified supervision.
MAINTENANCE AND REPAIR
• A fused isolation switch must be fitted between the
main power supply and the X8I. • Maintenance, repairs or modifications must only be
carried out by competent personnel under qualified
• The X8I should be mounted in such a location as to supervision.
allow operational and maintenance access without
obstruction or hazard and to allow clear visibility of • If replacement parts are required use only genuine
indicators at all times. parts from the original equipment manufacturer, or
an alternative approved source.
• If raised platforms are required to provide access
to the X8I they must not interfere with normal • Carry out the following operations before opening or
operation or obstruct access. Platforms and stairs removing any access panels or carrying out any work
should be of grid or plate construction with safety on the X8I:
rails on all open sides. i. Isolate the X8I from the main electrical power
supply. Lock the isolator in the ‘OFF’ position
and remove the fuses.
2) The ir-485 Gateway Interface module that is designed Compressors 1-4 connect via the X8I and Compressors 5-8
to interface to any Ingersoll Rand Intellisys controlled connect via the EXP Box
(Non-Nirvana) compressor. The X8I communicates to the The EXP Box is suitable for wall mounting and must be
ir-485 Gateway via a two wire, RS485 network utilizing the located adjacent to the X8I unit (max 33ft or 10m).
ir485 protocol. All IR compressors equipped with Intellisys
controllers (Non-Nirvana) require this interface. Ingersoll Rand
102 psi
1 1 2 3 4
18:35 #2
5 6 7 8
ir-485
The EXP Box connects to the X8I controller via a two wire,
The ir-485 Gateway interface module is installed within dedicated RS485 network
the compressor control cabinet and connected to the X8I Use Belden 9841 or Equivalent In Grounded Conduit
using Belden 9841 or equivalent RS485 cable. No Greater Than 33ft (10m)
3) The irV-485 Gateway Interface module that is Up to four air compressors can be connected to the EXP
designed to interface to any Ingersoll Rand Nirvana Box using a 6 or 7 wire cable and a compressor interface
compressor. The X8I communicates to the irV-485 ir-PCB (330ft (100m) max). The ‘ir-PCB’ connections are
Gateway via a two wire, RS485 network utilizing the ir485 identical to the X8I.
protocol. All Nirvana Compressors, 20 HP (15KW) and
above, require this interface.
102
1
psi
1 2 3 4
8 Digital Inputs
18:35 #2
CAP
5 Analog Inputs
5 6 7 8
6 Relay Outputs
4000ft (1219) max
Ingersoll Rand
102 psi
1 1 2 3 4
18:35 #2
CAP
5 6 7 8
102 psi
1 1 2 3 4
18:35 #2
5 6 7 8
From VSD Pressure Transducer 0–232 PSI (16 bar), but the X8I can accept any pressure
To VSD Pressure Transducer Input
sensor with a 4–20 ma output and a range of up to 8700
PSI (600 bar).
a b User Interface :
102
PSI a) System Pressure Value
c b) System Pressure Units
d 1 c) Unit Status
d) Unit Active Functions
e
17:30 #1 e) User Menu Item
Ingersoll Rand
a
102 psi
1 2 3 4
b
1
A: 85% c 1
CAP
5 6 7 8
a) Start
b) Reset
a b c
c) Stop
g
d) Menu
e) Enter
f d
f) Escape
g) Up (Plus)
h e
h) Down (minus)
PRESSURE TRANSDUCER
To Plant Air
System
RECEIVER
Ir-PCB Compressor #1 Ir-PCB Compressor #2
Control Cable Control Cable
ir-485 Gateway
Ingersoll
Ingersoll Ingersoll Ingersoll
Rand Rand Rand Rand
102 psi 102 psi 102 psi
ir-485
For All 102 psi
ir-PCB
XPM-TAC24 2
1 2 3 4 1 2 3 4
X04
VOLTAGE SELECT
Pressure Sensor Located After Individual Cleanup
X01 230Vac Equipment
1 2 3 4
N LE X04
VOLTAGE SELECT
Ensure each compressor is equipped with
independent excess pressure shutdown. An increase in
115Vac
pressure differential across air treatment equipment can
result in excess compressor discharge pressure.
