Topic 1.2
Topic 1.2
PHASE SYSTEM
CONFIGURATION
General Principle
of
Generation 3 Phase EMF
General Principle of Generation 3‐phase EMF
• Consider an elementary
3‐phase, two pole generator
N and S as shown in Fig 1.
Fig 1 : Generation of 3 phase emf
General Principle of Generation 3‐phase EMF
• The armature has 3 coils
(3 phases) AA1, BB1 and CC1 ,
whose axes are displaced from
each other by 120° in space. The
three windings can be
represented schematically as
shown in Fig 2.
Fig 2 : Schematic representation of
coil windings
General Principle of Generation 3‐phase EMF
• When the 3 coil windings are rotated in
an anticlockwise direction, they cut the
magnetic field due to the magnetic poles
NS and emfs are generated in the three
phases (accordance Faraday’s Law of
electromagnetic induction).
• If we consider the position of the
windings as shown in Fig 1, the induced
emf in coil A (EA) is zero and the induced
emfs in coils B and C (EB and EC) are
finite. Fig 1 : Generation of 3 phase emf
General Principle of Generation 3‐phase EMF
• When the coils have rotated by 90°, EA will have maximum
value and EB and EC will have finite values.
• When the set coils are rotated by 120°, EB attains its
maximum value and similarly, EC attains the maximum value
when it is rotated by another 120°.
General Principle of Generation 3‐phase EMF
• When the coils make one
complete rotation
(0° to 360°), all the three
emf will have varied
sinusoidally and will have
waveforms as shown in
Fig 3.
Fig 3 : Waveforms of 3 phase emf
General Principle of Generation 3‐phase EMF
• All the three emfs waveforms will have exactly the same
amplitude if the flux distribution is uniform.
• If the flux distribution over the poles is truly sinusoidal, the
three emf waves will also have a phase difference of 120°
corresponding to their axes being displaced by 120° in space .
General Principle of Generation 3‐phase EMF
• The phasor diagram of the rms value of
the three emfs is shown in Fig 4.
• If EA is taken as the reference emf, then :
EA = E∠0° = E + j∠0°
EB = E∠ − 120° = E (−0.5 − j 0.866)
EC = E∠ − 240° = E (−0.5 + j 0.866)
• If it is assumed that the voltages are
balanced, then
EA = EB = EC = E Fig 4: Vector diagram of 3‐phase emf
SINGLE‐LINE DIAGRAM
SINGLE‐LINE DIAGRAM
Single line representation of a simple power system
SINGLE‐LINE DIAGRAM
• A one‐line diagram of a power system shows the main
connections and arrangement of components.
• Any particular component may or may not to shown
depending on the information required in a system study, e.g.
circuit breakers need not be shown in a load flow study but
are a must for a protection study.
• Power system networks are represented by single line
diagram using suitable symbol for generators, motors,
transformers and loads.
SINGLE‐LINE DIAGRAM
• It is a convenient practical way of network representation
rather than drawing the actual three‐phase diagram which
may indeed be quite cumbersome and confusing for a
practical size power network.
• Generator and transformer connections – star, delta, and
neutral grounding are indicated by symbols drawn by the side
of the representation of these elements.
• Circuit breaker are represented as rectangular blocks.
IMPEDANCE DIAGRAM
IMPEDANCE DIAGRAM
Impedance diagram of power system
IMPEDANCE DIAGRAM
• The impedance diagram on single phase basis under balanced
operating conditions can be easily drawn from single line
diagram.
• Single phase transformer equivalent are shown as ideal
transformer with transformer impedances are indicated on the
appropriate side.
• Magnetizing reactances of the transformers are been neglected.
This is a good approximation for most power system studies.
IMPEDANCE DIAGRAM
• The generators are represented as voltage sources with series
resistance and inductive reactance.
• Loads are assumed to be passive and are represented by
resistance and inductive reactance in series.
• Neutral grounding impedance do not appear in the diagram
as balanced conditions are assumed.
Concept of
Electrical Energy Demand
INTRODUCTION
• The function of a power station is to deliver power to a
large number of consumers.
• However, the power demands of different consumers
vary in accordance with their activity.
• The result of this variation in demand is that load on a
power station is never constant.
• Most of the complexities of modern power plant
operation arise from the inherent variability of the load
demanded by the users.
INTRODUCTION
• Unfortunately, electrical power cannot be stored and,
therefore, the power station must produce power as and
when demanded to meet the requirements of the
consumers.
Variable Load on Power Station
The load on a power station varies
from time to time due to
uncertain demands of the
consumers and is known as
variable load on the station
Variable Load on Power Station
• Load on a power station or a group of power stations
varies during the day in accordance with the daily
activities of the consumers.
• Maximum load on the station during the day is called
Peak Load.
• The power station (or group of stations) should have
enough installed capacity to meet peak demand.
• During the off peak period the installed capacity will not
be fully loaded and the installed capacity is under-utilized.
Demand Curve for Load
Consumption in 24 hours
Load Curves
The curve showing the variation
of load on the power station with
respect to time is known as a load
curve.
Demand Curve for Load Consumption
in 24 hours
• A load at a particular point on the power system is the
power flow expressed in terms of kW or MW through that
point (3 phase).
• The load varies during the hours of the day, days of the
week and during seasons.
Demand Curve for Load Consumption
in 24 hours
• These load variations, during the whole day (i.e 24
hours) are recorded half-hourly or hourly and are plotted
against time on the graph.
