Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 8

PREPARATION OF HARDWARE AND SOFTWARE.

1. Prepare and install IEDScount software in a Test Laptop/Desktop for running IED simulator.
2. Copy all IED 61850 CID files in the test laptop/desktop.
3. Configure the IP address of the laptop/desktop IED simulator. (IEDScout can only simulate one
IED at a time so for example configure 192.168.0.136/255.255.254.0 for simulating IED
93BBA02).
4. Go to Ovation DCS, DROP200 and open Developer Studio.
5. Navigate to ELC module location at 1.1.8 and 1.2.1, Open module configuration and check IP
address configured. (Currently using PRIMARY:192.168.2.245/255.255.254.0
PARTNER:192.168.2.246/255.255.254.0).

6. On DROP200 open System Viewer Application and navigate to DROP1/51 and 1.1.8.
7. Check status of ELC modules like below. A Primary Module value of 0x4061 means good status.

8. Connect the
UTP cables of
the test
laptop/PC and PRIMARY & PARTNER ELC modules into a network switch.
9. Check the connectivity if the test laptop/PC can Ping the IP of PRIMARY & PARTNER ELC
modules.
10. Once network connectivity is verified, run the IEDScout application on the test laptop/PC.
11. Select Simulate IED option on the IED scout,

12. Browse to the location of the CID files, for example to simulate 93BBA02 select this CID file like
below.

13. Once the CID file is selected, click Start in the IEDScout. Select the IP address that you configured
for listening.
14. Once the IED simulator correctly starts you will be able to browse IEC-61850 Data Object, logical
devices and data sets within the selected CID File.
VERIFY THE IEC-61850 ELC CONFIGURATION POINT MAPPING

1. To start, check IEC-61850 ELC configuration. Go to DROP1/51->1.1.8 Module, right click and
select Engineer.

2. The Ovation CPS application will pop-up. Here you can verify the ELC configuration.

3. To verify the IP address of the IED, go to IEC 61850 MMS Client Line-> IEC 61850 MMS RTU,
for example below is for 93BBA02. CID file location is also available here.
4. Make sure that the IP address IEC 61850 MMS RTU/IED is same as the test Laptop/PC for
IEDScout.

5. To verify the Logical device of the IED, go to MMSSCANBLOCK. For example below is the
MMSSCANBLOCK for GetDataValues (Read DI/SOE Status).

Also, you can check all the available Logical Device in the CID file by click the dotted
symbol,
6. To verify the IEC-61850 mapping for each Ovation point. Go to Scan Points Tab,

Also, you may verify the available data attributes from the CID file by clicking the dotted
lines,

7. Please verify the ELC Mappings vs. the IEC-81650 IO information from the IED vendor.
SIMULATING FOR DI/SOE

1. On Ovation DCS open Graphics application and Load and browse the ELC commissioning
graphics at ELC_51005115.diag

2. Start the IEDScout on the test laptop/PC. For example, to simulate IED for 93BBA02 DI/SOE
points focus on the SOE points on the graphics.

Ovation Point Name

IEC61850 MAPPING

POINT VALUE

POINT QUALITY
(BLANK MEANS GOOD)

You may click the Ovation name to see the Point description,

3. On the IEDScout, Navigate to the Data Attribute for example, on the vendor IEC Information.

Select this data


attribute stVal for
Boolean data
4. Click Set Value bottom on top and change data window will pop-up. Change the value.

5. Once you change value, check the feedback value on the specific Ovation point in Graphics and
verify if correct.

You might also like