Download as pdf or txt
Download as pdf or txt
You are on page 1of 17

EQIX CH3-6

SECTION 21 10 00 – FIRE SUPPRESSION SYSTEMS

PART 1 – GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following fire-suppression piping inside the building:

1. Wet-pipe sprinkler systems.


2. Double interlocked pre-action fire sprinkler systems.

B. Related Sections include the following:

1. Division 28 Section "Digital Addressable Fire Alarm" for alarm devices not specified in this Section.

1.3 SYSTEM DESCRIPTIONS

A. Wet-Pipe Sprinkler Systems: Automatic sprinklers are attached to piping water. Opening of sprinklers
releases water.

B. Pre-action Sprinkler System: Automatic sprinklers are attached to piping containing nitrogen. Actuation of
fire-detection system in same area as sprinkler fusing opens deluge valve, permitting water to flow into piping
and to discharge from sprinklers that have opened.

1.4 PERFORMANCE REQUIREMENTS

A. Standard Piping System Component Working Pressure: Listed for at least 175 psig.

B. Fire-suppression sprinkler system design shall be designed and installed in accordance with FM Global
requirements, and approved by authorities having jurisdiction.

1. Margin of Safety for Available Water Flow and Pressure: 10 psi, including losses through water-service
piping, valves, and backflow preventers.
2. Sprinkler Occupancy Hazard Classifications:

a. As per NFPA 13 or FM Global, whichever is more stringent.

3. Minimum Density for Automatic-Sprinkler Piping Design:

a. As per NFPA 13 or FM Global, whichever is more stringent.

4. Maximum Protection Area per Sprinkler:

a. As per NFPA 13 or as per UL listing and FM approval.

Date Issued: 09/27/2019 Section 21 10 00


Date Revised: Fire Suppression Systems
Rev. CONFIDENTIAL 1 of 17
EQIX CH3-6

C. Seismic Performance: Fire-suppression piping shall be capable of withstanding the effects of earthquake
motions determined according to NFPA 13 and ASCE 7, "Minimum Design Loads for Buildings and Other
Structures".

1.5 SUBMITTALS

A. Product Data: For the following:

1. Piping materials, including dielectric fittings, flexible connections, and sprinkler specialty fittings.
2. Pipe hangers and supports, including seismic restraints.
3. Valves, including listed fire-protection valves, unlisted general-duty valves, and specialty valves and
trim.
4. Sprinklers, escutcheons, and guards. Include sprinkler flow characteristics, mounting, finish, and other
pertinent data.
5. Alarm devices, including electrical data.
6. Pre-action system equipment. Include electrical data.
7. Nitrogen generation systems and piping systems for pre-action piping system pressurization.

B. Shop Drawings: Diagram power, signal, and control wiring.

C. Fire-hydrant flow test report.

D. Approved Sprinkler Piping Drawings: Working plans, prepared according to NFPA 13, that have been
approved by FM Global and authorities having jurisdiction, including hydraulic calculations, system materials,
and layout. Drawings shall also be approved by the Architect.

E. Field Test Reports and Certificates: Indicate and interpret test results for compliance with performance
requirements and as described in NFPA 13. Include "Contractor's Material and Test Certificate for
Aboveground Piping".

F. Welding certificates.

G. Field quality-control test reports.

H. Operation and Maintenance Data: For sprinkler specialties to include in emergency, operation, and
maintenance manuals.

1.6 QUALITY ASSURANCE

A. The Contractor is fully responsible for the integrity of the complete sprinkler piping systems, throughout this
project space.

B. Installer Qualifications:

1. Installer's responsibilities include designing, fabricating, and installing fire-suppression systems and
providing professional engineering services needed to assume engineering responsibility. Base
calculations on results of fire-hydrant flow test.

a. Engineering Responsibility: Preparation of working plans, calculations, and field test reports by
a qualified professional engineer.

C. Welding: Qualify processes and operators according to ASME Boiler and Pressure Vessel Code: Section IX.

Date Issued: 09/27/2019 Section 21 10 00


Date Revised: Fire Suppression Systems
Rev. CONFIDENTIAL 2 of 17
EQIX CH3-6

D. Standards: Fire-suppression-system equipment, specialties, accessories, installation, and testing shall


comply with the following:

1. NFPA 13, "Installation of Sprinkler Systems."


2. Latest edition of FM Global Approval Guide and FM Global Data Sheets.

1.7 COORDINATION

A. Coordinate layout and installation of sprinklers with other construction that penetrates ceilings, including light
fixtures, HVAC equipment, and partition assemblies.

1.8 EXTRA MATERIALS

A. Furnish extra materials described below that match products installed and that are packaged with protective
covering for storage and identified with labels describing contents.

1. Sprinkler Cabinets: Finished, wall-mounting, steel cabinet with hinged cover, with space for minimum
of six spare sprinklers plus sprinkler wrench. Include number of sprinklers required by NFPA 13 and
sprinkler wrench. Include separate cabinet with sprinklers and wrench for each type of sprinkler on
Project.

PART 2 – PRODUCTS

2.1 MANUFACTURERS

A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product
selection:

1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products


that may be incorporated into the Work include, but are not limited to, manufacturers specified.

