Counter Autonics
Counter Autonics
Counter Autonics
Ordering Information
FX 4 H 2P 4
Power supply
4 100-240VAC 50/60Hz
1P 1-stage setting
Output
2P 2-stage setting
I Indicator
4 9999 (4-digit)
Display digit
6 999999 (6-digit)
8 99999999 (8-digit)
Item
FX Counter/Timer
Specifications
1-stage settingFX4H-1P4 FX4M-1P4 FX6M-1P4 FX8M-1P4
Model 2-stage settingFX4H-2P4 FX4M-2P4 FX6M-2P4 -
Indicator - FX4M-I4 FX6M-I4 FX8M-I4
Display digit 4-digit 6-digit 8-digit
Character size (W×H) 6×10mm 4×8mm 3.8×7.6mm
Power supply 100-240VAC~ 50/60Hz
Permissible voltage range 90 to 110% of rated voltage
Power consumption ● 1-stage: Max. 4.6VA ● 2-stage: Max. 5.8VA ● Indicator: Max. 3.8VA
Max. counting speed of CP1/CP2 Selectable 1cps/30cps/2kcps/5kcps (DIP switch)
Return time Max. 500ms
Min. signal width INHIBIT, RESET: approx. 20ms
Selectable voltage input (PNP) method or no-voltage input (NPN) method
[Voltage input (PNP) method]-input impedance: max. 10.8kΩ, [H]: 5-30VDC , [L]: 0-2VDC
Input method
[No-voltage input (NPN) method]-short-circuit impedance: max. 470Ω , short-circuit residual voltage: max. 1VDC,
open-circuit impedance: min. 100kΩ
One-shot output time ● 1-stage: 0.05 to 5 sec ● 2-stage: 1st setting 0.5 sec fixed, 2nd setting 0.05 to 5 sec
● 1-stage: Instantaneuos SPDT (1c)
Type
Contact ● 2-stage: OUT1-Instantaneuos SPDT (1c), OUT2-Instantaneuos SPDT (1c)
Control Capacity 250VAC~ 3A resistive load
output
Type ● 1-stage: 1 NPN open collector ● 2-stage: OUT1-1 NPN open collector, OUT2-1 NPN open collector
Solid state
Capacity ● Load voltage: Max. 30VDC ● Load current: Max. 100mA ● Residual voltage: Max. 1VDC
Relay Mechanical Min. 5,000,000 operations
life cycle Electrical Min. 100,000 operations (250VAC 3A resistive load)
Repeat/Set/Voltage/Temp. error Max. ±0.01% ±0.05 sec
Insulation resistance Over 100MΩ (at 500VDC megger)
External power supply Max. 12VDC ±10% 50mA
Memory retention Approx. 10 years (non-volatile memory)
Dielectric strength 2,000VAC 50/60Hz for 1 min (between all terminals and case)
Noise immunity ±2kV the square wave noise (pulse width 1μs) by noise simulator
J-50
Up/Down Counter/Timer
Specifications (A)
Photoelectric
1-stage setting FX4H-1P4 FX4M-1P4 FX6M-1P4 FX8M-1P4 Sensors
Connections (H)
Temperature
Controllers
(M)
Tacho /
Speed / Pulse
Meters
※INHIBIT: In case of timer mode, this terminal is for time hold.
