Professional Documents
Culture Documents
Spec - 2017-02 - A01-Instrument Signal Lines
Spec - 2017-02 - A01-Instrument Signal Lines
Spec - 2017-02 - A01-Instrument Signal Lines
DEP 32.37.20.10-Gen.
February 2017
All rights reserved. No part of this document may be reproduced, stored in a retrieval system, published or transmitted, in any form or by any means, without the prior
written permission of the copyright owner or Shell Global Solutions International BV.
PREFACE
DEP (Design and Engineering Practice) publications reflect the views, at the time of publication, of Shell Global Solutions
International B.V. (Shell GSI) and, in some cases, of other Shell Companies.
These views are based on the experience acquired during involvement with the design, construction, operation and
maintenance of processing units and facilities. Where deemed appropriate DEPs are based on, or reference international,
regional, national and industry standards.
The objective is to set the standard for good design and engineering practice to be applied by Shell companies in oil and
gas production, oil refining, gas handling, gasification, chemical processing, or any other such facility, and thereby to help
achieve maximum technical and economic benefit from standardization.
The information set forth in these publications is provided to Shell companies for their consideration and decision to
implement. This is of particular importance where DEPs may not cover every requirement or diversity of condition at each
locality. The system of DEPs is expected to be sufficiently flexible to allow individual Operating Units to adapt the
information set forth in DEPs to their own environment and requirements.
When Contractors or Manufacturers/Suppliers use DEPs, they shall be solely responsible for such use, including the
quality of their work and the attainment of the required design and engineering standards. In particular, for those
requirements not specifically covered, the Principal will typically expect them to follow those design and engineering
practices that will achieve at least the same level of integrity as reflected in the DEPs. If in doubt, the Contractor or
Manufacturer/Supplier shall, without detracting from his own responsibility, consult the Principal.
The right to obtain and to use DEPs is restricted, and is typically granted by Shell GSI (and in some cases by other Shell
Companies) under a Service Agreement or a License Agreement. This right is granted primarily to Shell companies and
other companies receiving technical advice and services from Shell GSI or another Shell Company. Consequently, three
categories of users of DEPs can be distinguished:
1) Operating Units having a Service Agreement with Shell GSI or another Shell Company. The use of DEPs by these
Operating Units is subject in all respects to the terms and conditions of the relevant Service Agreement.
2) Other parties who are authorised to use DEPs subject to appropriate contractual arrangements (whether as part of
a Service Agreement or otherwise).
3) Contractors/subcontractors and Manufacturers/Suppliers under a contract with users referred to under 1) or 2)
which requires that tenders for projects, materials supplied or - generally - work performed on behalf of the said
users comply with the relevant standards.
Subject to any particular terms and conditions as may be set forth in specific agreements with users, Shell GSI disclaims
any liability of whatsoever nature for any damage (including injury or death) suffered by any company or person
whomsoever as a result of or in connection with the use, application or implementation of any DEP, combination of DEPs
or any part thereof, even if it is wholly or partly caused by negligence on the part of Shell GSI or other Shell Company. The
benefit of this disclaimer shall inure in all respects to Shell GSI and/or any Shell Company, or companies affiliated to these
companies, that may issue DEPs or advise or require the use of DEPs.
Without prejudice to any specific terms in respect of confidentiality under relevant contractual arrangements, DEPs shall
not, without the prior written consent of Shell GSI, be disclosed by users to any company or person whomsoever and the
DEPs shall be used exclusively for the purpose for which they have been provided to the user. They shall be returned
after use, including any copies which shall only be made by users with the express prior written consent of Shell GSI. The
copyright of DEPs vests in Shell Group of companies. Users shall arrange for DEPs to be held in safe custody and Shell
GSI may at any time require information satisfactory to them in order to ascertain how users implement this requirement.
All administrative queries should be directed to the DEP Administrator in Shell GSI.