2.2 STEEL PIPE AND FITTINGS

A. Threaded-End, Standard-Weight Steel Pipe: ASTM A 53/A 53M, ASTM A 135, or ASTM A 795, coated
interior for all piping systems, and with factory- or field-formed threaded ends.

1. Cast-Iron Threaded Flanges: ASME B16.1.


2. Malleable-Iron Threaded Fittings: ASME B16.3.
3. Steel Threaded Pipe Nipples: ASTM A 733, made of ASTM A 53/A 53M or ASTM A 106, Schedule 40,
seamless steel pipe. Include ends matching joining method.
4. Steel Threaded Couplings: ASTM A 865.

B. Grooved-End, Standard-Weight Steel Pipe: ASTM A 53/A 53M, ASTM A 135, or ASTM A 795, coated
interior for all piping systems, and with factory- or field-formed, square-cut- or roll-grooved ends.

1. Grooved-Joint Piping Systems:

a. Available Manufacturers:

1) Victaulic Co. of America.


2) Tyco Fire Suppression & Building Products/Grinnell Grooved Products.

Date Issued: 09/27/2019 Section 21 10 00


Date Revised: Fire Suppression Systems
Rev. CONFIDENTIAL 3 of 17
EQIX CH3-6

b. Grooved-End Fittings: UL-listed and FM approved, ASTM A 536, ductile-iron casting with OD
matching steel-pipe O.D.
c. Grooved-End-Pipe Couplings: UL 213 and AWWA C606, rigid pattern, unless otherwise
indicated; gasketed fitting matching steel-pipe OD. Include ductile-iron housing with keys
matching steel-pipe and fitting grooves, pre-lubricated rubber gasket listed for use with housing,
and steel bolts and nuts.

2.3 DIELECTRIC FITTINGS

A. Assembly shall be copper alloy, ferrous, and insulating materials with ends matching piping system.

B. Dielectric Unions: Factory-fabricated assembly, designed for 250-psig minimum working pressure at 180
deg F. Include insulating material that isolates dissimilar materials and ends with inside threads according to
ASME B1.20.1.

1. Available Manufacturers:

a. Capitol Manufacturing Co.


b. Central Plastics Company.
c. Epco Sales, Inc.
d. Hart Industries International, Inc.
e. Watts Industries, Inc.; Water Products Div.
f. Zurn Industries, Inc.; Wilkins Div.

C. Dielectric Flanges: Factory-fabricated companion-flange assembly, for 250-psig minimum working-pressure


rating as required for piping system.

1. Available Manufacturers:

a. Capitol Manufacturing Co.


b. Central Plastics Company.
c. Epco Sales, Inc.
d. Watts Industries, Inc.; Water Products Div.

2.4 SPRINKLER SPECIALTY FITTINGS

A. Sprinkler specialty fittings shall be UL listed and FMG approved, with 175-psig minimum working-pressure
rating, and made of materials compatible with piping.

B. Outlet Specialty Fittings:

1. Available Manufacturers:

a. Anvil International, Inc.


b. Tyco Fire Suppression & Building Products.
c. National Fittings, Inc.
d. Victaulic Co. of America.
e. Ward Manufacturing.

2. Mechanical-T and -Cross Fittings: UL 213, heavy duty, ductile-iron housing, with gaskets, bolts and
nuts (minimum of 2 bolts and nuts per fitting), and threaded or grooved outlets.

Date Issued: 09/27/2019 Section 21 10 00


Date Revised: Fire Suppression Systems
Rev. CONFIDENTIAL 4 of 17
EQIX CH3-6

C. Sprinkler Drain and Alarm Test Fittings: Cast- or ductile-iron body; with threaded inlet and outlet, test valve,
and orifice and sight glass.

1. Available Manufacturers:

a. Tyco Fire Suppression & Building Products.


b. Fire-End and Croker Corp.
c. Viking Corp.
d. Victaulic Co. of America.

D. Sprinkler Branch-Line Test Fittings: Brass body with threaded inlet, capped drain outlet, and threaded outlet
for sprinkler.

1. Available Manufacturers:

a. Elkhart Brass Mfg. Co., Inc.


b. Fire-End and Croker Corp.
c. Potter-Roemer; Fire-Protection Div.

E. Sprinkler Inspector's Test Fitting: Cast- or ductile-iron housing with threaded inlet and drain outlet and sight
glass.

1. Available Manufacturers:

a. AGF Manufacturing Co.


b. Tyco Fire Suppression & Building Products.
c. G/J Innovations, Inc.
d. Triple R Specialty of Ajax, Inc.

F. Dry-Pipe-System Fittings: UL listed and FM approved for dry-pipe service. Include Grade 'E' EPDM gaskets
on all dry piping systems.

2.5 LISTED FIRE-PROTECTION VALVES

A. Valves shall be UL listed and FMG approved, with 175-psig minimum pressure rating.

B. Ball Valves: Comply with UL 1091, except with ball instead of disc.

1. NPS 1-1/2 and Smaller: Bronze body with threaded ends.


2. NPS 2 and NPS 2-1/2: Bronze body with threaded ends or ductile-iron body with grooved ends.
3. NPS 3: Ductile-iron body with grooved ends.
4. Available Manufacturers:

a. NIBCO.
b. Victaulic Co. of America.

