Download as pdf or txt
Download as pdf or txt
You are on page 1of 36

Sections 

VII Part A – Overhead line 
Table of Contents 
1‐GENERAL TECHNICAL REQUIREMENTS .............................................................................................. 2 
2 ‐ GENERAL TECHNICAL SPECIFICATIONS ................................................................ 错误!未定义书签。 
3 ‐ MATERIAL AND INSTALLATION SPECIFICATIONS ................................................. 错误!未定义书签。 

4 – WORK & TECHNICAL SCHEDULES ....................................................................... 错误!未定义书签。 
   
1‐GENERAL TECHNICAL REQUIREMENTS 
 

TABLE OF CONTENTS 
 

1  GENERAL ............................................................................................................................... 4 
1.1  PURPOSE OF DOCUMENT ............................................................................................................................. 4 
1.2  BRIEF PROJECT DESCRIPTION ....................................................................................................................... 4 
1.3  SCOPE OF WORKS ......................................................................................................................................... 5 
2  CODES AND STANDARDS ....................................................................................................... 6 
3  SUBMITTALS ......................................................................................................................... 7 
3.1  WORK CONTROL SCHEDULES ....................................................................................................................... 8 
3.2  PROGRESS REPORT ....................................................................................................................................... 8 
4  DOCUMENTATION................................................................................................................. 9 
4.1  DRAWINGS .................................................................................................................................................... 9 
4.1.1  Outline Drawings............................................................................................................................................................ 9 
4.1.2  Assembly Drawings ........................................................................................................................................................ 9 
4.2  TECHNICAL DATA SCHEDULES ...................................................................................................................... 9 
4.3  LANGUAGE .................................................................................................................................................... 9 
5  ENVIRONMENTAL CONDITIONS ........................................................................................... 10 
5.1  SEISMIC REQUIREMENTS ............................................................................................................................ 10 
5.2  ENVIRONMENTAL CONDITIONS AND TROPICALIZATION ........................................................................... 10 
6  GALVANIZATION ................................................................................................................. 11 
6.1  GENERAL ..................................................................................................................................................... 11 
6.2  GALVANIZATION LAYERS ............................................................................................................................ 11 
6.3  MINOR DEFECTS ......................................................................................................................................... 11 
6.4  DEFECTS AND MAJOR DAMAGE ................................................................................................................. 11 
7  WELDING (ONLY WHERE PERMITTED) ................................................................................. 12 
8  WEIGHTS AND MEASUREMENTS ......................................................................................... 12 
9  QUALITY ASSURANCE PROGRAM ........................................................................................ 12 
9.1  PROGRAM ................................................................................................................................................... 12 
9.2  PLANT TESTS ............................................................................................................................................... 12 
10  INTERPRETATION OF THE TECHNICAL SPECIFICATION .......................................................... 13 
11  NAMEPLATES ...................................................................................................................... 13 
12  PACKING AND MARKING ..................................................................................................... 14 
12.1  GENERAL ..................................................................................................................................................... 14 
12.2  INTERIOR PACKING ..................................................................................................................................... 14 
12.3  EXTERIOR PACKING ..................................................................................................................................... 15 
12.4  PACKING OF ELECTRICAL EQUIPMENT ....................................................................................................... 15 
12.5  PACKING OF STRUCTURAL STEEL ................................................................................................................ 16 
12.6  PACKING OF SPARES ................................................................................................................................... 16 
12.7  PROTECTION AGAINST HUMIDITY .............................................................................................................. 16 
12.7.1  Waterproofing .....................................................................................................................................................16 
12.7.2  Dehydrating Agents ..............................................................................................................................................16 
12.8  CLOSED CRATES (SEE APPENDIX 4, 5, 6 AND 7) .......................................................................................... 17 
12.9  OPENWORK CRATES ................................................................................................................................... 18 
12.10  MATERIALS TO BE TRANSPORTED ON PALLETS .......................................................................................... 18 
12.11  MATERIALS TO BE TRANSPORTED IN METALLIC DRUMS ........................................................................... 18 
12.12  REELS FOR CONDUCTORS AND CABLES ...................................................................................................... 18 
12.13  PACKING MATERIALS .................................................................................................................................. 18 
12.14  MARKING .................................................................................................................................................... 19 
12.14.1  Marking Models ...................................................................................................................................................19 
12.15  PACKING MODELS ...................................................................................................................................... 20 
12.15.1  Appendix 1 ‐Drawings Title Block (sample) ...........................................................................................................21 
12.15.2  Appendix 2 ‐Wood Defects ...................................................................................................................................22 
12.15.3  Appendix 3 ‐Wood Deformations .........................................................................................................................23 
12.15.4  Appendix 4 ‐Closed Crates ....................................................................................................................................24 
12.15.5  Appendix 5 ‐Closed Crates ....................................................................................................................................25 
12.15.6  Appendix 6 ‐Closed Crates ....................................................................................................................................26 
12.15.7  Appendix 7 ‐Closed Crates ....................................................................................................................................27 
12.15.8  Appendix 8 ‐Openwork Crates ..............................................................................................................................28 
12.15.9  Appendix 9 ‐ Openwork Crates .............................................................................................................................29 
12.15.10  Appendix 10 ‐Wooden Pallets ..............................................................................................................................30 
12.15.11  Appendix 11 ‐ Packing of Barrels on Pallets ..........................................................................................................31 
12.15.12  Appendix 12 ‐Packing in Drums ............................................................................................................................32 
12.15.13  Appendix 13 ‐Reels for Cables ..............................................................................................................................33 
12.15.14  Appendix 14 ‐ Packing of Steel ..............................................................................................................................34 
12.15.15  Appendix 15 ‐ Pictograms .....................................................................................................................................35 
 

 
1 GENERAL 
1.1 PURPOSE OF DOCUMENT 

The  purpose  of  this  document  is  to  define  the  standard  general  requirements  applicable  to  all  transmission  line 
equipment and material. 

