WWW.PRIORITYWIRE.COM Type MC-HL Continuously Welded Armor Cable


Part Number PN M-LIT-CABLEX
©Priority Wire & Cable Novemer 2017
In U.S. 1-800-945-5542 • In Canada 1-877-611-5122
from Priority Wire & Cable
©

CableX
Priority Wire & Cable’s CableX© cables are the answer for industrial and hazardous location
power, instrumentation and control wiring for a wide variety of applications as it can be
CableX© Type MC-HL 16 AWG
installed in direct sunlight, direct buried, in cable trays or raceways and in wet or dry locations.
It is a cost effective alternative to wire in conduit as it has excellent compression and impact
Shielded Pair & Triad with Overall Shield (SP-OS) Class 1
resistance and is impervious to gas and liquid entry due to its continuously welded corrugated Instrumentation Cable MC-HL Aluminum Armor
armor and jacketing.
It is intended for use in petrochemical or oil & gas processing plants, food processing, metals, Application: CableX Control Cable features 16 AWG pairs or triad construction with an overall foil shield and
mining, power generation, pulp & paper, transportation, and other industrial plant settings. drain wire. It is suitable for use in Class I, II & III Division 1 and 2 hazardous locations. This
includes Remote-Control Signaling circuits, or where 600V cable is needed for process control,
instrumentation or computer cable transmitting at levels above 100 mili-volts in circuits where
minimum noise is required. The individual group shields along with the overall shield provide
protection from interference among groups as wells as external interference. It may be installed
indoors or outside, in wet or dry locations and is sunlight resistant and can be direct buried. It
may also be used in cable tray. It is often used in industrial plant settings including oil, gas,
CableX© Type MC-HL 16 AWG petrochemical, chemical, food processing plants, metals, mining, petrochemical, power generation,
pulp & paper, transportation, etc…
Shielded Paired and Triad (OS) Class 1 Conductors: Primary conductors are stranded, soft drawn annealed copper.
Instrumentation Cable MC-HL Aluminum Armor Insulation: Polyvinyl Chloride (PVC), 15 mils plus 4 mils of Nylon, color coded for identification.
Assembly: Pairs or Triads are assembled with a left hand lay, and non-wicking fillers as needed for a round
Application: CableX Control Cable features 16 AWG pairs or triad construction with an overall foil shield and
finish, each with an overlapping aluminum / polyester shield with 7-strand tinned copper drain wire
drain wire. It is suitable for use in Class I, II & III Division 1 and 2 hazardous locations. This
and an overall overlapping cable shield of aluminum / polyester with 7-strand tinned copper drain wire.
includes Remote-Control Signaling circuits, or where 600V cable is needed for process control,
instrumentation or computer cable transmitting at levels above 100 mili-volts in circuits where Inner Jacket: Polyvinyl Chloride (PVC) with rip cord for easy removal.
minimum noise is required. The overall shield provides protection from external interference but Armor: Continuously welded, impervious, corrugated aluminum armor.
not between group interference. It may be installed indoors or outside, in wet or dry locations and Exceeds the grounding requirements of NEC 250.122.
is sunlight resistant and can be direct buried. It may also be used in cable tray. It is often used in
industrial plant settings including oil, gas, petrochemical, chemical, food processing plants, metals, Outer Jacket: Black Polyvinyl Chloride (PVC)
mining, petrochemical, power generation, pulp & paper, transportation, etc… Standards: UL Listed MC Cable
UL Listed as Type MC-HL
Conductors: Primary conductors are stranded, soft drawn annealed copper. UL Listed for cable tray use
Insulation: Polyvinyl Chloride (PVC), 15 mils plus 4 mils of Nylon, color coded for identification UL83, UL1581, UL1569, UL2225
Meets NEC Articles 250-118, 501, 502, 503, 504, 505, and 725 for hazardous locations.
Assembly: Pairs or Triads are assembled left hand lay, with non-wicking fillers as needed for a round
Sunlight Resistant, Direct Burial, Oil Resistant
finish with an overall aluminum / polyester shield with 7-strand tinned copper drain wire.
Inner Jacket: Polyvinyl Chloride (PVC) with rip cord for easy removal. #16AWG - Pairs & Triads (P-OS) Type MC-HL

