Performance Testing of Different Grounding Systems

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Performance Testing of Different Grounding Systems

S. Saleh, D. Jewett, and J. Cardenas A. Al-Durra and S. Kanukollu M. Valdes S. Panetta


ECE Department, UNB Advanced Power & Energy Center ABB Industrial Solutions I-Gard Corporation
2022 IEEE/IAS 58th Industrial and Commercial Power Systems Technical Conference (I&CPS) | 978-1-6654-0918-6/22/$31.00 ©2022 IEEE | DOI: 10.1109/ICPS54075.2022.9773920

Fredericton, NB, Canada Khalifa Uni., Abu Dhabi, UAE Cary, NC Mississauga, ON
asaleh@unb.ca; djewett3@unb.ca ahmed.aldurra@ku.ac.ae USA Canada
jcardena@unb.ca saikrishna.kanukollu@ku.ac.ae marcelo.valdes@us.abb.com spanetta@ieee.org

Abstract—This paper presents a performance comparison of the un-faulted phase(s) [4]–[7]. In some cases, ground faults can
solid, low impedance, high impedance, frequency-selective, and also evolve into arcing current faults that may create additional
isolated grounding systems. A grounding system (for any power damages and safety risks [15]–[19]. Such adverse impacts of
system component) is designed as an impedance (Z̄G ) that connects
the neutral point to the ground. The impedance Z̄G is constructed ground faults can be minimized by an adequate design of a
using a combination of R, L, and C elements. The values and grounding system that is capable of influencing ground currents
combination type (series or parallel) of R, L, C, determine the and potentials [5].
possible influence of Z̄G on ground currents and potentials. Each
grounding system is related to a system voltages level, a specific B. Features and Capabilities of Grounding Systems
combination of R, L, C, and a range of R, L, C values. The solid,
low impedance, high impedance, frequency-selective, and isolated Several designs of grounding systems have been developed
grounding systems are designed for laboratory 3φ transformer and and deployed in power systems. These designs can offer differ-
3φ synchronous generator in order to compare their influences ent levels of influence on ground currents and potentials during
on ground currents and potentials during ground faults. The ground fault events. The diverse features and capabilities of
transformer and generator are tested for line-to-ground and double grounding system designs suggest the need to introduce system
line-to-ground faults with all designed grounding systems. Test
results show that some grounding systems can reduce ground operation constraints, such as [1]–[7]:
currents only, while others can reduce ground potentials only. Such • the service continuity;
capabilities can be used to fulfill certain system and operation • the ground capacity (maximum current to flow to the
requirements (e.g. service continuity, ground capacity, etc.).
ground);
Index Terms—power system grounding, grounding system de-
signs, power system ground faults, and power system protection. • the cost and maintenance;
• the harmonic and circulating currents through the ground.

The following paragraphs overview the grounding system de-


I. I NTRODUCTION
signs that are used in medium voltage systems.
 
A. General In systems with an isolated grounding Z̄G = ∞ , the neutral
A proper grounding system design (for any power system) point is viewed to be connected to the ground through the sys-
aims to reduce voltage and thermal stresses created by faults, tem equivalent parasitic capacitance (non-physical connection)
increase personnel safety, minimize the interference on commu- [1], [2]. Ground faults in systems with an IG initiate ground
nications systems, provide a non-damaging path for lightning currents, whose magnitudes depend on the fault impedance, z F ,
strikes, support the function of ground fault protection, and and zero-sequence component of the system capacitance, x C0 .
improve the power quality [1]–[6]. These objectives can be These systems can remain operational (continue their service)
translated into the need for reducing ground currents and during sustained ground faults [4]–[8]. However, ground faults
potentials during fault and non-fault (harmonics flow to the in systems with an IG may trigger high transient voltages that
ground, and circulating ground-neutral currents for systems may excite arcing currents. Moreover, voltage transients may
with multiple sources) conditions. A grounding system can be fuel over-voltage in the un-faulted phase(s) [5]. In addition, the
designed as a solid grounding (SG), a low-impedance ground- IG can make it difficult to locate ground faults. 
ing (LIG), a high-impedance grounding (HIG), a frequency- In systems with a solid grounding Z̄G = 0 , the neutral
selective grounding (FSG), and an isolated grounding (IG) (also is directly connected the ground. The SG allows connecting
known as ungrounded) [6]–[10]. multiple neutrals to the same grounding point [16], [17]. When
The majority of grounding system design objectives can a SG is used, ground faults can trigger ground currents with
be met by the IG and HIG [11]–[13]. However, the IG and high magnitudes that can cause equipment damage. Responses
HIG may fail to support the function of the ground fault to such faults may lead to service interruption, the duration
protection due to the significant reduction of ground currents of which can be reduced by deploying automatic multishot-
[14]–[19]. The SG, LIG, and FSG can support the function reclosers [9], [12], [13]. The use of SG can minimize the
of ground protection, but they may fail to prevent thermal possibility of transient over-voltage experienced by non-faulty
damage to equipment [1]–[4], [20], [21]. Ground faults (line-to- phase(s). Furthermore, the SG is found effectively capable of
ground and double line-to-ground faults) can be experienced by supporting the operation of the ground fault protection [1], [2],
different power system components (transformers, generators, [5]. However, the SG does not offer any reductions on ground
motor drives, etc.). These undesired events can adversely impact currents triggered by ground faults, thus increasing the risk of
faulted components, equipment, and instrumentation [1]–[3]. equipment damage. In addition, systems with a SG are prone to
Furthermore, ground faults can initiate rapid increases in ground have ground faults that can quickly evolve into arcing current
potential, which may lead to transient over-voltages on the faults [9].