Power Supply Terminals
1 P
10
102 psi
Installation Kit
1 1 2 3 4
18:35 #2
CAP
5 6 7 8
102 psi
1 1 2 3 4
18:35 #2
CAP
5 6 7 8
Ingersoll
Ingersoll
Rand
Rand
102 psi 102 psi
EX I/O
11
12
PL
TOLERANCE
b
point “b” is reached. Once point “b” is reached, the X8I will PH
PL - TO
PH
PT
Figure 3 — Tolerance in Relation to PH and PL
PL
Tolerance (TO) is expressed as a pressure defining the
width of the band above PH and below PL in which
energy efficient control will be in effect.
When system pressure is in the tolerance band, the
X8I will continuously calculate the moment at which
Figure 2 — Typical VSD Pressure Control vs. Time compressors will be loaded or unloaded based on the rate
The variable speed compressors in the system will run of change of system pressure. When the system pressure
on their target pressure and smooth out the variations in strays outside of the tolerance band, the X8I will abandon
system pressure. This assumes that system demand does energy efficiency and begin to protect the system air
not vary more than the capacity of the variable speed pressure by loading or unloading the compressors.
compressor. Loading will be delay controlled.
13
14
15
#1 A B C D
When the X8I is instructed to change between tables,
it will not abruptly change the system operating
#2 B A D C parameters. The X8I will adjust the system target pressure
upward or downward to the next table’s settings.
#3 A B C D
This transition will occur gradually to preserve energy
#4 B A D C efficiency and safe, reliable control:
16
The Prefill feature provides a controlled and energy To manually skip Prefill mode, press and hold Start
efficient method of increasing pressure to normal for several seconds.
operating levels at system start. This feature avoids the Insufficient Capacity Alarm
inefficient potential for all available system compressors
to start and load before pressure reaches the normal
operating level.
CAP
17
The ‘Insufficient Capacity’ advisory alarm function FILO: TIMER ROTATION MODE
can be de-activated. In this instance the unit’s Alarm
indicator will still illuminate but no group alarm, group
fault, or a remote indication is generated. The primary function of Timer Rotation mode is to
efficiently operate a compressed air system consisting of
Restricted Capacity Alarm fixed capacity output compressors. The routine rotation
assignments can be modified using ‘Priority’ settings
to accommodate for a differentially sized or variable
capacity output compressor(s).
CAP Rotation:
Each time the rotation interval elapses, or the rotation
time is reached, a sequence rotation occurs and the
sequence assignment for each compressor is re-arranged.
The X8I is equipped with a dedicated ‘Restricted Capacity’ The compressor that was assigned for duty (A) is re-
Advisory Alarm (Warning) indication. assigned as last standby (D) and all other compressor
assignments are incremented by one.
This indication will flash if all available compressors are
loaded and further capacity is required but one or more,
compressors are: 21 1 2 3 4
18
19
a b User Interface :
102
PSI a) System Pressure Value
c b) System Pressure Units
d 1 c) Unit Status
d) Unit Active Functions
e
17:30 #1 e) User Menu Item
Ingersoll Rand
a
102 psi
1 2 3 4
b
1
A: 85% c 1
CAP
5 6 7 8
a) Start
b) Reset
a b c
c) Stop
g
d) Menu
e) Enter
f d
f) Escape
g) Up (Plus)
h e
h) Down (minus)
20
Active Functions :
Power Failure Auto-Restart
1 Table #1 System Pressure Status :
Increasing to normal operational levels (Prefill,
2 Table #2 target pressure change or at system start)
3 Table #3 Below the active lower, or load, pressure set point
4 Table #4 Between the lower, or load, and upper, or unload,
active pressure set points
Standby Mode Active Above the upper, or unload, active pressure set point
Prefill Function
Pressure Schedule
Function Inhibited (Manual Override)
Remote Manual Override
Shutdown (Trip)
21
17:30 #1
17.30 (24r system)
# 1 = Monday to # 7 = Sunday
User Manu
A number of User menu information displays are
1
A: 100%
available that can be accessed directly from the
front panel using the Up and Down navigation
buttons.