This  document  shall  be  used  in  conjunction  with  the  standard  technical  specifications,  relative  to  each  of  the 
equipment that will be part of procurement and construction contracts involving supply of equipment. 

1.2 BRIEF PROJECT DESCRIPTION 

The Employer intends to evacuate power between 220/132/33kV Masaka (West) and 220/132kV Mbarara (South) 
substations. 

A 400 kV Double Circuit (DC) Transmission Line from Masaka West substation to Mbarara south substation with the 
length of line as 132kms is to be constructed including the works related to the proposed line crossing of existing 
132kV Masaka‐ Mbarara Transmission line. Regarding this line crossing, two options are possible; the EPC must quote 
for both options in the BOQ. 

Option 1: OVERHEAD LINE  

 Cross the existing 132kV line at crossing point between AP134 and AP134A (Option 1 coordinates)  
 Remove  the  existing  skyrap  shield  wire  (only  between  towers  405  and  406  of  the  existing  132kV  Masaka‐
Mbarara line) and clamping at both sides  
 String an appropriate ADSS cable starting from the nearest joint box to the Mbarara North substation  
 Place the ADSS cable under the phase conductors  
 Control the loading of the existing 132kV towers to avoid any overloading following the addition of the ADSS 
(all accessories are to be included) 
 Perform all the necessary commissioning tests  

Option 2: UNDERGROUND LINE 

 Cross the existing 132kV line at crossing point between AP134 and AP134A (Option 2 coordinates)  
 Convert  the  existing  132kV  Masaka‐Mbarara  overhead  transmission  line  between  towers  405  and  406  to 
underground cable at crossing point, including but not limited to  
 cable tap‐off (according to the tender drawings),  
 cable termination,  
 surge arrester,  
 downlead connection between OHL and cable head,  
 laying of 1cct of 500 sq.mm underground cable. 
 Replace  towers  405  and  406  of  the  132kV  line  with  two  special  towers  (see  “Cable  tap‐off  tower”  drawing 
provided)  
 String an appropriate ADSS cable from the nearest joint box to the Mbarara North substation  
 ADSS cable could be attached to the 400kV 
 Control the loading of the new 132kV towers (towers 405 and 406) to avoid any overloading following 
the addition of the ADSS (all accessories are to be included) 
 Perform all the necessary commissioning tests  

(B) CONSTRUCT A TEMPORARY 132KV OHL TO BYPASS THE LINE CROSSING DURING CONSTRUCTION WORKS
(EMERGENCY RESTORE SYSTEM TOWERS (ALUMINIUM TYPE) TO BE PURCHASED, USED, AND HANDED OVER
TO THE CLIENT AFTER COMPLETION OF THE WORKS).

(C) DISMANTLE AND TRANSPORT TO UETCL STORE THE CURRENT 405 AND 406 TOWERS AND ALL OTHER
NECESSARY EQUIPMENT

(D) SET THE RELAYS FOR THE EXISTING 132KV LINE AT THE TWO SUBSTATIONS.

(E) PERFORM NEW IMPEDANCE CALCULATIONS.

For both options, the Contractor might have to do the profiling of the 132kV line. In case any field work is required, 
it is under the responsibility of the Contractor (as part of contract costs). 

Page 4 sur 36 
 
The EPC will determine the location of the dead‐end towers for Line In‐Line Out (LILO) into the proposed 400/220kV 
Masaka and Mbarara substations. The details of the substation land, layout and coordinates shall be provided by 
UETCL to EPC 

1.3 SCOPE OF WORKS 

The scope of the 400kV Transmission Line shall comprise of all engineering, detailed design, manufacture, factory 
testing, delivery to site, earthworks, civil works, erection, testing, commissioning, maintenance prior to take over, 
supply and delivery of spare parts, relevant trainings and defects notification and correction for the transmission line 
and substation extensions. Regarding the scope of works of the transmission line, services will include but not be 
limited to: 

 Construction  of  a  132km,  400kV  Double  Circuit  Steel  Lattice  Tower  Transmission  line  from  220/132kV 
Masaka West Substation to 220/132kV Mbarara South Substation 
 Construction and installation of all required infrastructure and equipment around the transmission line, in 
particular  the  installation  of  Concrete  Markstones  to  demarcate  the  extents  of  the  transmission  line 
wayleaves corridor and the construction of a motorable access road under the transmission line and shall 
be  handed  over  at  commissioning.  These  access  roads  shall  be  continuous  along  the  line  and  shall  be 
suitable for the vehicles which will be used (cars, forklifts, trucks/trailers etc.) to reach up to the point of 
unloading of the equipment. 

In  addition,  all  consultation  and  coordination  of  respective  engineering,  technical  data  and  activities  being 
implemented  with  respect  to  the  400kV  Double  Circuit  Masaka  Mbarara  Transmission  line  and  associated 
substations project are under the responsibility of the Contractor. 

Page 5 sur 36 
 
2 CODES AND STANDARDS 
The last edition of the reference Codes and Standards shall be applied, unless something to the contrary is noted, in 
connection with the General Technical Requirements. 

ANSI/AWS D1.1  American Welding Society.  The structural welding code 

ASTM A90  Test method for weight of coating on Zinc‐coated (galvanized) iron or steel articles. 

ASTM A123  Zinc (hot‐dip galvanized) coating on iron and steel products. 

