Professional Documents
Culture Documents
Tiltle: Swadhin Kumar Hota, Chandrasekhar N. Bhende
Tiltle: Swadhin Kumar Hota, Chandrasekhar N. Bhende
Abstract: This should be informative and suitable for direct inclusion in abstracting services as a self-
contained article. It should not exceed 200 words. It should summarise the general scope and also state the
main results obtained, methods used, the value of the work and the conclusions drawn. No figure numbers,
table numbers, references or displayed mathematical expressions should be included. The abstract should
be included in both the Manuscript Central submission step (Step 1) and the submitted paper.
1
problem in cooperative control system. Less 2. Structure of the Test System
communication requirement is the major advantage
Fig.1 shows, single line diagram of 9-bus test
of using decentralized control in micro-grid. In [15,
micro grid including local loads. Each PV units are
16], authors have investigated a decentralized control
connected to a load bus through coupling inductor
of active and reactive power of each DGs for voltage
(LC=0.185mH). Then all the load buses are
and frequency regulation in micro-grid.
connected to another load bus which is nothing but
When system has limited ESSs i.e., when
point of common coupling (PCC). Then PCC is
there is not sufficient storage capacity then active
connected to a weak grid through a (Y g-Δ)
power curtailment is performed to mitigate over
transformer (500 kVA).
voltage and thermal stressing (over loading in
conductors) on the system [5,17,18,19]. In this paper, Table.1 Impedance of the line
de-loaded power of each unit is calculated from
algorithm used for cooperative control and modified Impedance (Ω) Length(km)
Perturb and observe (P & O) algorithm is used to
perform the Z L1 0.1 +j0.31 5
de-loading operation of the PV units.
Traditionally, the reactive power sharing Z L2 0.14+j0.434 7
among various PV inverters can be achieved using Z L3 0.13+j0.403 6.5
droop characteristics [2, 19, 20, 21]. Traditional
droop-controlled systems assume that the generators ZL 4 0.15+j0.46 7.5
are able to provide sufficient power as required. This
is however not always true, especially in renewable
Table.2 Load at different buses
systems, where the energy sources (e.g., photovoltaic
source) may not be able to provide enough power Load Real power Reactive power
due to the intermittency. Moreover, the kVA rating (kW) (kVAR)
of PV inverters are different from each other. Under Load1 15 5
such situations, conventional droop method may not
provide proper sharing among inverters. Hence, in Load2 20 10
this paper, instead of droop method, direct fuzzy- Load3 10 5
control based strategy is proposed so that power Load4 12 7.5
sharing varies dynamically with the Load5 Not fixed Not fixed
operating conditions.
Looking at the above mentioned requirements
and challenges, the objective of the papers are : Line impedance and loads at different buses are
given in Table.1 and Table.2 respectively. The
I. To maintain the voltage of the point of specifications of transformer and grid are given in
common coupling (PCC) at a nominal value Fig.1.
by injecting reactive power into the PCC
bus from PV inverters.
II. Cooperative sharing of reactive power
among the PV inverters in such a way that,
the utilization factor of each inverters
should be same.
III. Active power curtailment (APC) during
heavy power penetration into the grid and
cooperative sharing of curtailed power
among the PV units.
.
2
PV generator can supply real power only
when solar insolation is available but it can be
used for voltage support even in the night time. In
this paper, reactive power of the PV inverter is
controlled to maintain the PCC voltage (VPCC) at
it’s nominal value. Here, PV-inverter is controlled
to supply or absorb the reactive power, so that PV
inverter is operated as the source of variable
reactive power.
3
Fig.2. Current controller of inverter for real and reactive power control
4
Then md and mq are transformed into abc frame to get 3
ma , mb and mc then subsequently pulses are generated Q= (V q I d−V d I q )
2
for inverter using PWM technique.