102 psi
The Pressure detected on the unit’s
primary pressure sensor.
00:00 #1
The next scheduled sequence rotation:
00 : 00 Time (24 hr system)
#1 Monday
22
a
1sec
23
P00
To view detailed information applicable to the
selected User menu display item press Enter. 102 psi 2
1 1 98 psi 3
To view detailed information applicable to the
selected User menu display item press Enter. 80 psi 4
P00
Shows the next Pressure Schedule event.
#4 18:00
1: The Current Active Table
2: Day (#1=Monday, #7=Sunday)
18 / 05 / 2006
3: Time (24hr system) ABCD
4: Table
Items 2 and 3 show the day and time that the unit
will change to use the ‘Table’ shown in item 4.
Day of the week (#4: Thursday), the time of day
Compressor Status: (18:00) and the date (18/05/2006) of the next automated
sequence rotation event.
P00
3 IRV-485 4
The active ‘mode’ of operation
1 100 % 5 “ABCD” The current active rotation sequence assignment.
1 1
1 20 % 6 Manual Sequence Rotation:
24
Prefill
To manually skip the Prefill function, press and hold
Start for several seconds.
When Prefill is complete, if applicable, the X8I will enter
normal operating mode.
The X8I will operate in accordance with the parameters
and options set in the active ‘Table’.
Tables
Each compressor in the system must be started
(running or in a standby or auto restart condition) before
X8I control of the compressor can be established. The X8I
will not start a compressor that is in a stopped condition.
25
26
P00
To select a menu ‘page’ press UP or DOWN. To enter the
highlighted menu ‘page’ press ENTER; the first item of the
menu ‘page’ will be highlighted. Press UP or DOWN to
scroll though the selected menu ‘page’ items.
27
Page 0 Page 1
Page 2
Item 1 Value
Item 2 Value Page 3 Item 1 Value
Item 3 Value Item 2 Value
Page 4
Item 4 Value Item 3 Value
Item 5 Value Page 5 Item 4 Value
Item 6 Value Item 5 Value
28
C01
TABLE #2 to #4 (as Table #1)
01 01 Compressor #1 Running Hours
to
Pressure Schedule
08 08 Compressor #8 Running Hours
P01
01 01 Schedule Setting #1
to Compressor Maintenance
01 01 Compressor #1 Maintenance
to
08 08 Compressor #8 Maintenance
Prefill
P02
01 PF Prefill Function
02 PT Prefill Time Fault Log
03 PP Prefill Pressure E01
04 01 Compressor #1
to
01 01 Fault Log #1 (most recent)
11 08 Compressor #8
to
15 15 Fault Log #15
29
S02 D01
01 P> Pressure Units 01 D1 Digital Input #1 (Di 1)
02 NC Number Of Compressors to
03 PM Maximum Pressure Alarm 08 D8 Digital Input #8 (Di 8)
04 CF Stop Control Function 09 R1 Output Relay #1 (R1)
05 TO Tolerance to
06 DA Damping 14 R6 Output Relay #6 (R6)
07 PC Pressure Change Time 15 A1 Analog Input #1 (Ai1)
08 CA CAP Alarm Inhibit 16 A2 Analog Input #2 (Ai2)
09 MA Max Cap Restricted Alarm Inhibit 17 A3 Analog Input #3 (Ai3)
10 AI Auxiliary Input Function 18 Ao Analog Output (Ao)
11 AO Auxiliary Output Function
12 ER Error Log Reset
Diagnostic Menu 2
D02
01 SI Screen Invert
Auxiliary Box Monitoring 02 LT LED Panel Test
S03
Diagnostic Menu 5
Sensor Calibration
XPM Expansion Module C:5-8 Diagnostic Menu
S04
only available when applicable EXP Expansion Box is
01 1O Pressure Offset installed and registered (detected) by the X8I.