Date Issued: 09/27/2019 Section 21 10 00


Date Revised: Fire Suppression Systems
Rev. CONFIDENTIAL 5 of 17
EQIX CH3-6

C. Butterfly Valves: UL 1091.

1. NPS 2 and Smaller: Bronze body with threaded ends.

a. Available Manufacturers:

1) Global Safety Products, Inc.


2) Milwaukee Valve Company.

2. NPS 2-1/2 and Larger: Bronze, cast-iron, or ductile-iron body; wafer type or with flanged or grooved
ends.

a. Available Manufacturers:

1) Tyco Fire Suppression & Building Products.


2) Global Safety Products, Inc.
3) McWane, Inc.; Kennedy Valve Div.
4) Mueller Company.
5) NIBCO.
6) Pratt, Henry Company.
7) Victaulic Co. of America.

D. Check Valves NPS 2 and Larger: UL 312, swing type, cast-iron body with flanged or grooved ends.

1. Available Manufacturers:

a. Tyco Fire Suppression & Building Products.


b. NIBCO.
c. Potter-Roemer; Fire Protection Div.
d. Reliable Automatic Sprinkler Co., Inc.
e. Stockham.
f. Victaulic Co. of America.
g. Watts Industries, Inc.; Water Products Div.

E. Gate Valves: UL 262, OS&Y type.

1. NPS 2 and Smaller: Bronze body with threaded ends.

a. Available Manufacturers:

1) Crane Co.; Crane Valve Group; Crane Valves.


2) Hammond Valve.
3) NIBCO.
4) United Brass Works, Inc.

2. NPS 2-1/2 and Larger: Cast-iron body with flanged ends.

a. Available Manufacturers:

1) Clow Valve Co.


2) Crane Co.; Crane Valve Group; Crane Valves.
3) Crane Co.; Crane Valve Group; Jenkins Valves.
4) Hammond Valve.

Date Issued: 09/27/2019 Section 21 10 00


Date Revised: Fire Suppression Systems
Rev. CONFIDENTIAL 6 of 17
EQIX CH3-6

5) Milwaukee Valve Company.


6) Mueller Company.
7) NIBCO.
8) Tyco Fire Suppression & Building Products.

F. Indicating Valves: UL 1091, with integral indicating device and ends matching connecting piping.

1. Indicator: Electrical, 115-V ac, prewired, 2-circuit, supervisory switch.


2. NPS 2 and Smaller: Ball or butterfly valve with bronze body and threaded ends.

a. Available Manufacturers:

1) Milwaukee Valve Company.


2) NIBCO.
3) Victaulic Co. of America.
4) Tyco Fire Suppression & Building Products.

3. NPS 2-1/2 and Larger: Butterfly valve with cast- or ductile-iron body; wafer type or with flanged or
grooved ends.

a. Available Manufacturers:

1) Tyco Fire Suppression & Building Products.


2) McWane, Inc.; Kennedy Valve Div.
3) Milwaukee Valve Company.
4) NIBCO.
5) Victaulic Co. of America.

G. Backflow Preventer Assembly: UL Listed, FM approved.

1. Provide backflow preventer assembly with flanged connections, UL listed and FMG approved resilient-
seated outside screw and yoke (OS&Y) gate valves and test cocks per assembly’s listing and approval.

2.6 UNLISTED GENERAL-DUTY VALVES

A. Ball Valves NPS 2 and Smaller: MSS SP-110, 2-piece copper-alloy body with chrome-plated brass ball, 600-
psig minimum CWP rating, blowout-proof stem, and threaded ends.

B. Check Valves NPS 2 and Smaller: MSS SP-80, Type 4, Class 125 minimum, swing type with bronze body,
nonmetallic disc, and threaded ends.

C. Gate Valves NPS 2 and Smaller: MSS SP-80, Type 2, Class 125 minimum, with bronze body, solid wedge,
and threaded ends.

D. Globe Valves NPS 2 and Smaller: MSS SP-80, Type 2, Class 125 minimum, with bronze body, nonmetallic
disc, and threaded ends.

Date Issued: 09/27/2019 Section 21 10 00


Date Revised: Fire Suppression Systems
Rev. CONFIDENTIAL 7 of 17
EQIX CH3-6

2.7 SPECIALTY VALVES

A. Sprinkler System Control Valves: UL listed and FMG approved, cast- or ductile-iron body with flanged or
grooved ends, and 175-psig minimum pressure rating.

1. Available Manufacturers:

a. Tyco Fire Suppression & Building Products.


b. Firematic Sprinkler Devices, Inc.
c. Globe Fire Sprinkler Corporation.
d. Reliable Automatic Sprinkler Co., Inc.
e. Victaulic Co. of America.
f. Viking Corp.

B. Automatic Drain Valves: UL 1726, NPS 3/4, ball-check device with threaded ends.

1. Available Manufacturers:

a. AFAC Inc.
b. Grinnell Fire Protection.

2.8 SPRINKLERS

A. Sprinklers shall be UL listed and FMG approved, with 175-psig minimum pressure rating.

B. Available Manufacturers:

1. Tyco Fire Suppression & Building Products.


2. Reliable Automatic Sprinkler Co., Inc.
3. Victaulic Co. of America.
4. Viking Corp.

C. Automatic Sprinklers: With heat-responsive element complying with the following:

1. UL 199, for nonresidential applications.


2. UL 1767, for early-suppression, fast-response applications.

D. Sprinkler Types and Categories: Nominal 1/2-inch orifice for "Ordinary" temperature classification rating,
unless otherwise indicated or required by application.

