Professional Documents
Culture Documents
IET Renewable Power Gen - 2014 - Liu - Power Control Strategy For Photovoltaic System Based On The Newton Quadratic
IET Renewable Power Gen - 2014 - Liu - Power Control Strategy For Photovoltaic System Based On The Newton Quadratic
org
Published in IET Renewable Power Generation
Received on 5th March 2013
Revised on 16th August 2013
Accepted on 4th November 2013
doi: 10.1049/iet-rpg.2013.0067
ISSN 1752-1416
Abstract: To maximise the economic benefit, photovoltaic (PV) systems in general operate in the so-called maximum power
point tracking (MPPT) mode. However, in certain occasions (e.g. in a microgrid or in a weak system), it is beneficial for a
PV system not to always operate in the MPPT mode, but occasionally in the power dispatch mode, because of the top priority
of maintaining system stability. To this end, a Newton quadratic interpolation-based power control strategy for PV system is
proposed to iteratively obtain the required terminal voltage of PV system by approximating the power–voltage characteristic
curve with a quadratic curve. With this control strategy, PV systems can operate in the power dispatch mode to flexibly adjust
the active power output in a wide range, or adaptively switch to the MPPT mode if necessary. Details on the convergence
rate and the way to achieve the fault ride-through capability are also discussed. Simulation is performed based on a detailed
PV dynamical model, illustrating that the proposed method has fast convergence rate and robust performance compared with
a revised perturb and observe method which can attain the same function.
IET Renew. Power Gener., 2014, Vol. 8, Iss. 6, pp. 611–620 611
doi: 10.1049/iet-rpg.2013.0067 & The Institution of Engineering and Technology 2014
www.ietdl.org
the PV array until the PV terminal voltage reaches a steady
state. This control strategy drives the operating point to
converge at the downhill section of the P−V characteristic
curve, but it malfunctions if the dispatched power command
is more than the maximum PV power output. Besides, both
the control strategies in [16, 17] need a logic signal to
switch between the two modes, which are not discussed in
the papers.
Motivated by the idea of [15–17], a novel power control
strategy based on the Newton quadratic interpolation (NQI)
is presented. With this strategy, the required reference
voltage of the PV array can be iteratively calculated by Fig. 1 P−V characteristic curve
approximating the P−V characteristic curve with a quadratic
curve. The proposed strategy enables the PV system to
increased. This trend stops when PPV reaches the maximum
adaptively switch between the MPPT mode and the power
value; beyond this voltage, PPV decreases as UPV is
dispatch mode according to the relationship between the
increased. This behaviour implies that PPV can be
dispatch command (e.g. the reference power) and maximum
controlled by adjusting UPV [20]. Therefore the problem to
power output. To be specific, when the reference power is
be solved can be described as follows.
more than the maximum power output, the PV system
Design a power control strategy for the PV system such that
operates in the MPPT mode; otherwise, the PV system
the active power injecting to the utility grid Pgrid can converge
operates in the power dispatch mode and tracks the ref
reference power. Details on measures to guarantee to a given reference Pgrid when the power output of the PV
MPP
convergence and the fault ride-through (FRT) capability of array satisfies PPV , PPV (corresponding to UPV1 and
the PV system are also discussed. It is demonstrated that UPV2 in Fig. 1), or converge to the maximum power that
max
the proposed strategy can work well in various scenarios. can be injected to the utility grid Pgrid such that
The paper is organised as follows. Section 2 introduces the MPP MPP
PPV = PPV (corresponding to UPV in Fig. 1), where PPV MPP
main problem and the layout of the grid-connected PV represents the maximum available power of the PV array.
system. The power control strategy based on the NQI is Thus, it follows from (2) that the main task is to design an
introduced in Section 3, and some discussions are provided updating rule of UPVref, such that it converges to UPVref ∗
,
in Section 4. Section 5 validates the proposed strategy which satisfies
under several scenarios by simulation. Conclusions are
drawn in Section 6. max ref ∗
min (Pgrid , Pgrid ) = PV (UPVref , a) − Ploss (3)
2 Problem formulation
where Ploss denotes the loss of the inverter which connects the
For a PV array, the current IPV and terminal voltage UPV are PV array to the grid.
related by [18, 19] A single-stage inverter topology, which has the merits of
saving components and reducing cost, is adopted in this
0
IPV = IPV − Is0 [e(UPV +Rs IPV )/(Vt a) − 1] − (UPV + Rs IPV )/Rp study to illustrate the control design, as shown in Fig. 2.