02 1R Pressure Range
D05
01 D1 Digital Input #1 (Di 1)
to
Compressor Configuration 08 D8 Digital Input #8 (Di 8)
09 R1 Output Relay #1 (R1)
C03
to
01 Compressor #1 Configuration 14 R6 Output Relay #6 (R6)
to 8 Compressor #8 Configuration 15 Ao Analog Output (Ao)
30
T0# – PH High Pressure Set Point FILO – First In Last Out. The Rotation and Control
functionality of the FILO mode is the first compressor
The ‘upper’ or ‘unload’ pressure set point that will be loaded is the last compressor to be unloaded
used when the ‘Table’ is active. The default setting for this
parameter is 102 PSI. The values for this parameter are: EHR – Equal Hours Mode. The Rotation and Control
functionality of the EHR mode is to equalize the Run
The highest value for the High Pressure setpoint = PM Hours on all compressors
“Maximum Pressure Alarm” minus 2 times TO “Tolerance”.
T0# - 01 Compressor #1 Priority
If PM is set for 145 PSI and TO is set for 3.0 PSI, then the
The ‘priority’ setting for compressor number 1 that will be
highest value for the High Pressure setpoint would be 139
used when the table is active.
PSI.
T0# - 02 Compressor #2 Priority
The lowest value for the High Pressure setpoint = PL “Low
Pressure” setpoint plus TO “Tolerance” The ‘priority’ setting for compressor number 2 that will be
used when the table is active.
If PL is set for 98 PSI and TO is set for 3.0 PSI, then the
lowest value for the High Pressure setpoint would be 101 T0# - ‘n’ Compressor #’n’ Priority
PSI.
The ‘priority’ setting for compressor number ’n’ that will be
T0# - PL Low Pressure Set Point used when the table is active.
The ‘lower’ or ‘load’ pressure set point that will be used ‘n’ = number of compressors in the system. 8 is the
when the ‘Table’ is active. The default setting for this maximum number of compressors for the X8I
parameter is 98 PSI. The values for this parameter are:
The highest value for the Low Pressure setpoint = PH
Priority Settings:
“High Pressure” setpoint minus TO “Tolerance”.
: compressor(s) can be inhibited from use while a
If PH is set for 102 PSI and TO is set for 3.0 PSI, then the
table is active by selecting “X” priority. The compressor
highest value for the Low Pressure setpoint would be 99
will be held offload and will not be utilised under any
PSI.
circumstances.
The lowest value for the Low Pressure setpoint = Pm
“Minimum Pressure Alarm” setpoint plus 2 times TO
“Tolerance”
If Pm is set for 80 PSI and TO is set for 3.0 PSI, then the
lowest value for the Low Pressure setpoint would be 86
PSI...
T0# - Pm Minimum Pressure Alarm
The miniumum pressure ‘Warning’ or ‘Alarm’ level that will
be used when the ‘Table’ is active. The default setting for
this parameter is 80 PSI. The values for this parameter are:
The lowest Minimum Pressure Alarm setpoint = “The
minimum range of the pressure transducer used.“
The highest Minimum Pressure Alarm setpoint = “The
value from the Table PL – Low Pressure Setpoint” minus 2
times TO “Tolerance””
31
“1” for Monday to “7” for Sunday (a specific day Compressor(s) can be pre-selected as ‘Primary
of the week) Pre-fill’ compressor(s) or ‘Backup Pre-fill’
compressor(s). If a primary pre-fill compressor
“8” for every working day of the week (every experiences a shutdown, or is stopped, it is
day, Monday through Friday, excluding replaced by a pre-defined backup compressor
Saturday and Sunday) and pre-fill continues.