Authorized licensed use limited to: Francisco Guillen. Downloaded on June 04,2022 at 11:31:19 UTC from IEEE Xplore. Restrictions apply.
In systems with a low impedance grounding, the neutral is The achievement of these objectives support the following
connected to the ground through a low-impedance resistor or contributions:
inductor to create Z̄G . The value of Z̄G is selected to limit i) An experimental testing of grounding systems to demon-
ground currents, during ground faults, to 100 A for low voltage strate their capabilities and features.
systems, and 400 A for medium voltage systems [1]–[6]. The ii) A performance comparison between grounding systems.
LIG can effectively reduce equipment thermal stress during
ground faults, and support the function of ground fault protec- II. D ESIGNING G ROUNDING S YSTEMS FOR A 3φ
tion. This grounding system design can reduce ground potentials T RANSFORMER AND A 3φ G ENERATOR
and minimize the possibility for transient over-voltages. The The capabilities and features of the IG, SG, LIG, HIG, and
LIG is popular in industrial plants and distributed generation FSG are evaluated and compared for a 3φ synchronous genera-
units [10]. The main disadvantages of LIG include the ratings, tor and a 3φ transformer. These grounding systems are designed
size, cost, high maintenance requirements, and possible needs for the test transformer and generator. The specifications for the
for tripping upstream circuit breakers (CBs) [5], [6]. test 3φ generator and 3φ transformer are provided in the next
In systems with a high impedance grounding (HIG), the subsection.
neutral is connected to the ground through a high-impedance
resistor or inductor to create Z̄G . The value of Z̄G is selected A. Data for the Tested Components
to limit ground currents, during ground faults, to 10 A for low The test 3φ generator is a laboratory 4 kVA 3φ synchronous
voltage systems and 25 A for medium voltage systems [6]. Some machine, whose parameters are listed in Table I.
industrial practices recommend the value of Z̄G to be selected
equal to the total system equivalent capacitive impedance x C . TABLE I
The HIG can offer service continuity during ground faults with PARAMETERS FOR THE T EST 3φ S YNCHRONOUS G ENERATOR
low magnitude ground currents. This grounding system design
Rated Power 4.0 kVA
can also reduce the transient over-voltages, and can be used with Rated Voltage 208 V
grounding transformers [6]. Nonetheless, the HIG has limited Number of Poles 4
support for locating ground faults, and may not be effective in Rated Frequency 60 Hz
supporting the function of ground fault protection [5]. x1 2.66 Ω
r1 0.45 Ω
In systems with a frequency-selective grounding, the neutral x2 2.93 Ω
is connected to the ground through a parallel R − C circuit r2 0.80 Ω
to create Z̄G . The value of the resistive part (r G ) is selected x0 1.80 Ω
r0 0.48 Ω
to limit ground currents similar to the LIG, and the value Configuration Y -Connected
of capacitive part (c G ) is selected to have an impedance of Inertia H 0.193 sec.
xcG = 5rG [10], [12]. The FSG can be deployed for low and
This generator is grid-connected through a short cable that has
medium voltage systems that may have harmonic distortions
a negligible capacitance (x C0 ≈ ∞).
(e.g. battery storage systems). This grounding system design
The test 3φ transformer is a 35 kVA, 3φ, 60 Hz, core-type,
offers support to functions of ground fault protection, along with
power transformer that is fed by a 3φ supply with an accessible
an effective reduction of voltage transients during ground faults.
neutral and ground points [22]. The data for this transformer is
Moreover, the FSG can reduce ground currents during faults,
provided in Table II.
thus reducing the thermal stresses on grounded equipment. The
cost and maintenance are the main disadvantages for the FSG
TABLE II
[5], [10]. PARAMETERS FOR THE T EST 3φ T RANSFORMER