−3
3.1.1 Controller to Estimate Id-ref : Q= (V d I q )
2
To regulate the real power from the PV- inverter, Then, Iq-ref can be written as
( )
Id-ref should be generated accurately. Fig.3 shows the
−2 Qref
controller to generate Id-ref. DC-link reference voltage I q−ref = (4)
(Vdc-ref) and actual DC-link voltage (Vdc) are 3 Vd
compared and the error is processed through PI-
controller and power limiter (limits the power with in So to generate Iq-ref , it is necessary to find
the rating of PV unit) to generate reference real reference reactive power Qref. To maintain the PCC
power (Pref), subsequently Id-ref is generated by using voltage (VPCC) at it’s nominal value, all the inverter
equation (3). connected to PCC must provide reactive power in
cooperative manner to avoid overloading on any
Real power in dq-frame is given by: inverter.
3 3.2 Cooperative Controller for Zero
P= (V d I d +V q I q ) Voltage Regulation mode of Operation
2
If PLL (phase looked loop) in steady state then Vq=0 There is some droop or rise in PCC voltage
3 depending upon direction and amount of power flow
P= (V d I d ) (either real power or reactive power or both), which
2 leads to non-zero voltage regulation. It is considered
Then, Id-ref can be written as that, when there is no power flow, the VPCC =400V.
Controller for generation of Qref is given in Fig.4,
I d−ref =
( )
2 Pref
3 Vd
(3) where the difference between reference PCC voltage
(VPCC-ref) and VPCC is passed through PI-controller to
get total reference reactive power (Qref-T). After
getting Qref-T, it is shared among the inverters
connected with the PCC to estimate the reference
reactive power (Qref-i) for each inverter.
3.1.1 Controller to Estimate Iq-ref : Fig.4. Controller for zero voltage regulation
5
By using Algorithm-1 Qref-T is shared among all
the inverter in such a way that utilization factor ( ) of
all the inverter are same and subsequently Iq-ref for
each inverter can be calculated using equation (4).
Fig.5. Block diagram of Fuzzy controller. Each input is assigned 5 membership functions
(MFs), namely, “Least”, “Less”, “Medium”, “High”
The membership functions and their and “Very High” for Qres-i; and “NH”, “NL”, “Z”,
corresponding ranges for input and output variables “PL”, “PH” for VPCC, where “N”, “P”, “Z” , “H”
are shown in Fig.6 (a-c). The fuzzy set rules are and “L” stand for negative, positive, zero, high and
given in Table.3. low respectively. The output, Qref-i is assigned five
MFs, namely NHR, NLR, ZR, PLR and PHR, where
“N”, “P”, “Z” , “H” , “L” and “R” stand for negative,
positive, zero, high, low and reactive power
respectively. The rule base is illustrated in Table.3,
in which final crisp output of the controller is derived
by defuzzification using centroid method.
4. Active Power Curtailment PV units
When available PV power is much more than
load demand, then large amount of PV power
(a) penetrates to the grid. This affects adversely on the
distribution lines, transformers and grid as they are
generally weak in rural areas [23-24]. Therefore,
6
under this situation, PV power needs to be reduced Pde Pde Pd e
through de-loading operation. This can be achieved
PV 1
= PV 1
=…= PVn
=(10)
by shifting the operating point of PV from maximum P mpp PV 1
P mpp PV 1
P mp p PVn
shown in P-V curve in Fig.7 [24]. Pmpp Maximum power shared by nth PV unit
PVn
For the same power, there is two operating point
namely, “A” and “B”, which are shown in Fig.7. The above mentioned objective is fulfilled by
Operating point “A” is in the left side of MPP (i.e., modifying the perturb and observe (P&O) algorithm
dP/dV >0) and B is on the right side of MPP (i.e., mentioned in Fig.8. From the algorithm, the unique
dP/dV >0). PV should operate at point B, as it is a de-loaded voltage (Vde) is calculated so that Eq.(9)
stable operating point [21]. The stability of the and Eq.(10) are satisfied and this Vde becomes the
operating point could be explained as: If dc-link reference dc-link voltage (Vdc_ref) for the controller
voltage (Vdc) is below the MPP voltage, any positive given in Fig.3 to generate d-axis reference current
load step will lead to drop in Vdc due to discharging (Id-ref ).
of stored energy from capacitor. Due to the drop in
Vdc, the output power from PV panel decreases,
which further decreases the Vdc, so dc-link finally
collapse.
