FXM/FXH Series

DIN W72×H72, W48×H96mm Counter/Timer


Features
● Counting speed: 1cps/30cps/2kcps/5kcps
● Selectable voltage input (PNP) method or
Shaded parts( ) are changed and added
no-voltage input (NPN) method
● Input mode: Up, Down, Up/Down functions from previous FX/FXH Series.
● Power supply: 100-240VAC 50/60Hz
● Dot for Decimal Point / Hour. Min. Second by RESET key
● Selectable Counter/Timer by internal DIP switch
● [Counter]
20 input modes/18 output modes
● [Timer]
16 output modes
Various time setting range - 8-digit model: 0.01 sec to 99999 hour 59.9 min /
6-digit model: 0.1 sec to 99999.9 hour /
4-digit model: 0.01 sec to 9999 hour
● Output: Indicator, 1-stage setting, 2-stage setting
Please read “Safety considerations” in operation
manual before using.

Ordering Information
FX 4 H 2P 4
Power supply
4 100-240VAC 50/60Hz
1P 1-stage setting
Output
2P 2-stage setting
I Indicator

Size H DIN W48×H96mm


M DIN W72×H72mm

4 9999 (4-digit)
Display digit
6 999999 (6-digit)
8 99999999 (8-digit)
Item
FX Counter/Timer
Specifications
1-stage settingFX4H-1P4 FX4M-1P4 FX6M-1P4 FX8M-1P4
Model 2-stage settingFX4H-2P4 FX4M-2P4 FX6M-2P4 -
Indicator - FX4M-I4 FX6M-I4 FX8M-I4
Display digit 4-digit 6-digit 8-digit
Character size (W×H) 6×10mm 4×8mm 3.8×7.6mm
Power supply 100-240VAC~ 50/60Hz
Permissible voltage range 90 to 110% of rated voltage
Power consumption ● 1-stage: Max. 4.6VA ● 2-stage: Max. 5.8VA ● Indicator: Max. 3.8VA
Max. counting speed of CP1/CP2 Selectable 1cps/30cps/2kcps/5kcps (DIP switch)
Return time Max. 500ms
Min. signal width INHIBIT, RESET: approx. 20ms
Selectable voltage input (PNP) method or no-voltage input (NPN) method
[Voltage input (PNP) method]-input impedance: max. 10.8kΩ, [H]: 5-30VDC , [L]: 0-2VDC
Input method
[No-voltage input (NPN) method]-short-circuit impedance: max. 470Ω , short-circuit residual voltage: max. 1VDC,
open-circuit impedance: min. 100kΩ
One-shot output time ● 1-stage: 0.05 to 5 sec ● 2-stage: 1st setting 0.5 sec fixed, 2nd setting 0.05 to 5 sec
● 1-stage: Instantaneuos SPDT (1c)
Type
Contact ● 2-stage: OUT1-Instantaneuos SPDT (1c), OUT2-Instantaneuos SPDT (1c)
Control Capacity 250VAC~ 3A resistive load
output
Type ● 1-stage: 1 NPN open collector ● 2-stage: OUT1-1 NPN open collector, OUT2-1 NPN open collector
Solid state
Capacity ● Load voltage: Max. 30VDC ● Load current: Max. 100mA ● Residual voltage: Max. 1VDC
Relay Mechanical Min. 5,000,000 operations
life cycle Electrical Min. 100,000 operations (250VAC 3A resistive load)
Repeat/Set/Voltage/Temp. error Max. ±0.01% ±0.05 sec
Insulation resistance Over 100MΩ (at 500VDC megger)
External power supply Max. 12VDC ±10% 50mA
Memory retention Approx. 10 years (non-volatile memory)
Dielectric strength 2,000VAC 50/60Hz for 1 min (between all terminals and case)
Noise immunity ±2kV the square wave noise (pulse width 1μs) by noise simulator