“9’” for every working day of the week (every
day, Monday through Sunday) ! X = Prefill, Standard Mode
“–“ represents the Pressure Schedule is
If one or more of the pre-defined pre-fill
disabled.
compressors experiences a shutdown, or is
Hours (Military Time). The values for this parameter stopped, the pre-fill function is cancelled and
are: normal operation begins.
“00” to “23” the hours in a day
“–-“ represents the Pressure Schedule is A = Prefill, Automatic Mode
disabled.
No Prefill compressor selection is necessary;
Minutes. The values for this parameter are: any selection set is ignored. The management
unit automatically selects compressor(s)
“0” to “59”. the minutes in the hour
dynamically to achieve pressure in accordance
“__“ represents the Pressure Schedule is with the set Prefill time. If a compressor is
disabled. stopped, or shuts down, it is automatically
Table / Standby mode selection. This instructs the system substituted with an alternative compressor.
to change from one ‘Table’ to another, or put the system P02 - PT Prefill Time
in to ‘Standby’ mode for the Pressure Schedule. The values
The Pre-fill Time Setpoint (in minutes) sets the maximum
for this parameter are:
time allowed for a system to start and load the
“T01”, “T02”, “T03” or “T04” for the 4 different designated Compressor/s to increase system pressure
Tables to normal operational levels. The default setting for this
“– – “ for Standby Mode parameter is – . (Represents the Prefill is disabled)
“ __ “ represents the Pressure Schedule is The values for this parameter are:
disabled. “–” the Pre-fill Time is Off
“1 to 120” the number of minutes
32
‘n’ = number of compressors in the system. 8 is the The ‘Day of the Week’ (1= Monday to 7=Sunday) is
maximum number of compressors for the X8I automatically calculated and set in accordance with
the Day, Month and Year. The default setting for this
This parameter set the function of compressor 1 to ‘n’ parameter is - --.--. (Represents the clock has not been
during the ‘Prefill’ period. The default for this parameter is initialized))
. (Represents this compressor is not used by the The values for this parameter are:
Prefill Function) The values for this parameter are:
“1” to “7” the ‘Day of the Week’ (1= Monday to
“ ” for this compressor will not be used by the Pre- 7=Sunday) which is automatically calculated and set
fill Function in accordance with the Day, Month and Year entered.
“ ” for this compressor will be used as a primary “00” to “23” the Hour for the Real Time Clock.
compressor by the Pre-fill Function
“0” to “59” the Minutes for the Real Time Clock.
“!” for this compressor will be used as an emergency
Backup compressor by the Pre-fill Function “1” to “31” the Day for the Real Time Clock.
These settings are applicable to Prefill – Standard “1” to “12” the Month for the Real Time Clock.
and Prefill - Back-up modes only. In Automatic mode “2005” to “2100” the Year for the Real Time Clock.
the system management unit dynamically utilizes S01 - PS Pressure Schedule Enable
compressors as required.
This parameter enables or disables the Pressure Schedule
function in the X8I. The default setting for this parameter
Press and hold ‘Start’ for 5 seconds to manually skip is . (Represents the Pressure Schedule is disabled)
Prefill mode at start up.
The values for this parameter are:
= inhibit Pressure Schedule
“ ” = enable Pressure Schedule
S01 - AR Auto Restart Enable
This parameter enables or disables X8I restart function
after a power loss. When enabled, after a power
disruption or failure, the X8I will automatically restart
when power is restored if the X8I was in an operational
‘Started’ state when the power loss or disruption
occurred. The X8I will not automatically restart if the X8I
was in a “Stopped” state when the power disruption or
failure occurred. The default setting for this parameter is
. (Represents the Auto Restart is enabled)
The values for this parameter are:
= inhibit Power Failure Auto Restart
“ ” = enable Power Failure Auto Restart
33
34
35
36
NO NO
01:D1 01:AF
The function of the Auxiliary input. The function of the Auxiliary output ‘volt-free’ relay
01:DI Digital Input contacts.
