60% RH ± 5% 24 ± 1°C Residential Tower, Common Areas that are air 60% RH ± 5% conditioned.
iii. Minimum Supply Air Quantity (l/s/m²)
Based on the E20 Carrier cooling load calculations software.
iv. Minimum Outdoor Air Quantity (l/s/m²)
5.5 L/s per person
v. Cooling Load Estimation
a. External load - Glazing System
The following glazing data has been assumed for preliminary load estimation:
Glazing Type 6mm Single Glazing
• U-Value (w/m2 K) 6.2 • Shading Coefficient 0.71 • Vision area for glazing 30% for Podium 40% for Residential Tower 50% for Office • U-Value for non-vision area 2.5 w/m2 K