ASTM A143  Recommended  practice  for  safeguarding  against  embrittlement  of  hot‐dip  galvanized 
structural steel and procedure for detecting embrittlement. 

ASTM A153  Specifications for Zinc coated (hot‐dip) on iron and steel hardware. 

ASTM B201  Standard practice testing chromate coating on Zinc and Cadmium surfaces. 

ASTM D522   Standard Test Method for mandrel bend test of attached organic coating.  

ASTM D523   Standard test method for specula gloss. 

ASTM D870   Standard Practice for testing water resistance of coating using water immersion 

ASTM D2247  Standard Practice for testing water resistance of coating in 100 % relative humidity.  

ASTM D2794   Standard  Test  Method  for  resistance  of  organic  coating  to  the  effects  of  rapid 
deformation (Impact).  

ASTM D3359.  Standard Test Method for measuring adhesion by tape test  

ASTM D3363   Standard Test method for film hardness by pencil test 

IEC 60068‐3‐3.  Environmental Testing – Part 3: Guidance seismic test methods for equipment. 

ISO 9001  Quality  Systems  –  Model  for  quality  assurance  in  design,  development,  production, 
installation and servicing. 

British Standards specifications (BS) and International Electro‐technical Commission (IEC) publications equivalent to 
above  mentioned  specifications  shall  also  apply.  If  the  Contractor  wants  to  use  any  other  standards  then  the 
comparison has to be provided to the above international standards. In case the standards are not in English, subject 
to the Employer approval only, necessary translation of relevant standards shall be provided and the translation shall 
be stamped by the standards organisation in the country of origin and by the Chamber of commerce. 

Page 6 sur 36 
 
3 SUBMITTALS 
The Contractor shall provide as a minimum the following technical information, in the English language, at the time of 
submitting his proposal: 

a) General outline drawings for towers and foundations. 

b) The  tower  weights  for  each  type  of  tower  and  foundation  details  (excavation,  lean  concrete,  concrete  and 
reinforcing) for each type of foundation.  

c) Estimated work control schedules 

d) Completed technical data schedules 

e) Type test reports 

f) Quality assurance program 

g) Complete set of catalogues 

The successful Contractor is responsible for any discrepancies, errors or omissions in the submittals, whether these have 
been reviewed by the Employer’s Engineer or not, provided that such discrepancies, errors and omissions are not due to 
inaccurate information or particulars furnished in writing by the Employer / Employer’s Engineer to the Contractor. 

During  the  contract’s  implementation  period,  the  successful  Contractor  shall  provide  the  following  additional 
information. 

1/ For Approval

Before Manufacture

a) Manufacturers’ Technical Data Sheets for all major plants and equipment
b) All detailed design documents including calculations, structural drawings and other
construction drawings
c) Program for Production/manufacture and Testing including Quality Assurance Plan

Before Delivery of major equipment

a) Guaranteed rated values and characteristics of the major plants.


b) Detailed physical and electrical drawings
c) Detailed erection, operation and maintenance instructions.
d) Summary of routine tests with copies of the test reports for the major plants including
the FAT reports if applicable

Before Construction/ Installation

a) Construction Schedule
b) Detailed geotechnical tests and reports
c) All detailed design calculations and drawings where appropriate
d) Line Profile design and drawings
e) Substation electrical designs (one line diagram, and three line diagram, general
arrangement and section details, lightning protection and grounding design, protection
and control designs, Battery & Battery Charger capacity design, etc.)
f) substation embankment design
g) Equipment Foundations and Steel Structure design
h) Distribution Network design drawings
i) Environmental, Social, Health and Safety Management Plan
j) Change proposals and associated documentation

Before Commissioning and hand over

a) Pre-commissioning test results


b) Commissioning procedures and check list;
c) As built drawings and documentations (Operations and Maintenance Manuals)

Page 7 sur 36 
 
B/ For Review

a) Work program and time schedule


b) Design documents
c) Calculations and drawings
d) Progress reports
e) As built drawings
f) Supervision formats
g) Commissioning procedures
h) Completion reports
i) All milestone hold points as shall be detailed in the QA programme.

The Employer's representative retains the right to request any additional relevant document
during the contract's implementation.

3.1 work control schedules 

The Contractor must submit within fifteen (15) days following award of Contract a detailed Control Schedule of Work in 
Microsoft Project format. This schedule shall be updated weekly and submitted to the Employer’s Engineer. The Delivery 
Schedule  shall  be  consistent  with  the  Employer  requirements  and  shall  form  part  of  the  Control  Schedules.    The 
Contractor shall carry out the Work accordingly. 

The Work Control Schedules shall indicate for each section and sub section of the Work as given in the Schedule of Prices 
the commencement and completion dates for the principal activities of the Works including: 

(a) Design 

(b) Submittal of drawings for review 

(c) Receipt of final drawings 

(d) Placement of purchase orders 

(e) Fabrication or manufacture 

(f) Factory testing 

(g) Shipment 

(h) Receipt of material 

(i) Instruction manuals 

Tentative General Time Schedule of works – Overhead line part 

 
OHL Number of months from Start date (S)*
Activities S+1 S+2 S+3 S+4 S+5 S+6 S+7 S+8 S+9 S+10 S+11 S+12 S+13 S+14 S+15 S+16 S+17 S+18
Engineering & Design

Manufacturing & Transport

Installation

Testing & Commissioning
* Start date = signature of contract
 

3.2 progress report 

The Contractor shall submit monthly progress report indicating progress made the preceding period. The report shall 
show cumulative progress towards schedule  completion, expressed as a percentage of all  items  shown  in  the  Work 
Control Schedules. 