04:T3 Override > Table 3 Any Shutdown (Trip) or Compressor Not Available.
06:TS Override > Standby Any compressor Alarm (Warning), Shutdown (Trip) or Not
Available
07:AA Remote Alarm (always active)
04:CA Compressor Alarm
08:AR Remote Alarm (active when unit running,
inhibited when unit stopped or in Standby) Any compressor Alarm (Warning)
10:TR Remote Trip (active when unit running, inhibited Any compressor Shutdown (Trip) or Not Available
when unit stopped or in Standby) 06:SF System Fault
11:SS Remote Start/Stop Any unit Alarm (Warning) or Shutdown (Trip)
NO (Normally Open) 07:ON System On
The selected function is activated when the input is Unit Started and Active, including Pre-Fill period and
closed circuit (input terminals are connected together by Standby mode (not active when unit stopped)
remote volt-free contacts)
08:SA System Active
NC (Normally Closed)
Unit Active, including Pre-Fill period (not active when unit
The selected function is activated when the input is open stopped or in standby mode)
circuit (input terminals are open circuit)
09:LP Low Pressure Alarm
10:HP High Pressure Alarm
11:PO Pressure Control Override
Normal, or Pressure Schedule’ operation is being manually
overriddenThe function of the Auxiliary output ‘volt-free’
relay contacts.
S02 - ER Error Log Reset
This parameter clears and resets the ‘Error Log’. The
default setting for this parameter is . (Represents the
Error Log Reset is disabled)
The values for this parameter are:
“ ” Error log reset is disabled
“ “ Error log reset enabled. Adjust the item setting to
‘ ’ and press ENTER. The display will return to the main
menu and all existing entries in the error log will be
permanently deleted.
37
38
C02
08 08
01 01
02 02
03 03
04 04
C02 – 01 to C02 – ‘n’ Compressor Maintenance
‘n’ = number of compressors in the system. 8 is the
maximum number of compressors for the X8I
This parameter is set for a compressor(s) that is
unavailable for use for a prelonged period for time due to
maintenance or repair. The compressor will not be utilised
under any circumtances; any Alarm (Warning) or Trip
(shutdown) fault will be ignored. The default setting
for this parameter is . (Represents the compressor is
available) The values for this parameter are:
= Remove compressor from operation
= Compressor can be utilised
39
C03 01.01 01
1 100 % 5
1 IR-485
2 10 s
IRV-485:
C03 01.01 01
1 100 % 5
1 IRV-485 50 % 6
2 10 s 60 % 7
40
41
42
E: ERR.01
16/05/2006 14:25
1
43
The X8I is equipped with comprehensive diagnostic A1: System Pressure, 4-20mA
functions. Each input can be examined individually and A2: Digital: ir-PCB #4 – Alarm/Serv.
each output can be manually activated or manipulated
individually. A3: Digital: Auxiliary Input (D1)
D4 Digital Input 4 OFF The analog output is utilized on the Terminal PCB to
switch the ir-PCB V outputs. Set the analog output to the
D5 Digital Input 5 Pulsing following to switch each ‘V’ output as required.
D6 Digital Input 6 4.0mA All ‘V’ outputs OFF
D7 Digital Input 7 7.0mA V1 = ON; V2, 3 and 4 = OFF
D8 Digital Input 8 11.0mA V2 = ON; V1, 3 and 4 = OFF
------------------------------------------------------------- 15.0mA V3 = ON; V1, 2 and 4 = OFF
R1 Relay Output 1 19.0mA V4 = ON; V1, 2 and 3 = OFF
R2 Relay Output 2 OFF
R3 Relay Output 3 D02 Diagnostics – LED Panel
R4 Relay Output 4 ON
D02
R5 Relay Output 5
R6 Relay Output 6
01 SI 0
-------------------------------------------------------------
02 LT 00
A1 Analog Input 1 bar <> mA
A2 Analog Input 2 v
A3 Analog Input 3 v
------------------------------------------------------------- SI: Screen Invert
44
ON (closed circuit)
Pulsing
45
Compressor Alarm (Warning) conditions are automatically Each individual fault has a unique numeric code.
reset when the condition has been resolved and reset on ERR.01 Pressure Sensor Fault
the compressor.