C. Objectives and Contributions Rated Power 35.0 kVA


Rated Voltage 380/208 V
The overview of grounding system designs has highlighted
Rated Frequency 60 Hz
the capabilities and features of each grounding system design. x1 3.28 Ω
The variety of such capabilities and features provides options r1 0.66 Ω
for accommodating the requirements and operational constraints x2 3.33 Ω
r2 0.90 Ω
mandated by grounded components and equipment. Further- x0 2.94 Ω
more, the various capabilities and features of grounding systems r0 0.53 Ω
can be considered for changing and upgrading existing ground- Configuration ∆−Y
ing systems. This paper intends to experimentally test different The cable connecting the primary side of the test 3φ transformer
grounding system designs, and assess their performance. The to the supply is a short cable with x C0 ≈ ∞. The grounding
objectives of this paper can be summarized as: capacity in the testing laboratory is 300 A.
• to evaluate the performance of grounding systems during
ground faults; B. The Design of the LIG, HIG, and FSG
   
• to compare the performance of grounding systems in terms The designs of a SG Z̄G = 0 and IG Z̄G = ∞ do not
of ground currents and potentials; involve specifying a value for Z̄G . The LIG is designed
 by
• to examine the impacts of grounding systems on the selecting a value for its grounding impedance Z̄G to limit
grounded equipment during non-fault conditions. the ground current to 100 A for a low-voltage (LV). Since the

Authorized licensed use limited to: Francisco Guillen. Downloaded on June 04,2022 at 11:31:19 UTC from IEEE Xplore. Restrictions apply.
 
test transformer and generator have their voltage ratings as LV, with rGff being the resistive part of the FSG impedance Z̄Gff .
the value of Z̄G has to limit the maximum ground current The aforementioned discussion leads to stating the following
(|iG |max ) to 100 A. The LIG can be designed as a low-resistance equations for determining r gff and CGff :
or a low-inductance as:  
0.4VP = |iG |max Z̄Gff  (11)
• A low-resistance:
VP
VP |iG |max = (12)
|iG |max = ≤ 100 (1) rGff
rG xGff = 8rGff (13)
where VP is the line-to-neutral voltage, and r G is the
The solution of these equations provides r Gff ≥ 1.84 Ω and
low-resistance of the LIG. The voltage ratings of the test
CGff ≤ 181.19 µF.
generator and transformer is 208 V (line-to-line), which
simplifies equation (1) to: III. H ARDWARE -I N -T HE -L OOP T EST R ESULTS
208 The Hardware-In-the-Loop (HIL) testing was conducted us-
√ ≤ 100 =⇒ rG ≥ 1.21 Ω (2)
3rG ing the dSPACE MicrolabBox (ds1202) platform. This platform
compiled models created using the real-time interface (RTI), and
• A low-inductance:
executed them using field-programmable gate arrays (FPGAs)
VP [23], [24]. Tested faults were created by circuit breakers (CBs)
|iG |max = ≤ 100 (3)
xG that were activated with pulses generated by the ds1202 plat-
form. Voltages, currents, and ground potentials were collected
Substituting for VP simplifies equation (3) to:
using analog output ports of the ds 1202 platform, and were
208 collected using digital oscilloscopes. All HIL tests were con-
√ ≤ 100 =⇒ xG ≥ 1.21 Ω (4)
3xG ducted with a time step of 20 µsec. Several faults were created
on the secondary side of the test 3φ transformer, and on the
The value of the LIG inductance L G is determined as: terminals of the test 3φ synchronous generator. These tests were
xG created for both tested components, as they were grounded using
LG = =⇒ LG ≥ 3.2 mH (5)
2π60 different grounding system designs (as described in Section II).
  The following subsections present and discuss sample HIL test
The HIG can be designed with a grounding impedance Z̄Ghh
results. It should be noted that all line-to-ground faults were
to limit the ground current to 25 A. Similar to the LIG, the HIG
created as phase A-to-ground, while all double-line-to-ground
can be designed as either a high-resistance or a high-inductance
faults were created as phase B-to-phase C-to-ground faults.
as:
These settings were made to support a fair comparison between
• A high-resistance: the different tested grounding system designs.
VP
|iG |max = ≤ 25 (6) A. 3φ Transformer Testing
rGhh
These tests were created with secondary side grounded using:
where rGhh is the high-resistance of the HIG. Substituting
• A low resistance grounding (LRG): designed as a LIG;
for VP simplifies equation (6) to:
• A low inductance grounding (LXG): designed as a LIG;
208 • A high resistance grounding (HRG): designed as a HIG
√ ≤ 100 =⇒ rGhh ≥ 4.80 Ω (7)
3rGhh • A high inductance grounding (HXG): designed as a HIG
• A frequency selective grounding (FSG);
• A high-inductance: • A solid grounding (SG);