Figure 1 : Load curve
Demand Curve for Load Consumption
in 24 hours
• It is clear that load on the power station is varying, being
maximum at 6pm in this case.
i. The daily load curve shows the variations of load on the power
station during different hours of the day.
ii. The area under the daily load curves gives the number of units
generated in the day.
Units generated/day = Area (in kWh) under daily load curve.
Demand Curve for Load Consumption
in 24 hours
iii. The highest point on the daily load curve represents the
maximum demand on the station on that day.
iv. The area under the daily load curve divided by the total number
of hours gives the average load on the station in the day.
Average load = Area (in kWh) under daily load curve
24 hours
Demand Curve for Load Consumption
in 24 hours
v. The ratio of the area under the load curve to the total area
rectangle in which it is contained gives the load factor.
= Area (in kWh) under daily load curve .
Total area of rectangle in which the load curve is contained
Demand Curve for Load Consumption
in 24 hours
vi. The load curve helps in selecting the size and number of
generating units.
vii. The load curve helps in preparing the operation schedule of the
station.
Important Terms and Factors
1) Connected load. It is the sum of connected loads in its
network or supply system. It is expressed in MW. It is a
fixed quantity during the day of or the month.
For instance , if a consumer has connections of five 100
watt lamps and a power point of 500 watts, then the
connected load of the consumer is 5 x 100 + 500 = 1000
watts. The sum of the connected loads of all the
consumers is the connected load to the power station.
Important Terms and Factors
2) Maximum demand. It is the greatest demand of load on the
power station during a given period.
Demand factor = Maximum demand
Connected load
The value of demand factor is usually less than 1. It is expected
because maximum demand on the power station is generally
less than the connected load.
If the maximum demand of on the power station is 80 MW, then
demand factor = 80/100 = 0.8. The knowledge of demand factor
is vital in determining the capacity of the plant equipment.
Important Terms and Factors
4) Average Load. The average of loads occuring on the power
station in a given period (i.e. a day or month or year) is known as
average load or average demand.
Daily average load = No. of units (kWh) generated in a day
24 hours
Monthly average load = No. of units (kWh) generated in a month
No. of hours in a month
Yearly average load = No. of units (kWh) generated in a year
8760 hours
Important Terms and Factors
5) Load factor. The ratio of average load to the maximum demand
during a given period is known as load factor.
Load Factor = Average load
Max. demand
If the plant is in operation for T hours,
Load Factor = Average load x T
Max. demand x T
= Units generated in T hours
Max. demand x T hours
Important Terms and Factors
• The load factor may be daily load factor, monthly load factor or
annually load factor if the time period considered is a day or
month or year.
• Load factor is always less than 1 because average load is smaller
than the maximum demand.
• The load factor plays key role in determining the overall cost per
unit generated.
• Higher the load factor of the power station, the lesser will be the
cost per unit generated. It is because higher load factor means
lesser maximum demand. The station capacity is so selected that
it must meet the maximum demand. Now, lower maximum
demand means lower capacity of the plant which, therefore,
reduces the cost of the plant.
EXAMPLE
A generating station has the following daily load cycle :
Time
0 – 6 6 – 10 10 – 12 12 – 16 16 – 20 20 – 24
(hours)
Load
40 50 60 50 70 40
(MW)
Find :
i. Average load
ii. Load factor
ANSWER
=
[( 40 × 6) + (50 × 4) + (60 × 2) + (50 × 4) + (70 × 4) + ( 40 × 4)]MWh
24 h
1200MWh
= = 50MW = 50,000kW
24h
ANSWER
50 MW
= ×100% = 71.4%
70 MW
EXERCISE
A generating station has the following daily load cycle :
Time
0 – 6 6 – 10 10 – 12 12 – 16 16 – 20 20 – 24
(hours)
Load
20 25 30 25 35 20
(MW)
• While designing and building a power station, efforts should
be made to achieve overall economy so that the per unit cost
of production is as low as possible.
Significant of Power Quality
• There has recently been a great emphasis on revitalizing
industry with more automation and more modern equipment.
• This usually means electronically controlled, energy‐efficient
equipment that is often much more sensitive to deviations in
the supply voltage than were its electromechanical
predecessors.
Factors Effecting
Power Quality
Factors Effecting Power Quality
• The economics of power generation has assumed a great
importance in this fast developing power plant engineering.
• While designing and building a power station, efforts should
be made to achieve overall economy so that the per unit cost
of production is as low as possible.
• This will enable the electrical energy at a profit and ensure
reliable service.
Factors Effecting Power Quality
• There are several factors which influence the production cost such
as land and equipment, depreciation of equipment, interest on
capital investment etc.
• Economics consideration include cost of power generation,
metering, tariffs and revenues, and power factor improvement.
• Common aspects for planning and economic consideration include
choice of generating plants, operating costs, plant scheduling and
economic loading.
Factors Effecting Power Quality
1.0 Transients
• Impulsive 3.0 Long‐duration variations
• Oscillatory • Interruption, sustained
• Undervoltages
2.0 Short‐duration variations • Overvoltages
• Instantaneous • Voltage unbalance
• Momentary • Waveform distortion
• Temporary • DC offset
• Interruption • Harmonics
• Sag (dip) • Interharmonics
• Swell
Methods to Enhance
Power Quality
Methods to Enhance Power Quality
• There are several method to enhance power quality :
1) Installing capacitors (KVAR Generators)
2) Minimizing operation of idling or lightly loaded motors
3) Avoiding operation of equipment above its rated voltage.
4) Replacing standard motors as they burn out with energy‐
efficient motors.