Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

CERTIFICATE OF CALIBRATION

Calibration Date Calibration Due Date Issue Date S.R.F No. & Date Certificate No.
17-05-2022 16-05-2023 19-05-2022 MQS/2022/113 & 15-05-2022 MQS/2022/113/17
A. Company Name and Address: B. Description and Identification of UUC*
Havatek Makina Sanayi Inst. Name Pressure Safety Valve
Erbil-Iraq Make/Model Crosby / 1D2JLTOS-E35J-N2
I.D. No. B1-PSV-25-237B
Sr. No. 1101-1907-200187
Range 0 to 22 bar
Resolution/L.C N/A*
Company ID C-008 Accuracy ± 3 % F.S
C. Environmental Condition Connection 1'' (IN) x 2'' (OUT)
Temperature 20.2 °C Calibration done at At Site
Relative Humidity 50.2 % RH Medium of Calibration Pneumatic
D. Details of Standard Used in Calibration
Sr. Serial No./ Source of
Instrument Name Make/Model Range Uncertainty Valid up to
No. ID No. Traceability
Digital Pressure Additel/ 211H19AB
1 0 to 70 bar ± 0.025 bar 28-04-2023 GAC
Gauge ADT681 0048
E. Principle/Methodology of Calibration:
Comparison Method as per Calibration Procedure CP/M-06 ,API-527,526
No.:
F. Results:
Set Pressure: (22 bar) Seat Pressure: (19.8 bar) Test Medium: Air
1. Safety Valve Components Pre-Conditions and Visual Inspection
(A) Fouling and Pitting † (E) Body Condition ;
(B) Leaking Through Seat † (F) Valve Jammed †
(C) Bellow Leaking/Broken † (G) Valve in Satisfactory State ;
(D) Spring Broken/Corroded † (H) Seat Tightness ;
2. Pop Up Test
Expanded
Sr. No. Applied Range (bar) As Left
Uncertainty (±)
1 0.000 Not Popping Pass 0.03 bar
2 5.507 Not Popping Pass 0.03 bar
3 11.024 Not Popping Pass 0.03 bar
4 16.503 Not Popping Pass 0.03 bar
5 21.762 Popping Pass 0.03 bar
3. Seat Leakage Test
Applied Value Test Pressure Leakage Rate
Result
(bar) (bar) (Bubble/Minute)
19.811 19.8 0 Pass
The Reported Uncertainty at Coverage factor k = 2, and confidence level is 95 %
Remarks: 1) Reported values of standard are mean of 2 values
2) These Calibration Results comply with the requirements of ISO/IEC 17025:2017
3) At all Cal. Points UUC* readings are found within limits and hence calibration passes.
Page 1 of 2 Sarbasti (32 Park), 8th Avenue, Building No. 266, Erbil (Iraq)
E: support@miqias.com | www.miqias.com Security Number: 8885
Format: 7.8F-01 M: +964-7725579191, 7738218454
CERTIFICATE OF CALIBRATION

™ This Certificate refers only to the particular item submitted for calibration.
™ This certificate Shall not be reproduced except in full, without the written permission of the Laboratory
™ Results Reported are valid at the time of and under the stated condition of Measurement
Note: ™ UUC* : Unit Under Calibration , N/A* : Not Applicable
™ Traceability: The Measurement was performed using traceable reference standards. The measurement made by
MIQIAS as reported in this certificate are traceable to S.I. unit through National/International Institutes
End of Calibration Results

Accreditation No Certificate No. Certificate No. Certificate No.


CL-013 IAS2002Q1756 IAS2002E1757 IAS310301901

Calibrated by Checked By Authorised by


Calibration Engineer Quality Manager C.E.O / TM

Page 2 of 2 Sarbasti (32 Park), 8th Avenue, Building No. 266, Erbil (Iraq)
E: support@miqias.com | www.miqias.com Security Number: 8885
Format: 7.8F-01 M: +964-7725579191, 7738218454

You might also like