(voltage input (PNP): connect with 12VDC, no-voltage input (NPN): connect with 0VDC)
J-51
FXM/FXH Series
Dimensions
※Nameplate design is changed and rear length is shorten than previous. (unit: mm)
FXM Series
89.3 ● Bracket ● Panel cut-out
Min. 90
3.3
72 11.8 75
4
46
68 +0.7
0
67.5
37.5
Min. 90
40.5
68 +0.7
0
12
23.9
FXH Series
3.3
4
46
+0.8
092
37.5
40.5
Min. 115
91.5
96
+0.6
12 45 0
23.9
Input Connections
Voltage input (PNP)
● Solid-state input (standard sensor: PNP output type sensor) ● Contact input
Black Black
Inner circuit Inner circuit Inner circuit
※ ※
10.8kΩ 10.8kΩ 10.8kΩ
Blue Blue
0V 0V 0V
(PNP output) (PNP open collector output) ※Counting speed
: Set as 1 or 30cps
※CP1, CP2 (INHIBIT), RESET input part
J-52
Up/Down Counter/Timer
Input & Output Connections (A)
Photoelectric
When operation load by sensor power When operating load by external power
Sensors
(B)
Fiber
Optic
(+)Constant-voltage Sensors
(-) circuit
Load1 ※ Load1 (C)
Door/Area
Sensors
PR18-5DP 8 9 10 11 12 13 14 8 9 10 11 12 13 14
CP1 CP2 +12VDC 0VDC (D)
CP1 CP2 +12VDC 0VDC Proximity
Sensors
(E)
Pressure
Sensors
N.O. N.C. N.O. N.C.
COM COM (F)
Rotary
Encoders
1 2 3 4 5 6 7 1 2 3 4 5 6 7
(G)
Connectors/
(power for (power for Connector Cables/
operating load) Load2 operating load) Load2 SOURCE Sensor Distribution
SOURCE Boxes/Sockets
(H)
● The sum of operating current capacity of load 1 and ● The capacity of load 1 should not be over transistor
Temperature
Controllers
sensor should not be over external power capacity switching capacity (max. 30VDC, 100mA)
(50mA). ● Do not supply the reverse polarity power. (I)
SSRs / Power
※when using inductive load (relay, etc.), connector surge Controllers
8 9 10 11 12 13 14 (L)
Panel
Meters
CP1 CP2 +12VDC 0VDC
(M)
Tacho /
Speed / Pulse
Meters
(FX4M)
(N)
Display
Units
(P)
Switching
Mode Power
Supplies
(Q)
PR18-5DP Stepper Motors
Black Brown Blue Black +12VDC Blue & Drivers
& Controllers
8 9 10 11 12 13 14 8 9 10 11 12 13 14 (R)
CP1 CP2 +12VDC 0VDC 0VDC Graphic/
CP1 CP2 Logic
Panels
(S)
Field
Network
(FX4M) (FX6M-I) Devices
(T)
Software
J-53
FXM/FXH Series
DIP Switch Setting
FXM Series
One-shot of OUT1
Output operation mode
8 7 6 5 4 3 2 1 5 4 3 2 1
ON Up/Down mode
Input operation mode (counter)
Counter/ Time range (timer)
Timer Memory backup
Counter/Timer
Max. counting speed (counter)
※1 ※2
Input logic (NPN/PNP)
8 7 6 5 4 3 2 1 5 4 3 2 1
FXH Series ON
Factory default
ON
OFF
8 7 6 5 4 3 2 1 5 4 3 2 1
SW1 SW2
※1: Only 2-stage setting model has no. 8 of SW1.
※2: Indicator model does not have no. 5, 6, 7, 8 of SW1.