I lim ¿
x=I g − (8)¿
Ig
Fig.8. Modified P&O algorithm for de-loading
I gActual grid current operation
I lim ¿¿ Maximum permissible grid current References
Once, total de-loaded power (Pde_T) is calculated [1] X. Wu, C. Shen and R. Iravani, "A Distributed,
from Eq.(6), the de-loaded power shared by each PV Cooperative Frequency and Voltage Control for
need to be found out. As ratings PV systems may be Microgrids," IEEE Transactions on Smart
different, question comes how the Pde_T can be shared Grid,vol. 9, no. 4, pp. 2764-2776, July 2018.
among PV systems. By using equations (9) and (10),
[2] J. C. Vasquez, R. A. Mastromauro, J. M.
de-loaded power for each unit (Pde_PVi) can be
Guerrero and M. Liserre, "Voltage Support
calculated such that the utilization factor of each
Provided by a Droop-Controlled Multifunctional
units will be equal.
Inverter," IEEE Transactions on Industrial
Pde =Pde + Pde +…+ Pd e (9) Electronics, vol. 56, no. 11, pp. 4510-4519, Nov.
2009.
T PV 1 PV 2 PVn
7
[3] Y. Han, H. Li, P. Shen, E. A. A. Coelho and J. M. [13] F. Luo, Y. Chen, Z. Xu, G. Liang, Y. Zheng and
Guerrero, "Review of Active and Reactive Power J. Qiu, "Multiagent-Based Cooperative Control
Sharing Strategies in Hierarchical Controlled Framework for Microgrids’ Energy Imbalance,"
Microgrids," in IEEE Transactions on Power in IEEE Transactions on Industrial Informatics,
Electronics, vol. 32, no. 3, pp. 2427-2451, March vol. 13, no. 3, pp. 1046-1056, June 2017.
2017.
[14] N. Mahmud, A. Zahedi and A. Mahmud, "A
[4] Y. Wang, K. T. Tan, X. Y. Peng and P. L. So, Cooperative Operation of Novel PV Inverter
"Coordinated Control of Distributed Energy- Control Scheme and Storage Energy
Storage Systems for Voltage Regulation in Management System Based on ANFIS for
Distribution Networks," in IEEE Transactions on Voltage Regulation of Grid-Tied PV System,"
Power Delivery, vol. 31, no. 3, pp. 1132-1141, in IEEE Transactions on Industrial Informatics,
June 2016. vol. 13, no. 5, pp. 2657-2668, Oct. 2017.
[5] M. Zeraati, M. E. Hamedani Golshan and J. M. [15] K. Hirata, H. Akutsu, A. Ohori, N. Hattori and Y.
Guerrero, "A Consensus-Based Cooperative Ohta, "Decentralized Voltage Regulation for PV
Control of PEV Battery and PV Active Power Generation Plants Using Real-Time Pricing
Curtailment for Voltage Regulation in Strategy," in IEEE Transactions on Industrial
Distribution Networks," in IEEE Transactions on Electronics, vol. 64, no. 6, pp. 5222-5232, June
Smart Grid, vol. 10, no. 1, pp. 670-680, Jan. 2017.
2019.
[16] P. H. Divshali, A. Alimardani, S. H. Hosseinian
[6] Y. Xu, W. Zhang, G. Hug, S. Kar and Z. Li, and M. Abedi, "Decentralized Cooperative
"Cooperative Control of Distributed Energy Control Strategy of Microsources for Stabilizing
Storage Systems in a Microgrid," in IEEE Autonomous VSC-Based Microgrids," in IEEE
Transactions on Smart Grid, vol. 6, no. 1, pp. Transactions on Power Systems, vol. 27, no. 4,
238-248, Jan. 2015. pp. 1949-1959, Nov. 2012.
[7] V. N. Lal and S. N. Singh, "Control and [17] M. Ghapandar Kashani, S. Bhattacharya, J.