E. Sprinkler Characteristics: As indicated on the drawings.

F. Sprinkler Finishes: As indicated on the drawings.

G. Special Coatings: Wax, lead, and corrosion-resistant paint.

H. Sprinkler Escutcheons: Materials, types, and finishes for the following sprinkler mounting applications.
Escutcheons for concealed, flush, and recessed-type sprinklers are specified with sprinklers.

1. Ceiling Mounting: 2 piece, with 1-inch.


2. Sidewall Mounting: 1 piece, flat.

I. Sprinkler Guards: Wire-cage type, including fastening device for attaching to sprinkler.

Date Issued: 09/27/2019 Section 21 10 00


Date Revised: Fire Suppression Systems
Rev. CONFIDENTIAL 8 of 17
EQIX CH3-6

2.9 FIRE DEPARTMENT CONNECTIONS

A. Available Manufacturers:

1. Elkhart Brass Mfg. Co., Inc.


2. Fire-End and Croker Corp.
3. Guardian Fire Equipment Incorporated.
4. Potter-Roemer; Fire-Protection Div.
5. Reliable Automatic Sprinkler Co., Inc.

B. Flush-type, Fire Department Connection: UL 405, 175-psig minimum pressure rating; with corrosion-
resistant-metal body with brass inlets, brass lugged caps with gaskets and brass chains, and brass lugged
swivel connections. Include inlets with threads according to NFPA 1963 and matching local fire department
sizes and threads, outlet with pipe threads, extension pipe nipples, check devices or clappers for inlets, and
escutcheon plate with marking, or placard, similar to "AUTO SPRINKLERS" for preaction systems.

2.10 ALARM DEVICES

A. Alarm-device types shall match piping and equipment connections.

B. Water-Flow Indicator: UL 346, electrical-supervision, paddle-operated-type, water-flow detector with 175-


psig pressure rating and designed for horizontal or vertical installation. Include two single-pole, double-throw
circuit switches for isolated alarm and auxiliary contacts, 7 A, 125-V ac and 0.25 A, 24-V dc; complete with
factory-set, field-adjustable retard element to prevent false signals and tamperproof cover that sends signal
if removed.

1. Available Manufacturers:

a. ITT McDonnell & Miller.


b. Potter Electric Signal Company.
c. System Sensor.
d. Viking Corp.
e. Watts Industries, Inc.; Water Products Div.

C. Valve Supervisory Switch: UL 753, electrical, single-pole, double-throw switch with normally closed contacts.
Include design that signals controlled valve is in other than fully open position.

1. Available Manufacturers:

a. McWane, Inc.; Kennedy Valve Div.


b. Potter Electric Signal Company.
c. System Sensor.

2.11 PRESSURE GAGES

A. Available Manufacturers:

1. AGF Manufacturing Co.


2. AMETEK, Inc.; U.S. Gauge.
3. Brecco Corporation.
4. Dresser Equipment Group; Instrument Div.
5. Marsh Bellofram.
6. WIKA Instrument Corporation.

Date Issued: 09/27/2019 Section 21 10 00


Date Revised: Fire Suppression Systems
Rev. CONFIDENTIAL 9 of 17
EQIX CH3-6

B. Description: UL 393, 3-1/2- to 4-1/2-inch- diameter, dial pressure gage with range of 0 to 250 psig.

1. Water System Piping: Include caption "WATER" on dial face.

2.12 PACKAGED DOUBLE INTERLOCK PREACTION SPRINKLER MODULAR SYSTEM

A. Packaged preaction modular system specifications have been taken from the catalogs of Victaulic Co. of
America. Equipment of other manufacturers will be acceptable, provided dimensions of the cabinets are
coordinated with the room dimensions for required layout of all of the systems, and proper service area is
maintained. A complete list of comparable equipment, and shop drawings indicating the fire protection room
cabinet layout, shall be submitted to the Engineer for approval prior to placing the order.

B. Preaction system riser components shall be installed in a 12 gauge steel cabinet with removable back and
side panels for service access, Victaulic Series 745, or equal to. The Fire-Pac shall be provided with a
standard releasing panel PDRP-2001, including power supply, standby batteries and a battery charger,
connections for the smoke detection systems, waterflow and tamper switches, and the solenoid valve. The
cabinet shall house a Victaulic series 769-EPA double interlock electric/pneumatic release valve, of size
required for each sprinkler zone as per hydraulic calculations. The valve trim assembly to include a series
767 Pneumatic / Electric DI LP actuator (solenoid integral), System drain valves, system control valve w/
tamper switch, alarm line pressure switches, air supervisory pressure switches, supervisory pump switches,
and pressure gauges which shall be easily viewed through a window in the cabinet door. Provide
maintenance trim assembly for use with nitrogen piping interconnection. The Fire-Pac shall be UL listed and
FM approved. Nitrogen will be used to maintain system pressure at 18-25 PSI, or pressure recommended
by the Nitrogen Generation Equipment Supplier, in conjunction with the Fire-Pac. Wiring to cabinet shall be
Standard (US) UL-Class B.