TABLE OF CONTENTS
1. INTRODUCTION ........................................................................................................ 4
1.1 SCOPE ....................................................................................................................... 4
1.2 DISTRIBUTION, INTENDED USE AND REGULATORY CONSIDERATIONS ......... 4
1.3 DEFINITIONS ............................................................................................................. 5
1.4 CROSS-REFERENCES ............................................................................................. 6
1.5 SUMMARY OF MAIN CHANGES............................................................................... 6
1.6 COMMENTS ON THIS DEP ....................................................................................... 7
1.7 DUAL UNITS............................................................................................................... 7
1.8 NON NORMATIVE TEXT (COMMENTARY) .............................................................. 7
2. ELECTRIC CABLING................................................................................................. 8
2.1 GENERAL ................................................................................................................... 8
2.2 SIGNAL SEGREGATION IN MULTICORE CABLES ................................................. 8
2.3 SELECTION AND SPECIFICATION OF INSTRUMENT CABLES .......................... 10
2.4 PROTECTION OF CABLES AGAINST FIRE DAMAGE .......................................... 13
2.5 SYSTEM CABLING .................................................................................................. 13
3. CABLE SEGREGATION, ROUTING AND INSTALLATION ................................... 13
3.1 CABLE SEGREGATION ........................................................................................... 13
3.2 ROUTING ................................................................................................................. 14
3.3 JUNCTION BOXES FOR MULTICORE CABLES .................................................... 15
3.4 CABLE GLANDS ...................................................................................................... 16
3.5 CABLE TRAYS ......................................................................................................... 17
3.6 TRENCHES .............................................................................................................. 18
3.7 CABLE PULLING AND INSTALLATION ASPECTS ................................................ 19
3.8 CONTROL ROOM/AUXILIARY ROOM AREAS ....................................................... 20
4. EARTHING (GROUNDING) AND BONDING .......................................................... 21
4.1 GENERAL ................................................................................................................. 21
4.2 CONNECTIONS TO THE EARTHING (GROUNDING) SYSTEMS ......................... 22
4.3 EARTHING (GROUNDING) OF INTRINSICALLY SAFE CIRCUITRY .................... 23
5. LIGHTNING PROTECTION OF INSTRUMENTATION ........................................... 23
5.1 GENERAL ................................................................................................................. 23
5.2 INSTRUMENTATION AND CABLING IN THE FIELD.............................................. 23
6. IDENTIFICATION AND MARKING .......................................................................... 24
7. REFERENCES ......................................................................................................... 25
APPENDICES
APPENDIX 1DISTANCE BETWEEN CABLE TRENCHES .......................................................... 27
APPENDIX 2ARRANGEMENT OF CABLE TRENCHES ............................................................. 28
1. INTRODUCTION
1.1 SCOPE
This DEP specifies requirements and gives recommendations for the design and
engineering of instrument signal lines and cabling. It covers design, material selection and
installation methods for onshore and offshore applications.
In the context of this DEP, instrument signal lines include electric signal lines from
transmitters to their receiving instruments, Process Automation Systems (PAS),
Instrumented Protective Systems (IPS) and the lines from these systems to the relevant
actuating elements such as solenoid valves, converters, transducers or control valves.
Signal lines for applications such as fire and gas detection and vibration monitoring
systems are also within the scope of this DEP.
Hydraulic and pneumatic signal lines, Ethernet (IEEE-802), Power Line Communication and
wireless connection types are not covered in this DEP.
Telephone System, Plant Radio System, Public Address and General Alarm (PAGA),
Computer Data Systems, Closed-Circuit Television and Security systems are covered in
DEP 32.71.00.10-Gen.
This is a revision of the DEP of the same number dated February 2014; see (1.5) regarding
the changes.
1.3 DEFINITIONS
1.3.1 General definitions
The Contractor is the party that carries out all or part of the design, engineering,
procurement, construction, commissioning or management of a project or operation of a
facility. The Principal may undertake all or part of the duties of the Contractor.