Page 8 sur 36 
 
4 DOCUMENTATION 
4.1 drawings 

The  Contractor  must  prepare  and  submit  for  the  review  of  the  Employer’s  Engineer,  the  drawings  indicated  in  this 
document. The drawings must be A1 format (841 x 594 mm), A3 (420 x 297 mm) or A4 (297 x 210 mm) format and 
include in the lower right‐hand corner, a title block as indicated in Appendix 1, Drawings Title Block. 

The Contractor must submit, no later than six (6) weeks after award of contract, one (1) AutoCAD 14 computer file on a 
USB flash drive and by E‐mail, plus four (4) paper copies of each of the drawings to the Employer’s Engineer. The copies 
marked by the Employer’s Engineer will be returned to the Contractor, at the latest, 28 days after presentation of these 
drawings. The corrected drawings will be submitted once more, following the same procedure, if necessary. 

An updated AutoCAD computer file, plus six (6) paper copies of the final version of the drawings, must be submitted by 
the Contractor, at the latest one (1) month before delivery of the purchased equipment. 

4.1.1 Outline Drawings 

Drawings to scale including dimensions, weight, center of gravity for transportation and installation, in the plan view and 
elevation. 

Design briefs and detailed drawings for the metallic structures and supports. 

Nameplates, to scale, must contain the values resulting from the plant tests, serial number, weight mass, etc. 

It must be indicated, for each different piece of material, connector, isolator, support, etc., the catalogue reference as 
well as the place where the characteristics are located by showing the code that was used. 

4.1.2 Assembly Drawings 

A complete bill of materials related to the drawings is an essential requirement for its review. 

4.2 technical data schedules 

The  Contractor  must  fill  out  completely  and  attach  to  his  proposal  the  Technical  Data  Schedules  included  in  the 
technical specification of the equipment.  The data shall include the values guaranteed by the Manufacturer. The 
Technical Data Schedules shall be duly stamped and signed by the Manufacturer. 

The Contractor shall guarantee that the equipment and the work are in accordance with all the requirements of the 
present specification including data from Technical Data Schedules. 

4.3 language 

All technical documents (such as: calculation schedules, curves, maintenance and service manuals, quality assurance 
control program report, plant tests and manufacturing schedule) presented by the Contractor to the Employer’s Engineer 
and Employer, shall be in English language. The drawings, nameplates and instruction manuals shall be in English. 

   

Page 9 sur 36 
 
5 ENVIRONMENTAL CONDITIONS 
5.1 seismic requirements 

Please  refer  to  IEC  60721‐  Classification  of  environmental  conditions  .The  Contractor  shall  bear  in  mind  that  the 
transmission line may be situated in a seismic zone, consequently, the equipment shall be designed so as to withstand, 
without damage or interruption, seismic movements of up to: 

‐ Horizontal acceleration:  Please refer to the table below. 

A study report including computer simulation (modal analysis) of complex construction or a vibration table test report 
regarding  the  verification  of  the  withstand  ability  of  the  support  structure  and  equipment  shall  be  submitted  for 
review upon written request by the Employer’s Engineer.  

5.2 environmentAL conditions and tropicalization 

The equipment shall function without exceeding the guaranteed values in the following ambient conditions: 

Environment Conditions  Unit  Value 

Maximum ambient temperature  °C  45 

Minimum ambient temperature  °C  5 

Mean maximum daily temperature  °C  30 

Annual average temperature  °C  30 

Maximum solar radiation (worst case)  W/m2  1200 

Isokeraunic level (max)     180 

Design altitude above sea level ( considering the highest in the project area)  m  1450 

Relative humidity, average  % rel.  80 

Average rainfall annually (using the highest in project area)  mm/a  2100 

Design Wind Speed   m/s  31 

Environment EMC Class (IEC 61000)  Industrial 

Seismicity (Peak Ground Acceleration)  0.15g 

Maximum Temperature rise of Conductors above ambient (45°C)  °C  +35 

Environment (mountain, forest etc.)    Tropical 

Page 10 sur 36 
 
6 GALVANIZATION 
6.1 general 

All  the  small  pieces  such  as:  washers,  bolts,  screws,  nuts,  counter‐nuts  (if  they  are  not  made  of  stainless)  and  steel 
supports shall be hot‐dip galvanized. 

6.2 galvanization layers 

The material including: bolts, nuts and counter‐nuts, unless otherwise indicated, shall be corrected and galvanized, once 
the manufacturing work is completed, in accordance with ASTM Standards (A90, 123, 143, 153). 

All the steel presenting defective galvanization or important imperfections shall be galvanized once more. In case of 
major  defects  or  damages,  repair  shall  be  permitted  neither  at  the  plant  nor  at  the  site.  Repair  procedures  such  as 
metallic outpouring, welding or similar methods shall not be permitted either. All steel rejected because of defects or 
major damages on the galvanized surface, must be treated with acid, corrected and properly prepared for hot dip re‐
galvanization. 

The zinc coating must be clean, smooth, of even thickness, with no defects and firmly adhered to the metallic surface. 
The Contractor must replace the galvanized piece which is imperfect or presents important defect. All the holes in the 
galvanized pieces must be free from knots and/or zinc concentration. 

6.3 minor defects 

The defects of lesser importance in well located places may be considered as minor if the bare metal is not exposed in 
these places. The surface must not present any trace of rust or lack of adherence of the original coating. 

Repair  on  the  previously  mentioned  minor  defects  shall  be  permitted  using  touch‐ups  performed  with  special  paint 
according to a method proposed by the Contractor which must be accepted by the Employer’s Engineer. 

