Professional Documents
Culture Documents
Proposal of A 5KVA Single-Phase On-Line UPS With High Frequency Isolation and Power Factor Correction
Proposal of A 5KVA Single-Phase On-Line UPS With High Frequency Isolation and Power Factor Correction
net/publication/261239702
CITATIONS READS
3 4,564
5 authors, including:
Some of the authors of this publication are also working on these related projects:
A Five-Level Stacked Neutral Point Clamped Converter Based on Multi-State Switching Cell View project
All content following this page was uploaded by Carlos G C Branco on 17 September 2015.
Abstract – A high performance isolated double of such magnetic component increases both weight and
conversion uninterruptible power supply (UPS) with volume, and also adds cost and difficulties in the
power factor correction using a high frequency transportation to the installation site.
transformer, and input voltages equal to 110V/220V is Transformerless UPS incorporating common neutral bus
proposed. The arrangement is suitable to rack type line could be a solution to improve power conversion
structures because it has small size and reduced weight. efficiency, volume and weight reduction [3], [4]. Although
For both input voltages, the proposed converter has this UPS topology offered a way to obtain these advantages,
almost the same efficiency processing the same output this type is more susceptible to interference from spikes and
power. Other relevant features are soft commutation of transients caused by assorted devices connected to the utility
the controlled switches in the chopper and the boost grid [5].
stage, simple control strategy that can be implemented Several UPS topologies with high frequency isolation
with well-known integrated circuits, and the use of few characteristic have been proposed in [6]-[10]. These
batteries in series due to the step-up stage. Qualitative configurations belongs to topologies derived from isolated
analysis and experimental results obtained for a 5kVA boost full-bridge converter [6-8], flyback [9], and chopper-
prototype show a normal efficiency of over 87% for the boost [10].
worst case of input voltage and an input power factor of A common drawback found in most of approaches are the
over 99%. hard commutation of the controlled switches that
compromises efficiency, several batteries in series
Keywords - double conversion UPS system, high connection to achieve high DC-link voltage and pulsed
frequency transformer, power factor correction (PFC), current drawn by the battery bank that affects the reliability
soft commutation. of the battery set.
The topology proposed in [10] with modifications and
I. INTRODUCTION adjustments were adopted in this work to increase the output
power level. The advantages of such topology compared to
With the increased dependence on the critical loads such the previous ones are: it allows the UPS operation with two
as medical support systems and communications systems, values of input voltage (110V/220V), simple control strategy
more priority certainly will be placed on supplying and presents soft commutation of main switches from the
continuous and disturbance-free power in the future. For this isolated AC-DC Stage.
purpose extensive work have been done to provide
equipments more reliable, with reduced size and weight. II. THE PROPOSED UPS
This type of equipment is called uninterruptible power
systems (UPS) and they are extensively used to protect
sensitive loads against a wide variety of utility voltage A. Topology Description
disturbances and power outages. Most of such systems The proposed UPS is shown in Fig. 1. It is composed by
consist in the true on-line UPS configuration. In general, this the following parts: an isolated chopper comprising of the
is the most reliable UPS configuration due to its simplicity, rectifier diodes D1-D4, a high frequency input filter
and the continuous charge of the batteries, which means that comprising of the inductor Lf and capacitors Cf1 and Cf2, a
they are always ready for the next power outage. This kind of controlled full-bridge comprising of the switches S1-S4, a
UPS provides total independence between input and output high frequency transformer Tr, coupled inductors Lr1-Lr2, and
voltage amplitude and frequency, and, thus, high output rectifier diodes Dr1-Dr4; a traditional boost converter
voltage quality can be obtained [1]. comprising of the inductor Lb, switch Sb, diode Db and
Most of true on-line UPS operates with a low frequency capacitor Cb; a full-bridge voltage source inverter (VSI)
transformer using a silicon-steel core. In this configuration, it comprising of the switches S5-S8; and the output filter formed
is normally required an isolating transformer for proper by inductor Lfi and capacitor Cfi. In addition, the waveforms
operation of the bypass circuit and also to improve reliability corresponding to the operation of each stage are indicated in
of the system, since the transformer offers a galvanic this figure.
isolation to the load from undesirable disturbances of the
main supply [2]. Such transformer is placed at the input or
output depending on the topology arrangement. The addition
0 t 0 t 0 t 0 t 0 t
Fig. 2. Operating intervals of the chopper circuit when the input voltage is 110V.
-nILb
t
vcd (rms ) = nVi ( pk )110V (D − ΔD ) (8)
vS1
-Vi where Vcd(rms) is the chopper rms output voltage, and D is the
2Vi
iS1 vS1 nILb duty cycle. The inductor peak current is calculated with
iS1
2 P0
t I Lb ( pk ) ≅ (9)
Vcd (rms )
to t1 t2 t3 t4 t5 t6 t7 t8
where Po is the UPS active output power.