J-50
Up/Down Counter/Timer
Specifications (A)
Photoelectric
1-stage setting FX4H-1P4 FX4M-1P4 FX6M-1P4 FX8M-1P4 Sensors

Model 2-stage setting FX4H-2P4 FX4M-2P4 FX6M-2P4 - (B)


Fiber
Indicator - FX4M-I4 FX6M-I4 FX8M-I4 Optic
Sensors
Mechanical 0.75mm amplitude at frequency 10 to 55Hz (for 1 min) in each X, Y, Z direction for 1 hour
Vibration
Malfunction 0.5mm amplitude at frequency 10 to 55Hz (for 1 min) in each X, Y, Z direction for 10 minutes (C)
Door/Area
Mechanical 300m/s2 (approx. 30G) in each X, Y, Z direction for 3 times Sensors
Shock
Malfunction 100m/s2 (approx. 10G) in each X, Y, Z direction for 3 times
Environ- Ambient temp. -10 to 55℃, storage: -25 to 65℃ (D)
Proximity
ment Ambient humi. 35 to 85%RH, storage: 35 to 85%RH Sensors

Protection structure IP20 (front part, IEC standard)


(E)
Approval Pressure
Sensors
1-stage setting Approx. 245g (approx. 180g)

Weight 1 2-stage setting Approx. 265g (approx. 200g)
(F)
Indicator Approx. 225g (approx. 160g) Rotary
Encoders
※1: The weight includes packaging. The weight in parenthesis is for unit only.
(G)
※Environment resistance is rated at no freezing or condensation. Connectors/
Connector Cables/
Sensor Distribution
Boxes/Sockets

Connections (H)
Temperature
Controllers

FX M-1P4 FX M-2P4 FX M-I4 (I)


SOLID STATE OUT SOLID STATE OUT SSRs / Power
30VDC 100mA 12VDC Controllers
30VDC 100mA
12VDC 12VDC CP1 CP2 50mA 0VDC RESET
CP1 CP2 50mA 0VDC RESET CP1 CP2 50mA 0VDC RESETOUT1 OUT2
8 9 10 11 12 13 14
8 9 10 11 12 13 14 8 9 10 11 12 13 14 (J)
Counters
※ (INHIBIT)
※(INHIBIT) ※(INHIBIT)
OUT OUT2 OUT1
17 (K)
Timers
1 2 3 4 5 6 7
1 2 3 4 5 6 7 1 2 3 4 5 6 7
SOURCE
CONTACT SOURCE CONTACT SOURCE 100-240VAC (L)
250VAC 3A 100-240VAC 250VAC 3A 100-240VAC 50/60Hz 3.8VA Panel
RESISTIVE LOAD 50/60Hz 4.6VA RESISTIVE LOAD 50/60Hz 5.8VA Meters

(M)
Tacho /
Speed / Pulse
Meters

FX4H-1P4 FX4H-2P4 (N)


Display
Units

1 10 CP1 1 10 CP1 (O)


Sensor
CONTACT ※ CONTACT Controllers
250VAC 3A 2 OUT (INHIBIT) 11 CP2 250VAC 3A 2 OUT2 (INHIBIT) 11 CP2
RESISTIVE RESISTIVE
(P)
LOAD LOAD Switching
3 12 12VDC 3 12 12VDC Mode Power
50mA 50mA Supplies

4 13 0VDC 4 13 0VDC (Q)


CONTACT Stepper Motors
250VAC 3A & Drivers
5 14 0VDC RESISTIVE 5 OUT1 14 0VDC & Controllers
LOAD
(R)
6 15 RESET 6 15 RESET Graphic/
Logic
SOLID Panels
7 16 SOLID 7 16 OUT1 STATE
STATE OUT: (S)
Field
8 17 OUT: 8 30VDC
17 OUT2 Network
30VDC 100mA Devices
SOURCE 100mA SOURCE
100-240VAC 9 18 100-240VAC 9 18
50/60Hz 4.6VA 50/60Hz 5.8VA (T)
Software