Input logic
(CP1, CP2, INHIBIT, RESET input) Max. counting speed (counter)
SW2 Function 32 32 32 32
ON NPN SW2 ON ON ON ON
OFF OFF OFF OFF OFF
(no-voltage input)
1
ON PNP Function 1cps 30cps 2kcps 5kcps
OFF (voltage input)
J-54
Up/Down Counter/Timer
Input Operation Mode (Counter) ※CP: Clock Pulse (A)
Photoelectric
Sensors
Input mode SW1 Voltage input (PNP) method No-voltage input (NPN) method
(B)
H CP1 H
CP1 L L
Fiber
Optic
Up/ A A A A Sensors
Down-A 3 2 H
ON CP2 L CP2 H
L
(command 3 3 3 3 (C)
OFF 2 2 2 2 2 2 Door/Area
input) Count 1 1 Count 1 1 Sensors
0 0
(D)
H H
CP1 CP1 L Proximity
Up/ L Sensors
3 2 H
Down-B ON CP2 L CP2 H
L
(individual 3 3 3 3 (E)
OFF 2 2 2 2 2 2
input) 1 1 1 1 1 1 Pressure
Count 0 Count 0 Sensors
CP1 H CP1 L
H (F)
Up Up/ L Rotary
BBBB BBBB Encoders
mode Down-C 3 2
(phase ON CP2 H
L CP2 L
H
(G)
3 3 3 3 Connectors/
4 difference OFF 2 2 2 2 2 2 Connector Cables/
1 1 1 1 Sensor Distribution
ON input) Count 0 Count 0 Boxes/Sockets
OFF
CP1 H
L CP1 H
L
(H)
Temperature
A A A A Controllers
CP2 H CP2 H
L
L
No counting 5 No counting 5 (I)
4 3 4 SSRs / Power
2 3 2 Controllers
1 Count 1
Up 3 2 Count 0 0
(adding ON
No counting H (J)
input) OFF CP1 H
L
CP1 No counting Counters
L
A A A A
H H
CP2 L CP2 L (K)
4 5 5 Timers
3 3 4
1 2 Count 2
Count 0 1
0 (L)
Panel
Meters
CP1 H
L CP1 L
H
Up/ A A A A (M)
Down-D 3 2 H Tacho /
CP2 L H
ON CP2 L Speed / Pulse
(command n n Meters
OFF n-1 n-2 n-1 n-1 n-2 n-1
input) Count n-2 n-2 Count n-2 n-2 n-3
n-3 n-3 n-3 (N)
0 0 Display
Units
CP1 H
L CP1 H
L
Up/ (O)
3 2 H H Sensor
Down-E CP2 L CP2 L Controllers
ON
(individual OFF n n
n-1 n-2 n-1 n-1 n-2
input) Count n-1 n-2 n-2 n-1 n-1 n-2 Count n-3 n-2 n-3
(P)
n-3 n-3 Switching
0 0 Mode Power
Supplies
Down CP1 H
L CP1 L
H (Q)
Up/ Stepper Motors
mode BBBB BBBB & Drivers
Down-F 3 2 H & Controllers
ON CP2 L H
(phase CP2 L
4 OFF n n-1 n (R)
ON difference n-1 n-1 n-2 n-1 Graphic/
Count n-2
input) n-3 n-2 n-2
n-3 Count
n-3
n-2 n-2 n-3 Logic
OFF 0 0
Panels
(S)
CP1 H
L CP1 H
L Field
Network
A A A A Devices
H H
CP2 L CP2 L
n No counting n n-1 No counting (T)
n-1 n-2 n-2 Software
n-3 n-3 n-4 n-5
Count n-4 n-5 Count
Down 3 2 0 0
(subtracting ON
H No counting H
input) OFF CP1 L CP1 No counting
L
A A A A
CP2 H
L CP2 L
H
n n n-1
n-1 n-2 n-2
Count n-3 n-4 n-3 n-4
n-5 Count n-5
0 0
※A: over min. signal width, B: over than 1/2 of min. signal width. If the signal is smaller than these width, it may cause counting error (±1).
J-55
FXM/FXH Series
Output Operation Mode
One-shot output of OUT2 Self-holding output
One-shot output of OUT1 Self-holding output
(0.05 to 5 sec)
(0.5 sec fixed)
4 4
Output ON Up mode ON Down mode
mode OFF OFF Operation
(SW1) Up, Up/Down-A, B, C Down, Up/Down-D, E, F
F RESET RESET
2nd setting 2nd setting
1st setting 1st setting
After count-up, counting display value increases
765
0 0 or decreases until reset signal input is applied
ON
OFF OUT1 OUT1 and self-holding output is maintained.