The classical double-loop scheme is applied to the PWM
(1)
control, as shown in Fig. 3. The upper channel controls PPV
0 by regulating UPV: the outer loop forces UPV to track UPVref
where IPV is the light induced current depending on the
irradiance level G and array temperature T; Is0 is the diode and generates the current command Idref , which is delivered
saturation current depending on T only; Rp is the equivalent to a dq-frame current-control scheme (inner loop), forcing
parallel resistance of PV array; Rs is the equivalent series Id to track Idref . The lower channel adopts the same
resistance of PV array; a is the diode ideality constant and philosophy to directly control reactive power Q, by which
Vt is the thermal voltage depending on T only. some ancillary functions can be attained, for example,
It follows from (1) that the power generating from the PV voltage regulation and oscillation damping (which is
array can be expressed as beyond the scope of the paper and thus is skipped).
The feedforward of Id and Iq by a gain ωL is added to the
PPV = UPV · IPV = PV(UPV , a) (2)
612 IET Renew. Power Gener., 2014, Vol. 8, Iss. 6, pp. 611–620
& The Institution of Engineering and Technology 2014 doi: 10.1049/iet-rpg.2013.0067
www.ietdl.org
polynomial can be written as [24]
P2 − P1
C0 = [P1 ] = P1 , C1 = [P1 , P2 ] = ,
U2 − U1
(7)
[P2 , P3 ] − [P1 , P2 ]
C2 = [P1 , P2 , P3 ] =
U3 − U1
Pout (U ) = aU 2 + bU + c (8)
PWM control outputs to decouple the dynamics. The
current-control strategy also enhances protection of the
inverter against overload and external faults by limiting where the coefficients are a = C2, b = C1−C2U1−C2U2 and
Idref and Iqref , details of which is to be illustrated in Section c = C0−C1U1 + C2U1U2.
Equation (8) can be used to estimate the PV reference
4 [20, 21]. It is worth mentioning that the control strategy voltage when the reference power Pgrid ref
is given. The
to be developed can be used for various types of PV following quadratic equation can be acquired by equating
systems with different inverter topologies (such as the ref
Pout (U ) with Pgrid
dual-stage, multiple-stage topologies etc. [22]) and PWM
control strategies (such as the feedback linearisation method
in [23]). aU 2 + bU + (c − Pgrid
ref
)=0 (9)
The grid-injected power Pgrid is used to update the reference
voltage of the PV array. Assume that the dynamics of the Define
inverter are very fast compared to the change of reference
voltage, the dynamics of the inverter can be approximately
described as a first-order delay link by ignoring the small D = b2 − 4a(c − Pgrid
ref
) (10)
power loss [16]
MPP ref
Δ < 0 indicates that PPV is less than Pgrid and the PV system
Pgrid = PPV /(1 + Td s) (4) operates in the MPPT mode, as shown in Fig. 4a. Select the
extreme point of the predicted P−V characteristic curve as
As the time constant Td is rather small, it is reasonable to the reference point in the next iteration step, the PV voltage
assume that Pgrid is approximately equal to PPV. Therefore at the maximum power point (MPP) can be approximated as
∗
the required reference voltage of the PV array UPVref
satisfying (4) can be simplified as satisfying b
k
UPVref =− (11)
MPP ref ∗ 2a
min (PPV , Pgrid ) = PV (UPVref , a) (5)
MPP ref
Δ ≥ 0 indicates that PPV is more than Pgrid . It should be noted
Since α is time-varying and there are some unknown that there are two solutions for the dispatch purpose. Figs. 4b
parameters of the PV array, it is difficult to obtain the exact and c show that the PV system operates on the uphill and
MPP
expression of PPV = PV(UPV, α) and the value of PPV . A downhill section of the P−V characteristic curve,
feasible solution is to use an iterative method by respectively. Clearly, both of them can be easily obtained
considering the convex property of the P−V characteristic by solving (9). The left-hand side solution (denoted by
curve, for example, the P&O method for tracking the MPP. NQIL) can be written as
Quadratic interpolation is another good option to improve
the results. This idea will be used to solve the above √
problem and the details will be discussed next. k −b + D
UPVref = (12)
2a
3 Control strategy based on the NQI
whereas the right-hand side solution (denoted by NQIR) can
3.1 Basic idea of the NQI-based power control be written as
strategy for PV system
√
Consider the kth step in the iteration and assume that there are k −b − D
UPVref = (13)
three sampling points on the P−V characteristic curve. Their 2a
voltage and power values are noted as (U1k , P1k ), (U2k , P2k ) and
(U3k , P3k ), satisfying U1k , U2k , U3k . The basic idea of the
proposed strategy is to use the quadratic curve passing the The characteristics of the two solutions will be compared in
three points to approximate the P−V characteristic curve. the next section and in the simulations, which show that the
Once the points are chosen, the Newton quadratic NQIR is generally better than the NQIL.