※INHIBIT: In case of timer mode, this terminal is for time hold.
(voltage input (PNP): connect with 12VDC, no-voltage input (NPN): connect with 0VDC)

J-51
FXM/FXH Series
Dimensions
※Nameplate design is changed and rear length is shorten than previous. (unit: mm)

FXM Series
89.3 ● Bracket ● Panel cut-out
Min. 90

3.3
72 11.8 75

4
46

68 +0.7
0
67.5

37.5

Min. 90
40.5
68 +0.7
0

12
23.9

FXH Series

83 ● Bracket ● Panel cut-out


48 13 70 Min. 65

3.3
4
46

+0.8
092
37.5
40.5

Min. 115
91.5
96

+0.6
12 45 0

23.9

Input Connections
Voltage input (PNP)
● Solid-state input (standard sensor: PNP output type sensor) ● Contact input

Sensor Counter/Timer Sensor Counter/Timer Counter/Timer


Brown ※
Brown
+12V +12V +12V

Black Black
Inner circuit Inner circuit Inner circuit
※ ※
10.8kΩ 10.8kΩ 10.8kΩ
Blue Blue
0V 0V 0V
(PNP output) (PNP open collector output) ※Counting speed
: Set as 1 or 30cps
※CP1, CP2 (INHIBIT), RESET input part

No-voltage input (NPN)


● Solid-state input (standard sensor: NPN output type sensor) ● Contact input
Sensor Counter/Timer Sensor Counter/Timer Counter/Timer
Brown Brown
+12V +12V +12V

5.4kΩ 5.4kΩ 5.4kΩ


Black Black ※
Inner circuit Inner circuit Inner circuit
※ ※
Blue Blue
0V 0V 0V

(NPN output) (NPN open collector output) ※Counting speed


: Set as 1 or 30cps
※CP1, CP2 (INHIBIT), RESET input part

J-52
Up/Down Counter/Timer
Input & Output Connections (A)
Photoelectric

When operation load by sensor power When operating load by external power
Sensors

(B)
Fiber
Optic
(+)Constant-voltage Sensors
(-) circuit
Load1 ※ Load1 (C)
Door/Area
Sensors

PR18-5DP 8 9 10 11 12 13 14 8 9 10 11 12 13 14
CP1 CP2 +12VDC 0VDC (D)
CP1 CP2 +12VDC 0VDC Proximity
Sensors

(E)
Pressure
Sensors
N.O. N.C. N.O. N.C.
COM COM (F)
Rotary
Encoders
1 2 3 4 5 6 7 1 2 3 4 5 6 7
(G)
Connectors/
(power for (power for Connector Cables/
operating load) Load2 operating load) Load2 SOURCE Sensor Distribution
SOURCE Boxes/Sockets

(H)
● The sum of operating current capacity of load 1 and ● The capacity of load 1 should not be over transistor
Temperature
Controllers
sensor should not be over external power capacity switching capacity (max. 30VDC, 100mA)
(50mA). ● Do not supply the reverse polarity power. (I)
SSRs / Power
※when using inductive load (relay, etc.), connector surge Controllers

absorber at both ends of the load 1


(J)
Counters

How to count by external power supply (+) External (K)


This unit starts to count when [H] (5-30VDC) is applied at Limit switch (-) power supply Timers

CP1 or CP2 after selecting PNP. contact

8 9 10 11 12 13 14 (L)
Panel
Meters
CP1 CP2 +12VDC 0VDC
(M)
Tacho /
Speed / Pulse
Meters
(FX4M)
(N)
Display
Units

Using 2 counters with one sensor


(O)
Please connect as the power of sensor is supplied from only one of counters and design input logic with same way. Sensor
Controllers

(P)
Switching
Mode Power
Supplies

(Q)
PR18-5DP Stepper Motors
Black Brown Blue Black +12VDC Blue & Drivers
& Controllers
8 9 10 11 12 13 14 8 9 10 11 12 13 14 (R)
CP1 CP2 +12VDC 0VDC 0VDC Graphic/
CP1 CP2 Logic
Panels

