Professional Documents
Culture Documents
Topic 4 DET3053
Topic 4 DET3053
Topic 4 DET3053
FAULT ANALYSIS
1
Introduction
• Transformer introduces various voltage levels.
• So far we can only reflect the load from one side of the transformer to
another. Still we need to consider different voltage level at each side
of the transformer when we try to find voltage and current.
• It is difficult to calculate voltage and current of the system at various
points.
• It is even more difficult for the system operator to observe the current
situation of the system.
2
Per Unit System
• Per unit system is when we normalize the voltage and current at each
location.
• The normalization typically follows transformer ratings.
• This makes the per unit value of either voltage or current to be
around 1.0 per unit.
• Per unit system allows the system operator to overlook abnormalities
in the system easily.
3
Per Unit Quantity
•
•
5
Base Value Selection
6
Base Value Selection
7
Base Value Selection
8
KVL, KCL, Complex Power Calculation
9
Example 2 : Per Unit Value
10
Example 2 : Per Unit Value
Solution : Find per-unit leakage impedance :
11
Example 3 : Per Unit Circuit
12
P.U. Unit Equivalent Circuit of a
Transformer
13
Change of Base Value
14
Steps of Per Unit Analysis
1
1. Choose SB for the system.
2. Select VB for different zones (usually follows
transformer voltage ratings).
3. Calculate ZB for different zones.
4. Express all quantities in p.u.
5. Draw impedance diagram and solve for p.u.
quantities.
6. Convert back to actual quantities if needed.
15
Example 5 : 1ɸ, Per Unit Analysis
16
Example 5 : Base Value of Each Zone
17
Example 5 : P.U Transformer Reactance
18
Example 5 : Per Unit Circuit
19
Example 6
Solution :
20
Example 6…continue
21
Example 6…continue
22
Advantages of Per Unit Analysis
23
Fault Analysis in Power
System
24
Fault Analysis in Power System
30
Single-phase to earth fault
34
Triple phase fault
37
Symmetrical Component
- magnitude
- displaced from each other by
120°
- have same phase sequence
as the original power system
(in clockwise Figure 1 :
direction). Positive Sequence
Components;
A-B-C
39
Symmetrical Component :
Negative Sequence Component
- magnitude
- displaced from each
other by 120°
- have opposite phase
sequence as the original
power system (in clockwise
direction). Figure 2 :
Negative Sequence
Components;
A-C-B40
Symmetrical Component :
Zero Sequence Component
- magnitude
- phase.
Figure 3 :
Zero Sequence
Components
41
Symmetrical Component
• If the voltages in phases of
the original power system
are designed VA,VB and VC,
then the:
•
VA = VA1 + VA2 +
Phase VA0
VB = VB1 + VB2 +
VB0 Symmetrical Components
43
Symmetrical Component
Similarly,
a 3 I I (1360)
I
0
I (cos 360 j sin 360)
3
a 1
Figure A
49
The a Constant
• Each multiplication by a rotates by 120° without
changing its magnitude. Therefore,
a 1120
2
a 1240
3
a 1360 10 1
50
Representing Symmetrical
Components with the a Constant
Phase
(is use for conversion from phase to
sequence) 56
Conversion Phase to Sequence
Phase
IA 10030 A
IB 50300 A
IC 30180 A
Calculate the positive, negative and zero sequence
currents.
58
EXERCISE 2
QUESTION :
The following currents were recorded under the
following conditions in the three phase system:
IA 15045V
IB 250150V
IC 100300V
Calculate the values of the zero sequence
components of the current for each line.
59Ans : 52.2 112.7°
Symmetrical Components of an
Unbalanced 3Φ Current
• The current in neutral (ground) of a power system (in
Y-connection generator) is given by :
I N = IA + I B + I C
• The current in neutral (ground) of the power system
is equal to 3 times the zero sequence current :
IN = 3IA0
60
Symmetrical Components of an
Unbalanced 3Φ Current
61
EXAMPLE 1
QUESTION :
An ungrounded Y-connected
three phase load is shown in
Figure A. The currents in each
leading to the load are :
IA 100 A IB 10 180 A
IC 00 A
Determine the symmetrical
components of current in eachFigure A : An ungrounded Y-
connected 3Φ load with unbalanced
phase in this load. currents 62
EXAMPLE 1
SOLUTION :
The zero sequence current for phase a of this load
is given by :
IA0 = 1/3(IA + IB + IC) zero sequence
1
IA0 (100 10180 00)
3
IA0 0 A
Continue……..
63
EXAMPLE 1
SOLUTION : a 1120
The positive sequence current for phase a of this
load is given by :
IA1 = 1/3(IA + aIB + a2IC) +ve
sequence
1 2
IA1 [100 a(10180) a (0)]
3
1
IA1 [100 10 60) 0]
3
IA1 5.77 30 A Continue……..
64
EXAMPLE 1
SOLUTION : a 1120
The negative sequence current for phase a of this
load is given by :
IA2 = 1/3(IA + a2IB + aIC ) -ve
sequence 1 2 2
IA2 [100 a (10180) a (0)]
3
1
IA 2 [100 1060) 0]
3
IA 2 5.7730 A Continue……..