The Manufacturer/Supplier is the party that manufactures or supplies equipment and
services to perform the duties specified by the Contractor.
The Principal is the party that initiates the project and ultimately pays for it. The Principal
may also include an agent or consultant authorised to act for, and on behalf of, the
Principal.
The word shall indicates a requirement.
The word should indicates a recommendation.
The word may indicates a permitted option.
1.3.2 Specific definitions
Term Definition
Fieldbus A digital, serial, multidrop, data bus for communication with industrial
control and instrumentation devices such as, but not limited to,
transducers, actuators and local controllers. This standard only covers
the fieldbus physical layer.
1.3.3 Abbreviations
Term Definition
PE Polyethylene
VA Volt-ampere
1.4 CROSS-REFERENCES
Where cross-references to other parts of this DEP are made, the referenced section or
clause number is shown in brackets ( ). Other documents referenced by this DEP are listed
in (7).
Section/Clause Change
2. Restructured requirements.
2.3.1 Removed redundant references.
3 Clarification of trenching and requirements for slack in cables;
restructured requirements.
4 Restructured requirements.
5 Restructured requirements.
6 Removal of complete section, transfer to DEP 01.00.09.10.
Feedback that has been registered in the DEP Feedback System by using one of the above
options will be reviewed by the DEP Custodian for potential improvements to the DEP.
2. ELECTRIC CABLING
2.1 GENERAL
Single cables are used to connect field instruments to field mounted junction boxes.
Multicore cabling subsequently connect the junction box to a main distribution frame
(MDF) or cabinets in the central control room (CCR) or field auxiliary room (FAR).
1. System cables may be used to connect cabinets to other cabinets and the MDF.
2. Multicore cabling should be routed underground, wherever possible and consistent
with the design of other plant facilities. Aboveground cabling is acceptable provided a
definite cost advantage is demonstrated, or where it is the local standard practice.
NOTES: 1. The classification is based on the use of cables with metal screen for signal level classes 1, 2, 3
and 4.
2. The classification is based on de-coupled solenoids to limit induction. A solenoid-operated valve
shall be equipped with an arc suppression device across the coil if the digital output channel of the
associated system does not have this feature built-in.
3. For North American application, 24 VDC solenoids may be combined with signal levels class 2 if
the wire size is adequate for the current.
4. From a signal level perspective thermocouple and RTD conductors do not require segregation.
However, considering conductor materials and number of conductors per point, these two types of
cables are not normally combined in a multicore cable.
5. From a signal level perspective, FF cables may be combined with other Level 2 cables. However,
FF requirements regarding conductor specification and distance limitation normally preclude such
combinations in multicore cables.
6. Signal level class 5 falls under the electrical discipline.
2. Segregation of signals by function is not required, e.g., signal level class 2 signals for
IPS, PAS and FGS may be connected to the same junction box and in the same
multicore cable.
a. Where practical, functional segregation may be required for operability and
maintainability reasons (e.g., segregation between process units or segregated
cabling for fire and gas systems).
b. where practical, thermocouples and Resistance Temperature Detector signals,
should be converted locally in the field to become standard 4-20 mA or fieldbus
signals which then fall in signal level class 2.
3. Where field devices using signal level classes 2 or 3 require a low power 24 VDC
supply, this may be combined in the same single cable as the signal.
7. For thermocouple signals, the conductors shall consist of pairs of dissimilar materials
with the correct thermo-electric voltage as a function of temperature, based on
IEC 60584-3. For all other signals, the conductor material shall be copper.
8. For resistance thermometer elements, the conductor resistance shall be compatible
with the requirements as specified by the Manufacturer of the resistance thermometer
elements and/or the instrument.
9. Wires of the same signal loop shall be twisted in pairs.
10. For signals requiring four wires, either two individually twisted pairs or a single twisted
quad shall be used.
11. For North American applications, conductors shall meet the requirements of
DEP 33.64.20.10-Gen.
