Professional Documents
Culture Documents
Acceptance Criteria For Special Unbonded Post-Tensioned Precast Structural Walls Based On Validation Testing and Commentary
Acceptance Criteria For Special Unbonded Post-Tensioned Precast Structural Walls Based On Validation Testing and Commentary
Acceptance Criteria For Special Unbonded Post-Tensioned Precast Structural Walls Based On Validation Testing and Commentary
1-07
An ACI Standard
Copyright by the American Concrete Institute, Farmington Hills, MI. All rights reserved. This material
may not be reproduced or copied, in whole or part, in any printed, mechanical, electronic, film, or other
distribution and storage media, without the written consent of ACI.
The technical committees responsible for ACI committee reports and standards strive to avoid ambiguities,
omissions, and errors in these documents. In spite of these efforts, the users of ACI documents occasionally
find information or requirements that may be subject to more than one interpretation or may be
incomplete or incorrect. Users who have suggestions for the improvement of ACI documents are
requested to contact ACI. Proper use of this document includes periodically checking for errata at
www.concrete.org/committees/errata.asp for the most up-to-date revisions.
ACI committee documents are intended for the use of individuals who are competent to evaluate the
significance and limitations of its content and recommendations and who will accept responsibility for the
application of the material it contains. Individuals who use this publication in any way assume all risk and
accept total responsibility for the application and use of this information.
All information in this publication is provided “as is” without warranty of any kind, either express or implied,
including but not limited to, the implied warranties of merchantability, fitness for a particular purpose or
non-infringement.
ACI and its members disclaim liability for damages of any kind, including any special, indirect, incidental,
or consequential damages, including without limitation, lost revenues or lost profits, which may result
from the use of this publication.
It is the responsibility of the user of this document to establish health and safety practices appropriate to
the specific circumstances involved with its use. ACI does not make any representations with regard to
health and safety issues and the use of this document. The user must determine the applicability of all
regulatory limitations before applying the document and must comply with all applicable laws and regulations,
including but not limited to, United States Occupational Safety and Health Administration (OSHA) health
and safety standards.
Order information: ACI documents are available in print, by download, on CD-ROM, through electronic
subscription, or reprint and may be obtained by contacting ACI.
Most ACI standards and committee reports are gathered together in the annually revised ACI Manual of
Concrete Practice (MCP).
Charles W. Dolan
Chair
Consulting member
S. K. Ghosh
This document applies to structures in regions of high seismic risk or to In this document, consistent with the format of ACI 318-05, the word
structures assigned to high seismic performance or design categories. It “Section” is not included before a reference to a section of ACI 318-05. To
defines the minimum experimental evidence that can be deemed to satisfy more clearly designate a section in this document, however, the word
the use of unbonded post-tensioned precast structural walls (shear walls) “Section” is used before any reference to a section of this document.
for bearing wall and building frame special reinforced concrete shear wall The section numbering for the Commentary is the same as that for the
systems, as defined in ASCE/SEI 7-05, when those walls do not fully satisfy Standard, with numbers preceded by an “R” and the text in italics to distin-
the intent of the prescriptive requirements of Chapter 21 of ACI 318-05. guish them from the corresponding section numbers of the Standard.
This document includes mandatory Acceptance Criteria and nonmandatory
Commentary, and has been written in such a form that its requirements can Keywords: acceptance criteria; coupling element; drift; drift angle;
be coordinated directly with the requirements for special precast structural energy dissipation; lateral resistance; post-tensioning; precast concrete;
walls in 21.8 of ACI 318-05. Among the subjects covered are requirements prestressed concrete; seismic design; shear wall; structural wall; test
for the procedures that shall be used to design unbonded post-tensioned module; toughness.
precast test modules and their configurations, as well as requirements for
testing, reporting, and assessing satisfactory performance of the test modules.
The references of the Commentary provide documentary evidence,
CONTENTS
additional to the references of Chapter 21 of ACI 318R-05, that support the
Chapter 1—Introduction and scope, p. ITG-5.1-2
acceptance criteria. Consistent with the approach of ACI 318, no comparison
is made, either in the body of the Acceptance Criteria or Commentary, of Chapter 2—Notation and definitions, p. ITG-5.1-5
research results for precast test modules satisfying ACI 318 with those for
modules that, although not satisfying ACI 318, do satisfy the Acceptance Chapter 3—Design procedure, p. ITG-5.1-8
Criteria. Such comparisons, both experimental and analytical, are available in
the Commentary references. Chapter 4—Test modules, p. ITG-5.1-9
ITG-5.1-1
ITG-5.1-2 ACI STANDARD
CHAPTER 1—INTRODUCTION AND SCOPE wall systems, not satisfying all the prescriptive requirements
of Chapter 21 of ACI 318.