C. Smoke detection system for release interface will be furnished, mounted, and wired under the Division 28
Contract.

D. All conduit and wiring systems, associated with the smoke detection systems, will be furnished and installed
under the Division 28 Contract.

E. E. All power wiring, 120 volt and greater will be provided under the Electrical Contract.

2.13 NITROGEN PRESSURIZATION FOR DRY AND PREACTION PIPING SYSTEMS

A. Description of Work

1. Provide all required labor, materials, equipment and services necessary for a complete and operational
Corrosion Management Program for the fire protection system(s) (FPS) as hereinafter described and
as indicated on the drawings.

B. Corrosion Management Work shall include the following listed products and services:

1. Corrosion Management Products shall be as specified herein:

a. ECS Protector - Nitrogen Generation System (PGEN-30) equipped with ECS Protector
Automatic AirVent(s) (PAV-W).

2. ECS Inspector - Corrosion Monitoring Station(s) (ICMS).


3. ECS Detector - Corrosion Monitoring Probe(s) (DCMP).
4. ECS Protector - Gas Analyzer (PGA-1).
5. Installation of air compressor and FPS air maintenance device.

Date Issued: 09/27/2019 Section 21 10 00


Date Revised: Fire Suppression Systems
Rev. CONFIDENTIAL 10 of 17
EQIX CH3-6

6. Miscellaneous piping, fittings, couplings, valves, etc. as required.


7. Water testing.
8. Coordination of work and schedules with other trades.
9. System pressure testing.

C. References

1. All corrosion management work shall be designed, installed inspected, tested and maintained in
accordance with all applicable codes, referenced standards, documents listed herein, the
manufacturer’s instructions and the provisions of this specification:

a. NFPA 13, Standard for Installation of Sprinkler Systems - 2010 Edition


b. NFPS 25, Standard for the Inspections, Testing and Maintenance of Water-Based Fire
Protection Systems - 2011 Edition.
c. FM Data Sheets
d. FM Approval Guide

D. Engineered Corrosion Solutions – ECS Protector - Nitrogen Generation System (PGEN-30) Refer to
engineering drawings for quantity and locations:

1. The fire sprinkler contractor shall furnish and install the ECS Protector - Nitrogen Generation Systems
(PNGS) at the locations indicated on the design documents or as directed by the design engineer.
Install per manufacturer’s instructions.
2. The ECS Protector – Nitrogen Generation System (PNGS(s)) must be installed with a compressor
sized appropriately for the application and capable of achieving system pressure within 30 minutes in
accordance with NFPA 13. When the ECS Protector and the compressor are serving more than a
single FPS, a larger capacity or multiple compressors may be required.
3. The Nitrogen Generation System shall be designed to achieve a nitrogen concentration of 95% or
greater and maintain that concentration within the FPS continuously. The output nitrogen quality shall
be monitored by ECS Protector Electronic Gas Stream Analyzers.
4. The fire sprinkler contractor shall install the provided ECS Protector Automatic AirVents (PNGS-V) at
the locations shown on the commissioning drawings provided by fpsCMI.
5. Provide fpsCMI Consulting Service Package for commissioning of the ECS Protector - Nitrogen
Generation System.

E. Air Compressor - Refer to engineering drawings for quantity and locations:

1. Furnish and install an air compressor to serve the fire protection system and the ECS Protector. The
air compressor shall have a dedicated un-switched power source of 460V/ 3 Phase/60Hz. Specified
unit is 5HP.
2. Air compressor shall be rated by the manufacturer for continuous duty service.
3. Air compressor shall have an output pressure rating of at least 100 psi.
4. Air compressor shall be capable of producing a continuous volume of compressed air that is sufficient
to meet the design requirements of the fire protection system and the ECS Protector – Nitrogen
Generation System.
5. Air compressor shall be equipped with an air receiver tank of 60 gallons.
6. Air compressor shall be equipped with an automatic blow down device that automatically empties
condensed water from the air receiver tank. This water discharge shall be piped to a drain.
7. Air compressor shall be connected to the ECS Protector – Nitrogen Generator and from the ECS
Protector to the fire protection system’s air maintenance device with metal piping that is at least 1/2 in.
diameter.
8. Compressor shall be the Ingersoll-Rand Model 2340L5, or equal to.

Date Issued: 09/27/2019 Section 21 10 00


Date Revised: Fire Suppression Systems
Rev. CONFIDENTIAL 11 of 17
EQIX CH3-6

F. Air Maintenance Device - Refer to engineering drawings for quantity and locations:

1. Air Maintenance Device shall be equipped with a field adjustable pressure regulator for use in setting
the maximum system pressure.
2. Air Maintenance Device shall be installed per the manufacturer’s instructions.