(S)
Field
Network
(FX4M) (FX6M-I) Devices

(T)
Software

J-53
FXM/FXH Series
DIP Switch Setting
FXM Series
One-shot of OUT1
Output operation mode
8 7 6 5 4 3 2 1 5 4 3 2 1
ON Up/Down mode
Input operation mode (counter)
Counter/ Time range (timer)
Timer Memory backup
Counter/Timer
Max. counting speed (counter)
※1 ※2
Input logic (NPN/PNP)
8 7 6 5 4 3 2 1 5 4 3 2 1
FXH Series ON
Factory default
ON
OFF
8 7 6 5 4 3 2 1 5 4 3 2 1

SW1 SW2
※1: Only 2-stage setting model has no. 8 of SW1.
※2: Indicator model does not have no. 5, 6, 7, 8 of SW1.

Input logic
(CP1, CP2, INHIBIT, RESET input) Max. counting speed (counter)
SW2 Function 32 32 32 32
ON NPN SW2 ON ON ON ON
OFF OFF OFF OFF OFF
(no-voltage input)
1
ON PNP Function 1cps 30cps 2kcps 5kcps
OFF (voltage input)

Counter/Timer Memory backup Up/Down mode


SW2 Function SW2 Function SW1 Function
ON
Counter mode ON No memory ON
Down mode
OFF OFF backup OFF
4 5 4
ON Memory ON
OFF
Timer mode ON
OFF
Up mode
OFF backup

Time range (timer) One-shot output of OUT1


SW1 4-digit 6-digit 8-digit SW1 Function
321 ON
ON
One-shot output of OUT1
99.99sec 99999.9sec 999999.99sec OF F
OFF 8
ON
Self-holding output of OUT1
321 OF F
ON 999.9sec 999999sec 9999999.9sec ※This function is for setting one-shot output (0.5 sec
OFF
fixed) or self-holding output (until OUT2 turns OFF)
321 99min of OUT1 at 2-stage setting model.
ON 9999sec 99999999sec
OFF 59.99sec ※Example of output operation mode F

321 99min 999min 99999min


ON RESET
OFF 59sec 59.9sec 59.9sec
2nd setting
321
ON 999.9min 99999.9min 9999999.9min 1st setting
OFF
321 99hour 999hour 0.5 sec
99hour
ON 59min 59min
OFF 59min One-shot output
59sec 59.9sec
321 9999hour OUT1
9999hour
ON 999.9hour 59min Self-holding output
OFF 59min
59sec
OUT2
321 Self-holding output
99999hour (OUT)
ON 9999hour 99999.9hour
OFF 59.9min

J-54
Up/Down Counter/Timer
Input Operation Mode (Counter) ※CP: Clock Pulse (A)
Photoelectric
Sensors
Input mode SW1 Voltage input (PNP) method No-voltage input (NPN) method
(B)
H CP1 H
CP1 L L
Fiber
Optic
Up/ A A A A Sensors
Down-A 3 2 H
ON CP2 L CP2 H
L
(command 3 3 3 3 (C)
OFF 2 2 2 2 2 2 Door/Area
input) Count 1 1 Count 1 1 Sensors
0 0

(D)
H H
CP1 CP1 L Proximity
Up/ L Sensors
3 2 H
Down-B ON CP2 L CP2 H
L
(individual 3 3 3 3 (E)
OFF 2 2 2 2 2 2
input) 1 1 1 1 1 1 Pressure
Count 0 Count 0 Sensors

CP1 H CP1 L
H (F)
Up Up/ L Rotary
BBBB BBBB Encoders
mode Down-C 3 2
(phase ON CP2 H
L CP2 L
H
(G)
3 3 3 3 Connectors/
4 difference OFF 2 2 2 2 2 2 Connector Cables/
1 1 1 1 Sensor Distribution
ON input) Count 0 Count 0 Boxes/Sockets
OFF
CP1 H
L CP1 H
L
(H)
Temperature
A A A A Controllers