1.1—Introduction This document assumes that the unbonded post-tensioned
For seismic design, 21.2.1.5 of ACI 318 specifies that “a precast wall system to be tested has details that differ from
reinforced concrete structural system not satisfying the those prescribed by 21.7 of ACI 318 for conventional
requirements of this chapter (Chapter 21) shall be permitted monolithic reinforced concrete construction. Such walls
if it is demonstrated by experimental evidence and analysis may, for example, involve the use of precast elements,
that the proposed system has strength and toughness equal to precast prestressed elements, post-tensioned reinforcement,
or exceeding those provided by a comparable monolithic or combinations of those elements and reinforcement. Life
reinforced concrete structure satisfying this chapter.” This safety and toughness are theoretically enhanced by mild
document defines the minimum experimental evidence steel reinforcement grouted across the wall to foundation
required to validate the use of special unbonded post- interface. The presence of mild steel reinforcement,
tensioned precast structural wall systems in regions of high however, makes erection more difficult, and may inhibit the
seismic risk or for structures assigned to high seismic self-centering action provided by unbonded post-tensioning
performance or design categories when those systems do not crossing the same interface. For an uncoupled wall, mild
satisfy fully the prescriptive requirements of Chapter 21 of steel reinforcement, or some other form of energy-dissipating
ACI 318. The provisions of this document are intended to base connection, is necessary to meet the relative energy
supplement the provisions of Chapter 21 of ACI 318 and not dissipation requirements of this document. For coupled
to supplant them. walls, however, energy-dissipating coupling elements can be
Consistent with the 21.2.1.5 requirement of ACI 318, this used along the vertical boundaries between walls so that
document specifies that, before the validation testing only unbonded post-tensioning tendons need to cross the
mandated by the document is undertaken, a design procedure wall to foundation interface. Life safety for coupled walls is
shall have been developed for prototype unbonded post- then more critically dependent on the unbonded post-
tensioned precast structural walls having the generic form tensioning not fracturing under the seismic event. In that
for which acceptance is sought. Further, the same design case, careful attention should be paid to corrosion protection of
procedure shall be used to proportion the test modules. The the tendon and to stress increases in the tendon during the
document also requires that the prototype buildings that seismic event.
contain the unbonded post-tensioned precast structural walls For monolithic reinforced concrete walls, a fundamental
have proportions that are essentially regular in the vertical design concept underlying the Chapter 21 provisions of ACI
direction, having no significant physical discontinuities in 318 is that walls with hw /lw exceeding 1.0 should be
plan, in vertical configuration, or in their lateral-force-resisting proportioned so that their inelastic response is dominated by
systems. flexural action on a critical section located near the base of
This document is intended for walls that might, for the wall. That same basic fundamental concept is retained in
example, involve the use of precast elements, precast/ this document. The limiting hw /lw value, however, is reduced
prestressed elements, post-tensioned reinforcement or combi- to 0.5. The basis for that lower limit is discussed in R1.2.2.
nations of those elements and reinforcement. Comprehensive Tests on modules, as envisioned in this document, cannot
prescriptive requirements for unbonded post-tensioned be extrapolated with confidence to the performance of
precast structural walls constructed with such elements are panelized walls of proportions differing from those tested for
not included in ACI 318. the development of Chapter 21 of ACI 318 if the shear-slip
displacement pattern or excessive joint opening pattern of
1.2—Scope and general requirements Fig. R2.3 is significant in the response developed in the test
on the module.
R1.2—Scope and general requirements Two other fundamental requirements of Chapter 21 of ACI
While only ACI Committee 318 can specify the requirements 318 are for closely spaced ties around heavily strained
necessary for unbonded post-tensioned precast walls to meet boundary element reinforcement and the provision of
the provisions of 21.2.1.5 of ACI 318, 1.4 of ACI 318 permits minimum amounts of uniformly distributed horizontal and
the building official to accept precast wall systems, other vertical reinforcement in the web of the wall. Ties around
than those explicitly covered by Chapter 21 of ACI 318, boundary element reinforcement to inhibit its buckling in
provided specific tests, load factors, deflection limits, compression are required where the strain in the extreme
construction procedures, and other pertinent requirements compression fiber exceeds 0.003 and spalling of the cover
have been established for acceptance of such systems concrete may occur. Those ties then provide confinement
consistent with the intent of the Code. This document that maintains the integrity of the boundary element and
provides a framework that establishes the specific tests, load permits the confined concrete to develop increasing
factors, deflection limits, and other pertinent requirements compressive forces with increasing lateral displacements in
appropriate for acceptance for regions of high seismic risk spite of the loss of the concrete cover. Minimum amounts of
or for structures assigned to high seismic performance or uniformly distributed horizontal and vertical reinforcement
design categories of unbonded post-tensioned precast wall over the height and length of the wall are required to restrain
systems, including unbonded post-tensioned precast coupled the opening of inclined cracks and allow the development of
SPECIAL UNBONDED POST-TENSIONED PRECAST STRUCTURAL WALLS ITG-5.1-3
the minimum acceptable drift angle capacities specified in unreliable. Rather, the behavior of such walls can be very
Section 5.4. Deviations from those tie and distributed reliable if shear stresses are low and the wall is not required
reinforcement requirements are possible only if a theory is to deform to displacements greater than the displacement
developed that can substantiate reasons for such deviations associated with the peak load capacity of the wall.
and that theory is tested as part of the validation testing. The wall heights to which this document can be applied
are not limited because a practical limit will be effectively
1.2.1 This document defines minimum acceptance criteria imposed by the combination of testing facility restrictions on
for unbonded post-tensioned precast structural walls, height and the minimum specimen scale limits imposed in
including coupled unbonded post-tensioned precast structural this document. Further, for heights greater than about 100 ft
walls, designed for regions of high seismic risk or for structures and the customary hw /lw ratios for precast panels, the
assigned to high seismic performance or design categories, design displacements result in stress level changes in the
where acceptance is based on experimental evidence and prestressing steel that are difficult to accommodate while
analysis. still maintaining the desirable self-centering characteristic
R1.2.1 This document is not intended for use directly with of an unbonded post-tensioned wall. For coupled walls, the
existing construction or for use with walls that are designed situation becomes even more severe because the
to conform to all the requirements of 21.7 of ACI 318. The prestressing steel stress changes are even greater for the
criteria of this document are at least as stringent as those for trailing wall than would be the case for an uncoupled wall of
walls designed to the minimum requirements of 21.7 of ACI the same height (Thomas and Sritharan 2004).
