Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

The

Commander
Series

TDM Universal Time Delay Module INSTALLATION INSTRUCTIONS

Section 1 Figure 2: Simple Time Delayed Output


General Description Figure 3: Electric Lock & Door Operator Sequencing
The TDM is a multipurpose timing module that can be Figure 4: Vestibule Door Sequencing
used for a variety of applications. Its unique design and Detailed Operating Display functions for the TDM are
open architecture allows the TDM to be used in any shown in Figure 5. For additional technical assistance,
application that requires timing control of up to two contact us toll free at 1-317-842-2545.
outputs with up to four inputs. Common applications
include: simple time delay, vestibule door sequencing Figure 5: TDM Operating Display Function
(only one device required) and electric lock/automatic
door operator sequencing. NOTICE: These instructions are provided for your

The four inputs on the TDM allow sequencing or ! convenience. Please verify your installation is in
compliance with all applicable standards upon
independent operation of the two outputs. Input 1 will completing installation of this device.
sequence Outputs 1 then 2. Input 2 will sequence
Outputs 2 then 1. Input 3 will operate Output 1
independently. Input 4 will operate Output 2 Section 3
independently. Technical Data
Model....................................... TDM
Both outputs on the TDM are fully programmable for "on Input Power.............................. 12-24V AC or DC
time" duration as well as the delay time between the two Power Consumption................ 2W Maximum
outputs from 0 to 99 seconds. Output Contacts.......................Form C, Rated at 3 Amps
Relay Contact Rating............... 3A:120V AC; 3A:60V DC
WARNING: Devices to be controlled by the TDM
!
Temperature Rating................ -22°F to 158°F
must be low voltage (12-24V) but can be (-30°C to 70°C)
inductive loads. Surge suppressors are standard Weight...................................... <0.25 lbs.
on the TDM. Physical Size............................ 4.75"L x 2.125"W x 0.75"H

WET/DRY CONTACT OPTION:


The TDM has the option to supply power to Relay Output Section 4
1 contacts. This is known as having a "Wet" contact Warranty
instead of the conventional "Dry" contact closure. To use MS SEDCO guarantees this product to be free from manufacturing
output 1 as a "Wet" contact, change the jumper setting defects for 1 year from date of installation. Unless MS SEDCO is
(see Figure 1). The voltage supplied to Output 1 will be notified of the date of installation, the warranty will be in effect for
the same as the voltage supplied to the input power wires 1 year from the date of shipment from our factory. If, during the
of the TDM. first year, this device fails to operate and has not been tampered
with or abused, the unit can be returned prepaid to factory and it
will be repaired free of charge. After 1 year, the unit will be
WARNING: Changing jumper settings to enable
!
repaired for a nominal service charge. This limited warranty is in
the “Wet” Contact option will apply a voltage to lieu of all other warranties expressed or implied, including any
the Output 1 relay contact. Please ensure that implied warranty of merchantability, and no representative or
any device connected to this output is capable of person is authorized to assume for MS SEDCO any other liability
accepting voltage. Failure to do so may result in in connection with the sale of our products. All warranties are
limited to the duration of this written warranty. In no event
damage to the device.
shall MS SEDCO be liable for any special, incidental,
consequential or other damages arising from any claimed
breach of warranty as to its products or services.
Section 2
Basic Installation
1. Mount the TDM in desired location. Questions? Call us toll-free at 1-317-842-2545 or
2. With power off, make all necessary wiring visit us online at www.mssedco.com.
connections to the wiring harnesses (Fig. 1).
Figure 1: TDM Layout and Wiring Connections
Detailed wiring and programming instructions for three
common applications are included.
8701 Castle Park Drive  Indianapolis, Indiana 46256 Page 1
Telephone: (317) 842-2545  www.mssedco.com  custsvc@mssedco.com (82A044) TDMv0913
The
Commander
Series

TDM Universal Time Delay Module INSTALLATION INSTRUCTIONS

FIGURE 1—TDM Layout & Wiring Connections


Input Actions Input Connections
Green
Input 1—Sequences Output 1 then Output 2 Input Power 12-24V
Input 2—Sequences Output 2 then Output 1 Green (AC or DC)
Input 3—Operates Output 1 only Blue
Input 4—Operates Output 2 only Switch Input #1
Wht/Blue
Wht/Red
Switch Input #2
Wht/Grn
Wht/Vio
Switch Input #3
Wht/Gray
Switch Input #4
Wht/Brown
Wht/Brown
Wht/Gray

Wht/Blue
Wht/Red
Wht/Grn
Wht/Vio

Green
Green
Blue

LED DISPLAY KEY


COM

COM
INPUT 2
INPUT 3
INPUT 4

INPUT 1
INPUT 1

d1 = delay 1

TDM
d2 = delay 2
12-24V AC/DC d3 = delay d1 to d2
d4 = delay d2 to d1
i1 = input 1 (n.o. / n.c.)
i2 = input 2 (n.o. / n.c.)
i3 = input 3 (n.o. / n.c.)
i4 = input 4 (n.o. / n.c.)
o1 = output 1 (n.o. / n.c.)
PROGRAM o2 = output 2 (n.o. / n.c.)
MODE BUTTON
DISPLAY
ADJUSTMENT
o1= wet

Output #2 Output #1
o1= dry
COM
COM
N.C.