6.4 defects and major damage 

These defects include non‐adherence of zinc on the steel, galvanization excessive thickness variations, thick zinc deposits, 
excessive roughness or any other defect showing that the galvanizing was not applied according to applicable standard. 
Such  defects,  caused  by  defective  application  of  acid  dip,  presence  of  grease,  lamination,  inadequate  draining  and 
handling of the vertically immersed steel or any other factors that result in a defective galvanization, shall constitute 
cause for rejection. 

Also,  the  thinning  of  the  zinc  coating  to  the  extent  of  exposing  the  bare  metal  shall  be  considered  a  major  defect. 
Consequent damage caused by abrasion during shop handling when loading and unloading will be cause for rejection. 

Page 11 sur 36 
 
7 WELDING (ONLY WHERE PERMITTED) 
This clause describes the welding procedure to be used, generally, for steel structures. This clause is complementary 
to the technical prescriptions of this document. 

For the steel structures, the welding must be performed in compliance with the last edition of AWS D1.1. 

All manual welding must be carried out using the protected metal arc welding procedure and automatic welding using 
the submerged or protected metal arc welding procedure. 

All important welding that, according to the Employer’s Engineer, may be subject to excessive efforts or do not seem 
to comply with the standards, may be x‐rayed at his request. 

8 WEIGHTS AND MEASUREMENTS 
The metric system SI of units for weighing and measuring must be used for the design. All pieces of hardware and steel 
angles shall be in accordance with the ASTM standards. 

The Contractor may propose as an alternative an equivalent metric standard for hardware and steel angle but subject to 
approval of Employer’s Engineer. 

All dimensions and weights indicated in these documents, drawings, manufacturer plates, etc., shall be expressed in SI 
metric units. 

9 QUALITY ASSURANCE PROGRAM 
9.1 program 

In general terms, the manufacturing quality assurance program must be in compliance with ISO 9000 standards. The 
Employer’s  Engineer  reserves  the  right  to  verify  the  document  pertaining  to  the  manufacturer’s  quality  assurance 
program, as well as the application of the same in the manufacturing plant. 

In general the assembly of all the equipment components shall be carried out in the manufacturer's workshops so that 
it shall possible to perform inspections, tests, etc. that will ensure a subsequent satisfactory operation. The exceptions 
to this rule will only be possible upon Employer’s Engineer consent. 

The Employer’s Engineer shall have the right of access to the plant and to inspect and verify the quality of materials used 
in the manufacturing process. 

9.2 plant tests 

The  materials  and  all  the  equipment  shall  be  tested  as  per  the  prescriptions  of  this  specification.  The  tests  shall  be 
performed by the Contractor and certified by the Employer’s Engineer. 

All the required tests must be performed in order to confirm that the materials and the equipment comply with these 
specifications, and to allow the Purchaser to detect any material or manufacturing defects. 

The  results  of  all  the  tests  shall  be  marked  down  in  the  reports  containing  all  the  necessary  information  to  enable 
verification of compliance with the present specification. 

The test certificates shall be written in English and shall show the results and real conditions of the tests performed the 
circuits, oscillogrammes, environmental conditions, nameplate drawings with measured values, graphs, etc. 

No later than two (2) weeks after having performed the tests, the Supplier shall submit to the Employer’s Engineer, four 
(4) copies of the report of all tests. The report must include the test results of all the equipment accessories. 

The report must also include a description of any failure that occurred while performing the plant tests, even if the test 
resumed after the failure. 

Page 12 sur 36 
 
The  tests  are  meant  to  verify  and  determine  the  characteristics  of  the  equipment.  Normally,  type  tests  shall  be 
performed  on  one  (1)  apparatus  of  each  type  and  with  different  technical  characteristics.  If  type  tests  have  been 
performed on identical material or equipment, within a period not exceeding eight (8) years from contract date, the 
results may be accepted provided that the reports of the tests are submitted within the following thirty (30) days after 
signature of the contract. 

The routine tests are intended to reveal any defective material or manufacture non‐conformity and shall be performed 
on all equipment supplied. 

The units to be assembled in the plant shall be assembled, adjusted and tested in the plant, as much as possible, under 
the same service conditions that will prevail at the site of installation, to ensure the accuracy of the wiring and the correct 
operation of the equipment. 

The Employer’s Engineer reserves the right to be present at any of the tests. 

The equipment to be tested must be totally assembled for an inspection before the tests. 

The Contractor must submit to the Employer’s Engineer a detailed program of tests for review, at least one (1) month 
before the tests take place. 

The Contractor shall inform the Employer’s Engineer in writing, at least thirty (30) days in advance, of the date of the 
tests. 

10 INTERPRETATION OF THE TECHNICAL SPECIFICATION 
The Technical Specification prevails over the reference standards and over the General Technical Requirements. 

11 NAMEPLATES 
The equipment shall be fitted with nameplates and indication plates, which must be manufactured of stainless steel or 
aluminum, with a minimum thickness of 1 mm engraved black letters on a light background. 

Page 13 sur 36 
 
12 PACKING AND MARKING 
12.1 general 

The purpose of the following general standards is to ensure that the Contractor pack and mark the materials according 
to acceptable standards and that the appropriate packing material is used. The Contractor is solely responsible for 
the quality of the packing material. 

The Employer’s Engineer, may, at any time, reject any packing or marking if it is deemed to be non‐conforming to the 
standards specified in this contract. 

If the packing is rejected, the Employer’s Engineer is entitled to have it redone, at the expense of the Contractor, and 
the later will not have the right to claim the incurred expenses. 

This specification is non‐limiting. 

The packing must resist all the risks associated with extensive handling by: 

‐ Fork lift 

‐ Cranes (slings) 

The packing must facilitate all types of handling. 