318. Some walls designed to 21.7, and having low height- Consistent with the concepts of 21.7.6.2 of ACI 318,
length ratios, may not meet the minimum acceptable drift procedures are based on the assumption that inelastic
angle capacity of Eq. (5-1) because their behavior may be response of the wall is dominated by flexure at a single critical
governed almost entirely by shear deformations (Hidalgo et jointed section that is a potential yielding section. The wall
al. 2002). The height-length ratio of 0.5 is the least value for should be proportioned so that the critical section occurs
which Eq. (5-1) is applicable. where intended. For walls with openings, the influence of an
opening or openings on flexural and shear strengths should
1.2.2 This document is applicable to unbonded post- be considered, and a load path around the opening or openings
tensioned precast structural walls, coupled or uncoupled, should be verified. The presence of the opening or openings
with height-to-length ratios, hw /lw , equal to or greater than should be verified to not affect the location of the critical
0.5. This document is applicable to either prequalifying jointed section that is the potential yielding section.
unbonded post-tensioned precast structural walls for a
specific structure or prequalifying an unbonded post- 1.2.3 The walls of the prototype structure shall be
tensioned precast wall type for construction in general. This permitted to be several panels long and several panels high,
document applies to walls that are effectively continuous to be constructed from subpanels, and to be either coupled or
from the base of the structure to top of wall and are designed uncoupled. Coupling elements shall be permitted to be
to have a single critical section for flexure and axial loads. devices or beams connecting adjacent vertical boundaries of
R1.2.2 The use of this document is limited to walls with the unbonded post-tensioned precast walls.
hw /lw values of 0.5 or greater primarily for two reasons. R1.2.3 For uncoupled walls, relative energy dissipation
First, for rectangular walls, elastic cracked section flexural ratios increase as the drift angle increases (Kurama 2002).
deformations start to exceed elastic cracked section shear Tests on slender monolithic walls have shown relative
deformations once the hw /lw value exceeds 0.5. Second, energy dissipation ratios, derived from rotations at the base
experimental evidence shows that postpeak load drift values of the wall, of approximately 40 to 45% at large drifts (Ali
for walls with hw / lw values less than 0.5 are unreliable and Wight 1990). The same result has been reported even
unless the walls contain considerably more horizontal and where there has been a significant opening in the web of the
vertical reinforcement than the 0.25% minimum required by wall on the compression side (Taylor et al. 1998). Kurama
21.7.2.1 in ACI 318 (Hidalgo et al. 2002). Further, for (2002) computed relative energy dissipation ratios at a
precast walls with grouted joints between panels, the likelihood 0.020 radians drift angle for uncoupled walls with height-
of sliding increases as the hw /lw value decreases and the length ratios of 4. Ratios were 30, 18, 12, and 6% for mono-
presence of post-tensioning becomes increasingly essential lithic reinforced concrete, hybrid reinforced/post-tensioned
in ensuring nonsliding behavior. For walls with hw /lw prestressed concrete with equal flexural strengths provided
values of 0.5 or greater, postpeak load drifts are about 0.5% by the prestressed and deformed bar reinforcement, hybrid
regardless of the hw /lw value of the wall (Hidalgo et al. reinforced/post-tensioned prestressed concrete with 25% of
2002). From Eq. (5-1), it follows that for walls with hw /lw the flexural strength provided by deformed bar reinforcement
values of 0.5, only about 0.4% drift angle is contributed by and 75% by the prestressed reinforcement, and post-
the prepeak load response. If the postpeak load drift is tensioned prestressed concrete special structural walls,
unreliable, the drift capacity becomes unreliable for hw /lw respectively. Thus, for slender precast uncoupled walls of
values less than 0.5. Limiting the use of this document to emulative or nonemulative design, it should be anticipated
walls with hw /lw values of 0.5 and greater does not imply that at least 27% of the flexural capacity at the base of the
that the behavior of walls with hw /lw values less than 0.5 is wall should be provided by deformed bar reinforcement if
ITG-5.1-4 ACI STANDARD
the requirement of a relative energy dissipation ratio of 1/8 based concepts consistent with the concepts of 21.7.6.2 for
is to be achieved. If more than approximately 40% of the monolithic walls.
flexural capacity at the base of the wall is provided by
deformed bar reinforcement (Kurama 2002), however, then 1.2.4.2 Tests on wall modules satisfy the conditions in
the self-centering capability of the wall following a major Chapters 3 and 7.
event is lost, and that is one of the benefits gained with the
use of post-tensioning. For squat walls with height-length 1.2.4.3 The prototype structure is designed using the
ratios between 0.35 and 0.69, the relative energy dissipation design procedure substantiated by the testing program.
has been reported (Hildalgo et al. 2002) as remaining constant
at 23% for drifts between that for first diagonal cracking and
1.2.4.4 The prototype structure is:
that for a postpeak capacity of 80% of the peak capacity. Thus,
regardless of whether the behavior of a wall is controlled by (1) Analyzed using stiffness properties consistent with
shear or flexural deformations, a minimum relative energy those validated as prescribed in Section 5.10;
dissipation ratio of 1/8 is a realistic requirement. (2) Demonstrated through analysis to have design
For an unbonded post-tensioned wall, it is difficult to displacements for all walls equal to or less than two thirds of
separate the strength provided by the post-tensioning from the displacement associated with the drift angles to which
the strength provided by the deformed bar reinforcement and the appropriate modules have been tested in accordance with
the strength provided by axial load because both the post- Section 5.4; and
tensioning and axial load move the neutral axis toward the (3) Shown to have factored engineering design values for
center of the wall and increase the moment strength. If self- all walls less than the nominal engineering design values
centering is a goal, it is recommended that the engineer used for the test modules in accordance with Section 4.2.