G. Engineered Corrosion Solutions - ECS Inspector – Corrosion Monitoring Station (ICMS) Refer to engineering
drawings for quantity and locations:

1. Furnish and install ECS Inspector – Corrosion Monitoring Station (ICMS(s)); for each automatic
sprinkler system provided in the project or at the locations indicated on the design documents when
shown. Install per manufacturer’s instructions. The fire sprinkler contractor shall confirm that the
manufacturer installed corrosion monitoring coupons and the ECS Detector – Corrosion Monitoring
Probe (DCMP) when specified, are installed in the ICMS when received. Verification shall be made by
viewing the devices through the sight glasses at the ends of the ICMS. The contractor shall not remove
the DCMP or corrosion monitoring coupons from the ICMS during the installation process.
2. Install the ECS Inspector – Corrosion Monitoring Station on the system side of the preaction valve
cabinet and a minimum of 3 feet above the cabinet.
3. After the installation of the ECS Inspector – Corrosion Monitoring Station and the ECS Detector –
Corrosion Monitoring Probe (DCMP) when specified, the isolation valve to the FPS shall be placed in
the open position including when filling the system for final hydrostatic testing or any testing allowing
water flow into the FPS.
4. The ECS Inspector – Corrosion Monitoring Station is assembled by the manufacturer and only requires
the contractor to connect two (2) parts at the provided coupling to achieve full assembly.

H. Engineered Corrosion Solutions – ECS Detector – Corrosion Monitoring Probe (DCMP) Refer to engineering
drawings for quantity and locations:

1. Furnish and install ECS Detector – Corrosion Monitoring Probe (DCMP(s)), at each of the provided
ECS Inspector – Corrosion Monitoring Station (ICMS-1). Install per manufacturer’s instructions.
2. The fire sprinkler contractor shall confirm that the corrosion monitoring probe for each fire protection
system is installed in each ECS Inspector (ICMS(s)); the ECS Detector will be installed by the
manufacturer when it is ordered with the ECS Inspector - Corrosion Monitoring Station. Verification
shall be made by viewing the devices through the sight glasses at the ends of the ICMS. The contractor
shall not remove the DCMP or corrosion monitoring coupons from the ICMS during the installation
process.
3. Connect the ECS Detector – Corrosion Monitoring Probe to a dedicated supervisory circuit on the
building fire alarm system.

I. Engineered Corrosion Solutions - ECS Protector - Gas Analyzer (PGA-1): Furnish and install ECS Protector
- Gas Analyzer (PGA-1) with each ECS Protector - Nitrogen Generation System (PGEN-30). Install per
manufacturer’s instructions. Refer to engineering drawings for quantity and locations:

1. The fire sprinkler contractor shall permanently mount the ECS Protector - Gas Analyzer to a vertical
wall within 20 feet of the ECS Protector - Automatic AirVent that will serve as the source for the fire
sprinkler system gas to be analyzed.
2. The fire alarm (Division 28) contractor shall provide the 24v DC power supply and the 0-5v DC signal
output line in a 1/2” conduit which connects to 7/8” inlet port on top of ECS Protector - Gas Analyzer
enclosure.
3. The fire sprinkler contractor shall attach and affix 5/32” gas supply tubing from quick connect fitting on
the ECS Protector - Automatic AirVent to corresponding quick connect fitting on the ECS Protector -
Gas Analyzer.

Date Issued: 09/27/2019 Section 21 10 00


Date Revised: Fire Suppression Systems
Rev. CONFIDENTIAL 12 of 17
EQIX CH3-6

4. The fire alarm (Division 28) contractor shall connect the 0-5v DC signal output line to the dedicated
supervisory circuit on the building fire alarm system.

J. Engineered Corrosion Solutions - ECS Protector Automatic Air Vent (PAV-W): Furnish and install ECS
Protector - Automatic Air Vent (PAV-W) for each fire protection zone in the project. Automatic air vents shall
be installed a remote ends of the zone piping system. Refer to drawings for required locations. Install per
manufacturer’s instructions. Refer to engineering drawings for quantity and locations:

PART 3 – EXECUTION

3.1 PREPARATION

A. Perform fire-hydrant flow test according to NFPA 13 and NFPA 291. Use results for system design
calculations required in Part 1 "Quality Assurance" Article.

B. Report test results promptly and in writing.

3.2 PIPING APPLICATIONS, GENERAL

A. Shop weld pipe joints where welded piping is indicated.

B. Flanges, flanged fittings, unions, nipples, and transition and special fittings with finish and pressure ratings
same as or higher than system's pressure rating may be used in aboveground applications, unless otherwise
indicated.

3.3 SPRINKLER SYSTEM PIPING APPLICATIONS

A. Standard-Pressure, Wet Fire Line and Preaction Sprinkler System, 250-psig Maximum Working Pressure,
(Piping shall be as manufactured by Allied Tube with "ABF II" interior coating, or equal to): Use any of the
following:

1. Sprinkler-Piping Fitting Option: Specialty sprinkler fittings, NPS 3 and smaller, including heavy duty
mechanical-T and -cross fittings, may be used downstream from sprinkler zone valves.
2. 2" and Smaller: Threaded-end, black with coated interior, standard-weight (Schedule 40) steel pipe;
cast- or malleable-iron threaded fittings; and threaded joints.
3. NPS 2-1/2 to NPS 6: Grooved-end, black with coated interior, standard-weight (Schedule 40) steel
pipe; grooved-end fittings; grooved-end-pipe couplings; and grooved joints.

3.4 VALVE APPLICATIONS

A. Drawings indicate valve types to be used. Where specific valve types are not indicated, the following
requirements apply:

1. Listed Fire-Protection Valves: UL listed and FMG approved for applications where required by
NFPA 13.

a. Shutoff Duty: Use ball, butterfly, or gate valves.