IET Renew. Power Gener., 2014, Vol. 8, Iss. 6, pp. 611–620 613
doi: 10.1049/iet-rpg.2013.0067 & The Institution of Engineering and Technology 2014
www.ietdl.org
3.2 Iteration process (14) implies that the three sampling points are so close to
k
each other that the calculation of (7) might result in
By the solutions of (11) and (12) or (13), a new UPVref can be numerical error. A feasible solution to prevent this is: after
k k k
obtained and the corresponding power output PPVref can be (14) is satisfied, point (UPVref , PPVref ) is eliminated in every
k
measured when the inverter makes UPV track UPVref . iteration step and the rest points keep unchanged.
By far, the information of four points, namely (U1k , P1k ), The P−V characteristic curve varies as to the irradiance and
(U2k , P2k ), (U3k , P3k ) and (UPVref
k k
, PPVref ) have been obtained. temperature. The above rule of iteration guarantees the new
To launch the next quadratic interpolation, one point steady state to be reached in a short time as the operating
should be removed from the four. The rule of iteration is to conditions change. The theoretical proof that the NQI
remove (U1k , P1k ) and k k
(U3 , P3 ) in turn, that is, to remove
converges to the desired operating point can be observed in
literatures: when operating in the MPPT mode, the
k k
U(−1) k +2 , P(−1)k +2 . Then, rearrange the rest of the three
algorithm can be viewed as a maximisation problem, which
is proved to have convergence rate with order 1.32 [25];
points as (U1k+1 , P1k+1 ), (U2k+1 , P2k+1 ) and (U3k+1 , P3k+1 ), and when operating in the power dispatch mode, the algorithm
k+1 k+1
(UPVref , PPVref ) can be obtained following the same can be viewed as a root finding problem, which is proved
procedure. to have convergence rate with order 1.84 [26].
k k
As k increases, the reference point (UPVref , PPVref ) obtained Fig. 5 is the flowchart of the NQI-based power control
in every iteration step gradually approaches the new steady strategy for PV system. Some measures to avoid
state. The iteration are considered converged if the miscalculation if the Newton quadratic polynomial fails to
following condition is satisfied estimate the real P−V characteristic curve and the way to
achieve the FRT capability are also included, which will be
discussed in the next section. The cycle of Fig. 5 is executed
max |Pik − PPVref
k
| , 1 (i = 1, 2, 3) (14)
every other sampling interval. The value of sampling interval
Ts needs to be carefully tuned in coordination with the
where ε is a predefined constant. In the simulation, ε = 2 × characteristics of the PV array and the PI parameters of the
10−4 pu (50 W in the base power of 0.25 MW). Equation inverter control. Specifically, if Ts is too small, the controller
614 IET Renew. Power Gener., 2014, Vol. 8, Iss. 6, pp. 611–620
& The Institution of Engineering and Technology 2014 doi: 10.1049/iet-rpg.2013.0067
www.ietdl.org
right solution randomly when the PV system operates in the
power dispatch mode. The left-hand side solution converges
slowly whereas the right-hand side solution leads to severe
power oscillation around the steady state, both of which are
not satisfactory. This method is implemented for simulation
in comparison with the proposed strategy.