VP • An isolated grounding (IG).


|iG |max = ≤ 25 (8)
xG The design of the LIG and HIG has been discussed in Section
II. The transformer was kept at 60% of its rated power, and all
Substituting for VP simplifies equation (8) to: tested ground faults were created with a fault impedance z̄ F =
208 0. The following test cases are sample cases to demonstrate
√ ≤ 25 =⇒ xGhh ≥ 4.80 Ω (9) the impacts of ground faults created with different grounding
3xGhh
systems.
The value of the HIG inductance L Ghh is determined as: Phase A-to-Ground Fault with LRG
xGhh The objective of this test was to examine the impacts of a line-
LGhh = =⇒ LGhh ≥ 12.70 mH (10) to-ground fault on the 3φ transformer, when grounded using a
2π60
LRG. This test was conducted as the 3φ transformer supplied
The FSG is designed as a parallel R − C circuit to limit
a linear (R − L) load. The phase A-to-ground fault was created
|iG |max to 66 A, and a ground potential |v G |max to 0.4VP [12].
on the secondary side of the test 3φ transformer. Fig. 1 shows
The value of the capacitance C Gff is selected as [10]:
the secondary side 3φ line voltages, 3φ currents, phase A
8 current, ground potential, and ground current (flowing through
CGff = the LRG).
2π60rGff

Authorized licensed use limited to: Francisco Guillen. Downloaded on June 04,2022 at 11:31:19 UTC from IEEE Xplore. Restrictions apply.
Fig. 1. The phase A-to-ground fault on the terminals of the 3φ transformer Fig. 2. The phase B-to-phase C-to-ground fault on the terminals of the
secondary side, when grounded with a LRG: (a) the 3φ line voltages, voltage 3φ transformer secondary side, with isolated grounding (IG): (a) the 3φ line
scale 300 V/Div. (b) the 3φ currents, current scale is 80 A/Div, (c) phase A voltages, voltage scale 300 V/Div. (b) the 3φ currents, current scale is 80 A/Div,
current, ground current, and ground potential, iA scale is 80 A/ Div, iG scale (c) phase B current, ground current, and ground potential, iB scale is 80 A/
80 A/Div., and vG scale is 300 V/Div. The time scale is 40 msec./Div. Div, iG scale 80 A/Div., and vG scale is 300 V/Div. The time scale is 40
msec./Div.
The results in Fig. 1 show that the solid line-to-ground fault,
with the LRG resulted in transient changes in the voltages and fault significantly reduced the line voltages v BC and vCA . The
currents. The phase A-to-ground fault caused a severe reduction phase B-to-phase C-to-ground fault resulted in large increases
in vAB , an over-voltage in v BC , and minor decrease in v CA , in iB and iC , with minor changes in i A , as shown in Fig.
as shown in Fig. 1 (a). Furthermore, the tested ground fault 2 (b). The tested ground fault eliminated the ground current,
triggered large increases in i A and iB , and slightly decreased while allowing the ground potential to increase (see Fig.2 (c).
iC (see Fig. 1 (b)). The solid line-to-ground fault also resulted The results of this test demonstrated that the IG allowed v G to
in high ground current i G and a small increase in the ground increase, which triggered a transient over-voltage in v AB .
potential vG , as could be seen from Fig. 1 (c). The results of this Phase A-to-Ground Fault with FSG
test demonstrated that the LRG was able to reduce the ground This HIL test aimed to examine the impacts of a line-to-
current that was triggered by the tested fault. However, the LRG ground fault on the secondary side of the 3φ transformer,
was not able to eliminate the ground potential that caused v BC when grounded using a FSG. This test was conducted as the
to reach more than 140% of its pre-fault value. 3φ transformer supplied a dynamic load. Fig. 3 shows the
Phase B -to-Phase C -to-Ground Fault with IG secondary side 3φ line voltages, 3φ currents, phase A current,
This HIL test aimed to examine the impacts of a solid double ground potential, and ground current flowing through the FSG.
line-to-ground fault, which was created on the secondary side
of the test transformer. The secondary side of the transformer One could see from Fig. 3 that the solid phase A-to-ground
was with an isolated grounding. This test was conducted as the fault on the secondary side, with a FSG, created transients in
transformer supplied a dynamic load (a 3φ induction motor). voltages and currents. The tested line-to-ground fault signif-
Fig. 2 shows the secondary side 3φ line voltages, 3φ currents, icantly reduced v AB , increased vBC (over-voltage), and de-
faulted phase B current, ground potential, and ground current. creased vCA , as shown in Fig. 3 (a). The phase A-to-ground
It could be seen from Fig. 2 (a) that the double line to ground fault triggered large increases in i A , with small changes to

