REF615 Over Current Test Format
REF615 Over Current Test Format
ELECTRICAL TESTS.
- FUNCTION TESTS.
1. Measurement Check
1.1 CURRENT MEASURMENT: ( C.T RATIO: A)
0.5
0.75
1
Note: Neutral Injection is Separate , - Current Tolerance= ± 1.5 %
25 % =16.59 1.04
50 %= 33.19 2.08
Relay
Setting Pick Up (A) Drop Off (A)
Stage
Is
R Y B R Y B
I>1 (PHLPTOC1) 1
I>> (PHHPTOC1) 2
I>>>(PHIPTOC1) 3
Pass Criteria
- ±1.5% of the set value or ±0.002 x In - Reset should occur at 0.95 Is. ±1.5%.
I>1 (PHLPTOC1) 1 3
I>> (PHHPTOC1) 2 1
I>>>(PHIPTOC1) 3 0.3
3- FINAL SETTINGS
DIRECTION :- NON-DIRECTIONAL
I> CURRENT SET ;-
TMS :-
OPERATING CURVE ;-
I>1 (PHLPTOC1)
DIRECTION :- NON-DIRECTIONAL
I>> CURRENT SET ;-
OPERATING TIME :-
I>>1 (PHHPTOC1)
DIRECTION :- NON-DIRECTIONAL
IN > E/F CURRENT SET ;-
TMS :-
OPERATING CURVE ;-
IN>1 (EFLPTOC1)
DIRECTION :- NON-DIRECTIONAL
IN>> E/F CURRENT SET ;-
OPERATING TIME :-
IN>>1 (EFHPTOC1)
LED FUNCTION
BI FUNCTION
X110- INPUT 1 CBF BLOCK
X110- INPUT 2 NOT USED
X110- INPUT 3 NOT USED
X110- INPUT 4 NOT USED
X110- INPUT 5 NOT USED
X110- INPUT 6 NOT USED
X110- INPUT 7 NOT USED
X120- INPUT 8 NOT USED
X120- INPUT 1 NOT USED
X120- INPUT 2 NOT USED
X120- INPUT 3 NOT USED
X120- INPUT 4 NOT USED
X130- INPUT 1 NOT USED
X130- INPUT 2 NOT USED
X130- INPUT 3 NOT USED
X130- INPUT 4 NOT USED
BO FUNCTION
X100- PO1 CBF STAGE-1 TRIP
X100- PO2 CBF STAGE-2 TRIP
X100- SO1 (SPARE)
X100- SO2 (SPARE)
X100- PO3 O/C & E/F TRIP
X100- PO4 (SPARE)
X110- SO1 O/C & E/F TRIP To Ann.
X110- SO2 (SPARE)
X110- SO3 (SPARE)
X110- SO4 O/C & E/F TRIP To DCS