Unit Overview
Chiller model Sintesis Prime
Model RTAF 105 SE SN AC
Unit application Air cooled chiller
Compressor type Screw
Refrigerant Type Pre-charge Factory R134a
Seasonal space energy
169 % 4.30 Compliant
efficiency (s,c) / SEER (1)
SEPRHT 5.51 Compliant
SEPRMT 3.27 Compliant
Free cooling No Free Cooling
Hydraulic module Pump signal On/Off
Electrical supply 400V/50Hz/3Ph
Project conditions
Cooling
Outdoor air dry bulb temperature 118.40 F
Fluid entering temperature 72.00 F
Fluid leaving temperature 64.00 F
Evap fluid type Water
Fluid Freezing Point 32.00 F
Fouling Factor 0.00025 hr-sq ft-deg F/Btu
Elevation 0.00 ft
Partload Information
NPLV.IP 5.46
Load % 100 75 50 25
Net Capacity tons 117.85 88.97 59.51 47.90
Efficiency EER (kW/kW) 2.73 4.36 6.06 7.25
Total Power kW 151.85 71.70 34.53 23.23
Fan Power kW 8.38 8.76 4.51 0.44
Leaving Water F 64.00 64.00 64.00 64.00
Entering Water F 72.00 70.04 68.04 66.01
Flow gpm 353.77 353.77 353.77 353.77
Pressure drop in H2O 218.36 218.25 218.40 218.47
Fouling Factor hr-sq ft-deg
0.00 0.00 0.00 0.00
F/Btu
Dry-bulb C 48.00 34.88 21.75 13.00
Altitude m 0.00 0.00 0.00 0.00
2022/03/23 10:36:02 Trane® Select Assist™ Version: 257 The certified standard performances and the certified software tool version can be verified in http://www.eurovent-certification.com Page 1 of 2
Job Name: David Selection March RTAF Unit Tag: ERTAF-2
Prepared For: Quantity: 1
Acoustic data
Outdoor sound power level 95 dBA (4)
Outdoor sound pressure level 62 dBA (3)
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
Outdoor sound
93 dB 92 dB 92 dB 92 dB 84 dB 76 dB 69 dB
spectrum (Lwa)
Electrical data
Electrical supply 400V/50Hz/3Ph
Compressor soft starter Not Included
Start-up current 320.90 A
Maximum running current 256.90 A
Displacement power factor (cos-phi) 0.86
Note: Dimensions and weight include sound attenuation, hydraulic module, heat recovery and/or free cooling - if selected. Image is for illustration
purposes only, options may not be shown.
Applicable standards
(1) According to EN14825:2018, considering average climate
(2) According to EN14511:2018
(3) Average sound pressure at 10 meter distance, unit in a free field on a reflective surface; non-binding value calculated from the sound power level
(4) Sound power measurements in accordance with ISO 9613
More information
https://www.trane.com/litweb/Litweb.aspx?#/category/bd13efa5-a5bf-4f0a-
afb4-9eab178d9081/range/a1a2a06b-b5ae-492a-bc17-
Ecodesign datasheet
b8ada8833fac/model/8234b149-20ff-41a9-9c2b-
e189f8956901/section/a41a3b61-a631-48b1-a8d8-3f25d0783c05
Model Number RTAF105D***NC2XHLXN2NNXXXBXEXXX1XLXXXXXXXX*X0XXX
2022/03/23 10:36:02 Trane® Select Assist™ Version: 257 The certified standard performances and the certified software tool version can be verified in http://www.eurovent-certification.com Page 2 of 2