CP2 H CP2 H
L
L
No counting 5 No counting 5 (I)
4 3 4 SSRs / Power
2 3 2 Controllers
1 Count 1
Up 3 2 Count 0 0
(adding ON
No counting H (J)
input) OFF CP1 H
L
CP1 No counting Counters
L
A A A A
H H
CP2 L CP2 L (K)
4 5 5 Timers
3 3 4
1 2 Count 2
Count 0 1
0 (L)
Panel
Meters
CP1 H
L CP1 L
H
Up/ A A A A (M)
Down-D 3 2 H Tacho /
CP2 L H
ON CP2 L Speed / Pulse
(command n n Meters
OFF n-1 n-2 n-1 n-1 n-2 n-1
input) Count n-2 n-2 Count n-2 n-2 n-3
n-3 n-3 n-3 (N)
0 0 Display
Units

CP1 H
L CP1 H
L
Up/ (O)
3 2 H H Sensor
Down-E CP2 L CP2 L Controllers
ON
(individual OFF n n
n-1 n-2 n-1 n-1 n-2
input) Count n-1 n-2 n-2 n-1 n-1 n-2 Count n-3 n-2 n-3
(P)
n-3 n-3 Switching
0 0 Mode Power
Supplies

Down CP1 H
L CP1 L
H (Q)
Up/ Stepper Motors
mode BBBB BBBB & Drivers
Down-F 3 2 H & Controllers
ON CP2 L H
(phase CP2 L
4 OFF n n-1 n (R)
ON difference n-1 n-1 n-2 n-1 Graphic/
Count n-2
input) n-3 n-2 n-2
n-3 Count
n-3
n-2 n-2 n-3 Logic
OFF 0 0
Panels

(S)
CP1 H
L CP1 H
L Field
Network
A A A A Devices
H H
CP2 L CP2 L
n No counting n n-1 No counting (T)
n-1 n-2 n-2 Software
n-3 n-3 n-4 n-5
Count n-4 n-5 Count
Down 3 2 0 0
(subtracting ON
H No counting H
input) OFF CP1 L CP1 No counting
L
A A A A
CP2 H
L CP2 L
H
n n n-1
n-1 n-2 n-2
Count n-3 n-4 n-3 n-4
n-5 Count n-5
0 0
※A: over min. signal width, B: over than 1/2 of min. signal width. If the signal is smaller than these width, it may cause counting error (±1).

J-55
FXM/FXH Series
Output Operation Mode
One-shot output of OUT2 Self-holding output
One-shot output of OUT1 Self-holding output
(0.05 to 5 sec)
(0.5 sec fixed)
4 4
Output ON Up mode ON Down mode
mode OFF OFF Operation
(SW1) Up, Up/Down-A, B, C Down, Up/Down-D, E, F
F RESET RESET
2nd setting 2nd setting
1st setting 1st setting
After count-up, counting display value increases
765
0 0 or decreases until reset signal input is applied
ON
OFF OUT1 OUT1 and self-holding output is maintained.
OUT2 OUT2
(OUT) (OUT)

N RESET RESET
2nd setting 2nd setting
1st setting 1st setting
After count-up, counting display value and self-
765
0 0
holding output are maintained until reset signal
ON
OFF
OUT1 OUT1 input is applied.
OUT2 OUT2
(OUT) (OUT)