The signal from the control pressure sensor is out-of-
Compressor Not Available (Shutdown, Trip) conditions are range (<3.5mA or >21.8mA).
automatically reset when the condition has been resolved
and reset on the compressor; and the compressor has ERR.04 Internal 24V Fault
been restarted. The 24VDC power supply, internal to the unit’s controller,
Compressor fault conditions are displayed by the is below 19.2V (internal controller fault)
compressor indicators and in the user menu status screen. ERR.05 Emergency Stop
Compressor fault conditions are not regarded as X8I unit
fault conditions. The wire link between terminals ‘+C’ and ‘C1’ of the unit’s
controller is open circuit. These terminals are permanently
connected together on the X8I Terminal PCB: this error
Compressor Status Sysmbols and Comressor Status will never occur in normal operational circumstances.
Indicators ERR.06 Real Time Clock Error
Fault Codes The Real Time Clock device, internal to the unit’s
Fault codes are separated in to unit faults ‘ERR’ and system controller, has failed.
Alarms (Warning) ‘SYS’. ERR.07 XPM-LED Module Error
ERR: Unit faults are errors with the X8I controller itself and Data communications with the internal XPM-LED (Status
are all conditions that prevent normal operation from LED Display) module have been disrupted or lost.
continuing.
ERR.12 ir-PCB Expansion Module C5-8
SYS: System faults are items that arise from conditions
external to the X8I controller; the X8I itself continues to Data communications with the external ir-PCB Expansion
function correctly. module ‘C:5-8’ have been disrupted or lost.
There are two types of Fault condition: ERR.13 ir-PCB Expansion Module C5-8
46
The auxiliary Input is set for ‘Trip/Shutdown (always Press and hold Reset then press Escape.
active)’ function and is in a Fault condition. The user menu display item will show the software
SYS.08 Remote Trip (Shutdown) version ID (example: “E01”).Fault Codes:
47
48
4-20mA
33 34 35 36
X06
+VDC C03
X08
C03
C05
X05
+VDC
C031 A-GND C04
4
Ai2 C06
C032 Ao +VDC C07 C05
3
C06
31 32
Ai3 C08 SEQ C08
X07
2
C07 C07
GND
X09
C08
1
C+ C019
27 28 29 30
C010
1 C020 C09
C09
X06
X08
XPM-LED
2 C021 C010
X02 3 C022
X04
4
L2 L1
C011
SEQ
1 C023
2 5 C024 C012
25 26
C04
X05
6 C025 C013 C03
7
XPM485
RS485#2
+
-
C015
V4 19 20 21 22 23 24
R-SEQ 10k
C016 C024
24Vac
C034
GND
150k
C017 C06
X04
C011 C018 150k
R5
C019 C012
C012
X02
24Vac
C020
C01/3 SEQ
C021
R6
L2 L1 RS485#1
C022
Multi485
C01/4
X07
C023
C024
10k
V3 13 14 15 16 17 18
C013
C09 R1 C025 C023
C014
GND
X03
C027
C015
X03
R3 C028 C018
C016
C029
C017 C030
24Vac
R4
X01
C018 C033
10k
V2 7 8 9 10 11 12
C034
2
1
C022
0VDC
C026
X02
C031
X02
XPM-TAC24
C016
-
C032 4-20mA
2
1
0Vac - earthed
+
NL E 24Vac
2 1 R-V4
X01
X03 10k
6
R-V3
C021
5
0Vac
C029 R-V2
C028 C025
X01
2 3 4
24Vac
R-V1
X01
XPM-PSU24
NL E C015
2 1 24Vac
230Vac 10%
V1 1
XPM-LED X03
1 2
XPM485 X02
L1 1
1 1 L1
L2 2
2 2 L2
Wiring Diagram
49
Terminal PCB
33 34 35 36
115V 'UL' @ 5A maximum.