IET Renew. Power Gener., 2014, Vol. 8, Iss. 6, pp. 611–620 615
doi: 10.1049/iet-rpg.2013.0067 & The Institution of Engineering and Technology 2014
www.ietdl.org
616 IET Renew. Power Gener., 2014, Vol. 8, Iss. 6, pp. 611–620
& The Institution of Engineering and Technology 2014 doi: 10.1049/iet-rpg.2013.0067
www.ietdl.org
Table 2 Main features of the schemes power output of the PV array cannot be fully delivered to
the utility grid, the extra power will charge the capacitor
Schemes Convergence rate Overshoot Steady error
parallel to the PV array, thus the voltage of the capacitor
P&O slow small large
increases until PPV equals the power limit of the inverter.
NQIL medium medium small As a result, UPV fails to track UPVref and all the sampling
NQIR fast large small points will converge to the same point and the interpolation
will fail when calculating (7).
To prevent the numerical error, an additional block (as
have the fault ride-through capability, which is similar to the shown in block 3 in Fig. 5) is designed, whose function is:
definition of the FRT for wind-turbines [28]. As the proposed the iteration is stopped when the low voltage is detected,
control strategy functions properly in case of overvoltage, and is reinitialised when the system recovers. In this way,
low-voltage ride-through capability is specifically concerned the three sampling points are separated and the system
in this paper. Low voltage limits the grid-injected power could return to normal state. Simulation on the FRT
because of the current protection of the inverter. When the characteristic of the PV system will be shown in the next
section.
5 Simulation results
In this section, a model of PV system is used to validate the
proposed NQI-based power control strategy. The PV system
capacity is 0.3 MW, connecting to a 10 kV external grid
IET Renew. Power Gener., 2014, Vol. 8, Iss. 6, pp. 611–620 617
doi: 10.1049/iet-rpg.2013.0067 & The Institution of Engineering and Technology 2014
www.ietdl.org
through a transformer. The parameters of the DC/AC inverter, point randomly converges to the right-hand side solution in
the PV array, and the PWM controller are listed in the the power dispatch mode.
Appendix. The value of the sampling interval Ts is 0.01 s in It also follows from Fig. 8 that the NQI-based schemes has
all cases unless otherwise stated. The initial operating larger overshoot than the P&O scheme in the transient from
ref
condition is Pgrid = 0.25 MW, irradiance G = 1000 W/m2 S1 to S2. This is because the variation of UPVref between
MPP
(PPV = 0.24 MW) and temperature T = 25°C, with the PV two samples is small and constant for the P&O scheme,
system operating in the MPPT mode. As the influence of whereas it is unpredictable and sometimes large for the
temperature on the P–V characteristic curve is trivial, it is NQI-based schemes. Specifically, the overshoot for the
kept constant and only the influence of solar irradiance is NQIR is more obvious than the NQIL, which coincides
studied. with the discussion in Section 4 that the downhill section
To analyse the characteristics of the proposed strategy, of the P–V characteristic curve is steeper than the uphill
three schemes are compared: (i) the NQIR, (ii) the NQIL section. The features of the three cases are summarised
and (iii) the P&O. The following scenario is considered: at in Table 2. Of the three features, the convergence rate
ref
0.5 s, Pgrid changes to 0.175 MW, the PV system switches is of more importance, for example, when there is
from the MPPT mode (S1) to power dispatch mode (S2) over-frequency in a microgrid, a shorter response time may
ref MPP
(Pgrid , PPV = 0.24 MW). At 1.5 s, the irradiance G easily help to keep the system stable. From this aspect, the
changes to 600 W/m2, the PV system switches back to the NQIR has the best performance. This case proves that the
ref MPP
MPPT mode (S3) (Pgrid , PPV = 0.144 MW). Fig. 7 plots proposed strategy with NQIR can operate well in response
ref
the simulation results, where (a) and (b) show the power to irradiance or Pgrid change and is more robust and
output and terminal voltage of the PV array, respectively. efficient than the P&O scheme.