OUT2 OUT2
(OUT) (OUT)
N RESET RESET
2nd setting 2nd setting
1st setting 1st setting
After count-up, counting display value and self-
765
0 0
holding output are maintained until reset signal
ON
OFF
OUT1 OUT1 input is applied.
OUT2 OUT2
(OUT) (OUT)
J-56
Up/Down Counter/Timer
Counting & Time Operation For Indicator (FX M-I4) (A)
Photoelectric
Sensors
Counting operation
(B)
● Input mode: Up ● Input mode: Down Fiber
Optic
Sensors
RESET RESET
+Display (C)
+Display Door/Area
value value Sensors
0
0 (D)
-Display Proximity
value Sensors
INHIBIT INHIBIT
+Max. time +Max. time (J)
range Counters
range
0
0 -Max. time (K)
range Timers
(L)
Panel
(M)
Tacho /
※In run mode, hold the RESET key for over 3 sec, and it Speed / Pulse
Meters
RUN mode enters setting mode [DP].
RESET 3 sec ※In setting mode, hold the RESET key for over 3 sec, and it (N)
RESET 3 sec Display
saves the setting and returns to RUN mode. Units
(S)
Field
Network
Devices
(T)
Software
J-57
FXM/FXH Series
Proper Usage INHIBIT (for timer)
Reset ※1 ※2
● Reset SW1
In case of changing the input mode after supplying the 8 9 10 11 12 13 14 ※1: Connection for PNP
power, please provide an external reset or manual reset. ※2: Connection for NPN
CP1 CP2 +12V 0V
If reset is not executed, the counter will be working in (INHIBIT)
previous mode.
● Reset signal width FX4M
It is reset perfectly when the reset signal is applied during ● INHIBIT mode is active when SW1 turns ON. (Time Hold)
min. 20ms regardless of the contact input & solid-state ● When power is applied, it starts to progress and INHIBIT
input. mode is used to stop the time is under the progress at
※1 the moment.
● When SW1 is OFF, timer starts to progress again.
Reset input
INHIBIT
※2 Max. display value
ON
Power
※2 ※2 OFF
100㎳ 500㎳
Unstable time for input signal
※1: Please make duty ratio (ON/OFF) as 1:1.
1cps: Min. 500ms ● Use the unit within the rated power supply.
30cps: Min. 16.7ms When supplying or cutting the power, use a switch not to
※2: Min. signal width
2kcps: Min. 0.25ms occur chattering.
5kcps: Min. 0.1ms
ON ON
Max. counting speed Power
OFF
Power
OFF
This is a response speed per 1 sec when the duty ratio
(ON:OFF) of input signal is 1:1. If the duty ratio is not 1:1,
the width between ON and OFF should be over min. signal
width and the response speed will getting slower against Detaching Case or DIP Switch Cover
input signal. If either ON or OFF signal is shorter than ※Turn OFF the power before detaching the case or DIP switch cover.
min. signal width, this product may not respond.
Ta Tb
● FXM Series
Ta (ON width) and
Tb (OFF width) needed to be Push and pull the groove of DIP
over min. signal width. switch cover with a flat head
3×Ta
Max. counting speed is 1/2 driver to the front. The cover is
value of rated spec. when detached from the case.
duty ratio is 1:3.
It can not respond if it is smaller
than min. signal width (Ta). ● FXH Series
①Push the groove of the front guide with a
Error flat head driver and pull it to the front.
Display Error Troubleshooting
Change the setting value
ERR0 Setting value is 0. anything but 0. ②Pull the front guide
to the front. The
※If error occurs, the output turns OFF. case is detached.
※In case of 2-stage setting model, error displays when
2nd setting value is 0 (zero).
※1st setting value is set as 0 (zero), OUT1 maintains OFF.
2nd setting value is smaller than 1st setting value, 1st
setting value is ignored and only OUT2 output operates. Be sure not to be wounded when using a tool.
※Indicator model does not have error display function.