The packing must be suitable to resist long periods of storage (that could extend to several months) under variable 
weather conditions, to take into account deterioration factors typical to this kind of project, such as: 

‐ Cold 

‐ Damp heat 

‐ Abundant rain 

‐ Temperature fluctuations 

‐ Saline air 

‐ Vibrations 

‐ Parasites 

‐ Insects Etc… 

The  technical  specifications,  dimensions,  material  and  equipment  weight  are  the  other  criteria  to  consider  when 
designing and performing the packing. 

12.2 interior packing 

The packing shall be adequate and sufficient so as to avoid any damage to the contents during the handling or difficult 
transport conditions. In all cases, the items shall be arranged or wrapped in such a manner so as to minimize the 
volume. 

The Contractor must wedge, shore or screw, as needed, or use any other available method in order to prevent the 
rupture of partitions, the free movement of pieces within the rigid container and prevent any damage resulting from 
shock or vibrations. 

Fragile  pieces  unable  to  endure  handling  and  difficult  transportation  conditions  and  those  which  cannot  be 
disassembled  shall  be  properly  supported  before  the  wrapping  is  done.  All  pieces  that  are  rotating,  sliding,  free‐
moving or mounted on springs and whose movement is not blocked by a safety device shall be wedged and bound 
securely. 

Page 14 sur 36 
 
12.3 Exterior packing 

The following paragraphs describe the minimum requirements for packing. The material not specified in the following 
paragraphs must be packed according to specifications for equivalent material. The Manufacturer can refer to the 
basic guidelines of packing in ANSI/NAS and ISO Standards. 

The packing shall be performed in conformance with the accepted standards for marine, railway or overland shipping. 
The materials shall be solidly packed so as to withstand the different means of transportation and on any kind of 
difficult roads. 

All the equipment must be packed so as to be protected against any possible damaging effect caused by salt water 
(maritime packaging). 

12.4 packing of electrical equipment 

It is the Contractor’s responsibility to insure that packing is adequate for transportation to site in order to guarantee 
integrity of equipment. 

Any material liable to deterioration or corrosion must be packed in tightly closed crates. 

Whenever fittings or accessories are removed from an apparatus for easier transportation, the openings left must be 
properly covered. 

Cables  or  plug  wires  coming  out  of  the  apparatus  must  be  wrapped  with  an  insulation  tape  and  covered  with  a 
polyethylene film of at least 0.12 mm thick, in order to protect them from outdoor conditions. They must also be 
firmly fastened to the equipment to avoid deterioration while handling. 

The equipment and/or the materials must be fastened to a structural wooden base built with wooden beams 100 mm 
minimum thickness. The equipment must be handled with cranes using slings. 

The packing of equipment to be transported by air must be made using plastic containers and the materials as light 
as possible without compromising efficient protection against the risks associated with air transportation. 

The items that can be gathered in bundles shall be sorted out according to length and size and the bundle shall be 
bound with steel strapping and shall not exceed 100 kg each. 

The equipment and all the accessories shall be packed in closed crates, designed to resist the effects of negligent 
handling during overland and maritime transportation while loading and unloading and to prevent losses or theft. 
Besides, the packing shall be adequate to resist long periods of storage and outside exposure to all kinds of weather 
in harbor yards or any other places. 

The crates containing the electrical equipment or fragile pieces must have an adequate mechanic reinforcement to 
ensure their stability.  Open crates shall not be accepted. 

All  heavy  crates  or  large  crates  must  be  clearly  marked  for  handling  while  unloading  and  during  overland 
transportation. 

In  particular,  the  marking  must  show  how  and  where  to  install  the  slings  and  hooks  for  hoisting,  pulling  and 
transporting the crate. 

All the crates must have the identification marks, as indicated in the marking chapter. When a shipment contains 
several packages, the latter must be identified in relation to the main equipment. In case there are ferrous pieces 
assembled with the non‐ferrous pieces, the former must be well protected. 

The  pieces  liable  to  be  affected  by  water  condensation  or  humidity  absorption  while  loading  and  during 
transportation must be packed with waterproof materials. All filling material must be of non‐hygroscopic type. 

Page 15 sur 36 
 
In order to absorb the humidity, drying products must be placed in every crate. 

The spare parts with precise machined surfaces or materials, with ferrous parts, must be specially treated and packed 
for perfect conservation during many years and under normal storing conditions. 

The packing may be subject to the acceptance of the inspector appointed by the Employer. 

The Contractor must submit the packing drawings for acceptance by the Employer’s Engineer. 

12.5 packing of structural steel 

Packing  methods  and  the  packing  lists  are  the  responsibility  of  the  Contractor  and  they  shall  be  submitted  for 
acceptance  to  the  Employer’s  Engineer  who  reserves  the  right  to  inspect  the  supplies  and  their  packing  before 
shipment. 

The metal pieces are not to be stacked or packed before the chromate treatment is completely dry. The galvanized 
metal pieces stored outside must be on an incline position so as to permit the runoff of water. 

All the galvanized materials shall be protected against the risk of corrosion such as “white rust” which might be caused 
by water, saline air or prolonged humidity. 

The bundles of angles are to be sufficiently attached and of sufficient size as to give them the resistance required for 
shipping. Each bundle is to contain the members of the same structure. The maximum weight of each bundle should 
be approximately three (3) metric tons. One example of steel packing is shown on Appendix 14. 

Care  must  be  taken  during  handling  and  shipping  to  avoid  damage  to  the  galvanization  and/or  to  the  chromate 
treatment. 

