1. BEFORE INSTALLATION
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
• Be sure to read “THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY” before installing the air conditioner.
• Be sure to observe the warnings and cautions specified here as they include important items related to safety.
• After reading this manual, be sure to keep it together with the OPERATING INSTRUCTIONS for future reference.
WARNING (Could lead to death, serious injury, etc.)
N Do not install the unit by yourself (user). extend the wires, or use intermediate connection. N Do not discharge the refrigerant into the atmosphere. If
Incomplete installation could cause fire or electric Incomplete connecting and securing could cause fire. refrigerant leaks during installation, ventilate the room.
shock, injury due to the unit falling, or leakage of water. N Do not install the unit in a place where inflammable If refrigerant comes in contact with a fire, harmful gas
Consult the dealer from whom you purchased the unit gas may leak. could be generated.
or a qualified installer. If gas leaks and accumulates in the area around the N Check that the refrigerant gas does not leak after
N Perform the installation securely referring to the unit, it could cause an explosion. installation has been completed.
installation manual. N Do not use intermediate connection of the power If refrigerant gas leaks indoors, and comes into contact
Incomplete installation could cause fire or electric cord or the extension cord and do not connect with the flame of a fan heater, space heater, stove, etc.,
shock, injury due to the unit falling, or leakage of water. many devices to one AC outlet. harmful substances will be generated.
N Install the unit securely in a place which can bear It could cause a fire or an electric shock due to defec- N Use appropriate tools and piping materials for installation.
the weight of the unit. tive contact, defective insulation, exceeding the permis- The pressure of R410A is 1.6 times more than R22.
If the installation location cannot bear the weight of the sible current, etc. Not using appropriate tools or materials and incomplete
unit, the unit could fall causing injury. N Be sure to use the parts provided or specified parts installation could cause the pipes to burst or injury.
N Electrical work should be performed by a qualified, for the installation work. N When pumping down the refrigerant, stop the com-
experienced electrician, according to the installation The use of defective parts could cause an injury or leakage pressor before disconnecting the refrigerant pipes.
manual. Be sure to use an exclusive circuit. Do not of water due to a fire, an electric shock, the unit falling, etc. If the refrigerant pipes are disconnected while the compres-
connect other electrical appliances to the circuit. N When plugging the power supply plug into the outlet, sor is running and the stop valve is open, air could be drawn
If the capacity of the power circuit is insufficient or there make sure that there is no dust, clogging, or loose in and the pressure in the refrigeration cycle could become
is incomplete electrical work, it could result in a fire or parts in both the outlet and the plug. Make sure that the abnormally high. This could cause the pipes to burst or injury.
an electric shock. power supply plug is pushed completely into the outlet. N When installing the unit, securely connect the re-
N Earth the unit correctly. If there is dust, clogging, or loose parts on the power sup- frigerant pipes before starting the compressor.
Do not connect the earth to a gas pipe, water pipe, light- ply plug or the outlet, it could cause electric shock or fire. If If the compressor is started before the refrigerant pipes
ning rod or telephone earth. Defective earthing could loose parts are found on the power supply plug, replace it. are connected and when the stop valve is open, air
cause electric shock. N Attach the electrical cover to the indoor unit and the could be drawn in and the pressure in the refrigeration
N Do not damage the wires by applying excessive service panel to the outdoor unit securely. cycle could become abnormally high. This could cause
pressure with parts or screws. If the electrical cover of the indoor unit and/or the service the pipes to burst or injury.
Damaged wires could cause fire or electric shock. panel of the outdoor unit are not attached securely, it could N Fasten a flare nut with a torque wrench as specified
N Be sure to cut off the main power in case of setting result in a fire or an electric shock due to dust, water, etc. in this manual.
up the indoor P.C. board or wiring works. N When installing or relocating the unit, make sure If fastened too tight, a flare nut may break after a long
Failure to do so could cause electric shock. that no substance other than the specified refriger- period and cause refrigerant leakage.
N Use the specified wires to connect the indoor and ant (R410A) enters the refrigerant circuit. N The unit shall be installed in accordance with na-
outdoor units securely and attach the wires firmly to Any presence of foreign substance such as air can tional wiring regulations.
the terminal block connecting sections so the stress cause abnormal pressure rise and may result in explo-
of the wires is not applied to the sections. Do not sion or injury.
CAUTION (Could lead to serious injury in particular environments when operated incorrectly.)
N Install an earth leakage breaker depending on the If there is defect in the drainage/piping work, water N Do not install the outdoor unit where small animals
installation place. could drop from the unit, soaking and damaging house- may live.
If an earth leakage breaker is not installed, it could hold goods. If small animals enter and touch the electric parts inside
cause electric shock. N Do not touch the air inlet or the aluminum fins of the unit, it could cause a malfunction, smoke emission,
N Perform the drainage/piping work securely accord- the outdoor unit. or fire. Also, advise user to keep the area around the
ing to the installation manual. This could cause injury. unit clean.