Fig. 3. Main theoretical waveforms when the input voltage is 110V.
IV. ANALYSIS OF THE CHOPPER OPERATION WITH
The duty cycle reduction can be obtained from the
INPUT VOLTAGE EQUAL TO 220V
inductor voltage given by
ΔiL
vL = L , (1) A. Principle of operation
Δt
In this mode, the selector switch SS must be set to the
as the involved parameters are
220V position. The control strategy is the same one used
vL = vi ( pk )110V sin(θ ) (2) when the input voltage is 110V.
Considering the positive semicycle of the input voltage,
ΔiL = 2nILb ( pk ) sin(θ ) (3) during half of the switching period, the converter operation
can be represented by four stages, as shown in Fig. 4, where
Δt = ΔDTS (4)
the theoretical waveforms are shown in Fig. 5. The
L = Lr1 = Lr 2 (5) description of the operation is similar to the case where the
where n is the transformer turns ratio, ILb(pk) is the peak input voltage is 110V.
current through the boost inductor, Vi(pk) is the peak input Although the current flows simultaneously through both
voltage, θ=ωt is the phase angle of the input voltage, and Ts inductors when the chopper operates with 220V, the
is the switching period. equivalent inductance, considering the mutual inductance
Substituting (2)-(5) in (1) results in the following and coupling coefficient nearly unity, is equal to four times
expression: Lr1 or Lr2, i.e., Lreq = 4 Lr1 = 4 Lr 2 .
iS1 iS1
+ +
S3 S1 vS1 S3 S1 vS1
D1 D2 c D1 D2 c
C f1 - C f1 - L
Lf L r1 D r1 D r2 Lf r1 D r1 D r2
220V 220V
iLr1+vLr1 - SS iLr1+ vLr1 -
SS Np Np
M M
Vi I Lb Vi Ns I Lb
110V Ns 110V
Np Np
iLr2 L r2 iLr2 L r2
- vLr2 + - vLr2 +
C f2 C f2
D r3 D r4 D3 D4 D r3 D r4
D3 D4 S2 S4 S2 S4
d d
Fig. 4. Operating intervals of the chopper circuit when the input voltage is 220V.
Ts/2 Ts Db
ILb Lb
c Ls
S1, S 2
DTs t +
S3, S 4 Cs1
t Da1
ΔDTs +
+
vLr1 Vi/2 Vcd Da2 Da3 Cb V bus
iLr1 Sb Cs2
nILb/2
Snubber
t
-
-nILb/2
vLr2 -Vi/2
d
Vi/2
iLr2
nILb/2 Fig. 6. DC/DC converter stage schematic.
t
-nILb/2
VI. BATTERY CHARGER
-Vi/2
vS1 Vi The battery charger is based on a non-isolated buck
iS1 vS1
nILb/2 converter, as shown in Fig. 7. The converter operates in
iS1
continuous conduction mode (CCM) of the current through
t
the filter inductor, and is supplied by the dc link bus voltage.
t0 t1 t2 t3 t4 t5 t6 t7 t8 The implemented charge control strategy is based in one
Fig. 5. Main theoretical waveforms when the input voltage is 220V. voltage and one current control compensator, where, both
operates using the OR logic. In this application the battery is
charged under constant current controlled by the current
V. DC/DC CONVERTER STAGE regulator, then when the battery reaches the fluctuation
voltage, the voltage controller acts to maintain the rated
The boost converter configuration used is shown in Fig. 6. voltage.
The converter choice was made based to its reliable and For this operation only the total battery bank voltage is
easier control implementation based on known control monitored and there isn’t another control to improve battery
techniques. Current mode control were used and health or battery cells voltage equalization.
implemented with the well-known pulse-width modulation
Lb Db
(PWM) IC UC3854B. c BOOST
Fig. 11. Voltage across the chopper stage switch S1. Operation in Fig. 14. Input voltage and current. Operation in 220 Vac.
110 Vac. (Ch1:200V/div.; 10us/div.) (Ch1:100V/div., Ch3:25A/div.; 4ms/div.)
TDHv = 4.41%
TDHi = 7.17%
Fig. 16. Voltage across the boost stage switch Sb. Operation in
220 Vac. (Ch1:100V/div.; 10us/div.)
Fig. 21. Voltage and current in the batteries bank during the
Fig. 18. Output voltage and current of the inverter for non-linear operation in battery mode.
load. Operation in 220 Vac. (Ch1:50V/div., Ch3:50A/div.; 4ms/div.) (Ch4:100V/div., Ch3:25A/div.; 4ms/div.)
Fig. 22. Efficiency and input power factor of the UPS system in
ACKNOWLEDGMENT
grid mode operation as a function of the output power for 110Vac. The authors would like to thank “CM Comandos Lineares
Ltda” due to research financial support with agreement of
MCT (Ministério de Ciência e Tecnologia do Brasil).
REFERENCES