From Fig. 8a, it can be observed that when the PV system As discussed in Section 4, the choice of the sampling
switches between the MPPT and power dispatch mode, the interval Ts has profound influence on the transient stability
convergence rate of the NQIR, the NQIL, and the P&O and convergence rate. Here, the transient responses of PV
schemes are much different: from S1 to S2, it, respectively, system under different sampling intervals are studied and
takes the three schemes about 0.08, 0.38 and 0.48 s to reach compared. The PV system switches from the MPPT mode
MPP ref
the new steady state; from S2 to S3, it, respectively, takes to the power dispatch mode (PPV . Pgrid = 0.1 MW) at
the three schemes about 0.09, 0.27 and 0.40 s to reach the 1 s. Fig. 9 shows the results of the PV system under
new steady state. The enlarged views of Fig. 8 illustrate that the NQIR scheme with Ts = 0.0005, 0.01 and 0.5 s,
for the P&O scheme, the operating point oscillates around respectively. It can be observed that the operating points
the steady state, slightly lowering the overall efficiency of converge in about 0.05, 0.1 and 1.0 s for the different
the MPPT mode. However, this phenomenon does not exist sampling intervals. However, Fig. 9b shows that the
in the NQI schemes. Notice that for the P&O, the step size algorithm becomes unstable when Ts = 0.0005 s. The reason
of perturbation and the sampling time have been tuned to can be explained as follows: in the control design, the
obtain a good performance. A larger step size might dynamics of the inverter is assumed to be much faster than
accelerate the convergence, but the oscillation around the that of the proposed PV power control strategy and can be
steady state will be more obvious. Moreover, the operating ignored. So the control design can be considered as an
618 IET Renew. Power Gener., 2014, Vol. 8, Iss. 6, pp. 611–620
& The Institution of Engineering and Technology 2014 doi: 10.1049/iet-rpg.2013.0067
www.ietdl.org
open-loop problem. However, when Ts is very small, the 7 Acknowledgements
above assumption will not hold and the dynamics of the
inverter and PV power control may undergo certain This work is jointly supported by the National High
interactions. By trial and error, it is found that Ts = 0.01 s is Technology Research and Development Program of China
a proper value to achieve the best effect in this study. This (2011AA050204), the National Natural Science Foundation
conclusion is also proved by the enlarged view of Fig. 9c of China (No. 51177146) and the Development Foundation
that UPV can almost track UPVref in each sampling interval. of the State Grid (field demonstration of the Luxi renewable
Next, the performance of the proposed control strategy is power grid).
studied under real operational scenario. The PV system is
simulated over a 60 s period of a typical cloudy day (real
irradiance data from [4] is used, as shown in Fig. 10a). The
sharp variation of the solar irradiance may be because of a 8 References
passing cloud, or the shade of a building. Figs. 10b and c
show the time responses of Pgrid, and UPV when the PV 1 Ahmed, S., Mohsin, M.: ‘Analytical determination of the control
parameters for a large photovoltaic generator embedded in a grid
system operates in the MPPT and power dispatch (Pref grid = system’, IEEE Trans. Sustain. Energy, 2011, 2, (2), pp. 122–130
0.13 MW) modes, respectively. It is proved that the PV power 2 Sheikh, N., Kocaoglu, D.: ‘A comprehensive assessment of solar
output can follow the change of irradiance immediately, photovoltaic technologies: literature review’. Proc. PICMET ’11:
although some voltage and power spikes can be observed Technol. Manage. Energy Smart World, August 2011, pp. 1–11
3 Hua, C., Lin, J., Shen, C.: ‘Implementation of a Dsp-controlled
when the irradiance changes too sharply. When the PV photovoltaic system with peak power tracking’, IEEE Trans. Power
system operates in the power dispatch mode, if the irradiance Electron., 1998, 45, (1), pp. 99–107
is abundant, the PV power output is exactly 0.13 MW, with 4 Tan, Y., Kirschen, D.: ‘Impact on the power system of a large
the excess energy discarded by raising UPV, otherwise, the PV penetration of photovoltaic generation’. IEEE Power Eng. Soc. Gen.