54 mm or more/
<Indoor unit> wire (A) from contacting Wall hole
100 m
metal parts in the wall and sleeve (C)
(using spacer)
m Fix the pipe to wall
or mo
(1) Installation plate 1 re to prevent damage by with pipe fixing
Installation plate fixing screw rodents in case the wall is band (E).
(2) 5 hollow.
4 × 25 mm Cut off the
110 m Pipe fixing band
(3) Remote controller holder 1 or mo m After the leak test, apply extra length. (E)
re insulating material tightly
Fixing screw for (3) 3.5 × 16 mm Fixing screw
(4) 2 so that there is no gap.
(Black) (F)
When the piping is to be at-
(5) Battery (AAA) for (6) 2
tached to a wall containing Outdoor unit installation (GE25, 33, 35 ,42/GE50)
(6) Wireless remote controller 1 metals (tin plated) or metal 800/840 mm
Felt tape netting, use a chemically 150/169
(7) 1 500 mm
(For left or left-rear piping) treated wooden piece 20 mm
mm or thicker between the Air inlet
304-325/360 mm
(8) Air cleaning filter 2
wall and the piping or wrap
344.5/392 mm
285/330 mm
<Outdoor unit> 7 to 8 turns of insulation vi-
nyl tape around the piping.
10 mm or more
(9) Drain socket (VA type only) 1
To use existing piping, per-
(10) Drain cap ø 33 (GE50VA only) 2 form COOL operation for
PARTS TO BE PROVIDED 30 minutes and pump down Air outlet
AT YOUR SITE before removing the old air 2/4-10 mm × 21mm slot 40 mm
conditioner. Remake flare
(A) Indoor/outdoor unit connecting wire* 1
according to the dimension Drain piping for outdoor unit
(B) Extension pipe 1 for new refrigerant. <VA type only>
(C) Wall hole sleeve 1 • Provide drain piping before indoor and
(D) Wall hole cover 1 outdoor piping connection.
(E) Pipe fixing band 2 to 5 GE25, 33, 35 ,42VA
• Connect drain hose (I) I.D.15 mm as
(GE25, 33, 35 ,42/GE50) shown in the illustration.
(F) Fixing screw for (E) 4 × 20 mm 2 to 5 100/500 mm or more
• Choose one hole for draining, and
(G) Piping tape 1 install drain socket (9). Close the re-
mm
(H) Putty 1 100more maining two holes with drain cap (10)
or (GE50VA only).
Drain hose (9) (I)
GE50VA • Make sure to provide drain piping with
(I) (or soft PVC hose, 15 mm inner 1 or 2 10
or m0 mm a downhill grade for easy drain flow.
diameter or hard PVC pipe VP16) ore Note:
(J) Refrigeration oil 1 Install the unit horizontally.
(K) Power supply cord* 1 Do not use drain socket (9) in cold
* Note: (9) (I) regions. Drain may freeze and make the
(10) fan stop.
Place indoor/outdoor unit connecting wire (A)
and power supply cord (K) at least 1 m away 350 IMPORTANT NOTES
from the TV antenna wire. (GE25, 33, 35 ,42/GE50) or m m
200/500 mm or more orem To comply with the requirements of Australian standard AS/NZS 3000 electri-
Units should be installed by licensed contractor Appearance of the outdoor unit may differ from cal installations (wiring rules), the electrical wiring required between the
according to local code requirements. some models. indoor and outdoor units must be installed by a licenced electrical contractor.
Ceiling 54 mm or more
130 mm or more for left and left
Bind the line to the center hole. back piping (using spacer)
Installation plate (1) Lead wire
Level
Indoor/outdoor unit
connecting wire (A)
100 mm 110 mm
or more or more Indoor terminal block
• For future servicing, give extra length to the
Wall 100 mm Wall connecting wires. Earth wire
• Make earth wire a little longer than others. (More (green/yellow)
than 60 mm)
• Do not fold the excess wire, or cram it into small
space. Take caution not to damage the wires. Indoor/outdoor
• Be sure to attach each screw to its unit
correspondent terminal when securing the cord connecting wire
Insert Align the Center of
Fixing screw (2) Align the plumb (A)
the scale with ø 65 mm hole and/or the wire to the terminal block.
line with the scale. *
mark . the line. * Note: Do not place the wires between the
Plumb indoor unit and the installation plate (1). Dam-
* Same for left hole. aged wire could cause heat generation or fire.
Outdoor terminal block
2-3. CONNECTING WIRES FOR INDOOR UNIT 2-4. PIPE FORMING AND DRAIN PIPING Liquid pipe
You can connect indoor/outdoor lead wire without removing the front panel. Pipe Forming Gas pipe
5 1) Open the front panel. • Place the drain hose below the refrigerant piping.