Armor: Continuously welded, impervious, corrugated aluminum armor. No of No of Inner Jacket Nom Core Armor Outer Jacket Approximate Cross Sectional Approximate Net
Part Number Pairs Triads Thick (mils) O.D. (inches) O.D. (inches) Thick (mils) O.D. (inches) Area (sq in) Weight (lbs/kft)
Exceeds the grounding requirements of NEC 250.122.
16-02PRCCA-SPOS 2 40 0.45 0.67 50 0.76 0.45 234
Outer Jacket: Black Polyvinyl Chloride (PVC) 16-04PRCCA-SPOS 4 50 0.56 0.80 50 0.91 0.65 335
Standards: UL Listed MC Cable 16-06PRCCA-SPOS 6 50 0.66 0.89 50 1.00 0.79 421
UL Listed as Type MC-HL 16-08PRCCA-SPOS 8 50 0.70 0.93 50 1.04 0.85 492
UL Listed for cable tray use 16-10PRCCA-SPOS 10 50 0.79 1.06 50 1.17 1.08 601
UL83, UL1581, UL1569, UL2225 16-12PRCCA-SPOS 12 50 0.85 1.11 50 1.22 1.17 674
Meets NEC Articles 250-118, 501, 502, 503, 504, 505, and 725 for hazardous locations. 16-16PRCCA-SPOS 16 50 0.98 1.29 50 1.40 1.54 842
Sunlight Resistant, Direct Burial, Oil Resistant 16-20PRCCA-SPOS 20 50 1.06 1.34 50 1.45 1.65 977
16-24PRCCA-SPOS 24 50 1.12 1.42 50 1.53 1.84 1118
#16AWG - Single Pair & Triad (SP-OS) Type MC-HL 16-36PRCCA-SPOS 36 50 1.37 1.69 60 1.82 2.60 1586
No of No of Inner Jacket Nom Core Armor Outer Jacket Approximate Cross Sectional Approximate Net 16-50PRCCA-SPOS 50 50 1.57 1.92 60 2.05 3.30 2124
Part Number Pairs Triads Thick (mils) O.D. (inches) O.D. (inches) Thick (mils) O.D. (inches) Area (sq in) Weight (lbs/kft) 16-04TRCCA-STOS 4 50 0.61 0.84 50 0.95 0.71 395
16-01PRCCA-OS 1 66 0.35 0.53 50 0.64 0.32 182 16-08TRCCA-STOS 8 50 0.82 1.06 50 1.17 1.08 637
16-01TRCCA-OS 1 58 0.35 0.53 50 0.64 0.32 190 16-12TRCCA-STOS 12 50 0.98 1.29 50 1.40 1.54 863
16-16TRCCA-STOS 16 50 1.10 1.37 50 1.48 1.72 1058
Conductor No. Base Color 16-24TRCCA-STOS 24 50 1.33 1.64 60 1.78 2.49 1485
1 Black 16-36TRCCA-STOS 36 50 1.58 1.96 60 2.09 3.43 2141
2 White
3 Red 1. Stranded Bare Copper Conductors Conductor No. Base Color 1. Stranded Bare Copper Conductors
2. PVC insulation / Nylon Insulation Jacket 1 Black 2. PVC insulation / Nylon Insulation Jacket
3. Twisted, Shielded Pairs or Triads 3. Twisted, Shielded Pairs or Triads
4. Tinned copper stranded Drain Wire 2 White 4. Tinned copper stranded Drain Wire
3 Red 1 2
2 1 5. Aluminum/Polyester Overlapping Shield for each group 5. Aluminum/Polyester Overlapping Shield for each group 5
7 5 8
6. Aluminum/Polyester Overlapping Shield for Overall Cable 6. Tinned copper stranded Drain Wire for Overall Shield
3 7. Black PVC Jacket 7. Aluminum/Polyester Overlapping Shield for Overall Cable 4 10
TYPE MC-HL (UL) 600V TFN CDRS 9
4 8. Rip Cord for easy Jacket Removal 8. Black PVC Jacket 6
10 9. Continuously Welded Aluminum Armor 9. Rip Cord for easy Jacket Removal 3
6 7 11
8 10. Black PVC Jacket 10. Continuously Welded Aluminum Armor
11. Black PVC Jacket 9
©

CableX
Priority Wire & Cable’s CableX© cables are the answer for industrial and hazardous location
power, instrumentation and control wiring for a wide variety of applications as it can be
CableX© Type MC-HL 16 AWG
installed in direct sunlight, direct buried, in cable trays or raceways and in wet or dry locations.
It is a cost effective alternative to wire in conduit as it has excellent compression and impact
Shielded Pair & Triad with Overall Shield (SP-OS) Class 1
resistance and is impervious to gas and liquid entry due to its continuously welded corrugated Instrumentation Cable MC-HL Aluminum Armor
armor and jacketing.