2.3.3 Cable construction
2.3.3.1 Cable construction for signal level classes 1/2/3/4
Multicore cabling is normally restricted to 5, 8, 10, 16 or 20 pair/triplet size; however, in
exceptional circumstances where a large number of signals of a similar classification
type exist in a remote area, a 50 pair/triple could be used.
1. If the ambient temperature is above 65 °C (150 °F), (e.g., in rotating equipment or in
close proximity to furnaces) thermocouple lead wire should have Teflon or Kapton
insulation.
2. Length and gauge of thermocouple lead wire should be sized so that resistance of
wire does not exceed 800 ohms.
3. Joining two sections of thermocouple extension wires shall not be allowed.
4. For vibrating or flexible service, the wire to the first junction box should have stranded
conductors.
5. Outdoor, aboveground cables shall be provided with steel wire braiding (SWB) even if
they are installed on cable trays.
6. For North America, non-armoured cable may be used when laid in cable tray.
7. Underground cable shall be provided with steel wire armouring (SWA).
a. Cables used indoors such as in CCR and FAR (e.g., Type 1) shall be constructed
of halogen free, flame retardant compound as specified in EN 50290-2-26.
8. Cables used aboveground in the plant (e.g., Type 2, Type 3 and Type 4) shall be
constructed of flame retardant compound.
9. Cables used underground do not require specific flame retardant properties, but for
standardisation reasons all cables used may be constructed of halogen free, flame
retardant compounds.
NOTES: 1. Cable types 1, 2 and 3 correspond with those mentioned in MESC 68.51/001 and
MESC 68.71/001.
2. Description of cable construction is from the centre to the outside.
3.2 ROUTING
1. Single cables connecting field instruments to junction boxes shall be supported and
protected against mechanical damage, for example, by cable trays, steel angles,
beams, open conduits.
2. With exception of North American application, closed conduits shall not be used.
3. Cables and cable trays shall not be supported by or attached to process equipment or
piping.
4. When aboveground routing for cables is selected, the following aspects shall be
evaluated:
a. constructability and cost: making optimum use of structures for process
equipment, pipe racks, etc. The need for special passages/ducts and crossings
will also affect the route selection;
b. required cable length and associated cost;
c. EMC aspects: apply cable segregation (3.1) and minimize routing cabling through
EM Zone 4 environments:
i. route cabling through areas that are protected against direct lightning
strikes;
ii. consider cable routing along and in the direct vicinity of earthed steel
structures and piping;
iii. layout should not obstruct traffic or interfere with the accessibility of process
equipment (pumps, compressors, motors, heat exchanger bundles, etc.).
d. provide assess for cable pulling and maintenance;
e. select the layout such that the cables are not prone to damage. This involves at
least the following:
i. route cabling through low fire risk areas;
ii. do not route cabling in the vicinity of sample points, drains, vents, hot pipes
and hot surfaces. Local shielding may be required to protect the cables;
iii. protect cable riser points which are liable to damage by traffic by free
standing, sturdy mechanical structures.
5. The route selection for underground cable trenches shall be evaluated based on the
following rules:
a. maintain an appropriate distance from power and lighting cables. For separation
distances, see (Appendix 1). When power cables intersect instrument signal
cables, the crossing shall be at right angles, with a minimum separation distance
of 0.3 m;
b. keep trenches away from buried hot surfaces (e.g., pipes) so that the properties
of the cable are not adversely affected.
i. Maintain a minimum separation distance of 0.2 m plus 0.1 m for every
100 °C temperature of the non-insulated surface.
6. The design for the cable routing shall be subject to approval of the Principal.
3.6 TRENCHES
1. Outside of North America underground instrument signal cables shall be laid in
dedicated trenches and their routing shall be indicated by aboveground markers.
Cross-sectional drawings of trenches should show the location and laying pattern of
each group of cables.
2. Refer to DEP 36.64.20.10-Gen for requirements pertaining to North America.
3. Instrument cables in trenches shall be laid as non-load carrying cables in accordance
with DEP 33.64.10.10-Gen. (5.3.3.2, item 2).