65
EXAMPLE 1
SOLUTION : a 1120
So, we can conclude that the zero, positive, and
negative sequence currents for phase a are:
IA0 0 A
IA1 5.77 30 A
IA 2 5.7730 A
Continue……..
66
EXAMPLE 1
SOLUTION : a 1120
The zero, positive, and negative sequence currents
for phase b are:
IB 0 IA0 0 A
2 2
IB1 a IA1 a (5.77 30 A) 5.77 150 A
IB 2 aIA 2 a (5.7730 A) 5.77150 A
Continue……..
67
EXAMPLE 1
SOLUTION :
The zero, positive, and negative sequence currents for
phase c are:
IC 0 IA0 0 A
IC1 aIA1 a (5.77 30 A) 5.7790 A
IC 2 a 2 IA 2 a 2 (5.7730 A) 5.77 90 A
Note that the zero sequence components of current in the
load are zero, which makes sense, since an ungrounded Y-
connected load cannot have a current flowing in the neutral.
68
SEQUENCE IMPEDANCES
&
SEQUENCE NETWORKS
69
SEQUENCE IMPEDANCES &
SEQUENCE NETWORKS
• To analyze an unsymmetrical fault, we must construct three
different per-phase equivalent circuit, for each type of
symmetrical component.
•
71
NEGATIVE SEQUENCE NETWORK
72
ZERO SEQUENCE NETWORK
73
SEQUENCE IMPEDANCES &
SEQUENCE NETWORKS
• The +ve, -ve and zero sequence voltages in phase a of
this generator can be found by applying Kirchoff’s
voltage law to each of the phase equivalent circuits.
74
SEQUENCE IMPEDANCES &
SEQUENCE NETWORKS
75
Analysis of Unsymmetrical
Faults
• Most faults that occur on power systems
are unsymmetrical faults, which result in
unbalanced current flows, and therefore
require symmetrical components to solve
for the voltages currents during the fault.
•
78
Single Phase to Earth Fault
• Hence,
IR
I0 I1 I 2 (as IB = IY = 0)
3
81
Single Phase to Earth Fault
•
VR ( E I 1Z 1) ( I 2 Z 2) ( I 0 Z 0) 0
•
• Eliminating I0 and I2, we obtain
•
•
•
E I 1( Z 1 Z 2 Z 0) 0
•
• Hence,
E
• I1
Z1 Z 2 Z 0 82
Single Phase to Earth Fault
• The fault current,
• IF IR 3I 1
• So, 3E
IF
• Z1 Z 2 Z 0
•
•
83
EXAMPLE 1
QUESTION :
A 3Φ, 10 MVA, 11kV generator with a solidly
earthed neutral point supplies a feeder. The relevant
impedances of the generator and feeder in ohms are
as under :
● Generator ● Feeder
● +ve sequence impedence ● j1.2 ● j1.0
● -ve sequence impedance ● j0.9 ● j1.0
● Zero sequence impedance ● j0.4 ● j3.0
Continue……..
84
EXAMPLE 1
QUESTION :
85
EXAMPLE 1
SOLUTION :
As refered to the diagram, the fault is assumed
to occur on the phase a. Taking phase a as
reference 11k
EA 6350V
Ø Phase e.m.f. of phase a, 3
Ø Z 1Total
j1impedence
.2 j1.0 : j 2.2
Z 2 j 0.9 j1.0 j1.9
Z 0 j 0.4 j 3.0 j 3.4 86 Continue……..
EXAMPLE 1
SOLUTION :
3EA
IA 3IA1
Z1 Z 2 Z 0
3(6350)
j 2540 A
j 2.2 j1.9 j 3.4
87 Continue……..
EXAMPLE 1
SOLUTION :
ii) Line-to-neutral voltage of phase a :
VA VA1 VA 2 VA0
VA ( EA IA1Z 1) ( IA2 Z 2) ( IA0 Z 0)
EA IA1( Z 1 Z 2, asZ 0) IA1 IA 2 IA0 IA
j 2540 IA
6350 ( )( j1.2 j 0.9 j 0.4) IA1 3
ii) 3
6350 j846.67( j 2.5)
6350 2116.67 4233.33V 88
EXERCISE
QUESTION :
A 3Φ, 75 MVA, 11.8kV star connected generator with
a solidly earthed neutral supplies a feeder. The relevant
impedances of the generator in ohms are as under :
● Generator ● Feeder
● +ve sequence impedence ● j1.7 ● j0.1
● -ve sequence impedance ● j0.18 ● j0.1
● Zero sequence impedance ● j0.12 ● j0.3
90
Phase to Phase Fault
Phase to
Phase Fault
V B = VY
IR = 0
I B = - IY
92
Phase to Phase Fault
• Substitute IR = 0 & IB = -IY into current sequence eq. :
•
I0 = 1/3(IR + IY + IB) zero sequence
•
I1 = 1/3(IR + aIY + a2IB) +ve sequence
•
• I 2 = 1/3 (IR + a 2IY + aIB ) -ve sequence
• We get that ,
•
1 2 1 2
I 1 IY ( a a ) , I 2 IY ( a a )
3 3
so, and
I0 0 I1 I 2 93
Phase to Phase Fault
and
•
V1 V 2 V0 0
94
Phase to Phase Fault
• As IO = 0 and V1 = V2 , sub into sequence network eq :
•
V1 = E1 – I1Z1 +ve sequence
•
•
•
V2 = – I2Z2 -ve sequence
• We get ,
V0 = – and
I0Z0 zero
sequence
• V V
1 2 V0 0
•
• E1 I 1Z 1 I 2 Z 2 as I1 = - I2
E1
E 1 I 1Z 1 I 1Z 2 so, I1
Z1 Z 2
95
Phase to Phase Fault
• This can be represented by the equivalent circuit in Figure 3,
where there is no zero sequence network. If the connection
between the two lines has an impedance Zf (the fault
impedance), this is connected in series.
