Download as pdf or txt
Download as pdf or txt
You are on page 1of 35

CONFIDENTIAL

LEVINE, LECTRONICS AND LECTRIC (L-3), MODULAR UPS WEBINAR, OCTOBER 28TH, 2020

ABB – Power Protection


Advances in Modular UPS
Joergen Madsen, Business Development Director

UPS - History – Topology
Why UPS ?
Critical load requiring constant uninterrupted power

October 29, 2020 Slide 3


Evolution of UPS Technology
1960’s 2020

– Low efficiency < 92% (-) – High efficiency up to 97% (+)


– High input harmonics (-) – Low input harmonics (+)
– Low input PF (-) – High input PF (+)
– Large footprint (-) – Small footprint (+)
– High weight (-) – Less weight (+)
– Galvanic isolation (+) – Grounding (-) 1 MW+
185 kVA

October 29, 2020



History of Static (Solid State) UPS
ECO-Mode with or without xFMR
~ 99%

Silicon Carbide (SiC) with 2-Level


2020 Up to 98% Online (Higher Cost)

Transformer-less UPS
2010 3-level IGBT
95% – 96.5%

2000 Transformer-less UPS


2-level IGBT
90% – 95%
1990
L
L
L1
2
3
IGBT UPS with xFMR
85% – 90% SCR based IGBT based
1980
Transistor UPS with xFRMR
80% – 85% SCR IGBT
1970 Step wave 2-Level PWM 3-Level PWM

SCR UPS with xFRMR


75% – 80%
1960

UPS Configurations - Paralleling
Early Paralleling – need for more Power and Availability

System Control Cabinet

=
=
UPS 1

= =
= =
UPS UPS 2
UPS
=
=
UPS 3
Single UPS Parallel with System Control Cabinet (SCC)
Single points of failure Centralized paralleling

October 29, 2020 Slide 7


Evolution of Parallel Architecture – Centralized to Decentralized
Need for higher availability
▪ SCC with centralized control
logic and centralized Static
=
= Switch represent single
System Control Cabinet UPS 1 points of failure
= ▪ Microprocessors allow
= decentralized (redundant)
UPS 1
= control logic
= = ▪ Paralleling standard single
= UPS 2
UPS systems
UPS 2
▪ Redundancy in bypass as
= well as normal online
= =
UPS 3 = operation
UPS 3
Centralized Paralleling Decentralized Paralleling
(w/SSC) (Paralleling Single UPS’s)

October 29, 2020 Slide 8


UPS design – Monolithic or Modular
UPS Technology - Monolithic (Monoblock) or Modular, Scalable

ABB TLE 500kW UPS ABB DPA 500kW UPS

Monolithic Modular

October 29, 2020 Slide 10


Power Protection – Monolithic UPS’s
Mid Power TLE Series – 40kW to 150kW

Mid Power TLE series


▪ 40 thru 150 kVA, UL
Parallelable to 4 Modules
▪ 480VAC, 3phase, 60Hz
▪ Unity (1.0) Output PF
▪ 3-Level IGBT Rectifier &
Inverter
▪ eBoost Mode, up to 98%
Efficiency
▪ Small footprint
High Power TLE Series – 160kW to 1000kW

TLE series
• 160 thru 1000 kVA, UL
• Parallelable to 6 Modules
• 480VAC 3phase, 60Hz
• Unity (1.0) Output PF
• 3-Level IGBT Rectifier &
1000kW TLE UPS Inverter
• eBoost Mode, up to 99%
Efficiency
• Small footprint

500kW TLE UPS Page #13


ABB MegaFlex UPS – 1100kW to 1600kW

MegaFlex seies
• 1100 thru 1600 kVA, UL
• Parallelable to 4 Modules
• 480VAC 3phase, 60Hz
• Unity (1.0) Output PF
• 3-Level IGBT Rectifier & Inverter
• eBoost Mode, up to 99% Efficiency
• Small footprint
• HRG compatible

400kW DC Boost
AC/DC Cap Assemblies

400kW Rectifier

400kW Inverter

October 29, Slide 14


2020
ABB Standalone (Monolithic) UPS portfolio, 480V

TLE Mid Power Series UL 480V TLE High Power Series, 480 V MegaFlex UL, 480V
Double-conversion online UPS Double-conversion online UPS Double-conversion online UPS
Standalone UPS Standalone UPS Standalone UPS

40 kW – 150 kW 160 kW - 1000 kW 1,100 kW – 1,600 kW

VFI 97% VFI 97% VFI 97%

Note: VFI = Voltage Frequency Independent (Double Conversion Mode)


October 29, 2020 Slide 15
Power Protection – Modular Scalable UPS
Why Modular UPS’s ?