2) Remove VA clamp. • Make sure that the drain hose is not heaved or snaked. Indoor/outdoor unit
- 3) Pass indoor/outdoor unit connecting wire (A) from the back of the indoor unit and proc- • Do not pull the hose when applying the tape. connecting wire (A)
r ess the end of the wire. • When the drain hose passes the room, be sure to wrap Felt tape (7)
insulation material (obtainable at a store) around it. Piping tape (G)
Rear, right, or downward piping Left or left-rear piping
Cut off in case of
1) Put the refrigerant piping and the drain hose right piping. Note:
together, then firmly apply piping tape (G) Be sure to reattach the drain
Piping tape (G) Cut off in case of left
from the end. hose and the drain cap in case piping.
2) Insert the piping and the drain hose into the Cut off in case of of left or left-rear piping. Felt tape (7)
downward piping. Drain cap
wall hole sleeve (C), and hook the upper part Otherwise, it could cause drops
of the indoor unit on the installation plate (1). of water to drip down from the
3) Check if the indoor unit is hooked securely on the installation plate (1) by moving drain hose.
the unit to left and right. Drain cap
4) Thrust the lower part of the indoor unit into the installation plate (1). 1) Put the refrigerant piping and the drain hose together,
then firmly apply felt tape (7) from the end.
Felt tape (7) overlap width should be 1/3 the tape
Drain Piping
width. Use a bandage stopper at the end of felt tape (7).
• If the extension drain hose has to pass through a room, be sure to wrap it with com-
2) Pull out the drain cap at the rear right of the indoor unit. Fig. 1
mercially sold insulation.
(Fig. 1)
• The drain hose should point downward for easy drain flow. (Fig. 1)
• Hold the convex section at the end and pull the
• If the drain hose provided with the indoor unit is too short, connect it with drain hose (I)
that should be provided at your site. (Fig. 2) drain cap.
• When connecting the drain hose to the hard vinyl chloride pipe, be sure to insert it 3) Pull out the drain hose at the rear left of the indoor unit.
securely into the pipe. (Fig. 3) (Fig. 2) Drain hose
• Hold the claw marked by the arrows and pull out the
drain hose forward. Fig. 2
Drain Drain hose
hose
4) Put the drain cap into the section to which the drain
Hard vinyl chloride
70 cm or
pipe I.D. 30 mm
hose is to be attached at the rear of the indoor unit.
Downward more (Fig. 3)
slope
Soft hose • Insert not sharp-edged tools such as screwdrivers
I.D. 15 mm Insert Drain cap
securely
into the hole at the end of the cap and insert the cap
Different fully into the drain pan. Fig. 3
diameter joint 5) Insert the drain hose fully into the drain pan at the rear Drain hose
Fig. 1 Fig. 2 Fig. 3 right of the indoor unit. (Fig. 4)
• Check if the hose is hooked securely to the projec-
tion of its inserting part at the drain pan.
Do not make drain piping as shown below. Fig. 4
6) Insert the drain hose into wall hole sleeve (C), and
hook the upper part of indoor unit on installation plate
Do not raise Accumulated (1). Then, move the indoor unit completely to the left in
drain water Tip of drain At least order to make placing the piping in the back space of
hose dipped 50 mm the unit easier.
Air
in water gap
7) Cut out a piece of cardboard from the shipping box, roll
it up, hook it onto the back rib, and use it as a spacer Fig. 5
Water Water Water to lift the indoor unit. (Fig. 5)
leakage leakage Waving leakage Ditch 8) Connect the refrigerant piping with the extension pipe (B).
9) Thrust the lower part of the indoor unit into the installation plate (1).
3) Run the vacuum pump. (Vacuumize for more than 15 minutes.) 4-4. EXPLANATION TO THE USER
4) Check the vacuum with gauge manifold valve, then close gauge manifold valve, and • Using the OPERATING INSTRUCTIONS, explain to the user how to use the air condi-
stop the vacuum pump. tioner (how to use the remote controller, how to remove the air filters, how to remove
5) Leave as it is for one or two minutes. Make sure pointer gauge manifold valve remains or put the remote controller in the remote controller holder, how to clean, precautions
in the same position. Confirm that pressure gauge shows –0.101 MPa [Gauge] (–760 for operation, etc.)
mmHg). • Recommend the user to read the OPERATING INSTRUCTIONS carefully.
6) Remove gauge manifold valve quickly from service port of stop valve.
7) After refrigerant pipes are connected and evacuated, fully open all stop valves on both
sides of gas pipe and liquid pipe. Operating without fully opening lowers the perform-
ance and this causes trouble.
8) Refer to 1-3., and charge the prescribed amount of refrigerant if needed. Be sure to
charge slowly with liquid refrigerant. Otherwise, composition of the refrigerant in the
system may be changed and affect performance of the air conditioner.
9) Tighten cap of service port to obtain the initial status.
10) Leak test
Lower
Push HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO
Square hole 100-8310, JAPAN