Authorized licensed use limited to: Francisco Guillen. Downloaded on June 04,2022 at 11:31:19 UTC from IEEE Xplore. Restrictions apply.
Fig. 3. The phase A-to-ground fault on the terminals of the 3φ transformer Fig. 4. The phase A-to-ground fault on the terminals of the 3φ transformer
secondary side, when grounded using a FSG: (a) the 3φ line voltages, voltage secondary side, when grounded with a SG: (a) the 3φ line voltages, voltage
scale 300 V/Div. (b) the 3φ currents, current scale is 80 A/Div, (c) phase A scale 300 V/Div. (b) the 3φ currents, current scale is 80 A/Div, (c) phase A
current, ground current, and ground potential, iA scale is 80 A/ Div, iG scale current, ground current, and ground potential, iA scale is 80 A/ Div, iG scale
80 A/Div., and vG scale is 300 V/Div. The time scale is 40 msec./Div. 80 A/Div., and vG scale is 300 V/Div. The time scale is 40 msec./Div.

iB and iC (see Fig. 3 (b)). The tested solid ground fault also was able to eliminate ground potentials, thus no over-voltage in
resulted in a high ground current i G with a medium increase in vBC and vCA . However, the SG was not able to limit or reduce
vG , as shown in Fig. 3 (c). The results of this test demonstrated the ground current i G triggered by the phase A-to-ground fault.
that the FSG was able to reduce i G (relative to the SG), and
limit vG (relative to the IG). However, medium changes could B. 3φ Synchronous Generator Testing
be observed in v BC and vCA . The HIL tests of the 3φ synchronous generator were created
Phase A-to-Ground Fault with SG with the stator grounded using the LRG, LIG, HRG, HIG, FSG,
This HIL test aimed to examine the impacts of a line-to- and IG (as designed in Section II). During these tests, the 3φ
ground fault on the secondary side of the 3φ transformer, which synchronous generator was grid-connected and delivered 60%
was grounded using a SG. This test was conducted as the 3φ of its rated power at a power factor PF = 0.87 lagging. All
transformer supplied a linear (R − L) load. Fig. 4 shows the ground faults on the terminals of the 3φ synchronous generator,
secondary side 3φ line voltages, 3φ currents, phase A current, were created as solid faults (i.e the fault impedance Z̄F = 0).
ground potential, and ground current flowing through the SG. The following test cases are sample cases to show the impacts of
Fig. 4 shows that the solid phase A-to-ground fault on the ground faults, when created with different grounding systems.
secondary side, with a SG, created transient changes in voltages Phase A-to-Ground Fault with HRG
and currents. The tested fault significantly reduced v AB , and The objective of this test was to examine the impacts of a
slightly decreased vBC and vCA (see Fig. 4 (a)). The phase line-to-ground fault on the terminals of the 3φ synchronous
A-to-ground fault triggered large increases in i A , with minor generator, when grounded using a HRG. Fig. 5 shows the stator
changes in iB and iC , as shown in Fig. 4 (b). The solid line- 3φ line voltages, 3φ currents, phase A current, ground potential,
to-ground fault also resulted in a very high ground current i G and ground current flowing through the HRG.
without changes in the ground potential v G , as could be seen The results in Fig. 5 demonstrate that the solid phase A-to-
from Fig. 4 (c). The results of this test demonstrated that the SG ground fault on the terminals of the 3φ synchronous generator,