It is intended for use in petrochemical or oil & gas processing plants, food processing, metals, Application: CableX Control Cable features 16 AWG pairs or triad construction with an overall foil shield and
mining, power generation, pulp & paper, transportation, and other industrial plant settings. drain wire. It is suitable for use in Class I, II & III Division 1 and 2 hazardous locations. This
includes Remote-Control Signaling circuits, or where 600V cable is needed for process control,
instrumentation or computer cable transmitting at levels above 100 mili-volts in circuits where
minimum noise is required. The individual group shields along with the overall shield provide
protection from interference among groups as wells as external interference. It may be installed
indoors or outside, in wet or dry locations and is sunlight resistant and can be direct buried. It
may also be used in cable tray. It is often used in industrial plant settings including oil, gas,
CableX© Type MC-HL 16 AWG petrochemical, chemical, food processing plants, metals, mining, petrochemical, power generation,
pulp & paper, transportation, etc…
Shielded Paired and Triad (OS) Class 1 Conductors: Primary conductors are stranded, soft drawn annealed copper.
Instrumentation Cable MC-HL Aluminum Armor Insulation: Polyvinyl Chloride (PVC), 15 mils plus 4 mils of Nylon, color coded for identification.
Assembly: Pairs or Triads are assembled with a left hand lay, and non-wicking fillers as needed for a round
Application: CableX Control Cable features 16 AWG pairs or triad construction with an overall foil shield and
finish, each with an overlapping aluminum / polyester shield with 7-strand tinned copper drain wire
drain wire. It is suitable for use in Class I, II & III Division 1 and 2 hazardous locations. This
and an overall overlapping cable shield of aluminum / polyester with 7-strand tinned copper drain wire.
includes Remote-Control Signaling circuits, or where 600V cable is needed for process control,
instrumentation or computer cable transmitting at levels above 100 mili-volts in circuits where Inner Jacket: Polyvinyl Chloride (PVC) with rip cord for easy removal.
minimum noise is required. The overall shield provides protection from external interference but Armor: Continuously welded, impervious, corrugated aluminum armor.
not between group interference. It may be installed indoors or outside, in wet or dry locations and Exceeds the grounding requirements of NEC 250.122.
is sunlight resistant and can be direct buried. It may also be used in cable tray. It is often used in
industrial plant settings including oil, gas, petrochemical, chemical, food processing plants, metals, Outer Jacket: Black Polyvinyl Chloride (PVC)
mining, petrochemical, power generation, pulp & paper, transportation, etc… Standards: UL Listed MC Cable
UL Listed as Type MC-HL
Conductors: Primary conductors are stranded, soft drawn annealed copper. UL Listed for cable tray use
Insulation: Polyvinyl Chloride (PVC), 15 mils plus 4 mils of Nylon, color coded for identification UL83, UL1581, UL1569, UL2225
Meets NEC Articles 250-118, 501, 502, 503, 504, 505, and 725 for hazardous locations.
Assembly: Pairs or Triads are assembled left hand lay, with non-wicking fillers as needed for a round
Sunlight Resistant, Direct Burial, Oil Resistant
finish with an overall aluminum / polyester shield with 7-strand tinned copper drain wire.
Inner Jacket: Polyvinyl Chloride (PVC) with rip cord for easy removal. #16AWG - Pairs & Triads (P-OS) Type MC-HL