developing the system calculate independently the deformed R1.2.4.4 Both IBC 2003 and NFPA 5000 contain allowable
bar reinforcement requirements because the values of the story drift limits. In IBC 2003, allowable story drifts Δa are
previous paragraph provide guidance only. specified in Table 1617.3, and likely values are discussed in
For coupled wall systems, theoretical studies (Stanton and the Commentary of Section 5.4 of this document. The limiting
Nakaki 2002) and tests (Priestley et al. 1999) have initial drift angle consistent with Δa equals Δa /φCdhw ,
demonstrated that the 1/8 relative energy dissipation ratio where φ is the strength reduction factor appropriate to the
can be achieved by using central post-tensioning only in the condition, flexure or shear, that controls the design of the
walls and appropriate energy-dissipating coupling devices test module. For example, for Δa/hw equal to 0.015, the
connecting adjacent vertical wall boundaries. required deflection amplification factor Cd of 5, and φ equal
to 0.9, the limiting initial drift angle, corresponding to B in
1.2.4 Unbonded post-tensioned precast structural walls Fig. R7.1, is 0.0033. The use of a φ value is necessary
shall be deemed to have a strength and toughness that is because the allowable story drifts of the IBC are for the
adequate to comply with 21.2.1.5 of ACI 318, and the design seismic load effect E, while the limiting initial drift
corresponding unbonded post-tensioned precast structural angle is at the nominal strength En , which should be greater
walls of the prototype structure shall be deemed acceptable than E/φ. The load-deformation relationship of a wall
when all of the conditions in Sections 1.2.4.1 through 1.2.4.5 becomes significantly nonlinear before the applied load
are satisfied. reaches Ent. While the load at which that nonlinearity
becomes marked depends on the structural characteristics of
1.2.4.1 The prototype structure satisfies all applicable the wall, the response of most walls remains linear up to
requirements of this document and of ACI 318 except 21.7. approximately 75% of Ent (Kurama et al. 1999).
R1.2.4.1 The precast walls should meet the strength,
minimum reinforcement, and detailing requirements of 1.2.4.5 The structure as a whole, based on the results of
Chapters 11 and 14 of ACI 318 as well as the structural the tests of Section 1.2.4.2 and analysis, is demonstrated to
integrity requirements of Chapter 16. The structural have the required global toughness.
integrity provisions of Chapter 16 require a minimum of R1.2.4.5 The criteria of Chapter 7 are for the test
two ties per panel with a nominal strength of not less than module. In contrast, the criterion of Section 1.2.4.5 is for the
10,000 lb per tie. Thus, at least two tendons per wall, or structural system as a whole, and can be satisfied only by the
one tendon and one grouted in-place deformed steel tie details used for the design and analysis of the building as a
bar, are required. whole. The criterion adopted herein is similar to that
By not requiring the walls to meet 21.7 of ACI 318, the described in the last paragraph of R21.2.1 of ACI 318. The
specific triggers of 21.7.6 of ACI 318 concerning the need intent is that test results and analyses demonstrate that the
for boundary elements in special structural walls are structure, after cycling three times through both positive and
rescinded. This does not mean, however, that boundary negative values of the minimum acceptable limiting drift
elements or confinement reinforcement in wall boundaries angle capacity specified in Section 5.4 of this document, is
will not be required. The need for such elements and reinforce- still capable of supporting the gravity load specified as
ment for jointed walls should be explored using displacement- acting on the structure during the earthquake.
SPECIAL UNBONDED POST-TENSIONED PRECAST STRUCTURAL WALLS ITG-5.1-5
CHAPTER 2—NOTATION AND DEFINITIONS Ks ,Ks′ = initial stiffness values for increasing and
decreasing drift angle, respectively, as
2.1—Notation defined in Section 5.10
Only symbols additional to those in ACI 318 are defined. R = response modification coefficient. See ASCE/
The terms in this list are used in the Acceptance Criteria and SEI 7-05, Section 12, Seismic Design
in the Commentary. Requirements
Emax = maximum measured lateral resistance of test βh = relative energy dissipation ratio
module determined from test results, lb. See Δ = lateral displacement, in. See Fig. R2.1, R2.2,
Section 7.1.1 and R2.3
En = nominal lateral resistance of test module calcu- Δa = allowable story drift, in. See Table 12.2-1 of
lated using the defined design procedure and ASCE/SEI 7-05
specified geometric properties of test members, θL = drift angle, radians
specified yield strength of reinforcement, speci- θL1,θL2 = measured drift angles at peak lateral resis-
fied compressive strength of concrete, a strain tance for increasing and decreasing drift
compatibility analysis or deformation compati- angle, respectively, for third cycle of loading
bility analysis, and a strength reduction factor φ sequence, radians
of 1.0, lb ′ ,θL2
θL1 ′ = measured drift angles for zero lateral load
for unloading at stiffness value of Ks, Ks′
Ent = nominal lateral resistance of test module
from peak positive and negative lateral resis-
calculated using the defined design procedure and
tance, respectively, for third cycle of loading
measured geometric properties of test members,
sequence, radians. See Fig. R2.4
the measured yield strengths of reinforcement,
compressive strengths of concrete, and strengths
2.2—Definitions
of coupling elements, obtained by testing per The following definitions, in addition to those in 21.1 of
Sections 5.6, 5.7, and 5.8, and a strength reduction ACI 318, shall apply:
factor φ of 1.0, lb coupling elements—devices or beams connecting adjacent
Epr = probable lateral resistance of test module at peak vertical boundaries of precast structural walls and used to
load, calculated using the defined design proce- provide stiffness and energy dissipation for the connected
dure and the measured geometric properties of assembly greater than the sum of those provided by the
the test members, measured stress-strain properties connected walls acting as separate units.
of reinforcement and concrete, a strain compati- drift—the lateral displacement at the top of the module or
bility analysis or deformation compatibility the prototype structure.