Modular UPS designs

CONCERNS …. ▪ Scalable – pay as you grow


▪ Rightsizing
RELIABILITY ▪ Eliminate stranded capacity
▪ Availability – integrated
redundancy
▪ Serviceability – low MTTR
▪ Flexibility – easily scalable to fit
current power/redundancy need

400kW + 400kW = 400kW N+1 Modular 5x100kW = 400kW N+1

October 29, 2020 Slide 17


Modular UPS (Gen 1) – Centralized design

Centralized Modular UPS

CONCERNS …. ▪ Traditional modular UPS design


▪ All control logic, static switch
etc., centralized in UPS frame
▪ UPS frame is system control
RELIABILITY
cabinet (SCC)
▪ Several single points of failure

October 29, 2020 Slide 18


Evolution of Modular UPS (Gen 2)
Decentralized Parallel Architecture (DPA)

Decentralized Modular UPS

CONCERNS …. ▪ All control logic, static switch


etc., in each power module
▪ Power module is a complete UPS
▪ Passive frame design
RELIABILITY
▪ High availability
▪ Eliminates single points of
failure
▪ Perfect load sharing
▪ Any UPS can be the logic leader
(multi-master system)

October 29, 2020 Slide 19


All about redundancy – eliminate single point of failure

If the demanded function is fly,


redundancy means:
CONCERNS ….
▪ Three (3) engines can fail, and
Single point of failure the demanded function is
maintained
RELIABILITY
REDUNDANCY N+3
▪ If one wing fails, the demanded
function is not maintained
NO REDUNDANCY

October 29, 2020 Slide 20


ABB DPA Power Module – Complete UPS
Bypass input

Rectifier input = Output


=
=
=

ABB DPA UPS Module

Each Power Module is a complete UPS:


• IGBT rectifier and inverter
20kW, 208V UPS Module • Control logic and display
100kW, 480V UPS Module
• Battery converter
• Static bypass switch
• Display/User interface
• Built-in back-feed protection

October 29, 2020 Slide 21


Modular UPS - DPA 120, 208V – 20kW to 120kW (or 100kW N+1)

20kW Power Module (UPS)

Normal operating mode on-line double conversion


Input/Output Voltage 208 V
Input Frequency 60 Hz
Input Configuration 3w + N + GND
Maximum power per cabinet 120 kW (100 kW N+1 )
System Power Range Up to 600 kW (5 cabinets)
Output power factor 1
Efficiency in double conversion up to 94 %
Input current distortion THDI <4%
Input power factor (PF) 0.99
Safety/ Compliance UL 1778 UPS Systems 5th Edition; CSA
IEC 62040-2 Category 3 Emissions
C.22.2 No. 107.3 UPS Systems

October 29, Confidential. Not to be copied, distributed, or reproduced without prior approval.
Slide 22
2020
Modular UPS - DPA 120, 208V – 20kW to 120kW (or 100kW N+1)

Integrate it into
a frame…

…Simple as a
mouse click

October 29, Confidential. Not to be copied, distributed, or reproduced without prior approval.
Slide 23
2020
Modular UPS - DPA 60, 208V – 20kW to 60kW (or 40kW N+1)
Internal Battery

20kW Power Module (UPS)

Normal operating mode on-line double conversion


Input/Output Voltage 208 V
Input Frequency 60 Hz
Input Configuration 3w + N + GND
Maximum power per cabinet 60 kW (40 kW N+1 )
System Power Range Up to 300 kW (5 cabinets)
Output power factor 1
Efficiency in double conversion up to 94 %
Input current distortion THDI <4%
Input power factor (PF) 0.99
Safety/ Compliance UL 1778 UPS Systems 5th Edition; CSA
IEC 62040-2 Category 3 Emissions
C.22.2 No. 107.3 UPS Systems
October 29, 2020 Slide 24
Modular UPS - DPA 500, 480V – 100kW to 500kW (400kW N+1)