C RESET RESET When count-up, counting display value is reset


2nd setting 2nd setting and it counts simultaneously.
1st setting 1st setting Self-holding output of OUT1 turns OFF after one-
765 0 0
ON shot output time of OUT2.
OUT1 OUT1
OFF
OUT2
One-shot output time of OUT1 is regardless of
OUT2
(OUT) (OUT) OUT2 output.
R RESET RESET
After count-up, counting display value is reset
2nd setting
2nd setting after one-shot output time of OUT2 and it counts
1st setting 1st setting simultaneously. Self-holding output of OUT1 turns
765 0
ON
0 OFF after one-shot output time of OUT2.
OUT1 OUT1
OFF One-shot output time of OUT1 is regardless of
OUT2 OUT2
(OUT) (OUT) OUT2 output.
K RESET
RESET After count-up, counting display value increases
2nd setting 2nd setting
or decreases until reset signal input is applied.
1st setting 1st setting
765
Self-holding output of OUT1 turns OFF after one-
0 0
ON shot output time of OUT2.
OUT1 OUT1
OFF
OUT2
One-shot output time of OUT1 is regardless of
OUT2
(OUT) (OUT) OUT2 output.
P RESET RESET After count-up, counting display value
2nd setting 2nd setting is maintained while OUT2 output is ON.
Counting value is internally reset and it counts
1st setting 1st setting
765
simultaneously. When OUT2 output is OFF,
0 0 displays counting value while OUT2 output is ON,
ON
OFF OUT1 OUT1 and it increases or decreases. Self-holding output
OUT2 OUT2 of OUT1 turns OFF after one-shot output time of
(OUT) (OUT) OUT2.
RESET RESET After count-up, counting display value increases
Q
2nd setting 2nd setting
or decreases during one-shot time of OUT2. Self-
1st setting 1st setting
holding output of OUT1 turns OFF after one-shot
765 0 0
ON output time of OUT2.
OUT1 OUT1
OFF
OUT2
One-shot output time of OUT1 is regardless of
OUT2
(OUT) (OUT) OUT2 output.
S Up Down
RESET RESET ● Up, Up/Down-A, B, C input mode
2nd setting 2nd setting : OUT1 output maintains ON when counting
1st setting 1st setting display value is larger or equal than 1st setting
0 0 value. OUT2 output maintains ON when
OUT1 OUT1 counting display value is larger or equal than
Counter OUT2 OUT2
mode (OUT) (OUT) 2nd setting value.
Up/Down-A, B, C Up/Down-D, E, F ● Down, Up/Down-D, E, F input mode
765
ON
RESET RESET : OUT1 output maintains ON when counting
OFF 2nd setting 2nd setting display value is smaller or equal than 1st
1st setting 1st setting setting value. OUT2 output maintains ON
0 0
when counting display value is smaller or
OUT1 OUT1
OUT2 OUT2
equal than 2nd setting value.
(OUT) (OUT)
S RESET RESET
2nd setting 2nd setting
Timer 1st setting 1st setting OUT1 and OUT2 turns OFF→ON→OFF
mode 0 0
765 OUT1
repeatedly (flicker).
OUT1
ON OUT2 OUT2
OFF (OUT) (OUT)
※Set one-shot output time by front TIME volume switch.

J-56
Up/Down Counter/Timer
Counting & Time Operation For Indicator (FX M-I4) (A)
Photoelectric
Sensors
Counting operation
(B)
● Input mode: Up ● Input mode: Down Fiber
Optic
Sensors
RESET RESET
+Display (C)
+Display Door/Area
value value Sensors

0
0 (D)
-Display Proximity
value Sensors

● Input mode: Up / Down-A, B, C ● Input mode: Up / Down-D, E, F (E)


Pressure
Sensors
RESET RESET
+Display +Display
(F)
value value Rotary
Encoders
0 0
(G)
-Display -Display Connectors/
value value Connector Cables/
Sensor Distribution
Boxes/Sockets

Time operation (H)


Temperature
Controllers
● Up mode ● Down mode
(I)
SSRs / Power
RESET RESET Controllers

INHIBIT INHIBIT
+Max. time +Max. time (J)
range Counters
range
0
0 -Max. time (K)
range Timers

(L)
Panel

Dot For Decimal Point / Hour. Min. Second


Meters

(M)
Tacho /
※In run mode, hold the RESET key for over 3 sec, and it Speed / Pulse
Meters
RUN mode enters setting mode [DP].
RESET 3 sec ※In setting mode, hold the RESET key for over 3 sec, and it (N)
RESET 3 sec Display
saves the setting and returns to RUN mode. Units