analysis, and a strength reduction factor φ of 1.0, lb drift angle—the lateral displacement at the top of the test
In ACI 318, hw is defined as “height of entire wall from module or prototype structure divided by the height of the
base to top or height of segment of wall considered.” In this module or structure.
document, hw is defined as height of test module from the top factored engineering design value—factored value of an
of the foundation to the point of application of the load. Also, engineering design characteristic such as shear stress, axial
in ACI 318, lw is defined as “length of entire wall or length stress, moment-to-shear ratio, for a given wall in the prototype
of segment of wall considered in direction of shear force.” In structure.
this document, for coupled walls, lw is the length of one of the nominal engineering design value—maximum
wall segments that is coupled in the direction of shear force. permitted value of an engineering design characteristic
defining a limit state mechanism such as shear, flexure, axial
R2.1—Notation load, or any combination thereof, assumed in the design
The terms in this list are used in the Commentary, but not procedure to control the behavior of the prototype structure
in the Acceptance Criteria. and the test module.
Ad = area of hysteresis loop prototype structure—the unbonded post-tensioned
precast concrete wall structure for which acceptance is
Cd = deflection amplification factor. See ASCE/
sought.
SEI 7-05, Section 12, Seismic Design
relative energy dissipation ratio—ratio of measured
Requirements
energy dissipated by the test module during reversing cyclic
E1,E2 = peak positive and negative lateral resistances displacements between given measured drift angles to the
for increasing and decreasing drift angle, maximum theoretical energy that can be dissipated for the
respectively, for third cycle of loading same drift angles. The quantity is expressed as the ratio of
sequence, lb the area of the hysteresis loop for that cycle to the area of the
EQ = horizontal force applied to test module and circumscribing parallelograms defined by the initial stiffness
representing earthquake load values during the first cycle to Ent and the peak resistances
f1 = live load factor defined in required global during the cycle for which the relative energy dissipation
toughness in Section R2.2 ratio is calculated. See Section 7.1.4.
ITG-5.1-6 ACI STANDARD
behavior being represented. Figure R2.2 illustrates several relative energy dissipation ratio—this concept is illus-
possible components of the displacement Δ for a wall that is trated in Fig. R2.4 for the third loading cycle to the drift
effectively solid, whereas Fig. R2.3 illustrates two undesirable angle required by Eq. (5-1) of Section 5.4. For Fig. R2.4, it
components of the displacement Δ. Regardless of the mode is assumed that the test module has exhibited different initial
of deformation of the wall, the lateral force causes the wall stiffness values, Ks and Ks′ , for positive and negative lateral
at B to displace horizontally by an amount Δ. The drift angle forces, and that the peak lateral resistances for the third
is the angular rotation of the wall chord with respect to the cycle for the positive and negative loading directions, E1 and
vertical and for the setup shown equals Δ/hw , where hw is E2, also differ. The area of the hysteresis loop for the third
the wall height and is equal to the distance between the cycle Ad is hatched. The circumscribing figure consists of
foundation support at A and the load point at B. two parallelograms, ABCD and DFGA. The slopes of the
The moment-shear ratio that exists at the base of the wall lines AB and DC are the same as the initial stiffness Ks for
in the test module should be representative of that acting on positive displacements, and the slopes of the lines DF and
the base of the wall in the actual structure. That moment- GA are the same as the initial stiffness Ks′ for negative
shear ratio is an engineering design criterion. There is no displacements. The relative energy dissipation ratio concept
requirement, however, that the test module duplicate the full is similar to the equivalent viscous damping concept used in
height of the wall in the prototype building. Section 17 of ASCE/SEI 7-05 for required tests of seismic
isolation systems.
For a given cycle, the relative energy dissipation ratio βh
is the area Ad inside the lateral force-drift angle loop for the
module, divided by the area of the effective circumscribing
parallelograms ABCD and DFGA. The areas of the parallelo-
grams equal the sum of the absolute values of the lateral
force strengths, E1 and E2, at the drift angles θL1 and θL2
multiplied by the sum of the absolute values for the drift
angles θL1′ and θL1 ′ .
required global toughness—the requirements of 21.2.1.5
of ACI 318 concerning toughness cover both the energy
dissipation of the wall system that, for monolithic construc-
tion, is affected primarily by local plastic hinging behavior
and the toughness of the prototype structure as a whole. In
this document, the former is termed “energy-dissipation
Fig. R2.3—Undesirable deformations along horizontal joints. toughness,” and the latter is termed “required global
toughness.” The required global toughness is a condition of ACI T1.1 and using the results of the half-scale tests, the
that does not apply to the walls alone and it can be satisfied NIST developmental tests, and other relevant data, ACI T1.2
only though analysis of the performance of the prototype was written and defined an industry standard for the design
structure as a whole when the walls perform to the criteria of one particular type of special hybrid moment frame. While
specified in this document. ACI T1.1 can be used to validate the performance of special
The required gravity load for global toughness evaluations is hybrid moment frames with a wide variety of design details,
the value given by ACI 318 provisions. For conformity with ACI T1.2 covers design requirements for moment frames
9.2.1 of ACI 318, UBC 1997, IBC 2003, and NFPA 5000, the with central unbonded post-tensioning and equal top and
required gravity load is 1.2D + f1L, where the seismic force bottom special energy dissipation reinforcement only. With
is additive to gravity forces, and 0.9D where the seismic the existence of ACI T1.2, ACI T1.1 provided the basis for
force counteracts gravity forces. The factor f1 is equal to 0.5 prequalifying one generic type of special hybrid moment
in all cases except for garages, areas occupied as places of frame for construction in general.