system adaptively switches to the MPPT mode. Meeting, June 2007, pp. 1–8
5 Omran, W., Kazerani, M., Salama, M.: ‘Investigation of methods for
Finally, the FRT capability of the proposed strategy is reduction of power fluctuations generated from large grid-connected
tested and analysed. Suppose that a three-phase short-circuit photovoltaic systems’, IEEE Trans. Energy Convers., 2011, 26, (1),
fault (the short-circuit resistance is 0.003 Ω) occurs at the pp. 318–327
PCC at 0.5 s and the fault is cleared at 1.5 s. Figs. 11a and 6 Xin, H., Qu, Z., Seuss, J., Maknouninejad, A.: ‘A self-organizing
strategy for power flow control of photovoltaic generators in a
b, respectively, show the current in dq-frame, voltage of the distribution network’, IEEE Trans. Power Syst., 2011, 26, (3),
DC and AC sides of the inverter, and the grid-injected pp. 1462–1473
power of the PV system when the PV system operates in 7 Datta, M., Senjyu, T., Yona, A., Funabashi, T., Kim, C.: ‘A frequency-
the MPPT mode and the power dispatch mode control approach by photovoltaic generator in a PV–diesel hybrid power
ref system’, IEEE Trans. Energy Convers., 2011, 26, (2), pp. 559–571
(Pgrid = 0.2 MW, G = 1000 W/m2 ). When the fault 8 Esram, T., Chapman, P.: ‘Comparison of photovoltaic array maximum
occurs, the AC side voltage of the inverter suddenly power point tracking techniques’, IEEE Trans. Energy Convers.,
decrease to 0.07 kV. Id must increase to sustain the PV 2007, 22, (2), pp. 439–449
9 Kish, G., Lee, J., Lehn, P.: ‘Modelling and control of photovoltaic panels
power output transmitted to the grid. Therefore Idref utilising the incremental conductance method for maximum power point
tracking’, IET Renew. Power Gener., 2012, 6, (4), pp. 259–266
increases until I ref = (Idref )2 + (Iqref )2 reaches the current 10 Noguchi, T., Togashi, S., Nakamoto, R.: ‘Short-current pulse-based
maximum-power-point tracking method for multiple photovoltaic-and-
limitation IMax = 0.9 kA. Pgrid is limited to about 0.1 MW. converter module system’, IEEE Trans. Ind. Electron., 2002, 49, (1),
The surplus PV power output charges the capacitor until pp. 217–223
UPV reaches 0.95 kV. When the short-circuit fault is 11 Femia, N., Petrone, G., Spagnuolo, G., Vitelli, M.: ‘Optimization of
cleared, the PV system returns to normal state in less than perturb and observe maximum power point tracking method’, IEEE
Trans. Power Electron., 2005, 20, (4), pp. 963–973
0.5 s. Thus, the simulation results indicate that the proposed 12 Piegari, L., Rizzo, R.: ‘Adaptive perturb and observe algorithm for
algorithm has the FRT capability in both the MPPT mode photovoltaic maximum power point tracking’, IET Renew. Power
and the power dispatch mode. Gener., 2010, 4, (4), pp. 317–328
13 Menniti, D., Burgio, A., Sorrentino, N., Pinnarelli, A., Brusco, G.: ‘An
incremental conductance method with variable step size for Mppt:
design and implementation’. Proc. Tenth Int. Conf. Electr. Power
6 Conclusions Qual. Utilis., September 2009, pp. 1–5
14 Ahmed, N., Miyatake, M.: ‘A novel maximum power point tracking for
photovoltaic applications under partially shaded insolation conditions’,
In this paper, a new strategy to control the power output of Electr. Power Syst. Res., 2008, 78, (5), pp. 777–784
PV system is presented. The strategy is based on the NQI 15 Pai, F., Chao, R.: ‘A new algorithm to photovoltaic power point tracking
algorithm and it enables the PV system to adaptively problems with quadratic maximization’, IEEE Trans. Energy Convers.,
switch between the MPPT and the power dispatch mode 2010, 25, (1), pp. 262–264
according to the operating condition. Namely, when the 16 Li, P., François, B., Degobert, P., Robyns, B.: ‘Power control strategy of