Typical arrangements for a number of formations are shown in Standard Drawing
S 68.009.
4. The bottom of the trench should be kept above the ground water level. For general
construction details for trenches in paved and unpaved areas, refer to (Appendix 2)
and Standard Drawings S 19.001, S 19.002 and S 68.009.
5. The distance between cables in trenches, as indicated on Standard Drawing S 68.009,
does not apply to instrument cables of signal level classes 1 through 4, which may be
laid without spacing.
6. The bottom of the trench shall not have a slope of more than 10 degrees with a
smooth transition to horizontal surfaces.
7. Where trenches for signal cables pass under roads or below other cable trenches or
pipes, protective DN 100 or DN 150 pipes or concrete ducting should be provided and
capped or plugged at both ends to facilitate future cable laying.
8. Particularly for cables entering buildings, the Contractor shall develop a detailed
proposal, subject to approval by the Principal, with respect to supporting the cables.
9. Backfilling of the trenches shall be carried out with sand, free of stones to grade
2 mm - 5 mm, and contain no contaminants which could cause deterioration of the
cable.
10. The top cable layer shall be covered with protective material, such as tiles, to provide
mechanical protection.
11. Alternatively, plastic cover plates may be applied, provided the same degree of
protection is obtained.
12. Where large quantities of signal cables cross or branch off, the trench depth may be
locally increased.
13. The curvature of the corners in trenches should be selected so that the permissible
bending radius of the cables is not exceeded.
14. Underground multicore cables in trenches shall enter the CCR or FARs via cable
transit frames fitted with sealing to prevent the ingress of water, dirt, gas, etc., (e.g.,
MCT frames, cable glands).
Multicore cabling and Minimum spare capacity for each signal level class 20 %
junction boxes
Trenches Minimum spare capacity 30 % per trench
Cable trays Minimum spare capacity 30 % per cable tray
Cable transit frames Minimum spare capacity 20 % per transit frame
MDF cabinets Minimum 20 % unused space per MDF cabinet
System cabling between Minimum spare capacity 10 % to add terminals in each
MDF and equipment MDF and equipment cabinet
cabinets
4.1 GENERAL
1. The purpose of earthing (grounding) systems can be split as follows:
a. protective Earth (E, green/yellow), for personnel safety;
b. functional Earth, for surge suppression and EMC:
i. instrument Earth (IE,RAL 6018 colour (green));
ii. intrinsically Safe Earth (IS, RAL 9010 colour (white)).
2. Protective earthing (grounding) systems are covered by Electrical Engineering and
provisions for earthing (grounding) are covered by DEP 33.64.10.10-Gen. For North
American application, refer to DEP 33.64.20.10-Gen.
3. The protective earth and the instrument earth/intrinsically safe earth shall be
connected at a single point only. For a typical configuration of a protective earth and
instrument earth system at the FAR/CCR, refer to S 37.101.
4. Instrument earth cables shall connect the instrument earth bar of the MDFs and
instrument cabinets.
5. Looping of instrument earth cables between cabinets shall not be applied.
6. The cross-sectional area of instrument earth cables connecting MDFs and equipment
2
cabinets to the instrument earth bar shall be at least 6 mm .
7. The terminal insulation of instrument earth cables connecting MDFs and equipment
cabinets to the instrument earth bar shall be RAL 6018 (green) colour.
8. Connections of instrument earth cables shall be made using cable lugs and not
terminals.
9. Earthing (grounding) bolts shall have a diameter of at least 10 mm.
10. For North American application, the minimum wire size of the earth cable shall be
10 AWG.
11. For North American application, the earth cable shall be green (RAL 6018) with a
yellow (RAL 1021) stripe.
12. Each instrument earth cable shall be identified, with the cabinet number, at the side of
the instrument earth bar, showing the MDF/cabinet number it is connected to.