※If there is no RESET key input for 60 sec when entering


DP Setting mode setting mode, it returns to RUN mode. (O)
Sensor
Controllers
RESET
(P)
Counter mode Timer mode Switching
Mode Power
Supplies
Set decimal point RESET
---- by front RESET CLR SET (Q)
Stepper Motors
Hour, Min, Sec are not Hour, Min, Sec are divided with dot. & Drivers
& Controllers
divided with dot. E.g.) )5(59: 59 min 59 sec
E.g.) 5959: 59 min 59 sec (R)
Graphic/
Logic
Panels

(S)
Field
Network
Devices

(T)
Software

J-57
FXM/FXH Series
Proper Usage INHIBIT (for timer)
Reset ※1 ※2
● Reset SW1

In case of changing the input mode after supplying the 8 9 10 11 12 13 14 ※1: Connection for PNP
power, please provide an external reset or manual reset. ※2: Connection for NPN
CP1 CP2 +12V 0V
If reset is not executed, the counter will be working in (INHIBIT)
previous mode.
● Reset signal width FX4M
It is reset perfectly when the reset signal is applied during ● INHIBIT mode is active when SW1 turns ON. (Time Hold)
min. 20ms regardless of the contact input & solid-state ● When power is applied, it starts to progress and INHIBIT
input. mode is used to stop the time is under the progress at
※1 the moment.
● When SW1 is OFF, timer starts to progress again.
Reset input
INHIBIT
※2 Max. display value

※1: In case of a contact reset, contact chattering will not Time


affect the reset as long as it is applied for a minimum 0
(UP mode)
of 20ms.
※2: Input signal at CP1 & CP2 must be applied for a
minimum of 50ms after the reset is removed.
Power
Min. count signal width ● The inner circuit voltage rises within 100ms after
※1 supplying the power to the unit. The input may be
unavailable at this period. Be sure that the inner circuit
1 1
voltage drops within 500ms after turning OFF the power.

ON
Power
※2 ※2 OFF
100㎳ 500㎳
Unstable time for input signal
※1: Please make duty ratio (ON/OFF) as 1:1.
1cps: Min. 500ms ● Use the unit within the rated power supply.
30cps: Min. 16.7ms When supplying or cutting the power, use a switch not to
※2: Min. signal width
2kcps: Min. 0.25ms occur chattering.
5kcps: Min. 0.1ms
ON ON
Max. counting speed Power
OFF
Power
OFF
This is a response speed per 1 sec when the duty ratio
(ON:OFF) of input signal is 1:1. If the duty ratio is not 1:1,
the width between ON and OFF should be over min. signal
width and the response speed will getting slower against Detaching Case or DIP Switch Cover
input signal. If either ON or OFF signal is shorter than ※Turn OFF the power before detaching the case or DIP switch cover.
min. signal width, this product may not respond.
Ta Tb
● FXM Series
Ta (ON width) and
Tb (OFF width) needed to be Push and pull the groove of DIP
over min. signal width. switch cover with a flat head
3×Ta
Max. counting speed is 1/2 driver to the front. The cover is
value of rated spec. when detached from the case.
duty ratio is 1:3.
It can not respond if it is smaller
than min. signal width (Ta). ● FXH Series
①Push the groove of the front guide with a
Error flat head driver and pull it to the front.
Display Error Troubleshooting
Change the setting value
ERR0 Setting value is 0. anything but 0. ②Pull the front guide
to the front. The
※If error occurs, the output turns OFF. case is detached.
※In case of 2-stage setting model, error displays when
2nd setting value is 0 (zero).
※1st setting value is set as 0 (zero), OUT1 maintains OFF.
2nd setting value is smaller than 1st setting value, 1st
setting value is ignored and only OUT2 output operates. Be sure not to be wounded when using a tool.
※Indicator model does not have error display function.