LOAD CALCULATION

Design Wind Speed ( Vz ) = Vb x k1 x k2 x k3 x k4 ( clause 6.3 )

Where,

Vb = basic wind speed = 47 m/s (see 6.2 IS 875 Part III: 2015)

K1 = probability factor (risk coefficient) (see 6.3.1 IS 875 Part III: 2015)

K2 = terrain, height & structure size factor (see 6.3.2 IS 875 Part III: 2015)

K3 = topography factor (see 6.3.3 IS 875 Part III: 2015)

K4 = importance factor for cyclonic region (see 6.3.4 IS 875 Part III: 2015)

K1 = 1 (for all general buildings and structures)

K2 = 1.0 (terrain category 2)

K3 = 1.0

K4 = 1.0
CONTRIVE DESIGNS
Civil & Structural Engineers
Regd. Off-Ist Floor Sharma market, Garh Road, Meerut
Contact no: +91 8791465711, +91 9045079045, +91 9719473990
E-mail: contrivedesignz@gmail.com

( Vz ) = Vb x k1 x k2 x k3 x k4

= 47 X 1 X 1 X 1

= 47 m/sec

Wind pressure at height pz = 0.6 (Vz )2

= 0.6 (47)2 = 1325.4 N / m2 = 1.3 KN/m2

Design wind pressure

Pd = Kd Ka Kc pz

Where

Kd = 1.0, wind directionality factor (Cl. 7.2.1)

Ka = 0.9, area averaging factor (Cl. 7.2.2)

Kc = 0.9, combination factor (Cl. 7.3.3.13)

Wind Load in X – Direction

Wind Load on members F = Cf x Ae x pd

Cf = 1.2 (table 26)

F = (1.2 x 23.52 x 1.1) / 18 = 1.72 KN


CONTRIVE DESIGNS
Civil & Structural Engineers
Regd. Off-Ist Floor Sharma market, Garh Road, Meerut
Contact no: +91 8791465711, +91 9045079045, +91 9719473990
E-mail: contrivedesignz@gmail.com

Wind Load in Z – Direction

Wind Load on members F = Cf x Ae x pd

Cf = 1.2 (table 26)

F = (1.2 x 113.26 x 1.1) / 88 = 1.7 KN