Professional Documents
Culture Documents
Fundamentals of Compressor
Fundamentals of Compressor
FLUID FLOW
August 1999 Vol. 78 No. 8
Feature Article
Understand
centrifugal compressor,
equipment interaction
Operating scenarios provide insights into predicting
behavior during changes
System curve. The plot of pressure drop versus flow gives the
system curve (Fig. 2a). The total pressure drop has two components,
the superincumbent pressure or static pressure difference between
points B and C, and the dynamic pressure drop, i.e., the drop due to
friction, velocity change, etc. The static pressure drop of any system is
constant and is independent of the flow through the system, whereas
dynamic pressure drop varies directly as the square of the velocity or
flowrate.
Fig. 4a. As the control valve closes, the system curve shifts
to the left.
Consequently, the operating point (a) also shifts to the left along the
compressor curve to the point of intersection (b) with the modified
system curve, where the compressor flow equals the reduced incoming
flow. So, in this type of arrangement, compressor capacity control is
achieved by shifting the system curve along the compressor curve
backward and forward, as shown by arrows in Fig. 4a.
Fig. 4b. Inlet flow is never allowed to fall below the surge
control point.
In this case both the ASV and pressure control valves mounted on the
compressor discharge line take action simultaneously, i.e., the former
opens and the latter closes.
Scenario 2.2: Incoming flow drops below surge control point. In case
of a variable speed compressor, if the incoming flow decreases below
the surge control point, the compressor first slows down similarly to
scenario 2.1. The operating point starts to shift down along the system
curve until the minimum sustainable speed is reached (Fig. 6b). If the
corresponding flowrate is still not reached, the surge control valve
begins to open along the minimum speed curve. The surge control
valve continues to open until the sum of forward and recycle flow is
equal to the flow corresponding to the intersection point of the system
and compressor curves (at the minimum operating speed).
Fig. 6b. The operating point starts to shift down along the
system curve.
It should be noted that under certain circumstances like this, the ASV
might open even when the discharge flow is higher than the surge
flow at the minimum speed. However, this sequence of control takes
place only if the speed controller and the driver are fast enough to
respond and rectify the changing condition. If the flow change is very
rapid, the fast-acting antisurge control system acts through the ASV
ahead of the speed controller to save the compressor from surging.
Besides the above many other scenarios are possible. It is not possible
to identify and discuss them all separately. However, some of the
common scenarios and problems presented will help to understand and
interpret the behavior of many others not described here.
BIBLIOGRAPHY
The author