2. Unlisted General-Duty Valves: For applications where UL-listed and FMG-approved valves are not
required by NFPA 13.

a. Shutoff Duty: Use ball, butterfly, or gate valves.

Date Issued: 09/27/2019 Section 21 10 00


Date Revised: Fire Suppression Systems
Rev. CONFIDENTIAL 13 of 17
EQIX CH3-6

3.5 JOINT CONSTRUCTION

A. Refer to Division 21 Section "Common Work Results for Fire Protection" for basic piping joint construction.

B. Threaded Joints: Comply with NFPA 13 for pipe thickness and threads. Do not thread pipe smaller than
NPS 8 with wall thickness less than Schedule 40 unless approved by authorities having jurisdiction and
threads are checked by a ring gage and comply with ASME B1.20.1.

C. Grooved Joints: Assemble joints with listed coupling and gasket, lubricant, and bolts.

1. Steel Pipe: Square-cut or roll-groove piping as indicated. Use grooved-end fittings and rigid, grooved-
end-pipe couplings, unless otherwise indicated.
2. Dry-Pipe Systems: Use fittings and gaskets listed for dry-pipe service.

D. Dissimilar-Metal Piping Joints: Construct joints using dielectric fittings compatible with both piping materials.

1. NPS 2 and Smaller: Use dielectric unions, couplings, or nipples.


2. NPS 2-1/2 to NPS 4: Use dielectric flanges.
3. NPS 5 and Larger: Use dielectric flange insulation kits.

3.6 WATER-SUPPLY CONNECTION

A. Connect new fire-suppression piping to new building fire service in fire protection service room downstream
of the backflow preventer.

3.7 PIPING INSTALLATION

A. Refer to Division 21 Section "Common Work Results for Fire Protection" for basic piping installation.

B. Locations and Arrangements: Drawing plans, schematics, and diagrams indicate general location and
arrangement of piping. Install piping as indicated, as far as practical.

1. Deviations from approved working plans for piping require written approval from authorities having
jurisdiction. File written approval with Architect before deviating from approved working plans.

C. Use approved fittings to make changes in direction, branch takeoffs from mains, and reductions in pipe sizes.

D. Install unions adjacent to each valve in pipes NPS 2 and smaller. Unions are not required on flanged devices
or in piping installations using grooved joints.

E. Install flanges or flange adapters on valves, apparatus, and equipment having NPS 2-1/2 and larger
connections.

F. Install "Inspector's Test Connections" in sprinkler system piping, complete with shutoff valve, sized and
located according to NFPA 13.

G. Install sprinkler piping with drains for complete system drainage.

H. Connect nitrogen supply to preaction sprinkler system cabinet.

I. Install alarm devices in piping systems.

Date Issued: 09/27/2019 Section 21 10 00


Date Revised: Fire Suppression Systems
Rev. CONFIDENTIAL 14 of 17
EQIX CH3-6

J. Hangers and Supports: Comply with NFPA 13 for hanger materials.

1. Install sprinkler system piping according to NFPA 13.

K. Install pressure gages on riser or feed main, and at each sprinkler test connection. Include pressure gages
with connection not less than NPS 1/4 and with soft metal seated globe valve, arranged for draining pipe
between gage and valve. Install gages to permit removal, and install where they will not be subject to freezing.

L. Pressurize and check preaction sprinkler system piping and nitrogen tanks.

M. Drain preaction sprinkler piping. Contractor shall use nitrogen to blow all moisture from the piping system.
After all moisture removal and closing of system, pressurize and check dry-pipe sprinkler system piping and
air compressor/nitrogen generation system.

N. All preaction sprinkler piping shall be sloped, and provide low point draining away from electrical equipment.

3.8 VALVE INSTALLATION

A. Install listed fire-protection valves, unlisted general-duty valves, specialty valves and trim, controls, and
specialties according to NFPA 13 and authorities having jurisdiction.

B. Install listed fire-protection shutoff valves supervised-open, located to control sources of water supply except
from fire department connections. Install permanent identification signs indicating portion of system
controlled by each valve.

C. Install check valve in each water-supply connection. Install backflow preventers instead of check valves in
potable-water supply sources.

3.9 SPRINKLER APPLICATIONS

A. Drawings indicate types and characteristics of sprinklers to be used.

3.10 SPRINKLER INSTALLATION

A. Install sprinklers in suspended ceilings in center of acoustical ceiling panels and tiles, where tiles are to be
installed.

B. Do not install pendent or sidewall, wet-type sprinklers in areas subject to freezing. Use dry-type sprinklers
with water supply from heated space.

C. Sprinkler wire guards shall be installed on all sprinklers in all Mechanical and Electrical areas.

3.11 FIRE DEPARTMENT CONNECTION INSTALLATION

A. Install flush-type, fire department connection(s) where indicated.

B. Install ball drip valve at each check valve for fire department connection.

3.12 CONNECTIONS

A. Drawings indicate general arrangement of piping, fittings, and specialties.

Date Issued: 09/27/2019 Section 21 10 00


Date Revised: Fire Suppression Systems
Rev. CONFIDENTIAL 15 of 17
EQIX CH3-6

B. Install piping adjacent to equipment to allow service and maintenance.

C. Connect water-supply piping to fire-suppression piping.

D. Connect piping to specialty valves, specialties, and accessories.

E. Electrical Connections: Power wiring is specified in Division 26.

F. Connect alarm devices to fire alarm.

G. Ground equipment according to Division 26 Sections.

H. Connect wiring according to Division 26 Sections.

I. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values.
If manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B.