Authorized licensed use limited to: Francisco Guillen. Downloaded on June 04,2022 at 11:31:19 UTC from IEEE Xplore. Restrictions apply.
Fig. 6. The phase B-to-phase C-to-ground fault on the terminals of the
Fig. 5. The phase A-to-ground fault on the terminals of the synchronous synchronous generator, when grounded with a FSG: (a) the 3φ line voltages,
generator, when grounded with a HRG: (a) the 3φ line voltages, voltage scale voltage scale 300 V/Div. (b) the 3φ currents, current scale is 80 A/Div, (c)
300 V/Div. (b) the 3φ currents, current scale is 80 A/Div, (c) phase A current, phase B current, ground current, and ground potential, iB scale is 80 A/ Div,
ground current, and ground potential, iA scale is 80 A/ Div, iG scale 80 A/Div., iG scale 80 A/Div., and vG scale is 300 V/Div. The time scale is 40 msec./Div.
and vG scale is 300 V/Div. The time scale is 40 msec./Div.
severe reductions in v BC and vCA , and an over-voltage in v AB ,
created transients in stator voltages and currents. The tested as shown in Fig. 6 (a). The tested ground fault triggered large
fault significantly reduced v AB , slightly decreased v BC , and increases in iB and iC , and a minor increase in i A (see Fig. 6
significantly increased v CA (see Fig. 5 (a)). The phase A-to- (b)). The solid double line-to-ground fault also resulted in high
ground fault triggered a large increase in i A , a big reduction ground current i G and a small increase in the ground potential
of iB , and an increase in i C , as shown in Fig. 5 (b). The solid vG , as could be seen from Fig. 6 (c). The results of this test
line-to-ground fault also resulted in a very small ground current demonstrated that the FSG was able to limit the ground current
iG with a large increase in the ground potential v G , as could be (lower than that with a SG). However, the FSG was not able to
seen from Fig. 5 (c). The results of this test demonstrated that completely eliminate the ground potential, which caused v AB
the HRG was able to significantly reduce the ground current to reach more than 120% of its pre-fault value.
that was triggered by the fault. However, the large increase in Phase B -to-Phase C -to-Ground Fault with LXG
vG resulted in an over-voltage experienced by v CA . The objective of this test was to examine the impacts of a double
Phase B -to-Phase C -to-Ground Fault with FSG line-to-ground fault on the terminals of the 3φ synchronous
This HIL test aimed to assess the impacts of a double line-to- generator, when grounded using a LXG. Fig. 7 shows the stator
ground fault on the terminals of the 3φ synchronous generator, 3φ line voltages, 3φ currents, phase A current, ground potential,
when grounded using a FSG. The stator 3φ line voltages, 3φ and ground current (flowing through the LXG).
currents, phase A current, ground potential, and ground current Fig. 7 shows that the solid double line-to-ground fault on
flowing through the FSG, are shown in Fig. 6. the terminals of the 3φ synchronous generator (with the LXG),
The results in Fig. 6 show that the solid double line-to- caused transient changes in stator voltages and currents. The
ground fault on the terminals of the 3φ synchronous generator phase B-to-phase C-to-ground fault resulted in severe reduc-
(with the FSG) caused in abrupt variations in stator voltages tions in vBC and vCA , and an over-voltage in v AB (see Fig. 7
and currents. The phase B-to-phase C-to-ground fault caused a (a)). This solid ground fault caused large increases in i B and

Authorized licensed use limited to: Francisco Guillen. Downloaded on June 04,2022 at 11:31:19 UTC from IEEE Xplore. Restrictions apply.
TABLE III
S UMMARY OF G ROUNDING S YSTEM I MPACTS ON G ROUND C URRENTS ,
G ROUND V OLTAGES , AND OVER -V OLTAGES , D URING S OLID G ROUND
FAULTS
Grounding System
iG [p.u] vG [p.u] Over-Voltage [%]
Design
Line-to-Ground Fault
SG 2.4 0.0 0.0
LRG 1.7 0.3 25.0
LXG 1.6 0.2 22.0
FSG 1.6 0.2 17.0
HRG 0.3 0.8 135.0
HXG 0.2 0.7 125.0
IG 0.0 1.1 167.0
Double Line-to-Ground Fault
SG 2.6 0.0 0.0
LRG 1.9 0.4 35.0
LXG 1.8 0.3 30.0
FSG 1.7 0.2 22.0
HRG 0.3 0.9 145.0
HXG 0.3 0.8 138.0
IG 0.0 1.1 167.0

The data in Table III shows a variety of impacts on the


ground current i G , ground potential v G , and over-voltage by
different grounding systems during ground faults. These impacts
 
