Professional Documents
Culture Documents
Cemex 15kV - Manual Interruptor
Cemex 15kV - Manual Interruptor
Cemex 15kV - Manual Interruptor
INSTRUCTION MANUAL
12/15KV 25 kA
NOTES
Description.......................................................................................1
1. Specifications.................................................................................2
Description
The Vitzro tech. vacuum circuit breakers are designed to handle all the switching that
occur primary distribution systems, their energy-storing mechanisms being capable of
triple-pole auto-reclosure.
The vacuum circuit breakers are extremely reliable in service, require only a minimum of
maintenance and long life expectancy.
The vacuum circuit breakers meet the requirements of IEC60056 and ANSI C37.06.
The energy-storing spring mechanism can be supplied for actuation by hand or motor.
The three breaker poles, each with a vacuum interrupter, are mounted on a common
truck housing.
The moving contacts in vacuum interrupters are opened and closed by springs.
In order to ensure the maximum performance and dependable operation, it is suggested
that the operator reads this instruction manual carefully to be well acquainted with all the
features of this vacuum circuit breaker.
Safety precaution
This vacuum circuit breaker uses powerful springs for energy storage.
Do not work on the interrupters and mechanisms unless both the closing
and tripping spring are discharged all electrical source is removed.
1.Specifications
Model No. KVA1625M KVA1125A KVA1225M
40 25
40 20
40
70
50
2- 13 4- 13
C
570
35 302 B
200 200
A
CONTROL PLUG
CHARGE HOLE
CLOSING BUTTON
E
TRIP BUTTON
A
678
M8 BOLT
EARTH
TERMINAL
COUNTER
D
87.5
187.5
ON/OFF INDICATOR
CHARGE/DISCHARGE INDICATOR
8- 13 MOUNTING HOLE
8- 13 MOUNTING HOLE
<Draw-out type>
DETAILS OF TERMINALS
200 200
INSULATION SHUTTER 2- 13
Disconnectiong position
Connecting position
50
(38.5) 180 40 20
"B"
35 <630A>
2- 13
10
70
"D"
40 20
"B"
"A"
<1250A>
(681.2)
2- 13
70
"C"
40 20
30
<2000A>
6- 11
116 329 329 20
(MOUNTING HOLES)
Earth terminal 60
859 115
570 Earth terminal
680
DETAILS OF
(MOUNTING HOLES) EARTHING TERMINAL
800
6
Type KVA 1625M KVA 1125M
Dimension
Spring with A B C D
TYPE 13
Operating mechanism motor reloading
12/15kV 25kA 630A
831 12 365 268
Rated voltage
40
12kV 12/15kV 25kA 1250A
Rated current 630A 1250A 2000A 12/15kV 25kA 2000A 844 25 384 249 40
40
70
40
254±1 254±1
METAL SHUTTER BCT(Option)
Disconnection Connection
250
75
132
12
280±1
830.5
12
359.2±1
4
67.2
1180 915
NOTE)
1. Tolerance : ±2%
4
7
300
301
102
103
201 302
6
202
203
104
2- 4
A
2- 14
2- 3
2- 1 2- 7
2- 9
C 2- 2
2- 14
2- 8
2- 1
☞
2- 8
☞
2- 10
2- 20
2- 24
☞
2- 3
2- 172- 12 Point to be
2- 6
2- 11 2- 23
Iuburicated
2- 4 2- 5
☞
2- 26 2- 19
☞ 2- 13
2- 16 B 2- 22
2- 5 2- 18 2- 25
2- 21
2- 27
Fig.6 Operating mechanism(View A)
Fig.8 Operating mechanism(B- B)
Fig.7 Operating mechanism(Reduction gear)
2- 12
2- 13
2- 14
2- 16
D
☞
D
3- 1 3- 8 3- 7 3- 9 3- 10
3- 7
Arrow D
Fig. 11
Breaker is closed.
Closing spring is
charged.
Fig. 12
Breaker is open.
Closing spring is charged.
Fig.13
Breaker is open.
Closing spring is discharged.
3-3 Interlock mechanism
3-3-1 Construction
The interlock plate fitted to the switchgear stand is provided with two locking
holes. The interlock pin 5-2 fitted to the vacuum circuit breaker is set in the
holes under "Connection" or "Disconnection" condition when the vacuum circuit
breaker is fixed in place.
When the vacuum circuit breaker is closed the lever 5-3 of the interlock pin
5-2 makes contact with the pin 3-5 fitted to the lever of the operating shaft
3-1, whereby the interlock pin 5-2 is locked to prevent the vacuum circuit breaker
from being shifted.
When the vacuum circuit breaker is open, the lever 5-3 is rotating so the
interlock pin 5-2 can be pulled out by menas of the handle 5-5 , allowing
the breaker to be shifted.
When the vacuum circuit breaker is set in the mid-position between "Connect-
ion" and "Disconnection", the interlock pin 5-2 is on the interlock plate and
hence the closing hook 2-24 is locked by the link 5-4 coupled with the interlock
pin 5-2 to prevent the vacuum circuit breaker from being closed.
5- 4
5- 4
5- 2
5- 5
2- 24
3- 1
5- 5
3- 5
LOCKING HOLE
5- 2
INTERLOCK PLATE
Fig. 15
3-4 Accessories
The KVA series vacuum circuit breaker is supplied with standard accessories and
special accessories (supplied on request).
Check all the 1/5 units against the delivery sheet furnished.
Table 3 shows a list of standard accessories, and Table 4 a list of special acc-
essories.
Table 3 Standard accessories
Item Q'ty Application Remarks
Manual charging of
Manual charging handle 1/5 units See 3-2-3
closing spring
Draw-out handle
1/5 units ― See 3-3-2
(for draw-out type)
Refer to
Wiring between internal
Control circuit lead wire 1 set/unit
circuit breaker and cubicle connection
diagram
Measurement of wear
Wipe gauge 1 set/unit
of VI electrode
4-2 Unpacking
It Is recommended unpack the vacuum circuit breaker earlier when it is arrived.
Be careful, not to damage the vacuum circuit breaker especially insulating, vac-
uum interrupters, main circuit connectors and front panel.
4-3 Transportation
L i f t t h e v a c u u m c i r c u i t b r e a k e r by a w i r e l o o p i f n e c e s s a r y .
Don't hold upper conductor 4-3 and lower conductor 4-4 move the vacuum
circuit breaker.
4-5 Storage
It is recommended to put the vacuum circuit breaker into operation as soon as
possible after unpacking.
However, if storage is un-avoidable, the followings shall be observed.
(1) Store unpacked.
(2) Store indoor on flat floor, in clean and dry atmosphere without corrosive gas,
water and dust (especially cement dust).
(3) Cover with plastic sheet to protect dust, dirt, small animals, insects
(especially spiders) from invasion.
(4) Open vacuum circuit breaker and release closing spring.
(2) Dust, dirt and spider web on surface of insulating material, if any clean with
dry clean cloth.
(3) Loss or loose fitting of bolts and damages.
4-7 Installation
(1) Confirm the vacuum circuit breaker is open and closing spring is discharged
with respective mechanical indicator.
(2) Check the vacuum circuit breaker following to the previous Item 4-6.
Item Criteria
MIN. operation voltage Less than 85%
Spring charge
Charging time Less than 10sec
MIN. operation voltage Less than 75%
Closing operation
Charging time Less than 60ms
MIN. operation voltage Less than 60%
Opening operation
Opening time Less than 50ms