public assembly, and all areas where the live load is greater The development and validation of design procedures for
than 100 lb/ft2 for which cases f1 is equal to 1.0. unbonded post-tensioned special precast walls have
followed the same pattern as that for special hybrid moment
CHAPTER 3—DESIGN PROCEDURE frames. As part of the Precast Seismic Structural Systems
(PRESSS) program, sponsored jointly by the National
3.1 Science Foundation (NSF) and the Precast/Prestressed
The design procedures used to proportion the test modules Concrete Institute (PCI), design concepts for unbonded post-
shall define the mechanisms by which the system resists tensioned precast walls and developmental testing were
gravity and earthquake effects. conducted by a consortium of universities and design
professionals. Those concepts were tested out in the five-
R3.1 story PRESSS building (Priestley et al. 1999); subsequently,
For a generic precast wall system to be accepted based on guidelines for the design of unbonded post-tensioned precast
this document, a design procedure should be developed walls were developed (Stanton and Nakaki 2002). The
before validation testing. The design procedure should be relation between those guidelines and the behavior of the
based on a consideration of material properties and force walls in the PRESSS building has also been evaluated
transfer mechanisms, and its development will usually (Thomas and Sritharan 2004). Thus, a design procedure for
require preliminary, and possibly extensive, physical testing one type of unbonded post-tensioned precast wall exists and
that is not part of the validation testing. Derivation of a the procedure has essentially been validated through the
method to calculate the stiffness of the walls, including those PRESSS building test. Based on that and other supporting
of the test modules, would be one outcome of the preliminary information, this consensus document defines acceptance
development program. Other outcomes should include criteria for unbonded post-tensioned precast walls in
methods for calculating En , Ent , and Epr . general. It is intended that a subsequent document define an
This requirement for the development of a design proce- industry standard for the design of the type of precast wall
dure before the validation testing is consistent with experi- used in the PRESSS building.
ence from the development of the special hybrid moment
frame system that is the subject of ACI T1.1 and T1.2. The 3.2
National Institute of Standards and Technology (NIST) Before testing, design procedures shall be developed for
carried out the basic development program for the innovative the prototype structure and its walls. The procedures shall
hybrid frame system. With financial help from a contractor, account for effects of material nonlinearity, including
multiple small-scale hybrid frame subassemblages, designed cracking, deformations of members and connections, and
to differing nominal engineering design values, were tested reversed cyclic loading. The design procedures shall include
to failure along with similar specimens of monolithic the procedures specified in Sections 3.2.1 through 3.2.4 and
construction, and a design procedure for hybrid frames shall be applicable to all unbonded post-tensioned precast
developed from that information. To be able to use the hybrid structural walls, coupled and uncoupled, of the prototype
frame concept in practice, ACI T1.1 was written to define the structure.
conditions under which the same R and Cd factors could be
used for special hybrid frames as those used for monolithic R3.2
special moment frames designed to Chapter 21 of ACI 318. The test program specified in this document is intended to
The contractor then used that hybrid frame system for a verify an existing design procedure for unbonded post-
39-story condominium building in San Francisco. To validate tensioned precast structural walls for a specific structure or
that the performance of that building would be satisfactory, for prequalifying a generic type of unbonded post-tensioned
subassemblages that were half-scale models of typical interior, precast wall system for construction in general. The test
exterior, and corner column connections were tested in program is not for the purpose of creating basic information
accordance with the requirements of ACI T1.1. The foregoing on the strength and deformation properties of such systems
represents the use of ACI T1.1 for prequalifying hybrid for design purposes. Thus, during the validation testing, the
frames for a specific structure. Then, following the development test modules should not fail before reaching the minimum
SPECIAL UNBONDED POST-TENSIONED PRECAST STRUCTURAL WALLS ITG-5.1-9
acceptable drift angle capacity specified in Section 5.4. That 3.2.4 Procedures shall be specified to ensure that undesirable
result is in contrast to what is usually necessary during mechanisms of response will not occur. These include a
testing in the development phase for a new or revised design story mechanism due to local buckling of the reinforcement,
procedure where specimens with widely varying character- splice failure, excessive opening of joints between panels
istics are tested to failure. and between panels and foundation, excessive shear slip
Special wall systems are likely to undergo inelastic along joints, shear failure of panels, misalignment between
responses during an event similar to the anticipated maximum panels or between panels and foundations due to panel
considered earthquake ground motion (ASCE/SEI 7-05). The twisting, or local or global instability of the wall.
design procedure should consider wall configuration,
equilibrium of forces, compatibility of deformations, 3.3
magnitudes of the lateral drifts, reversed cyclic displacements, The design procedures shall be used to design the test
the relative values of each nominal engineering design value modules, and shall be documented in the test report.
(for example, shear, axial load, and moment-shear ratio),
the possibility of excessive opening of horizontal joints
R3.3
between panels and between panels and the foundation, and
The justification for the small number of test modules
the possibility of shear-slip along such joints. The procedure
should also use appropriate constitutive laws for materials specified in Chapter 4 is that a previously developed design
that include considerations of effects of cracking, loading procedure is being validated by the test results. Thus, the test
reversals, and inelasticity. The development of appropriate modules for the experimental program should be designed
multiplication factors to be applied to specified material using the procedure intended for the prototype wall system,
strengths as a consequence of inelasticity and loading reversals and values for stiffness and strength should be predicted for
is particularly important. To account for strain-hardening the test modules before the validation testing is started. In
effects, multiplication factors should be applied to the practice, most building designers produce designs with more
specified yield strengths for reinforcing steels in the walls, robust sections and more reinforcement than required for
and for reinforcing steel, metals, and other materials used the design forces and code requirements. Test specimens,
for connecting elements between walls. To account for however, should be representative of walls that have properties
confinement effects in the compression zones of the toes of the closest to those satisfying exactly the nominal engineering
walls, factors should be applied to the specified compressive design values rather than specimens with more robust
strength of the concrete in that zone. sections and reinforcement because the authority having
The stiffness of the structural walls is important for jurisdiction is likely to limit the allowable maximum stresses
calculating the fundamental period of the prototype structure. to those achieved in the testing.