are directly related to the equivalent grounding impedance Z̄G ,
which has direct influences on i G and vG . On one hand,
grounding systems with high Z̄G  are able to significantly
reduce iG , thus minimizing possible damages due to ground
faults. Nonetheless, such grounding systems can not reduce
vG , and may fail to prevent over-voltages.
 On the other hand,
grounding systems with low Z̄G  can not effectively reduce i G ,
and may not prevent damages due  to ground faults. However,
grounding systems with low Z̄G  can reduce vG , and prevent
over-voltages.
Fig. 7. The phase B-to-phase C-to-ground fault on the terminals of the
synchronous generator, when grounded with a LXG: (a) the 3φ line voltages, IV. C ONCLUSIONS
voltage scale 300 V/Div. (b) the 3φ currents, current scale is 80 A/Div, (c)
phase C current, ground current, and ground potential, iC scale is 80 A/ Div, This paper has presented performance results for various
iG scale 80 A/Div., and vG scale is 300 V/Div. The time scale is 40 msec./Div. grounding system designs during ground faults. Performance
testing has been focused on the abilities of grounding systems to
iC , and a slight increase in i A as shown in Fig. 7 (b). The phase influence ground currents and potentials. Such influences are of
B-to-phase C-to-ground fault also caused a significant increase remarkable interests to support and facilitate the stable, reliable,
in the ground potential v G , while limiting the ground current and functional operation of any power system. The influence of
iG as could be seen in Fig. 7 (c). The LXG grounding was any grounding system on ground currents and potentials are
able to significantly reduce the ground current, however, it was  
 grounding impedance Z̄G .
directly related to its equivalent
not able to limit the ground potential to prevent over-voltage in  
Grounding systems with low Z̄G (SG, LRG, LXG, and FSG)
VAB . The ground potential v G resulted in vAB to have 130% can effectively minimize ground potentials and reduce possible
of its pre-fault value. over-voltages. However, SG, LRG, LXG, and FSG can not limit
The HIL test results obtained from ground faults in a 3φ ground currents, and may not prevent equipment damage or pos-
transformer and a 3φ synchronous generator, have demonstrated sible arcing current faults. Grounding systems with high Z̄G 
different impacts of grounding systems. These impacts have (IG, HRG, and HXG) can effectively minimize ground currents
been quantified by the ground currents, ground voltages, and and reduce possible equipment damage. Nevertheless, IG, HRG,
over-voltages triggered by solid ground faults for each ground- and HXG can not reduce ground potentials, and may not be
ing system. These results have provided several observations, able to eliminate over-voltages. These abilities of grounding
which are summarized as in Table III. The data in Table III systems have made their use recommended for different systems
was calculated as the following: and equipment. For example in medium voltage (MV) systems,
• The values of i G , vG , and over-voltage were calculated HRG is widely used. The LRG and LXG are used in generator
as the average value of those measured from the 3φ grounding, while the FSG is widely used for grounding grid-
transformer and 3φ synchronous generator. connected power electronic converters. Performance assessment
• The base value for i G , vG and over-voltage was taken as of various grounding system designs has shown the different
the rated current and line voltage of the 3φ transformer impacts on ground potentials and currents, which further help
and 3φ synchronous generator. employing grounding systems in industrial applications.

