Professional Documents
Culture Documents
Certificate of Calibration: Havatek Makina Sanayi Erbil-Iraq
Certificate of Calibration: Havatek Makina Sanayi Erbil-Iraq
Calibration Date Calibration Due Date Issue Date S.R.F No. & Date Certificate No.
17-05-2022 16-05-2023 19-05-2022 MQS/2022/113 & 15-05-2022 MQS/2022/113/17
A. Company Name and Address: B. Description and Identification of UUC*
Havatek Makina Sanayi Inst. Name Pressure Safety Valve
Erbil-Iraq Make/Model Crosby / 1D2JLTOS-E35J-N2
I.D. No. B1-PSV-25-237B
Sr. No. 1101-1907-200187
Range 0 to 22 bar
Resolution/L.C N/A*
Company ID C-008 Accuracy ± 3 % F.S
C. Environmental Condition Connection 1'' (IN) x 2'' (OUT)
Temperature 20.2 °C Calibration done at At Site
Relative Humidity 50.2 % RH Medium of Calibration Pneumatic
D. Details of Standard Used in Calibration
Sr. Serial No./ Source of
Instrument Name Make/Model Range Uncertainty Valid up to
No. ID No. Traceability
Digital Pressure Additel/ 211H19AB
1 0 to 70 bar ± 0.025 bar 28-04-2023 GAC
Gauge ADT681 0048
E. Principle/Methodology of Calibration:
Comparison Method as per Calibration Procedure CP/M-06 ,API-527,526
No.:
F. Results:
Set Pressure: (22 bar) Seat Pressure: (19.8 bar) Test Medium: Air
1. Safety Valve Components Pre-Conditions and Visual Inspection
(A) Fouling and Pitting (E) Body Condition ;
(B) Leaking Through Seat (F) Valve Jammed
(C) Bellow Leaking/Broken (G) Valve in Satisfactory State ;
(D) Spring Broken/Corroded (H) Seat Tightness ;
2. Pop Up Test
Expanded
Sr. No. Applied Range (bar) As Left
Uncertainty (±)
1 0.000 Not Popping Pass 0.03 bar
2 5.507 Not Popping Pass 0.03 bar
3 11.024 Not Popping Pass 0.03 bar
4 16.503 Not Popping Pass 0.03 bar
5 21.762 Popping Pass 0.03 bar
3. Seat Leakage Test
Applied Value Test Pressure Leakage Rate
Result
(bar) (bar) (Bubble/Minute)
19.811 19.8 0 Pass
The Reported Uncertainty at Coverage factor k = 2, and confidence level is 95 %
Remarks: 1) Reported values of standard are mean of 2 values
2) These Calibration Results comply with the requirements of ISO/IEC 17025:2017
3) At all Cal. Points UUC* readings are found within limits and hence calibration passes.
Page 1 of 2 Sarbasti (32 Park), 8th Avenue, Building No. 266, Erbil (Iraq)
E: support@miqias.com | www.miqias.com Security Number: 8885
Format: 7.8F-01 M: +964-7725579191, 7738218454
CERTIFICATE OF CALIBRATION
This Certificate refers only to the particular item submitted for calibration.
This certificate Shall not be reproduced except in full, without the written permission of the Laboratory
Results Reported are valid at the time of and under the stated condition of Measurement
Note: UUC* : Unit Under Calibration , N/A* : Not Applicable
Traceability: The Measurement was performed using traceable reference standards. The measurement made by
MIQIAS as reported in this certificate are traceable to S.I. unit through National/International Institutes
End of Calibration Results
Page 2 of 2 Sarbasti (32 Park), 8th Avenue, Building No. 266, Erbil (Iraq)
E: support@miqias.com | www.miqias.com Security Number: 8885
Format: 7.8F-01 M: +964-7725579191, 7738218454