Armor: Continuously welded, impervious, corrugated aluminum armor. No of No of Inner Jacket Nom Core Armor Outer Jacket Approximate Cross Sectional Approximate Net
Part Number Pairs Triads Thick (mils) O.D. (inches) O.D. (inches) Thick (mils) O.D. (inches) Area (sq in) Weight (lbs/kft)
Exceeds the grounding requirements of NEC 250.122.
16-02PRCCA-SPOS 2 40 0.45 0.67 50 0.76 0.45 234
Outer Jacket: Black Polyvinyl Chloride (PVC) 16-04PRCCA-SPOS 4 50 0.56 0.80 50 0.91 0.65 335
Standards: UL Listed MC Cable 16-06PRCCA-SPOS 6 50 0.66 0.89 50 1.00 0.79 421
UL Listed as Type MC-HL 16-08PRCCA-SPOS 8 50 0.70 0.93 50 1.04 0.85 492
UL Listed for cable tray use 16-10PRCCA-SPOS 10 50 0.79 1.06 50 1.17 1.08 601
UL83, UL1581, UL1569, UL2225 16-12PRCCA-SPOS 12 50 0.85 1.11 50 1.22 1.17 674
Meets NEC Articles 250-118, 501, 502, 503, 504, 505, and 725 for hazardous locations. 16-16PRCCA-SPOS 16 50 0.98 1.29 50 1.40 1.54 842
Sunlight Resistant, Direct Burial, Oil Resistant 16-20PRCCA-SPOS 20 50 1.06 1.34 50 1.45 1.65 977
16-24PRCCA-SPOS 24 50 1.12 1.42 50 1.53 1.84 1118
#16AWG - Single Pair & Triad (SP-OS) Type MC-HL 16-36PRCCA-SPOS 36 50 1.37 1.69 60 1.82 2.60 1586
No of No of Inner Jacket Nom Core Armor Outer Jacket Approximate Cross Sectional Approximate Net 16-50PRCCA-SPOS 50 50 1.57 1.92 60 2.05 3.30 2124
Part Number Pairs Triads Thick (mils) O.D. (inches) O.D. (inches) Thick (mils) O.D. (inches) Area (sq in) Weight (lbs/kft) 16-04TRCCA-STOS 4 50 0.61 0.84 50 0.95 0.71 395
16-01PRCCA-OS 1 66 0.35 0.53 50 0.64 0.32 182 16-08TRCCA-STOS 8 50 0.82 1.06 50 1.17 1.08 637
16-01TRCCA-OS 1 58 0.35 0.53 50 0.64 0.32 190 16-12TRCCA-STOS 12 50 0.98 1.29 50 1.40 1.54 863
16-16TRCCA-STOS 16 50 1.10 1.37 50 1.48 1.72 1058
Conductor No. Base Color 16-24TRCCA-STOS 24 50 1.33 1.64 60 1.78 2.49 1485
1 Black 16-36TRCCA-STOS 36 50 1.58 1.96 60 2.09 3.43 2141
2 White
3 Red 1. Stranded Bare Copper Conductors Conductor No. Base Color 1. Stranded Bare Copper Conductors
2. PVC insulation / Nylon Insulation Jacket 1 Black 2. PVC insulation / Nylon Insulation Jacket
3. Twisted, Shielded Pairs or Triads 3. Twisted, Shielded Pairs or Triads
4. Tinned copper stranded Drain Wire 2 White 4. Tinned copper stranded Drain Wire
3 Red 1 2
2 1 5. Aluminum/Polyester Overlapping Shield for each group 5. Aluminum/Polyester Overlapping Shield for each group 5
7 5 8
6. Aluminum/Polyester Overlapping Shield for Overall Cable 6. Tinned copper stranded Drain Wire for Overall Shield
3 7. Black PVC Jacket 7. Aluminum/Polyester Overlapping Shield for Overall Cable 4 10
TYPE MC-HL (UL) 600V TFN CDRS 9
4 8. Rip Cord for easy Jacket Removal 8. Black PVC Jacket 6
10 9. Continuously Welded Aluminum Armor 9. Rip Cord for easy Jacket Removal 3
6 7 11
8 10. Black PVC Jacket 10. Continuously Welded Aluminum Armor
11. Black PVC Jacket 9
CableX© Type MC-HL (XHHW-2)
600V Control Cable MC-HL Aluminum Armor
Application: CableX Control Cable features 2 to 37 conductors in 14, 12, and 10 AWG sizes. With non-wicking, Insulation Ground Core. Armor Jacket Approx. Cross Approx.
non-hygroscopic fillers, a binder tape then continuously welded aluminum armor with a PVC jacket Cond Size # of Thick # of Size O.D. O.D. Thick Overall Section Net Ampacity
making the cable impervious to environmental penetration. CableX Type MC-HL is suitable for use Part Number (AWG) Cond (mils) Grounds G H (in) (mils) O.D. (in) Area (sq in) Wt 90C - Wet
in Class I, II & III Division 1 and 2 hazardous locations making it a cost effective alternative to cable 14-02CCA600V+1G 14 (7 str) 2 30 1 14 (7 str) 0.28 0.49 50 0.60 0.28 142 15