N.C.
N.O.

N.O.

Output Connections
Orange

Yellow
Brown

White
Violet

White N.O. Wet/Dry


Gray

Gray COM Output #1 Contact Option


Violet N.C.
(Factory Setting = Dry Contact)
Yellow N.O.
Brown COM Output #2
Orange N.C.

8701 Castle Park Drive  Indianapolis, Indiana 46256 Page 2


Telephone: (317) 842-2545  www.mssedco.com  custsvc@mssedco.com (82A044) TDMv0913
The
Commander
Series

TDM Universal Time Delay Module INSTALLATION INSTRUCTIONS

FIGURE 2—Simple Time Delayed Output


This separate power source ( & associated wiring) can be eliminated
if the jumper is set for "WET" contacts instead of "DRY" contacts.
12-24V 12-24V (see page 6)
AC / DC

GRN

GRN
or Electric Exit Device
WHT/VIO VIO Mag Lock
PUSH
Wall TO Input #3
Switch WHT/RED
OPEN N.C. GRAY
Output #1
NOTE:
MS SEDCO Mag Lock uses N.C.
TDM SPRINKLER FIRE
(Gray & Violet)
Timing Control Module OR FIRE PROTECTION
JUMPER DETECTION SIGNALING Electric Exit device uses
INSTALLED SYSTEM
FOR "DRY"
SYSTEM N.O. (Gray & White)
CONTACTS (IF USED) (IF USED)

N.C. N.C.

PROGRAMMING LED DISPLAY KEY

COM

COM
INPUT 2
INPUT 3
INPUT 4

INPUT 1
INPUT 1
PROCEDURE d1 = delay 1

TDM
d2 = delay 2

12-24V AC/DC
d3 = delay d1 to d2
d4 = delay d2 to d1
i1 = input 1 (n.o. / n.c.)
i2 = input 2 (n.o. / n.c.)
i3 = input 3 (n.o. / n.c.)
i4 = input 4 (n.o. / n.c.)
o1 = output 1 (n.o. / n.c.)
PROGRAM o2 = output 2 (n.o. / n.c.)
MODE BUTTON
DISPLAY
ADJUSTMENT

o1= wet
Output #2 Output #1

o1= dry
COM
COM
N.C.

N.C.
N.O.

N.O.

Once the TDM has been wired for the above application, programming of the device is as follows:

1) Apply power to the unit, provided there is no smoke or fire, you can assume that your wiring job must
be somewhat successful.
2) Once properly powered, the display will flash double bars (––) indicating that the unit is in its normal
operating ready mode.
3) To begin programming, depress the PROGRAM MODE BUTTON one time. The first parameter to be
programmed will appear on the display. This is the delay time, or "on time" of the output #1 and is
displayed as d1 followed by the time setting (It will flash between the two). To adjust the time setting,
use a small screwdriver and rotate the DISPLAY ADJUSTMENT clockwise to increase and
counterclockwise to decrease the time setting. After the desired value is displayed, depress the
PROGRAM MODE BUTTON again to save the value. The display will now read d2. Now wait 30
seconds until the display again reads double bars (––) indicating that the unit is in its normal
operating ready mode.
4) You are now ready to test your installation. If the time delay has to be changed, make the change to
the d1 setting, press the PROGRAM MODE BUTTON once and then wait 30 seconds until the double
bars (––) appear again.
5) During operation of the unit, the display will indicate its operating status. Please refer to Figure 5 at
the end of this installation manual.