Certification Listings:
UL 1778 UPS Systems 5th Edition
CSA C.22.2 No. 107.3 UPS Systems

Compliance:
IEC 62040-2 Category 3 Emissions

Enclosure Safety Rating:


NEMA Type 1
IP20

Performance:
− Scalable from 100 kW to 500 kW per
cabinet (pay as you grow)
− Scalable from one to six cabinets
300 kW Cabinet
(500kW to 3 MW) (pay as you grow)*
500 kW Cabinet − Double conversion mode (AC/AC)
efficiency > 96% from 50-100% load
− Optional 100 kA short circuit
withstand rating (65 kA standard)

100 kW Power Module (UPS)


October 29, 2020 Slide 25 Confidential. Not to be copied, distributed, or reproduced without prior approval.
One line – ABB Modular Scalable UPS (DPA 500)

October 29, 2020 Slide 26


ABB Modular UPS portfolio, 208V and 480V
100 kW Power Module (UPS)
20kW Power Module (UPS)

DPA 60 UL, 208V DPA 120 UL, 208V DPA 300 UL, 480 V DPA 500 UL, 480V
Double-conversion online UPS Double-conversion online UPS, Double-conversion online UPS Double-conversion online UPS
Modular – Built-in Battery Modular Modular Modular
20 kW – 60 kW 20 kW – 120 kW 100 kW – 300 kW 100 kW – 500 kW
VFI 94% VFI 94% VFI 97% VFI 97%

Note: VFI = Voltage Frequency Independent (Double Conversion Mode)


October 29, 2020 Slide 27 Customer Presentation
UPS User Interface & Communication
DPA UPS - User interface

System Display 7” touchscreen display (one per frame)


DPA display (or module display) 2 x 20 character LCD display (one per module)
MIMIC diagram LED-indicator, 5x green/red LEDS (one per module)
RS232 on Sub-D9 port
For monitoring and integration in network management
RS232 on USB port
1 Remote Shut down [EMERGENCY OFF (Normally closed)]
Customer Interfaces : Inputs 1 GEN-ON (Normally open)
DRY PORT 1 Programmable Customer’s Inputs (Normally open)
1 Temp. Sensor for Battery Control
Customer Interfaces : Outputs 6 voltage free contacts
System/UPS Cabinet Display DRY PORT For remote signaling and automatic computer shutdown

Remote monitoring system with remote panel (graphical


RS485 on RJ45 port Optional
display)

RS485 on RJ45 port For multidrop purpose Optional


SNMP card
Slot for SNMP Optional
For monitoring and integration in network management

Power Module Display


October 29, Confidential. Not to be copied, distributed, or reproduced without prior approval.
Slide 29
2020
DPA UPS - Customer connections Customer Interface Board

October 29, 2020 Slide 30 Confidential. Not to be copied, distributed, or reproduced without prior approval.
DPA UPS Connectivity options
DATA PROTECTION - CLIENT DATA MONITORING AND MANAGEMENT

Shutdown service Web browser, Remote View, BMS

E-mails

LAN

SMS Selection of connectivity options including:

− Modbus (SNMP cards)

− Profibus Kit

− BacNet Kit
NETWORK INTERFACE CARD
AND SOFTWARE

October 29, Confidential. Not to be copied, distributed, or reproduced without prior approval.
Slide 31
2020
ABB Modular UPS – Summing up
DPA - Integrated Redundant Modular UPS architecture
Decentralized architecture eliminates single points of failure

DPA Modular UPS


Decentralized Parallel Architecture™ ▪ Flexibility – easily scalable to
fit current and future needs
▪ Integrated Redundant
▪ Online-swap modularity (OSM)
▪ Serviceability – low MTTR
▪ Scalable – 100kW to 3MW
• Pay as you grow
• Rightsizing
• Eliminate stranded capacity

October 29, 2020 Slide 33


Modular UPS Paralleling – Two-dimensional scalability

Vertical scalability
CONCERNS ….
1 – 5 modules in one
single cabinet

RELIABILITY

Horizontal scalability
Cabinets in parallel
configuration up to 3MW

October 29, 2020 Slide 34


Thank You
Questions ?

Joergen Madsen
Business Development Manager
ABB Power Protection
Phone: +1 518 381 0750
Email: joergen.madsen@us.abb.com

October 29, 2020 Slide 35

You might also like