and rigid conduit. It is perfect for use on feeders, branch circuits or services for signaling circuits, 14-03CCA600V+1G 14 (7 str) 3 30 1 14 (7 str) 0.30 0.49 50 0.60 0.32 153 15
power, lighting, and control. It may be installed indoors or outside, in wet or dry locations and is 14-04CCA600V+1G 14 (7 str) 4 30 1 14 (7 str) 0.33 0.53 50 0.64 0.36 181 15
sunlight resistant and can be direct buried. It may also be used in cable tray. It is often used in 14-05CCA600V+1G 14 (7 str) 5 30 1 14 (7 str) 0.37 0.58 50 0.69 0.41 210 15
industrial plant settings including oil, gas, petrochemical, chemical, food processing plants, metals, 14-06CCA600V+1G 14 (7 str) 6 30 1 14 (7 str) 0.41 0.62 50 0.73 0.46 254 15
mining, petrochemical, power generation, pulp & paper, transportation, etc… 14-08CCA600V+1G 14 (7 str) 8 30 1 14 (7 str) 0.50 0.71 50 0.82 0.57 308 15
14-11CCA600V+1G 14 (7 str) 11 30 1 14 (7 str) 0.57 0.8 50 0.91 0.71 381 12
Conductors: Primary conductors are stranded, soft drawn annealed copper. 14-18CCA600V+1G 14 (7 str) 18 30 1 14 (7 str) 0.69 0.93 50 1.04 0.84 537 12
Insulation: Cross-linked polyethylene, color coded for identification per ICEA Method 1.E-2 for sizes 14-36CCA600V+1G 14 (7 str) 36 30 1 14 (7 str) 0.96 1.24 50 1.35 1.43 946 10
6 and smaller. Sizes 4 and larger are surface printed with numbers and colors per ICEA 12-02CCA600V+1G 12 (7 str) 2 30 1 12 (7 str) 0.31 0.53 50 0.64 0.32 164 20
12-03CCA600V+1G 12 (7 str) 3 30 1 12 (7 str) 0.34 0.53 50 0.64 0.32 189 20
Method 3.
12-04CCA600V+1G 12 (7 str) 4 30 1 12 (7 str) 0.38 0.58 50 0.69 0.38 226 20
Armor: Continuously welded, impervious, corrugated aluminum armor. 12-05CCA600V+1G 12 (7 str) 5 30 1 12 (7 str) 0.42 0.62 50 0.73 0.42 262 20
Exceeds the grounding requirements of NEC 250.122. 12-06CCA600V+1G 12 (7 str) 6 30 1 12 (7 str) 0.47 0.67 50 0.78 0.48 324 20
1
Jacket: Black Polyvinyl Chloride (PVC). 12-08CCA600V+1G 12 (7 str) 8 30 1 12 (7 str) 0.56 0.8 50 0.91 0.65 405 20
12-11CCA600V+1G 12 (7 str) 11 30 1 12 (7 str) 0.65 0.89 50 0.99 0.79 503 15
Standards: UL Listed MC Cable 12-18CCA600V+1G 12 (7 str) 18 30 1 12 (7 str) 0.78 1.02 50 1.13 1.00 721 15
UL Listed as Type MC-HL 12-36CCA600V+1G 12 (7 str) 36 30 1 12 (7 str) 1.08 1.37 50 1.48 1.72 1301 12
UL Listed for cable tray use 10-02CCA600V+1G 10 (7 str) 2 30 1 10 (7 str) 0.36 0.58 50 0.69 0.38 202 30
UL44, UL1581, UL1569, UL2225 10-03CCA600V+1G 10 (7 str) 3 30 1 10 (7 str) 0.39 0.58 50 0.69 0.38 238 30
Meets NEC Articles 250-118, 501, 502, 503, 505, 10-04CCA600V+1G 10 (7 str) 4 30 1 10 (7 str) 0.44 0.67 50 0.78 0.48 297 30
725 for hazardous locations. 2 10-06CCA600V+1G 10 (7 str) 6 30 1 10 (7 str) 0.48 0.71 50 0.82 0.53 348 30
Sunlight Resistant, Direct Burial, Oil Resistant 10-08CCA600V+1G 10 (7 str) 8 30 1 10 (7 str) 0.54 0.75 50 0.86 0.58 436 28
3 10-11CCA600V+1G 10 (7 str) 11 30 1 10 (7 str) 0.74 0.89 50 1.00 0.79 544 28
1. Stranded bare copper conductors
2. Cross-linked polyethylene insulation
3. Non-wicking fillers
4. Binder tape Conductor Base Tracer Conductor Base Tracer Conductor Base Tracer
5. Continuously welded aluminum armor 4 Number Color Color Number Color Color Number Color Color
6. Black PVC jacket
1 Black - 13 Blue Red 25 Yellow Orange
2 Red - 14 Orange Red 26 Brown Orange
3 Blue - 15 Yellow Red 27 Black Yellow
4 Orange - 16 Brown Red 28 Red Yellow
5 Yellow - 17 Black Blue 29 Blue Yellow
6 Brown - 18 Red Blue 30 Orange Yellow
7 Red Black 19 Orange Blue 31 Brown Yellow
8 Blue Black 20 Yellow Blue 32 Black Brown
9 Orange Black 21 Brown Blue 33 Red Brown
10 Yellow Black 22 Black Orange 34 Blue Brown
5 11 Brown Black 23 Red Orange 35 Orange Brown
12 Black Red 24 Blue Orange 36 Yellow Brown
Ground Conductor is Green 37 Black -