8701 Castle Park Drive  Indianapolis, Indiana 46256 Page 3


Telephone: (317) 842-2545  www.mssedco.com  custsvc@mssedco.com (82A044) TDMv0913
The
Commander
Series

TDM Universal Time Delay Module INSTALLATION INSTRUCTIONS

FIGURE 3—Electric Lock and Door Operator


12-24V
AC / DC 12-24V

GRN

GRN
Wall
Switch VIO
BLU
PUSH
input #1 Magnetic
TO
WHT / BLU N.C. or Electric Exit Device
OPEN Output #1 GRAY Lock

MS SEDCO NOTE:
Jumper installed for Mag Lock uses N.C.
TDM "DRY" contacts
Timing Control Module (Gray & Violet)
YEL Electric Exit device uses
Door N.O. (Gray & White)
N.O.
Output #2 Operator
BROWN Control

PROGRAMMING LED DISPLAY KEY

COM

COM
INPUT 2
INPUT 3
INPUT 4

INPUT 1
INPUT 1
PROCEDURE
d1 = delay 1

TDM
d2 = delay 2

12-24V AC/DC
d3 = delay d1 to d2
d4 = delay d2 to d1
i1 = input 1 (n.o. / n.c.)
i2 = input 2 (n.o. / n.c.)
i3 = input 3 (n.o. / n.c.)
i4 = input 4 (n.o. / n.c.)
o1 = output 1 (n.o. / n.c.)
PROGRAM o2 = output 2 (n.o. / n.c.)
MODE BUTTON
DISPLAY
ADJUSTMENT

o1= wet
Output #2 Output #1

o1= dry
COM
COM
N.C.

N.C.
N.O.

N.O.

Once the TDM has been wired for the above application, programming of the device is as follows:
1) Apply power to the unit. The display will flash double bars (––) indicating that the unit is in its normal
operating ready mode.
2) To begin programming, depress the PROGRAM MODE BUTTON one time. The first parameter to be
programmed will appear on the display. This is the delay time, or "on time" of the output #1 and is
displayed as d1 followed by the time setting of 2.0 (Factory Setting) which indicates 2.0 seconds (It will
flash between the two). This is the time duration that you want the Electric Lock released (It's usually
set around 2-3 seconds). To adjust the time setting, use a small screwdriver and rotate the DISPLAY
ADJUSTMENT clockwise to increase and counterclockwise to decrease the time setting. After the
desired value is displayed, depress the PROGRAM MODE BUTTON again to save the value. The
display will now read d2. d2 is the delay time or "on time" of output #2. This is the time setting that
you want for the door (operator) to remain open. This is usually set around 3-5 seconds. To adjust the
setting, rotate the DISPLAY ADJUSTMENT until the desired value is displayed and then depress the
PROGRAM MODE BUTTON. The display should then read d3. This is the setting for the delay time
between the release of the Electric Lock and the opening of the door. This time is usually set around
0.5-1 second. Again, adjust the setting and then depress the PROGRAM MODE BUTTON. The display
should now read d4. Now wait 30 seconds until the double bars (––) appear, indicating that the unit is
in its normal operating ready mode. *NOTE: d1 should be longer than d3.
3) You are now ready to test your installation. If any of the time settings need to be changed, make the
change and press the PROGRAM MODE BUTTON once to save the new value. Then wait 30 seconds
until the double bars (––) appear again, indicating that the unit is in its normal operating mode.
4) During operation of the unit, the display will indicate its operating status. Please refer to Figure 5 at
the end of this installation manual.

8701 Castle Park Drive  Indianapolis, Indiana 46256 Page 4


Telephone: (317) 842-2545  www.mssedco.com  custsvc@mssedco.com (82A044) TDMv0913
The
Commander
Series

TDM Universal Time Delay Module INSTALLATION INSTRUCTIONS

FIGURE 4—Vestibule Sequencing


12-24V
These optional switches are AC / DC
mounted inside the vestibule

GRN

GRN
BLU
Interior PUSH WHT
Wall TO
WHT / BLU input #1 Interior
Switch OPEN
Door Operator
N.O.
switch that WHT / VIO Output #1 GRAY Control
opens interior WHT / GRAY
input #3
door Jumper installed for
MS SEDCO "DRY" contacts
TDM
switch that Timing Control Module
opens exterior WHT / BROWN YEL
input #4 Exterior
door N.O.
WHT / GRN Output #2 Door Operator
Exterior PUSH BROWN Control
Wall TO WHT / RED input #2
Switch OPEN

PROGRAMMING LED DISPLAY KEY

COM

COM
INPUT 2
INPUT 3
INPUT 4

INPUT 1
INPUT 1
d1 = delay 1

TDM
PROCEDURE d2 = delay 2

12-24V AC/DC
d3 = delay d1 to d2
d4 = delay d2 to d1
i1 = input 1 (n.o. / n.c.)
i2 = input 2 (n.o. / n.c.)
i3 = input 3 (n.o. / n.c.)
i4 = input 4 (n.o. / n.c.)
o1 = output 1 (n.o. / n.c.)
PROGRAM o2 = output 2 (n.o. / n.c.)
MODE BUTTON
DISPLAY
ADJUSTMENT

o1= wet
Output #2 Output #1

o1= dry
COM
COM
N.C.