Authorized licensed use limited to: Francisco Guillen. Downloaded on June 04,2022 at 11:31:19 UTC from IEEE Xplore. Restrictions apply.
R EFERENCES Industrial and Commercial Power Systems Technical Conference (I&CPS),
Niagara Falls, ON, pp. 1–9, 2018.
[1] IEEE Recommended Practice for System Grounding of Industrial and [23] Power System Toolbox User Guide. Natick, MA: MathWorks, 2017.
Commercial Power Systems, IEEE Std. 3003.1-2019. [24] Digital Signal Processing and Control Engineering, dSPACE Gmbh, Pader-
[2] IEEE Recommended Practice for Protection and Coordination of Industrial born, Germany, 2019.
and Commercial Power Systems (IEEE Buff Book), IEEE Std. 242-2001.
[3] IEEE Guide for the Application of Neutral Grounding in Electrical Utility
Systems, Part V-Transmission Systems and Subtransmission Systems, IEEE
Std. C62.92.5-2009.
[4] IEEE Standard for Interconnection and Interoperability of Distributed
Energy Resources with Associated Electric Power Systems Interfaces, IEEE
Std. 1547-2018.
[5] S. A. Saleh, D. Jewett, and S. Panetta, “Features and Capabilities of
Grounding System Designs,” In Proc. of the 58th IEEE IAS Industrial and
Commercial Power Systems Technical Conference (I&CPS), Las Vegas, NV,
pp. 1-10, May 2022.
[6] M. Fulczyk and J. Bertsch, “Ground-Fault Currents in Unit-Connected
Generators with Different Elements Grounding Neutral,” IEEE Trans. on
Energy Conversion, Vol. 17, No. 1, pp. 61–66, 2002.
[7] S. A. Panetta, “Hybrid Grounding of Electrical Systems,” IEEE Trans. on
Industry Applications, Vol. 53, No. 6, pp. 6033–6037, 2017.
[8] J. Rorabaugh, A. Swisher, J. Palma, G. Andaya, M. Webster, B. Kirkpatrick,
B. Garcia, M. Harrington, M. Hughes, A. Fresquez, A. Ojeda, J. Park, and
T. Tran, “Resonant Grounded Isolation Transformers to Prevent Ignitions
From Powerline Faults,” IEEE Trans. on Power Delivery, Vol. 36, No. 4,
pp. 2287–2297, 2021.
[9] J. P. Nelson, J. D. Billman, J. E. Bowen, and D. A. Martindale, “The Effects
of System Grounding, Bus Insulation, and Probability On Arc Flash Hazard
Reduction—Part 2: Testing,” IEEE Trans. on Industry Applications, Vol. 51,
No. 3, pp. 2665–2675, 2015.
[10] S. A. Saleh, “On the Design and Capacity of a Grounding Configuration
for Grid-Connected DGUs,” IEEE Trans. on Industry Applications, Vol. 51,
No. 6, pp. 5366–5375, 2015.
[11] J. M. Guerrero , G. Navarro, K. Mahtani, and C. A. Platero, “Ground Fault
Detection Method for Variable Speed Drives,” IEEE Trans. on Industry
Applications, Vol. 57, No. 3, pp. 2547–2558, 2021.
[12] S. A. Saleh, X. F. St-Onge, C. Richard, E. Ozkop, and S. A. R. Panetta,
“The Design and Testing of a Frequency-Selective Grounding for 3φ Power
Transformers,” IEEE Trans. on Industry Applications, Vol. 56, No. 1,
pp. 74–87, 2020.
[13] M. Yousaf, A. Jalilian, K. M. Muttaqi, and D. Sutanto, “An Adaptive
Grounding Scheme for Synchronous-Based DG to Prevent the Generator
Damage and Protection Malfunctioning During Ground Faults Under Dif-
ferent Operating Modes,” IEEE Trans. on Industry Applications, Vol. 57,
No. 3, pp. 2307–2316, 2021.
[14] A. Kotsonias, M. Asprou, L. Hadjidemetriou, and E. Kyriakides, “State
Estimation for Distribution Grids With a Single-Point Grounded Neutral
Conductor,” IEEE Trans. on Instrumentation and Measurement, Vol. 69,
No. 10, pp. 8167–8177, 2020.
[15] E. R. Collins and J. Jiang, “Analysis of Elevated Neutral-to-Earth Voltage
in Distribution Systems With Harmonic Distortion,” IEEE Trans. on Power
Delivery, Vol. 24, No. 3, pp. 1696–1702, 2009.
[16] G. Parise, L. Parise, L. Martirano, F. Tummolillo, G. Vagnati, and A. Bar-
resi, “Tests and Monitoring of Grounding Systems in HV/MV Substations,”
IEEE Trans. on Industry Applications, Vol. 53, No. 2, pp. 929–935, 2017.
[17] G. Parise, L. Parise, and L. Martirano, “Intrinsically Safe Grounding
Systems and Global Grounding Systems,” IEEE Trans. on Industry Ap-
plications, Vol. 54, No. 1, pp. 25–31, 2018.
[18] M. E. M. Rizk, M. Lehtonen, Y. Baba, and S. Abulanwar, “Performance
of Large-Scale Grounding Systems in Thermal Power Plants Against
Lightning Strikes to Nearby Transmission Towers,” IEEE Trans. on Elec-
tromagnetic Compatibility, Vol. 61, No. 2, pp. 400–408, 2019.
[19] G. Cafaro, P. Montegiglio, F. Torelli, A. Barresi, P. Colella, A. De Simone,
M. . Di Silvestre, L. Martirano, E. R. Morozova, R. Napoli, G. Parise,
L. Parise, E. Pons, E. R. Sanseverino, R. Tommasini, F. Tummolillo, G.
Valtorta, and G. Zizzo, “Influence of LV Neutral Grounding on Global
Earthing Systems,” IEEE Trans. on Industry Applications, Vol. 53, No. 1,
pp. 22–31, 2017.
[20] A. Nikander, “Development and Testing of New Equipment for Faulty
Phase Earthing by Applying RTDS,” IEEE Trans. on Power Delivery,
Vol. 32, No. 3, pp. 1295–1302, 2017.
[21] M. Popov, L. Grcev, H. Kr. Hoidalen, B. Gustavsen, and V. Terzija, “Inves-
tigation of the Overvoltage and Fast Transient Phenomena on Transformer
Terminals by Taking Into Account the Grounding Effects,” IEEE Trans. on
Industry Applications, Vol. 51, No. 6, pp. 5218–5227, 2015.
[22] S. A. Saleh, X. F. St. Onge, C. Richard, E. Ozkop, K. McDonald, and
S. Panetta, “Impacts of Grounding and Winding Configurations on Voltage
Harmonics in 3φ Power Transformers,” In Proc. of the 54rd IEEE IAS

Authorized licensed use limited to: Francisco Guillen. Downloaded on June 04,2022 at 11:31:19 UTC from IEEE Xplore. Restrictions apply.

You might also like