WWW.PRIORITYWIRE.COM
600V (UL) XHHW-2

We have a full line of Industrial Cable products


including Instrumentation, Control, 20/10 Control Cables,
Thermocouple, High Temp (MG, TGGT, SRML) and
others, call us at 1-800-945-5542 for your quotes on
specialty wire.
CableX© Type MC-HL (XHHW-2)
600V Control Cable MC-HL Aluminum Armor
Application: CableX Control Cable features 2 to 37 conductors in 14, 12, and 10 AWG sizes. With non-wicking, Insulation Ground Core. Armor Jacket Approx. Cross Approx.
non-hygroscopic fillers, a binder tape then continuously welded aluminum armor with a PVC jacket Cond Size # of Thick # of Size O.D. O.D. Thick Overall Section Net Ampacity
making the cable impervious to environmental penetration. CableX Type MC-HL is suitable for use Part Number (AWG) Cond (mils) Grounds G H (in) (mils) O.D. (in) Area (sq in) Wt 90C - Wet
in Class I, II & III Division 1 and 2 hazardous locations making it a cost effective alternative to cable 14-02CCA600V+1G 14 (7 str) 2 30 1 14 (7 str) 0.28 0.49 50 0.60 0.28 142 15
and rigid conduit. It is perfect for use on feeders, branch circuits or services for signaling circuits, 14-03CCA600V+1G 14 (7 str) 3 30 1 14 (7 str) 0.30 0.49 50 0.60 0.32 153 15
power, lighting, and control. It may be installed indoors or outside, in wet or dry locations and is 14-04CCA600V+1G 14 (7 str) 4 30 1 14 (7 str) 0.33 0.53 50 0.64 0.36 181 15
sunlight resistant and can be direct buried. It may also be used in cable tray. It is often used in 14-05CCA600V+1G 14 (7 str) 5 30 1 14 (7 str) 0.37 0.58 50 0.69 0.41 210 15
industrial plant settings including oil, gas, petrochemical, chemical, food processing plants, metals, 14-06CCA600V+1G 14 (7 str) 6 30 1 14 (7 str) 0.41 0.62 50 0.73 0.46 254 15
mining, petrochemical, power generation, pulp & paper, transportation, etc… 14-08CCA600V+1G 14 (7 str) 8 30 1 14 (7 str) 0.50 0.71 50 0.82 0.57 308 15
14-11CCA600V+1G 14 (7 str) 11 30 1 14 (7 str) 0.57 0.8 50 0.91 0.71 381 12
Conductors: Primary conductors are stranded, soft drawn annealed copper. 14-18CCA600V+1G 14 (7 str) 18 30 1 14 (7 str) 0.69 0.93 50 1.04 0.84 537 12
Insulation: Cross-linked polyethylene, color coded for identification per ICEA Method 1.E-2 for sizes 14-36CCA600V+1G 14 (7 str) 36 30 1 14 (7 str) 0.96 1.24 50 1.35 1.43 946 10
6 and smaller. Sizes 4 and larger are surface printed with numbers and colors per ICEA 12-02CCA600V+1G 12 (7 str) 2 30 1 12 (7 str) 0.31 0.53 50 0.64 0.32 164 20
12-03CCA600V+1G 12 (7 str) 3 30 1 12 (7 str) 0.34 0.53 50 0.64 0.32 189 20
Method 3.
12-04CCA600V+1G 12 (7 str) 4 30 1 12 (7 str) 0.38 0.58 50 0.69 0.38 226 20
Armor: Continuously welded, impervious, corrugated aluminum armor. 12-05CCA600V+1G 12 (7 str) 5 30 1 12 (7 str) 0.42 0.62 50 0.73 0.42 262 20
Exceeds the grounding requirements of NEC 250.122. 12-06CCA600V+1G 12 (7 str) 6 30 1 12 (7 str) 0.47 0.67 50 0.78 0.48 324 20
1
Jacket: Black Polyvinyl Chloride (PVC). 12-08CCA600V+1G 12 (7 str) 8 30 1 12 (7 str) 0.56 0.8 50 0.91 0.65 405 20
12-11CCA600V+1G 12 (7 str) 11 30 1 12 (7 str) 0.65 0.89 50 0.99 0.79 503 15
Standards: UL Listed MC Cable 12-18CCA600V+1G 12 (7 str) 18 30 1 12 (7 str) 0.78 1.02 50 1.13 1.00 721 15
UL Listed as Type MC-HL 12-36CCA600V+1G 12 (7 str) 36 30 1 12 (7 str) 1.08 1.37 50 1.48 1.72 1301 12
UL Listed for cable tray use 10-02CCA600V+1G 10 (7 str) 2 30 1 10 (7 str) 0.36 0.58 50 0.69 0.38 202 30
UL44, UL1581, UL1569, UL2225 10-03CCA600V+1G 10 (7 str) 3 30 1 10 (7 str) 0.39 0.58 50 0.69 0.38 238 30
Meets NEC Articles 250-118, 501, 502, 503, 505, 10-04CCA600V+1G 10 (7 str) 4 30 1 10 (7 str) 0.44 0.67 50 0.78 0.48 297 30
725 for hazardous locations. 2 10-06CCA600V+1G 10 (7 str) 6 30 1 10 (7 str) 0.48 0.71 50 0.82 0.53 348 30
Sunlight Resistant, Direct Burial, Oil Resistant 10-08CCA600V+1G 10 (7 str) 8 30 1 10 (7 str) 0.54 0.75 50 0.86 0.58 436 28
3 10-11CCA600V+1G 10 (7 str) 11 30 1 10 (7 str) 0.74 0.89 50 1.00 0.79 544 28
1. Stranded bare copper conductors
2. Cross-linked polyethylene insulation
3. Non-wicking fillers
4. Binder tape Conductor Base Tracer Conductor Base Tracer Conductor Base Tracer
5. Continuously welded aluminum armor 4 Number Color Color Number Color Color Number Color Color
6. Black PVC jacket
1 Black - 13 Blue Red 25 Yellow Orange
2 Red - 14 Orange Red 26 Brown Orange
3 Blue - 15 Yellow Red 27 Black Yellow
4 Orange - 16 Brown Red 28 Red Yellow
5 Yellow - 17 Black Blue 29 Blue Yellow
6 Brown - 18 Red Blue 30 Orange Yellow
7 Red Black 19 Orange Blue 31 Brown Yellow
8 Blue Black 20 Yellow Blue 32 Black Brown
9 Orange Black 21 Brown Blue 33 Red Brown
10 Yellow Black 22 Black Orange 34 Blue Brown
5 11 Brown Black 23 Red Orange 35 Orange Brown
12 Black Red 24 Blue Orange 36 Yellow Brown
Ground Conductor is Green 37 Black -