a photovoltaic power plant for microgrid applications’. Proc. ISES
given reference power is more than the maximum power World Congr., April 2009, pp. 1611–1616
output of the PV system, the power output is the 17 Delfino, F., Procopio, R., Rossi, M., Ronda, G.: ‘Integration of large-size
maximum power output; otherwise the PV system follows photovoltaic systems into the distribution grids: a P–Q chart approach to
the reference power. With this control strategy, various assess reactive support capability’, IET Renew. Power Gener., 2010, 4,
functions can be achieved, such as the frequency (4), pp. 329–340
18 Chatterjee, A., Keyhani, A., Kapoor, D.: ‘Identification of photovoltaic
regulation in an emergency condition, which are important source models’, IEEE Trans. Energy Convers., 2011, 26, (3), pp. 883–889
for a weak grid or a microgrid. Compared with the 19 Keyhani, A.: ‘Design of smart power grid renewable energy systems’
conventional P&O scheme, the propose control strategy (John Wiley & Sons, 2011)
has better performance in the respective of convergence 20 Yazdani, A., Dash, P.P.: ‘A control methodology and characterization of
dynamics for a photovoltaic (Pv) system interfaced with a distribution
rate and steady-state error. The simulation results validate network’, IEEE Trans. Power Deliv., 2009, 24, (3), pp. 1538–1551
the effectiveness of the proposed algorithm, even under 21 Keyhani, A., Marwali, M., Dai, M.: ‘Integration of green and renewable
some severe conditions. energy in electric power systems’ (John Wiley & Sons, 2009)
IET Renew. Power Gener., 2014, Vol. 8, Iss. 6, pp. 611–620 619
doi: 10.1049/iet-rpg.2013.0067 & The Institution of Engineering and Technology 2014
www.ietdl.org
22 Xue, Y., Chang, L., Kjaer, S., Bordonau, J., Shimizu, T.: ‘Topologies of 9 Appendix
single-phase inverters for small distributed power generators:
an overview’, IEEE Trans. Power Electron., 2004, 19, (5),
pp. 1305–1314
The parameters of the DC/AC inverter are: the rated capacity
23 Delfino, F., Denegri, G., Invernizzi, M., Procopio, R.: ‘Feedback 0.3 MW, the rated voltages of the DC side and the AC side
linearisation oriented approach to Q–V control of grid connected 0.75 and 0.25 kV, respectively.
photovoltaic units’, IET Renew. Power Gener., 2010, 6, (5), pp. 324–339 The PV array adopts the model in [18], of which the
24 Hildebrand, F.: ‘Introduction to numerical analysis’ (Dover Pubns, 1987, parameters are: short-circuit current Isc = 8.3125 A,
2nd edn.) open-circuit voltage UOC = 32.9 V, voltage and current at
25 Sun, W., Yuan, Y.: ‘Optimization theory and methods: nonlinear MPP MPP
programming’ (Springer, 2006)
MPP UPV = 26.3 V and IPV = 7.61 A, series resistance
26 Sharma, J.: ‘A family of methods for solving nonlinearequations using Rs = 0.2 Ω, parallel resistance Rp = 540 Ω, diode quality
quadratic interpolation’, Comput. Math. Appl., 2004, 48, (5–6), factor a = 1.3 pu, number of cells in series Ns = 30 and
pp. 709–714 number of cells in parallel Np = 40.
27 Chen, Y., Smedley, K.: ‘A cost-effective single-stage inverter with The parameters of the double-loop-based PWM
maximum power point tracking’, IEEE Trans. Power Electron., 2004,
controller are determined by trial and error: in the
19, (5), pp. 1289–1294
28 Mullane, A., Lightbody, G., Yacamini, R.: ‘Wind-turbine fault outer-loop, the d- and q-axis controls are 10 + 10/s and 1 +
ride-through enhancement’, IEEE Trans. Power Syst., 2005, 20, (4), 10/s; in the inner-loop, the d- and q-axis controls are both
pp. 1929–1937 0.1 + 10/s.
620 IET Renew. Power Gener., 2014, Vol. 8, Iss. 6, pp. 611–620
& The Institution of Engineering and Technology 2014 doi: 10.1049/iet-rpg.2013.0067