The packing may be prepared once the manufacturing is finished. The pieces shall be assembled in tightly attached 
bundles, using packaging materials that will not oxidize easily as not to damage the galvanization and/or chromate 
treatment. 

The bolts, nuts and washers are to be packed by type and size in airtight new 2 ½ gallon drums (11 liters).  (Please 
refer to Appendix 11)  

The maximum weight of the 2 1/2‐gallon drum is to be around 35 kg. The diameter, length, class and quantity along 
with the packing number and total weight of the drum is to be painted in black on the side and top of the drum. The 
maximum weight of a pallet is limited to 3000 kg. 

12.6 Packing of spares 

All spares shall be delivered in metallic containers of 20ft or 40ft, which shall be kept by the Employer for storage 
purposes.  

 
12.7 protection against humidity 

12.7.1 Waterproofing 

Since the packing must be waterproof, it is important to avoid water condensation which promotes metal corrosion. 
Therefore, a waterproof film such as polyethylene or tar paper must cover the equipment in such a manner as to 
allow sufficient ventilation for water evaporation. 

12.7.2 Dehydrating Agents 

All  goods  sensitive  to  humidity  and  to  contamination  must  be  wrapped  with  plastic  film  or  waterproof  paper 
thoroughly sealed using a waterproofing method. 

Page 16 sur 36 
 
The Contractor shall generally use polyethylene; however, aluminum compound sheets are required for all electric 
and electronic equipment sensitive to humidity and contamination. 

A silica gel, in bags of standard dimensions, must be placed in the most appropriate places inside the package to 
expose all the hollow spaces of the equipment to the dehydrating action of the siccative. 

The  quantity  of  silica  gel  bags  for  every  package  must  be  sufficient  to  maintain  the  humidity  rate  at  40  %  for  a 
minimum period of six (6) months. 

This method, based on water absorption, can be used for any type of material. 

12.8 closed crates (see AppendIX 4, 5, 6 and 7) 

The Contractor shall limit the weight of crates to 3 metric tons. 

The bottom of each crate must be reinforced so as to withstand the weight of the packed equipment and to resist 
vertical shocks. 

The pieces of compact equipment must be solidly bound to the crate. 

All lifting points must be identified. 

All crates must be mounted on skids. 

The structural wooden members as well as the ones intended for fork lifting must be placed on the points of high 
load concentration. They must be sufficiently thick (2.5 cm) to withstand the weight.  The structural members must 
have a width of at least 10 cm and be screwed to the skids with bolts.  There must be a spacing of at least 2.5 cm 
between the structural wooden members and the item, on the side and on the top.  Fragile items must be protected 
by allowing a space between them ranging from 2.5 to 10 cm. This free space must be increased for items requiring 
no impact mounting. 

The filling material that will fill the empty spaces inside the crates shall be synthetic. Wood shaving and shredded 
paper shall not be acceptable. The design of the crates must be in accordance with the weight of the material to be 
packed: 

(a) Less than 250 kg 

The  crates  to  contain  less  than  250  kg  shall  be  built  with  cleats  of  no  less  than  
2.5 cm and the wood or plywood to be used shall be 1.9 cm thick. 

The crate shall be the type “A” shown on Appendix 4.  The strapping must be steel belts 19 mm wide crimped 
with steel fasteners. 

(b) From 250 kg to 500 kg 

The  crates must  be  made  with wood  1.9  cm  thick.  The  bottom  of  the  crate  must  be  2.5 cm  thick  and  the 
uprights must be made with 5 x 10 cm boards. The crate shall be the type "B" shown on Appendix 4. The 
strapping must be steel belts 32 mm wide crimped with steel fasteners. 

(c) From 500 to 3000 kg 

The crates to contain more than 500 kg must be mounted on a base with supports of at least 10 x 10 cm. The 
support shall be bolted to the base with bolts of 1.25 cm diameter, minimum. The wood thickness of the base 
must be more than 2.5 cm. The uprights must be 5 x 7.5 cm or more. 

The walls must be made of wood or plywood 2.5 cm thick. 

The top must be made of wood 2.5 cm thick with waterproof paper in between the two layers of the double top. 

Page 17 sur 36 
 
Appendix 5, 6 and 7 show the construction of these crates. The corners can be reinforced with steel belts 3.2 cm wide. 
The crates will be strapped with steel belts 51 mm wide installed vertically and horizontally and in sufficient quantity 
proportionally to the dimensions of the crate. 

12.9 openwork crates 

Open work crates are used to ship material non‐sensitive to outdoor conditions. 

Appendix 8 and 9 shows an example of crate used to pack insulators whereas Annex 9 shows a type of crate that 
could be appropriate for heavy equipment. 

12.10 materials to be transported on pallets 

In  order  to  make  material  and  certain  containers  handling  easier  (drums,  crates)  the  usage  of  wooden  pallets  is 
required. 

These pallets shall be solid, sturdy and new. They shall be made according to the example shown on Appendix 10. 

Appendix 11 shows a method of arranging material on wooden pallets. The strapping must be carefully done and in 
sufficient quantity to prevent the packages from slipping. 

12.11 materials to be transported in metallic drums 

New 2 1/2‐gallon drums (11 liters) shall be used mainly to transport bolts. Any other material to be transported this 
way shall be subject to acceptance by Employer’s Engineer. These drums shall be airtight in order to prevent water 
from entering during transport and storage. The bolts or any other materials shall be regrouped by size and diameter 
and properly identified. 

The drums must set on pallets to facilitate handling. They must be placed in a maximum of two (2) rows. One wooden 
pallet must be placed on top of the drums to increase stability and compactness when stowing. See example shown 
on Appendix 11. 