N.C.
N.O.

N.O.
Once the TDM has been wired for the above application, programming of the device is as follows:
1) Apply power to the unit. The display will flash double bars (––) indicating that the unit is in its normal
operating ready mode.
2) To begin programming, depress the PROGRAM MODE BUTTON one time. The first parameter to be
programmed will appear on the display. This is the delay time, or "on time" of the output #1 and is
displayed as d1 followed by the time setting of 2.0 (Factory Setting) which indicates 2.0 seconds (It
will flash between the two). This is the time duration that you want the interior door to remain open
(It's usually set around 4-5 seconds). To adjust the time setting, use a small screwdriver and rotate
the DISPLAY ADJUSTMENT clockwise to increase and counterclockwise to decrease the time setting.
After the desired value is displayed, depress the PROGRAM MODE BUTTON again to save the value.
The display will now read d2. d2 is the delay time or "on time" of output #2. This is the time setting
that you want for the exterior door to remain open. This is usually set around 4-5 seconds. To adjust
the setting, rotate the DISPLAY ADJUSTMENT until the desired value is displayed and then depress
the PROGRAM MODE BUTTON. The display should then read d3. This is the setting for the delay
time between the activation of the interior door and the exterior door. This time is usually set around
1-4 seconds. Again, adjust the setting and then depress the PROGRAM MODE BUTTON. The display
should now read d4. This is the delay time between the opening of the doors going in the opposite
direction. Adjust this value in the same manner as before. When the PROGRAM MODE BUTTON is
depressed, i1 will then be displayed. Now wait 30 seconds until the double bars (––) appear,
indicating that the unit is in its normal operating ready mode.
3) You are now ready to test your installation. If any of the time settings need to be changed, make the
change and press the PROGRAM MODE BUTTON once to save the new value. Then wait 30 seconds
until the double bars (––) appear again, indicating that the unit is in its normal operating mode.
4) During operation of the unit, the display will indicate its operating status. Please refer to Figure 5 at
the end of this installation manual.

8701 Castle Park Drive  Indianapolis, Indiana 46256 Page 5


Telephone: (317) 842-2545  www.mssedco.com  custsvc@mssedco.com (82A044) TDMv0913
The
Commander
Series

TDM Universal Time Delay Module INSTALLATION INSTRUCTIONS

FIGURE 5—Operation Display & Additional Programming Options


When the unit is operating, the display will indicate which output is active for the duration of its
programmed time delay. For relay output #1, a 1 will be displayed and 2 will be displayed for relay output
#2. If the delays d3 or d4 are used (such as an installation using a Mag Lock or a Vestibule application),
the delay will be evident between the displaying of both outputs.

In addition to the settings already described in the previous sections, below is a listing of various options
which are programmable on the TDM. The LED display vs. function are as follows:

–– = Ready Mode (flashing)


d1 = Time Delay or "ON TIME" of relay output #1—0.0 to 99 seconds
d2 = Time Delay or "ON TIME" of relay output #2—0.0 to 99 seconds
d3 = Time Delay between d1 and d2—0.0 to 99 seconds
d4 = Time Delay between d2 and d1—0.0 to 99 seconds
i1 = Switch Input #1—(N.O. or N.C.)
i2 = Switch Input #2—(N.O. or N.C.)
i3 = Switch Input #3—(N.O. or N.C.)
i4 = Switch Input #4—(N.O. or N.C.)
o1 = Relay Output #1—(N.O. or N.C.)
o2 = Relay Output #2—(N.O. or N.C.)
- - = Error (flashing)

The PUSHBUTTON FAULT INDICATOR is a special feature designed to alert the installer if a pushbutton is
"stuck" in the active position or if the wires have shorted. If this occurs, the display will flash double dots
( . . ). Additionally, this could mean that the wiring did not match the programmed parameter. In other
words, the unit may be programmed for use with a normally open switch, but may be wired to a normally
closed switch. Normal operation will resume once the fault condition has been cleared.

WET/DRY CONTACT OPTION:


The TDM has the option of supplying power to relay output #1 contacts. This is known as "WET" contacts
instead of the conventional "DRY" contacts or simple contact closure. Providing this voltage can simplify
the wiring of installations where an Electric Locking device is used. However, the voltage supplied to the
output is the same voltage supplied to the input of the TDM and must be compatible with the Locking
device to be controlled. Please contact the factory for additional information.

8701 Castle Park Drive  Indianapolis, Indiana 46256 Page 6


Telephone: (317) 842-2545  www.mssedco.com  custsvc@mssedco.com (82A044) TDMv0913

You might also like