The procedure used to determine the stiffness of the walls Because the strength and stiffness of coupled walls depend
should be verified from the validation test results as on the degree of coupling between walls, the procedure also
described in Section 5.10. should define how to calculate the degree of coupling.
3.2.1 Procedures shall be specified for calculating the CHAPTER 4—TEST MODULES
stiffness of the unbonded post-tensioned precast structural
walls, and of coupled structural walls, that are applicable to all 4.1
the unbonded post-tensioned walls of the prototype structure. No fewer than two modules shall be tested.
3.2.2 Procedures shall be specified for calculating the
4.2
lateral strength of the unbonded post-tensioned precast struc-
At least one module shall be tested for each critical
tural walls, and of coupled structural walls, applicable to all
combination of nominal engineering design values for each
unbonded post-tensioned precast walls of the prototype
structure. characteristic configuration of unbonded post-tensioned
precast structural walls, including intersecting precast structural
3.2.3 Procedures shall be specified for designing and walls or coupled precast structural walls. Where all the
detailing the unbonded post-tensioned precast structural unbonded post-tensioned precast walls of the structure have
walls to achieve without failure the minimum acceptable the same configuration and the same nominal engineering
drift capacity specified for equivalence in Section 1.2.4.4, design value, no fewer than two modules shall be tested.
Item (2). The procedures shall cover wall shear strength, Where intersecting unbonded post-tensioned precast wall
sliding shear strength, boundary tie spacing to prevent bar systems are to be used, the response for the two orthogonal
buckling, concrete confinement, limiting reinforcement directions shall be tested unless analyses and other test
strains in tension and compression, limiting strains for results can be used to show that testing in two directions is
coupling device materials, wall web reinforcement details to not required. Such analyses shall consider seismic response
prevent vertical splitting in the inelastic range of behavior, for both diagonal directions and not the 100-0 or 100-30
and any other actions or elements of the wall system that can percentage force distribution that is permitted for design by
affect the drift capacity or strength. documents such as ASCE/SEI 7.
ITG-5.1-10 ACI STANDARD
rations other than those shown in Fig. R2.1 and R4.1 may be
appropriate when it is difficult to realistically model the
likely dominant earthquake deformations using orthogonal
direction testing only.
This provision should not be interpreted as implying that
only two tests will need to be made to qualify a generic
system. During the development of the proposed system, it is
likely that several more tests will have been made, resulting
in progressive refinements of the mathematical model used
to describe the likely performance of the generic structural
wall system and its construction details. Consequently, only
one test of each module type for each nominal engineering
design value, at a specified minimum scale and subjected to
(a) specific loading actions, may be required to validate the
system. As stated in Section 7.1, however, if any one of those
modules for the generic wall system fails to pass the validation
testing required by this document, the generic wall system has
failed the validation testing. Further, as stated in Section 7.2, if
any module fails to pass the validation testing, the reason for
that failure should be determined through analysis and, if
necessary, through additional developmental testing. The
design procedure should be revised and used for the design
of a full set of new modules before any further validation testing
is undertaken. Every module in the new set of tests should
not fail before achieving the minimum acceptable drift
angle capacity specified in Section 5.4.
In most prototype structures, a slab is usually attached to
the wall and, as demonstrated by the results of the PRESSS
building test (Priestley et al. 1999), the manner in which the
slab is connected to the wall should be carefully considered.
The connection should be adequate to allow the development
(b)
of drifts equal to those anticipated in this document. In
conformity with common practice for the subassemblage tests
R4.1—Coupled wall test module: (a) with coupling beams;
used to develop the provisions of Chapter 21 of ACI 318,
and (b) with vertical mechanical couplers.
however, there is no requirement for a slab to be attached to
the wall of the test module. The effect of the presence of the
R4.2 slab should be examined in the development program that
One module should be tested for each nominal engineering precedes the validation testing.
design value, such as shear, axial load, or moment-shear
ratio, for each characteristic configuration of walls. Thus, in 4.3
accordance with Section 4.2, if the test on the module results Where the design requires the use of coupling elements in
in a maximum shear stress of 3 f c′ , then the maximum the form of devices or beams connecting the adjacent
shear stress that can be used in the prototype is that same boundaries of the unbonded post-tensioned precast walls, those
value. Each characteristic in-plane configuration of walls, elements shall be included as part of the test module. Coupling
or coupled walls, in the prototype structure should also be devices shall be of the same type, material, and manufacture
tested. Thus, as a minimum for one-way structural walls, two as the devices used for the prototype structure.
modules with the configuration shown in Fig. R2.1, and, for
one-way coupled walls, two modules with the configuration 4.4
shown in either Fig. R4.1(a) or (b), should be tested. In Modules shall have a scale large enough to represent the
Fig. R4.1, deformations and gap openings are deliberately complexities and behavior of the real materials and of the
exaggerated to clearly show the behavior being represented. load transfer mechanisms in the prototype walls and their
In addition, if intersecting wall systems are to be used, then coupling elements, if any. Validation program modules shall
the response of the wall systems for the two orthogonal be full scale unless the validation testing has been preceded
directions should be evaluated and tested. If it can be shown by an analytical and experimental development program
that the behavior of the wall in one direction has already involving tests on multiple modules of not less than 1/10
been addressed with another test configuration, then testing scale. If that development program criterion is satisfied, the
in both directions may not be necessary. For two-way wall validation program modules shall have a scale not less than
systems and coupled wall-frame systems, testing of configu- one third. Similitude principles shall be used to design the
SPECIAL UNBONDED POST-TENSIONED PRECAST STRUCTURAL WALLS ITG-5.1-11
test modules and interpret results from less than full-scale they cross the wall to the foundation interface if there is any
tests. Regardless of the scale used for the modules for the likelihood of moisture accumulating in that region. In
validation tests, connecting elements for coupled walls shall addition, to ensure that failure does not occur in the end
be demonstrated to have the strength, ductility, and energy- anchors for the post-tensioning tendons, it is desirable that
dissipation toughness required for the full-scale prototype a portion of the tendon that includes the anchorage should
structure, either by the testing of those elements at half scale be sealed to obviate tendon anchor failure and allow the
or larger in the prior development program or by testing criterion of Section 7.1.2 to be met.
them at full scale as part of the validation program.
