ERTAF - ERTAF-2 - Product Report

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Job Name: David Selection March RTAF Unit Tag: ERTAF-2

Prepared For: Quantity: 1

Unit Overview
Chiller model Sintesis Prime
Model RTAF 105 SE SN AC
Unit application Air cooled chiller
Compressor type Screw
Refrigerant Type Pre-charge Factory R134a
Seasonal space energy
169 % 4.30 Compliant
efficiency (s,c) / SEER (1)
SEPRHT 5.51 Compliant
SEPRMT 3.27 Compliant
Free cooling No Free Cooling
Hydraulic module Pump signal On/Off
Electrical supply 400V/50Hz/3Ph

Project conditions
Cooling
Outdoor air dry bulb temperature 118.40 F
Fluid entering temperature 72.00 F
Fluid leaving temperature 64.00 F
Evap fluid type Water
Fluid Freezing Point 32.00 F
Fouling Factor 0.00025 hr-sq ft-deg F/Btu
Elevation 0.00 ft

Unit performance data


Cooling (1)
Gross capacity 116.18 tons
Net capacity 116.01 tons
Total absorbed power 151.76 kW
Why the net capacity and net Gross EER 2.69 EER (kW/kW)
EER different ? It should be Net EER 2.66 EER (kW/kW)
same.
Design flow rate 348.72 gpm
Evaporator Pressure drop (Design) 212.333 in H2O
Evaporator Min Flow 9.40 L/s
Evaporator Max Flow 34.70 L/s

Partload Information
NPLV.IP 5.46
Load % 100 75 50 25
Net Capacity tons 117.85 88.97 59.51 47.90
Efficiency EER (kW/kW) 2.73 4.36 6.06 7.25
Total Power kW 151.85 71.70 34.53 23.23
Fan Power kW 8.38 8.76 4.51 0.44
Leaving Water F 64.00 64.00 64.00 64.00
Entering Water F 72.00 70.04 68.04 66.01
Flow gpm 353.77 353.77 353.77 353.77
Pressure drop in H2O 218.36 218.25 218.40 218.47
Fouling Factor hr-sq ft-deg
0.00 0.00 0.00 0.00
F/Btu
Dry-bulb C 48.00 34.88 21.75 13.00
Altitude m 0.00 0.00 0.00 0.00

2022/03/23 10:36:02 Trane® Select Assist™ Version: 257 The certified standard performances and the certified software tool version can be verified in http://www.eurovent-certification.com Page 1 of 2
Job Name: David Selection March RTAF Unit Tag: ERTAF-2
Prepared For: Quantity: 1

Acoustic data
Outdoor sound power level 95 dBA (4)
Outdoor sound pressure level 62 dBA (3)
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
Outdoor sound
93 dB 92 dB 92 dB 92 dB 84 dB 76 dB 69 dB
spectrum (Lwa)

General data - refrigerant circuit


Refrigerant Type Pre-charge Factory R134a
Refrigerant GWP (AR5) 1430
Number of circuits 2
Number of compressors (circuit 1 / 2… n) 2
Compressor type Screw
Compressor regulation type Fixed Speed
Unit minimum load 30.00 %
Refrigerant charge per circuit 40 kg 38 kg
Oil charge per circuit 6 kg 6 kg

General data - fan section


Number of outdoor fans 8
Fan type AC Fan
Total condenser air flow 94278 cfm

Electrical data
Electrical supply 400V/50Hz/3Ph
Compressor soft starter Not Included
Start-up current 320.90 A
Maximum running current 256.90 A
Displacement power factor (cos-phi) 0.86

Shipping dimensions and weight


Length 177.962 in
Width 86.618 in
Height 100.556 in
Shipping weight including packaging 7275.3 lb
Operating weight 7429.6 lb

Note: Dimensions and weight include sound attenuation, hydraulic module, heat recovery and/or free cooling - if selected. Image is for illustration
purposes only, options may not be shown.

Applicable standards
(1) According to EN14825:2018, considering average climate
(2) According to EN14511:2018
(3) Average sound pressure at 10 meter distance, unit in a free field on a reflective surface; non-binding value calculated from the sound power level
(4) Sound power measurements in accordance with ISO 9613

More information
https://www.trane.com/litweb/Litweb.aspx?#/category/bd13efa5-a5bf-4f0a-
afb4-9eab178d9081/range/a1a2a06b-b5ae-492a-bc17-
Ecodesign datasheet
b8ada8833fac/model/8234b149-20ff-41a9-9c2b-
e189f8956901/section/a41a3b61-a631-48b1-a8d8-3f25d0783c05
Model Number RTAF105D***NC2XHLXN2NNXXXBXEXXX1XLXXXXXXXX*X0XXX
2022/03/23 10:36:02 Trane® Select Assist™ Version: 257 The certified standard performances and the certified software tool version can be verified in http://www.eurovent-certification.com Page 2 of 2