Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

CLIENT: CELEC EP - TRANSELECTRIC

BATTERY TYPE: VRLA NUMBER OF CELLS: 24 x BANCO

CAPACITY : 200 AH Equipment type : FP40R30 100 48V

BATTERY 1 BATTERY 2
Cell Cell Cell Cell Cell Cell Cell Cell
N° Vot N° Volt N° Volt N° Volt

1 2,257 21 2,223 1 2,249 21 2,254


2 2,224 22 2,218 2 2,219 22 2,211
3 2,262 23 2,249 3 2,255 23 2,238
4 2,226 24 2,245 4 2,247 24 2,260
5 2,248 25 -- 5 2,250 25 --
6 2,218 26 -- 6 2,246 26 --
7 2,223 27 -- 7 2,231 27 --
8 2,222 28 -- 8 2,245 28 --
9 2,44 29 9 2,250 29
10 2,220 30 10 2,237 30
11 2,273 31 11 2,205 31
12 2,215 32 12 2,250 32
13 2,273 33 13 2,230 33
14 2,240 34 14 2,243 34
15 2,243 35 15 2,246 35
16 2,221 36 16 2,251 36
17 2,224 37 17 2,253 37
18 2,270 38 18 2,247 38
19 2,267 39 19 2,249 39
20 2,229 40 20 2,210 40

OVERALL VOLTAGE B1: 53,53 V OVERALL VOLTAGE B2: 53,78V BATT ROOM TEMPERATURE : 22 °C

BATT SENSOR CONNECTED Y/N : Y

COMMENTS :
……………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………

COMPANY INSPECTION EMERSON / PROTECOMPU INSPECTION CUSTOMER


NETWORK POWER IS
NAME Rodrigo Torres B. Alvaro Cevallos
DATE 06/junio/2016 06/junio/2016

SIGNATURE

Checked
Date : Origin : Approval by :
by :
PCT 1.10
Page 1/1
Reference :

BATTERY CHECK OPEN CIRCUIT INS-E 09 EN Ind. 7


Revision Date : 01/08/2014
Model Reference : IMP00-006