Performance Analysis of a Single-Stage Utility- Matamoros, D. Kaiser and M. Cespedes,
Scale Grid-Connected PV System," in IEEE "Autonomous Inverter Voltage Regulation in a
Systems Journal, vol. 11, no. 3, pp. 1601-1611, Low Voltage Distribution Network," in IEEE
Sept. 2017. Transactions on Smart Grid, vol. 9, no. 6, pp.
6909-6917, Nov. 2018.
[8] Y. Yang, F. Blaabjerg, H. Wang and M. G.
Simões, "Power control flexibilities for grid- [18] F. Olivier, P. Aristidou, D. Ernst and T. Van
connected multi-functional photovoltaic Cutsem, "Active Management of Low-Voltage
inverters," in IET Renewable Power Generation, Networks for Mitigating Overvoltages Due to
vol. 10, no. 4, pp. 504-513, 4 2016. Photovoltaic Units," in IEEE Transactions on
Smart Grid, vol. 7, no. 2, pp. 926-936, March
[9] Y. Xu, H. Sun, W. Gu, Y. Xu and Z. Li, "Optimal
2016.
Distributed Control for Secondary Frequency and
Voltage Regulation in an Islanded Microgrid," [19] R. Tonkoski, L. A. C. Lopes and T. H. M. El-
in IEEE Transactions on Industrial Informatics, Fouly, "Coordinated Active Power Curtailment
vol. 15, no. 1, pp. 225-235, Jan. 2019. of Grid Connected PV Inverters for Overvoltage
Prevention," in IEEE Transactions on
[10] K. Kim, J. Kwon and B. Kwon, "Parallel
Sustainable Energy, vol. 2, no. 2, pp. 139-147,
operation of photovoltaic power conditioning
April 2011.
system modules for large-scale photovoltaic
power generation," in IET Power Electronics, [20] D.V. Bozalakov, J. Laveyne, J. Desmet, L.
vol. 7, no. 2, pp. 406-417, February 2014. Vandevelde, "Overvoltage and voltage unbalance
mitigation in areas with high penetration of
[11] M. Zolfaghari, S. H. Hosseinian, S. H. Fathi, M.
renewable energy resources by using the
Abedi and G. B. Gharehpetian, "A New Power
modified three-phase damping control strategy,"
Management Scheme for Parallel-Connected PV
Electric Power Systems Research, Vol.168,pp.
Systems in Microgrids," in IEEE Transactions on
283-294, March 2019.
Sustainable Energy, vol. 9, no. 4, pp. 1605-1617,
Oct. 2018. [21] W. Du, Q. Jiang, M. J. Erickson and R. H.
Lasseter, "Voltage-Source Control of PV Inverter
[12] H. Xin, Z. Lu, Z. Qu, D. Gan and D. Qi,
in a CERTS Microgrid," in IEEE Transactions
"Cooperative control strategy for multiple
on Power Delivery, vol. 29, no. 4, pp. 1726-1734,
photovoltaic generators in distribution networks,"
Aug. 2014.
in IET Control Theory & Applications, vol. 5, no.
14, pp. 1617-1629, 22 September 2011.
8
[22] M. Abdelkhalek Azzouz, H. E. Farag and E. F.
El-Saadany, "Real-Time Fuzzy Voltage
Regulation for Distribution Networks
Incorporating High Penetration of Renewable
Sources," in IEEE Systems Journal, vol. 11, no.
3, pp. 1702-1711, Sept. 2017.
[23] Zarina, P.P., S. Mishra, S.: 'Power oscillation
reduction contribution by PV in deloaded mode',
2016 IEEE 6th International Conference on
Power Systems (ICPS), New Delhi, March 2016,
pp. 1-4.
[24] Sang, S., Gao, N., Cai, X., & Li, R.: 'A Novel
Power-Voltage Control Strategy for the Grid-
Tied Inverter to Raise the Rated Power Injection
Level in a Weak Grid', IEEE Journal of
Emerging and Selected Topics in Power
Electronics, 2018, 6(1), pp.219–232.