WWW.PRIORITYWIRE.COM
600V (UL) XHHW-2

We have a full line of Industrial Cable products


including Instrumentation, Control, 20/10 Control Cables,
Thermocouple, High Temp (MG, TGGT, SRML) and
others, call us at 1-800-945-5542 for your quotes on
specialty wire.
CableX© Type MC-HL (XHHW-2)
600V Power MC-HL Cable Aluminum Armor
Application: CableX Power Cable features three (with three individual grounds) or four conductor configurations Insulation Ground Core Armor Jacket Approx. Cross Approx. Ampacity
(with three or single ground – see chart) with non-wicking, non-hygroscopic fillers, a binder tape Cond Size # of Thick Cond. O.D. O.D. Thick Overall Section Net Wt 90C -
Part Number (AWG) Cond (mils) (AWG) (in) (in) (mils) O.D. (in) Area (sq in) (lbs/kft) Wet or Dry
then continuously welded aluminum armor with a PVC jacket making the cable impervious to
environmental penetration. CableX Type MC-HL is suitable for use in Class I, II & III Division 1 14-03CCA600V-3G 14 3 30 3#18 0.33 0.53 50 0.64 0.32 160 15
and 2 hazardous locations making it a cost effective alternative to cable and rigid conduit. It is 14-04CCA600V-3G 14 4 30 3#18 0.37 0.58 50 0.69 0.37 222 15
perfect for use on feeders, branch circuits or services for signaling circuits, power, lighting, and 12-03CCA600V-3G 12 3 30 3#16 0.37 0.58 50 0.69 0.37 239 20
control. It may be installed indoors or outside, in wet or dry locations and is sunlight resistant and 12-04CCA600V-3G 12 4 30 3#16 0.45 0.67 50 0.78 0.47 286 20
can be direct buried. It may also be used in cable tray. It is often used in industrial plant settings 10-03CCA600V-3G 10 3 30 3#14 0.41 0.62 50 0.73 0.42 300 30
including oil, gas, petrochemical, chemical, food processing plants, metals, mining, petrochemical, 10-04CCA600V-3G 10 4 30 3#14 0.45 0.67 50 0.78 0.47 348 30
power generation, pulp & paper, transportation, etc… 8-03CCA600V-3G 8 3 45 3#12 0.50 0.71 50 0.81 0.52 385 55
8-04CCA600V-1G 8 4 45 1#10 0.58 0.8 50 0.9 0.64 465 44
6-03CCA600V-3G 6 3 45 3#12 0.58 0.8 50 0.9 0.64 525 75
Conductors: Primary and grounding conductors are stranded, soft drawn annealed copper. 6-04CCA600V-1G 6 4 45 1#8 0.66 0.89 50 0.99 0.77 630 60
Grounding conductors are bare copper. 4-03CCA600V-3G 4 3 45 3#12 0.68 0.89 50 0.99 0.77 704 95
Insulation: Cross-linked polyethylene, color coded for identification per ICEA Method 1.E-2 for sizes 4-04CCA600V-1G 4 4 45 1#8 0.77 0.97 50 1.08 0.92 845 76
6 and smaller. Sizes 4 and larger are surface printed with numbers and colors per ICEA 2-03CCA600V-3G 2 3 45 3#10 0.80 1.02 50 1.12 1 995 130
Method 3. 2-04CCA600V-1G 2 4 45 1#6 0.92 1.15 50 1.26 1.25 1245 104
1-03CCA600V-3G 1 3 55 3#10 0.92 1.15 50 1.26 1.25 1100 150
Armor: Continuously welded, impervious, corrugated aluminum armor. 1-04CCA600V-1G 1 4 55 1#6 1.04 1.29 50 1.4 1.54 1500 120
Exceeds the grounding requirements of NEC 250.122. 1
1/0-03CCA600V-3G 1/0 (19str) 3 55 3#10 1.00 1.24 50 1.34 1.41 1470 170
Jacket: Black Polyvinyl Chloride (PVC). 1/0-04CCA600V-1G 1/0 (19str) 4 55 1#6 1.12 1.37 50 1.48 1.72 1830 136
2/0-03CCA600V-3G 2/0 (19str) 3 55 3#10 1.09 1.34 50 1.44 1.63 1770 195
Standards: UL Listed MC Cable 3 2/0-04CCA600V-1G 2/0 (19str) 4 55 1#6 1.23 1.51 60 1.64 2.11 2310 156
UL Listed as Type MC-HL 4/0-03CCA600V-3G 4/0 (19str) 3 55 3#8 1.33 1.6 60 1.73 - 2675 260
UL Listed for cable tray use 4/0-04CCA600V-1G 4/0 (19str) 4 55 1#4 1.49 1.78 60 1.91 - 3430 208
UL44, UL1581, UL1569, UL2225 250-03CCA600V-3G 250 (37str) 3 55 3#8 1.48 1.74 60 1.87 - 3140 290
Meets NEC Articles 250-118, 501, 502, 503, 505, 250-04CCA600V-1G 250 (37str) 4 55 1#4 1.64 1.96 60 2.09 - 4070 232
2
725 for hazardous locations. 350-03CCA600V-3G 350 (37str) 3 55 3#7 1.66 1.96 60 2.09 - 4210 350
Sunlight Resistant, Direct Burial, Oil Resistant 4 350-04CCA600V-1G 350 (37str) 4 55 1#3 1.89 2.19 75 2.35 - 5440 280
500-03CCA600V-3G 500 (37str) 3 55 3#6 1.94 2.28 75 2.44 - 5930 430
Three conductor cables with 3 ground wires are also 500-04CCA600V-1G 500 (37str) 4 55 1#2 2.14 2.49 75 2.65 - 7570 344
excellent for use with variable frequency drives. In addition to 750-03CCA600V-3G 750 (61str) 3 55 3#5 2.37 2.75 75 2.92 - 8700 535
UL, these 3-conductor constructions are also certified to CSA 750-04CCA600V-1G 750 (61str) 4 55 1#1 2.61 3.03 85 3.21 - 11250 428
C22.2 No. 123 and CSA C22.2 No. 174. 5
Conductor No. Base Color
1 Black
1. Stranded bare copper conductors 2 Red
2. Cross-linked polyethylene insulation 3 Blue
3. Bare, stranded copper grounding conductors
4. Non-wicking fillers
4 Orange
5. Binder tape

WWW.PRIORITYWIRE.COM
6. Continuously welded aluminum armor
6
7. Black PVC jacket

We have a full line of Portable Cord Products including


SOOW, SJOW, SEOOW, SJEOOW, Welding Cable,
DLO, Type W, Type P, Type G-GC, and others, call us at
1-800-945-5542 for quotes on any rubber cables.