•
97
Double Phase to Earth Fault
Double
Phase to
Earth Fault
• We get,
1
V 1 V 2 V 0 VA
3
100
Double Phase to Earth Fault
• So as V1 = V2 = V3 ,
•
• VA1 VA 2
•
• EA1 IA1Z 1 IA 2 Z 2
•
IA1Z 1 EA1
•
IA 2 ……eq 1
Z2
101
Double Phase to Earth Fault
• And,
•
•
VA1 VA0
• E IA1Z 1 IA0 Z 0
A1
•
• IA1Z 1 EA1
• IA0 ……eq 2
Z0
102
Double Phase to Earth Fault
• Substituting eq 1 and eq 2 into this equation,
• I 0 I1 I 2
•
IA1Z 1 EA1 IA1Z 1 EA1
• IA1
Z0 Z2
•
IA1Z 1Z 2 EA1Z 2 IA1Z 0 Z 2 ( IA1Z 0 Z 1 EA1Z 0)
•
IA1Z 1Z 2 IA1Z 0 Z 2 IA1Z 0 Z 1 EA1Z 2 EA1Z 0
•
EA1( Z 2 Z 0) EA1
IA1
Z 1Z 2 Z 0 Z 1 Z 0 Z 2 Z 1 Z 2 Z 0
Z2 Z0
103
Double Phase to Earth Fault
• Hence,
E
I1
Z 2Z 0
Z1
Z2 Z0
Z0
I 2 I1
Z2 Z0
Z2
I 0 I 1
Z2 Z0 104
Double Phase to Earth Fault
108
Line Diagram of Power
System
• Any complex power system even
though they are three phase
circuits, can be represented by a
single line diagram, showing
various electrical components of
power system and their
interconnection.
109
Line Diagram of Power System
110
Line Diagram of Power System
111
112
Some of the standard symbols used to represent
substation components are given in Table 1 above.
113
Unsymmetrical Faults
on Power System
114
Unsymmetrical Faults on Power
System
• Consider calculating the voltages and currents in
unsymmetrical faults on a more complex power
system.
•
118
Example
Figure 3
119
Example
QUESTION
120
Example
ANSWER
1. The fence-like symbols at either end of the figure
represent “infinite buses”,or positive sequence
voltage sources.
121
Example
122
Example
123
EXERCISE
QUESTION
Figure 4
125
EXERCISE
SOLUTION
126
EXERCISE
SOLUTION
127
EXERCISE 1
QUESTION
Figure below is a three-phase single-line diagram. Sketch the :-
i. Positive sequence network.
ii. Negative sequence network.
iii. Zero sequence network.
129
EXERCISE 3
QUESTION
Figure below is a three-phase single-line diagram. Sketch the :-
i. Positive sequence network.
ii. Negative sequence network.
iii. Zero sequence network.
130
EXERCISE 4
QUESTION
Based on the diagram below, calculate the total impedance of :
i. Positive sequence.
ii. Negative sequence.
134
Solution Example 1
135
Solution Example 1
136
Solution Example 1
137
Example 2
138
Solution Example 2
139
Solution Example 2
140
Solution Example 2
141
SIGNIFICANT OF
FAULT LEVEL
142
Significant of Fault Level
• Fault level can be calculate. It is necessary to ensure
that all the components in your power system can
safely handle the maximum fault currents if they
occur.
• As a power system designer or maintenance person ,
you have to assume that during the life of the
facility, faults will develop.
• When they do , your design must be able to detect the
fault location and the protective devices must
respond fast enough to isolate the fault to prevent
significant disturbance to the system. 143
Significant of Fault Level
145
SIGNIFICANT OF REDUCING
FAULT CURRENT
146
Significant of Reducing Fault
Current
• To avoid large voltage drop in the system leading
simultaneous fault condition in other parts of
the system when the loads try to consume more
•
current to maintain the power requirements.
• To avoid effects on the component or lines as a
result of high current passing through
•
148
METHODS OF REDUCING
FAULT CURRENT
149
METHODS OF REDUCING FAULT
CURRENT
150