TECHNICAL SPECIFICATION SHEET for : FLOW TRANSMITTER

Rev GENERAL 1 Tag Number 321-FT-221


2 Service
3 P&ID No.
4 Design Pressure 9
5 Design Temperature 90
6 Elec.Haz.Area Class.STD/Zone/Method/Gr.Temp Non-Hazardous
7 Ex-Certification NA
PROCESS 8 Fluid Name Fluid State Fluid Phase Cut1, Cut2, Cut3, Liquid
R3 CONDITIONS 9 Flow Range (m3/hr) Min Nom Max 3 32 36
10 Operating Pressure Kg/cm2 g 7.7
11 Operating Temperature deg C 40
12 Viscosity cP 6.6
13 Density (Liq.) kg/m3 812
R3 14 Allowable Pressure Drop Kg/cm2 g 0.1
15
Sensor 16 Type Mass Coriollis Yes
17 Path NA
18 Operating Principle Coriollis
R2 19 Instrument Range (m3/hr) *
R2 20 Callibration Range (m3/hr) 0-45
21 Sensor / Measuring Tube Material SS 316L
22 Nozzle / Body Material Lining Material SS 304 NA
23 Flange Material SS316L
R4 24 Connection Size Rating Facing Finish Flanged VTA 150# RF
R3 25 Sensor Size VTA.
26 Pressure Loss @max flow *
R3 27 Power Supply 24 VDC.
R4 28 Temprature Ambient.
29 Sensor / Pre-amplifier Enclosure Material SS316
30
TRANSMITTER 31 Transmitter Type Microprocessor based
R3 32 Calibration Range 0-45
33 Accuracy < ± 1% of rate (reading)
R3 34 Ingress Protection IP66
35 Power Supply 24 VDC
R2 36 Output Signal Pulse Rate 4-20mA HART (4 Wired) Frequency Output
37 Serial Communication RS485
38 Integral Indicator YES
R4 39 Enclosure Material Cast Copper free Aluminium (0.6% max. Copper).
40 Mounting(Remote/Integral) Integral
R2 41 Installation In-Line Horizontal or Vertical
42 Remote Indicator NA
R2 43 Cable Entry 2 Nos 1/2" NPT
R2 44 Repeatability 0.5%
OPTION 45 Burn Out Direction Surge Protection NA NA
46 NACE Requirement NA
47 PWHT Requirement NA
48 Temperature Compensation In-Buit
LINE 49 Line No.
R4 50 Size Class Sch. Rating 3" B1A1M SCH 40 150 #
51 Insulation Type Thickness NA
52 Insulation / Lining Material NA
53
PURCHASE 54 Manufacturer *
55 Model *
R3 56 Requisition number *
Notes :- NA - Not Applicable
* - Vendor to Confirm
Pressure Loss @max flow will be submit along with Vendor FT sizing sheet

4
3
2
1 Issued for review 24-02-2020
No. Description Date Pred Chk App App Project