The weight of each pallet shall not exceed 3 metric tons. 

New 45‐gallon drums (204.5 liters) can be used for small pieces such: gussets, splices, the weight of each drum must 
not exceed 200 kg. The drums must be set on pallets and be fitted with a lifting device (crossbars or lifting eyelets). 
The drums must have three holes (approximately 1 cm diam.) at the bottom in order to allow drainage of any water 
that might enter the drum. 

The pieces transported shall not be in direct contact with the bottom of the drum, therefore wedges must be used. 
The pieces must not move inside the drum so an efficient blockage is necessary. A metallic lid must snugly cover the 
top to avoid water, mainly rain, from entering the drum. See example shown on Appendix 12. 

12.12 reels for conductors and cables 

All cables shall be packed on metallic reels which dimensions shall be as a function of the length and size of the cables. 
An example of reel is shown on Appendix 13. The AAAC conductor shall be packed on steel drums. 

12.13 packing materials 

The material specification described in this paragraph applies to all packing methods calling for this type of materials. 

(a) Solid Wood (see Appendix 2 and 3) 

The solid wood to be used for packing must be new, solid and well dried. It must be free from rot, wear, clinker, 
holes, loosen knots and excessive deformations. The humidity degree must be between 10 and 20 %. The knots 
must be healthy‐looking and not bigger than a 1/3 of the width of board. 

Page 18 sur 36 
 
(b) Plywood 

The plywood must be new, good quality and well‐dried. Three‐layer plywood must be used for the crates with 
cleats and five‐layer plywood for nailed crates. 

(c) Nails 

The nails must be circular and preferably covered with a coating of cement or chemical glue. 

Other types of nail that may be used are with helical or ring‐shaped shafts. 

(d) Strapping 

The metallic strapping shall be made of non‐annealed steel installed with a binding device and tied with steel 
fasteners. The steel must be treated against corrosion. Where the metallic belts touches the finished surfaces 
there must be protective pads at these points in order to avoid abrasion. 

The dimensions of steel belts will be in accordance with the Manufacturer’s specifications and in relation with 
the weight of the bundle to strap 

12.14 marking 

The marking must be in English and must also be as big as the available space on the crates allows without exceeding 
100 mm. A packing list, written in English, shall  go along with each shipment and be attached to each crate. The 
packing list shall be in a closed envelope, covered with plastic. 

All the crates must be marked on opposite sides. 

The Contractor must, according to the destination site, identify the packages by writing the appropriate code that has 
been allocated to each site of final destination. 

If tags are to be used, they shall be printed or typed with permanent ink and shall be solidly secured to the wooden 
surface by means of staples, nails or tacks; if this is possible, they must be fastened with metallic wire or a very solid 
rope (the tags shall be water‐proof). 

Warning signs such as: FRAGILE, KEEP DRY, POISON, etc. shall be clearly indicated if the nature of the merchandise 
calls for it (see Appendix 15). 

12.14.1 Marking Models 

Every item shipped must carry, on one side and on top, the following inscriptions: 

ATTENTION OF:    

DESTINATION:    

PROJECT:    

SITE:   COUNTRY:    

CONTRACT No.:    Equipment Code No.:     
   

BOX:     OF:   (Total number of crates shipped) 

Page 19 sur 36 
 
 

FINAL DESTINATION:            

Note:  If the shipment is not dispatched to the final destination, the container must carry the transit destination 
as well as the following: “TO BE DELIVERED TO (final destination)”. 

12.15 Packing Models 

Refer to Appendix 2 to 15. 

Page 20 sur 36 
 
12.15.1  Appendix 1 ‐Drawings Title Block (sample) 

Page 21 sur 36 
 
12.15.2  Appendix 2 ‐Wood Defects 

Page 22 sur 36 
 
12.15.3  Appendix 3 ‐Wood Deformations 

Page 23 sur 36 
 
12.15.4  Appendix 4 ‐Closed Crates 

TYPE A  PLYWOOD CASE WITH CLEATS 

TYPE B  2.5 cm THICK WOODEN CASE 

Page 24 sur 36 
 
12.15.5  Appendix 5 ‐Closed Crates 

Wooden Case, with Double‐Layer Top and Water‐Proof Paper, Reinforced 
With 32 mm Wide Steel straps at the Corners 
 

Page 25 sur 36 
 
12.15.6 Appendix 6 ‐Closed Crates 

Plywood Case, with Double‐Layer Top and Water‐Proof Paper, Reinforced  
With 32 mm Wide Steel belts at the Corners 
 

Page 26 sur 36 
 
12.15.7 Appendix 7 ‐Closed Crates 

Wooden Case for Heavy Equipment 

Page 27 sur 36 
 
12.15.8 Appendix 8 ‐Openwork Crates 

FIGURE 1  Cylindrical Configuration 
FIGURE 2  Tetrahedral Configurations 
 

Page 28 sur 36 
 
12.15.9 Appendix 9 ‐ Openwork Crates 

Wooden Open Case 

Page 29 sur 36 
 
12.15.10 Appendix 10 ‐Wooden Pallets 

Page 30 sur 36 
 
12.15.11 Appendix 11 ‐ Packing of Barrels on Pallets 

Page 31 sur 36 
 
12.15.12 Appendix 12 ‐Packing in Drums 

Page 32 sur 36 
 
12.15.13 Appendix 13 ‐Reels for Cables 

Page 33 sur 36 
 
12.15.14 Appendix 14 ‐ Packing of Steel 

Page 34 sur 36 
 
12.15.15 Appendix 15 ‐ Pictograms 

Page 35 sur 36 
 
 

Page 36 sur 36 
 

You might also like