X08
R1 Auxiliary Output #1
31 32
Auxiliary Input #1
X07
D1
330ft (100m) max
L2 L2
27 28 29 30
L1
X06
L1
Multi485
L2
L1
330ft (100m) max
-
25 26
- Ai1 System
X05
Pressure
+ +
+20VDC 6 4-20mA
V4 19 20 21 22 23 24
Di5 Ready/Run
i-PCB 4
5
Ai2 Alarm/Serv. 4
X04
- GND 3
330ft (100m) max
R5 LOAD 2
R1 SEQ 1
4
V4 VFD V V
IR-PCB 6-core
IRV-PCB 7-core
+20VDC
V3 13 14 15 16 17 18
Di4 Ready/Run
i-PCB 3
Di8 Alarm/Serv. 4
X03
R1 SEQ 1
3
V V
V3 VFD
IR-PCB 6-core
IRV-PCB 7-core
+20VDC 6
V2 7 8 9 10 11 12
Di3 Ready/Run
i-PCB 2
Di7 Alarm/Serv. 4
X02
- GND 3
330ft (100m) max
R3 LOAD 2
R1 SEQ 1
2
V2 VFD V V
IR-PCB 6-core
IRV-PCB 7-core
+20VDC 6
6
Di2 Ready/Run
i-PCB 1
5
5
Di6 Alarm/Serv. 4
X01
2 3 4
- GND 3
330ft (100m) max
R2 LOAD 2
R1 SEQ 1
1
V1 1
V1 VFD V V
IR-PCB 6-core
IRV-PCB 7-core
50
BLUE BLACK
BROWN ORANGE
RED WHITE
GREEN VIOLET
1 2 3 4 X04
T3.15A T1.6A T1.6A T1.0A 1 2 3 4
115V
115V +-10%
IEC T1.0A FH1
5x20mm
1 2 3 4
X03 X02
2 1 2 X01
N L E E
24Vac/2 24Vac/1
earthed isolated NL E
51
Comp #1 Manufacturer
Comp #1 Model/Type
psi cfm Comp #1 Working Pressure bar/psi
#1 kW VA Hz Comp #1 Full Load Capacity cfm
Comp #2 Manufacturer
psi cfm
Comp #2 Model/Type
#2 kW VA Hz Comp #2 Working Pressure bar/psi
Comp #2 Full Load Capacity cfm
Comp #3 Manufacturer
psi cfm Comp #3 Model/Type
#3 kW VA Hz Comp #3 Working Pressure bar/psi
Comp #3 Full Load Capacity cfm
Comp #4 Manufacturer
psi cfm Comp #4 Model/Type
#4 kW VA Hz
Comp #4 Working Pressure bar/psi
Comp #4 Full Load Capacity cfm
Comp #5 Manufacturer
Comp #5 Model/Type
psi cfm Comp #5 Working Pressure bar/psi
#5 kW VA Hz
Comp #5 Full Load Capacity cfm
Comp #6 Manufacturer
psi cfm Comp #6 Model/Type
#6 kW VA Hz Comp #6 Working Pressure bar/psi
Comp #6 Full Load Capacity cfm
Comp #7 Manufacturer
psi cfm Comp #7 Model/Type
#7 kW VA Hz Comp #7 Working Pressure bar/psi
Comp #7 Full Load Capacity cfm
Comp #8 Manufacturer
psi cfm Comp #8 Model/Type
#8 kW VA Hz Comp #8 Working Pressure bar/psi
Comp #8 Full Load Capacity cfm
52
53
54
55