7
V (UL) XHHW-2
CableX© Type MC-HL (XHHW-2)
600V Power MC-HL Cable Aluminum Armor
Application: CableX Power Cable features three (with three individual grounds) or four conductor configurations Insulation Ground Core Armor Jacket Approx. Cross Approx. Ampacity
(wCableX features three (with three individual grounds) or four conductor configurations (with Cond Size # of Thick Cond. O.D. O.D. Thick Overall Section Net Wt 90C -
Part Number (AWG) Cond (mils) (AWG) (in) (in) (mils) O.D. (in) Area (sq in) (lbs/kft) Wet or Dry
three or single ground – see chart) with non-wicking, non-hygroscopic fillers, a binder tape
then continuously welded aluminum armor with a PVC jacket making the cable impervious to 14-03CCA600V-3G 14 3 30 3#18 0.33 0.53 50 0.64 0.32 160 15
environmental penetration. CableX Type MC-HL is suitable for use in Class I, II & III Division 1 and 14-04CCA600V-3G 14 4 30 3#18 0.37 0.58 50 0.69 0.37 222 15
2 hazardous locations making it a cost effective alternative to cable and rigid conduit. It is perfect 12-03CCA600V-3G 12 3 30 3#16 0.37 0.58 50 0.69 0.37 239 20
for use on feeders, branch circuits or services for signaling circuits, power, lighting, and control. It 12-04CCA600V-3G 12 4 30 3#16 0.45 0.67 50 0.78 0.47 286 20
may be installed indoors or outside, in wet or dry locations and is sunlight resistant and can be 10-03CCA600V-3G 10 3 30 3#14 0.41 0.62 50 0.73 0.42 300 30
direct buried. It may also be used in cable tray. It is often used in industrial plant settings including 10-04CCA600V-3G 10 4 30 3#14 0.45 0.67 50 0.78 0.47 348 30
oil, gas, petrochemical, chemical, food processing plants, metals, mining, petrochemical, power 8-03CCA600V-3G 8 3 45 3#12 0.50 0.71 50 0.81 0.52 385 55
generation, pulp & paper, transportation, etc… 8-04CCA600V-1G 8 4 45 1#10 0.58 0.8 50 0.9 0.64 465 44
6-03CCA600V-3G 6 3 45 3#12 0.58 0.8 50 0.9 0.64 525 75
Conductors: Primary and grounding conductors are stranded, soft drawn annealed copper. 6-04CCA600V-1G 6 4 45 1#8 0.66 0.89 50 0.99 0.77 630 60
Grounding conductors are bare copper. 4-03CCA600V-3G 4 3 45 3#12 0.68 0.89 50 0.99 0.77 704 95
Insulation: Cross-linked polyethylene, color coded for identification per ICEA Method 1.E-2 for sizes 4-04CCA600V-1G 4 4 45 1#8 0.77 0.97 50 1.08 0.92 845 76
6 and smaller. Sizes 4 and larger are surface printed with numbers and colors per ICEA 2-03CCA600V-3G 2 3 45 3#10 0.80 1.02 50 1.12 1 995 130
Method 3. 2-04CCA600V-1G 2 4 45 1#6 0.92 1.15 50 1.26 1.25 1245 104
1-03CCA600V-3G 1 3 55 3#10 0.92 1.15 50 1.26 1.25 1100 150
Armor: Continuously welded, impervious, corrugated aluminum armor. 1-04CCA600V-1G 1 4 55 1#6 1.04 1.29 50 1.4 1.54 1500 120
Exceeds the grounding requirements of NEC 250.122. 1
1/0-03CCA600V-3G 1/0 (19str) 3 55 3#10 1.00 1.24 50 1.34 1.41 1470 170
Jacket: Black Polyvinyl Chloride (PVC). 1/0-04CCA600V-1G 1/0 (19str) 4 55 1#6 1.12 1.37 50 1.48 1.72 1830 136
2/0-03CCA600V-3G 2/0 (19str) 3 55 3#10 1.09 1.34 50 1.44 1.63 1770 195
Standards: UL Listed MC Cable 3 2/0-04CCA600V-1G 2/0 (19str) 4 55 1#6 1.23 1.51 60 1.64 2.11 2310 156
UL Listed as Type MC-HL 4/0-03CCA600V-3G 4/0 (19str) 3 55 3#8 1.33 1.6 60 1.73 - 2675 260
UL Listed for cable tray use 4/0-04CCA600V-1G 4/0 (19str) 4 55 1#4 1.49 1.78 60 1.91 - 3430 208
UL44, UL1581, UL1569, UL2225 250-03CCA600V-3G 250 (37str) 3 55 3#8 1.48 1.74 60 1.87 - 3140 290
Meets NEC Articles 250-118, 501, 502, 503, 505, 250-04CCA600V-1G 250 (37str) 4 55 1#4 1.64 1.96 60 2.09 - 4070 232
2
725 for hazardous locations. 350-03CCA600V-3G 350 (37str) 3 55 3#7 1.66 1.96 60 2.09 - 4210 350
Sunlight Resistant, Direct Burial, Oil Resistant 4 350-04CCA600V-1G 350 (37str) 4 55 1#3 1.89 2.19 75 2.35 - 5440 280
500-03CCA600V-3G 500 (37str) 3 55 3#6 1.94 2.28 75 2.44 - 5930 430
1. Stranded bare copper conductors
2. Cross-linked polyethylene insulation 500-04CCA600V-1G 500 (37str) 4 55 1#2 2.14 2.49 75 2.65 - 7570 344
3. Bare, stranded copper grounding conductors 750-03CCA600V-3G 750 (61str) 3 55 3#5 2.37 2.75 75 2.92 - 8700 535
4. Non-wicking fillers 750-04CCA600V-1G 750 (61str) 4 55 1#1 2.61 3.03 85 3.21 - 11250 428
5. Binder tape 5
6. Continuously welded aluminum armor
7. Black PVC jacket Conductor No. Base Color
1 Black
2 Red
3 Blue
4 Orange

WWW.PRIORITYWIRE.COM
6