13. Dedicated earth rods shall not be applied.
Some Manufacturers require a dedicated earth for their equipment: Manufacturers'
recommendations on the arrangement of earthing (grounding) and maximum
allowable resistance to earth shall be followed. However, the star point earthing is
to be connected to the overall plant earth grid inside equipment rooms.
14. In CCR and FARs Instrument Earth “rings” may be connected at the beginning and
end of interconnected Instrument Earth bars in adjacent cabinets.
a. Both “ring” ends shall be connected to the appropriate earth bars.
15. These “rings” shall be continuous conductors with crimp type connections for each
cabinet conductor as necessary.
2
16. Conductor cross-sectional area shall be a minimum of 16 mm .
17. Insulation colours shall be (RAL 6018) green and (RAL 1021) yellow for Protective
Earth (E) and RAL (6018) green for Instrument Earth (IE). For a typical configuration of
this arrangement, refer to S 37.101.
18. Intrinsically Safe earth “rings” shall only be used when each cabinet I.S. earth bar is
connected at each end to the ring in “daisy chain” manner to facilitate testing.
19. For requirements for earthing (grounding) and bonding of enclosures containing
electric and electronic components, refer to DEP 33.64.10.33-Gen. some additional
requirements may be dictated by local regulations (e.g., European standards
associated with CE-marking).
5. All cores of the multicore shall be terminated on a dedicated terminal on the MDF. The
terminals with unused cores shall be connected to:
a. intrinsically safe earth for cables used for intrinsically safe signals;
b. instrument earth for cables used for non-intrinsically safe signals.
4.2.2 Connections to protective earth
1. Steel wire armouring, steel wire braiding and metal sheathing of cables shall be
connected to protective earth ring, at least at both ends.
2. For typical protective earthing (grounding) installation details, refer to S 37.101,
S 37.121, S 37.131 and S 37.142.
3. Instrument housings, junction boxes, local panels and local cabinets shall be bonded
to cable trays/steel angles etc.
4. Earthing (grounding) or mounting bolts of instrument housings shall be fitted with two
shark rings to allow low resistance bonding to plant structures/protective earth.
5. Junction boxes, local panels and local cabinets shall be provided with earthing
(grounding) bolts to enable a proper earthing (grounding) connection to plant
structures/protective earth.
6. All cables entering the CCR and FAR building shall be earthed at the cable transit
frame which is connected to the protective earth ring. Refer to section 3.6 of
DEP 33.64.10.33-Gen.
7. Any outside earthing (grounding) connection shall comply with IEC 60079-0.
5.1 GENERAL
1. The lightning protection for instruments described in this section assumes that plants
are equipped with lightning protection as specified in DEP 33.64.10.10-Gen. For North
American applications, DEP 33.64.20.10-Gen. shall apply.
2. Lightning protection shall not interfere with the method of protection for use of
instruments in explosive atmospheres. Contractor shall submit, subject to approval of
the Principal, an instrument lightning protection plan.
7. REFERENCES
In this DEP reference is made to the following publications:
NOTES: 1. Unless specifically designated by date, the latest edition of each publication shall be used,
together with any amendments/supplements/revisions thereto.
2. The DEPs and most referenced external standards are available to Shell staff on the SWW (Shell
Wide Web) at http://sww.shell.com/standards/.
SHELL STANDARDS
STANDARD DRAWINGS
EX 'e'and EX 'i' - signal level classes 4/5 - 10 single pair cables and a S 37.603-003
21-conductor multicore
Instrument cable trunking S 37.604
Typical arrangements of cable trenches in plant areas S 68.009
Typical bonding details for field instrument cabling S 68.035
AMERICAN STANDARDS
Requirements for process sealing between electrical systems and ISA 12.27.01
flammable or combustible process fluids
Standard for local and metropolitan area networks: Overview and IEEE-802
architecture - IEEE Computer Society Document Issued by: IEEE -
The Institute of Electrical and Electronics Engineers, Inc.
EUROPEAN STANDARDS
INTERNATIONAL STANDARDS