J. Connect nitrogen supply to preaction sprinkler piping systems. Adjust pressures as per manufacturer's
instructions and recommendations.

3.13 LABELING AND IDENTIFICATION

A. Install labeling and pipe markers on equipment and piping according to requirements in NFPA 13.

B. All exposed sprinkler piping shall be painted red.

3.14 FIELD QUALITY CONTROL

A. Perform the following field tests and inspections and prepare test reports:

1. Leak Test: After installation, charge system and test for leaks. All piping and attached appurtenances
subjected to system working pressure shall be hydrostatically tested at 200 psi and shall maintain that
pressure without loss for 2 hours. NOTE: Repair leaks and retest until no leaks exist. Installations will
not be approved until systems are confirmed to be free of leakage.
2. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.
3. Energize circuits to electrical equipment and devices.
4. Flush, test, and inspect sprinkler systems according to NFPA 13, "Systems Acceptance" Chapter. Test
for leaks as hereinbefore specified.
5. Start and run air compressors, part of nitrogen generation system.
6. Coordinate with fire alarm tests. Operate as required.
7. Verify that equipment hose threads are same as local fire department equipment.

B. Report test results promptly and in writing to Architect and authorities having jurisdiction.

3.15 SUPERVISION AND TRAINING FOR NITROGEN PRESSURIZATION SYSTEMS

A. fpsCMI shall provide on-site supervision and training during the execution of the fpsCMI Consulting Services
Package for Commissioning.

B. Contact Product Specification Staff at fpsCMI, 1850 Craigshire Rd., Suite 302, St. Louis, MO 63146, phone
314-432-1377, e-mail: pss@fpsCMI.com to schedule Commissioning at least 2 weeks in advance.

Date Issued: 09/27/2019 Section 21 10 00


Date Revised: Fire Suppression Systems
Rev. CONFIDENTIAL 16 of 17
EQIX CH3-6

3.16 CORROSION PRODUCTS AND COMMISSIONING PROTOCOL FOR NITROGEN PRESSURIZATION


SYSTEMS

A. Preaction FPS:

1. The fire sprinkler contractor shall install all the ECS Protector Automatic AirVent(s) at the locations
shown on the design documents or the commissioning protocol. The isolation valve of the ECS
Protector Automatic AirVent(s) shall be closed during hydrostatic and air pressure testing of the FPS
and then placed in the open position for the commissioning and operation of the system.
2. The fire sprinkler contractor shall confirm the isolation valve to the ECS Inspector - Corrosion
Monitoring Station (ICMS) is in the open position during and after hydrostatic and air pressure testing
and that no water remains in the ICMS when the system is placed in service.
3. The fire sprinkler contractor shall confirm the ECS Detector - Corrosion Monitoring Probe installed in
the ECS Inspector - Corrosion Monitoring Station has been wired to the monitoring system specified.
4. The fire sprinkler contractor shall confirm the operation of the system air compressor and then connect
the air compressor and the nitrogen generator to the FPS.
5. The fire sprinkler contractor shall determine the operating pressure range for the dry pipe (preaction)
FPS and set the system air maintenance device to the correct setting.
6. The fire sprinkler contractor shall confirm the air maintenance device is taken out of the fast fill (by-
pass) setting when the system is placed in service.
7. The fire sprinkler contractor shall confirm the water discharge from the air compressor drain and the
ECS Protector Nitrogen Generator water drain(s) are piped to the appropriate facility water drain piping
as per the instructions in the fpsCMI Commissioning Protocol.
8. The fire sprinkler contractor shall have fpsCMI as a portion of the Consulting Services Package
establish and record the final pressure range settings on the ECS Protector Nitrogen Generator to
coordinate with the FPS operational pressure ranges.
9. The fire sprinkler contractor shall confirm the ECS Protector - Automatic Air Vents are installed and
that the back pressure regulator is set for a pressure to close above the lower air pressure limits of the
FPS and that the isolation valve to the system is open.
10. The fire sprinkler contractor shall install the ECS - Protector Gas Analyzer (PGA) at a location within
20 feet of the FPS connection (ECS Protector - Automatic Air Vent) at a location approved by the
design engineer and make connections from the FPS and the PGA as required by the Manufacturer's
Instruction.
11. The fire sprinkler contractor shall perform a site inspection after the final installation of the ECS
Protector - Nitrogen Generation System as a follow-up based on a schedule determined as a portion
of the commissioning of the system. Adjustments to the setting of the system may be required.

3.17 CLEANING AND PROTECTION

A. Clean dirt and debris from sprinklers.

B. Remove and replace sprinklers with paint other than factory finish.

C. Protect sprinklers from damage until Substantial Completion.

END OF SECTION

Date Issued: 09/27/2019 Section 21 10 00


Date Revised: Fire Suppression Systems
Rev. CONFIDENTIAL 17 of 17

You might also like