4.6
R4.4 Walls shall be at least two panels high unless the prototype
Test modules need not be as large as the corresponding structure is one for which a single panel is to be used for the
walls in the prototype structure. The scale of the test full height of the wall. The number of panels used shall be
modules, however, should be large enough to capture all the the number needed to validate the nominal engineering
complexities associated with the materials of the prototype design values for the prototype structure at the horizontal
wall, its geometry and reinforcing details, load transfer connection between the wall and the foundation, the horizontal
mechanisms, and joint locations. For modules that involve connection between the lowermost panel in the wall and the
the use of precast elements, for example, scale effects for panel immediately above that panel, and the horizontal
load transfer through mechanical connections should be of connection between the top panel of the prototype structure
particular concern (Schultz and Magana 1996). The issue of and the panel below it.
the scale necessary to capture fully the effects of details on
the behavior of the prototype should be examined in the
R4.6
development program that precedes the validation testing
For walls constructed using precast or precast/
(ACI T1.1). Information on similitude principles, applicable
prestressed panels and designed using nonemulative
to the testing of concrete models, is provided in ACI
methods, the response under lateral load can change signif-
Committee 444 (1979).
icantly with joint opening (Fig. R2.2(d) and R2.3(a)). The
number of panels used to construct a wall and the number of
4.5
subpanels used to construct a panel depend on wall height
The geometry, reinforcing details, fabrication procedures,
and design philosophy. If, in the prototype structure, there is
and material properties of the walls, connections, and
a possibility of horizontal joint opening under lateral
coupling elements shall be representative of those to be used
in the prototype structure. loading at a location other than the base of the wall, then the
consequences of that possibility should be considered in the
Where special corrosion protection measures are specified
development and validation test programs. Joint openings at
for the tendons, the same corrosion protection measures shall
locations other than the base can be minimized through the
be applied to the tendons of the test modules. Connecting
use of capacity design procedures (Paulay and Priestley
devices and couplers shall be commercially available
1992). For simple, regular low-rise structures, testing of
devices and not units made specifically for the test program
two-panel high modules is adequate. For more complex and
unless commercial devices are not available. In that case, the
higher-rise structures, however, modules more than two
same material and fabrication procedures shall be used for
the devices of the test modules and the prototype. panels high or additional tests may be necessary to appro-
priately bound the range of moment-shear values expected.
R4.5 Where coupled walls are used in the prototype structure,
It is expected that for a given generic unbonded post- particular attention should be given during the development
tensioned precast wall structure, such as a centrally post- phase as to how to represent gravity load effects in the test
tensioned wall constructed using multiple precast or precast modules and how that representation may affect the number
pretensioned concrete wall panels, validation testing of panels needed in the test module.
programs will initially use specific values for the specified
strength of the concrete and reinforcement in the walls, the 4.7
layout of the connections between panels, the location of the Where unbonded post-tensioned precast walls are to be
post-tensioning, the location of the panel joints, and the used to support axial loads due to gravity exceeding
design stresses in the wall. Pending the development of an 0.05Ag fc′ , the test modules shall be subject to an axial load
industry standard for the design of such walls similar to the stress representative of that anticipated in the prototype
standard for special hybrid moment frames (ACI T1.2), structure for the duration of lateral loading. The axial load
specified concrete strengths, connection layouts, post- level used shall be consistent with the nominal engineering
tensioning amounts and locations, and details used for such design values used for the test module, and the effects of
walls will need to be limited to the values and layouts used both minimum and maximum axial load shall be considered.
in the validation testing programs. An axial load shall not be used to justify acceptable test
For unbonded post-tensioned walls, special corrosion performance if analysis shows that axial load is not always
prevention measures are desirable for the tendons where present in the prototype structure.
ITG-5.1-12 ACI STANDARD
5.3
The maximum load for the first three cycles shall not
exceed 0.6Ent. Drift angle values for the subsequent three
cycles to a new maximum drift angle shall be to values not
less than 5/4 times, and not more than 3/2 times, the previous
maximum drift angle. For initial and subsequent drift angles
to loads less than 0.6Ent , however, it shall be permitted to
use subsequent drift angles not more than 2.5 times the
previous angle.
5.4
Testing shall be continued to failure of the module or until
the drift angle, in percent, exceeds the following value
R5.4
height of the wall increases and the drift angle demand used
For a structure subject to the design seismic shear force,
in the design of the wall increases, however, the likelihood of building codes such as UBC 1997, IBC 2003, and NFPA
extreme fiber crushing in compression at or before the 5000, and recommended provisions such as ASCE/SEI 7-05
maximum drift angle demand is reached increases, and the and FEMA 356, specify a maximum allowable drift. Structures
importance of the level of axial load increases. The significance designed to meet that drift limit, however, may experience
of the level of axial loading should be examined during the greater drifts during an earthquake equal to the design basis
development phase. earthquake, and are likely to experience greater drifts during
an earthquake equal to the maximum credible earthquake. In
5.1 addition to the characteristics of the ground motion, actual
Test modules shall be subjected to a sequence of displace- drifts will depend on the strength of the structure, its initial
ment-controlled cycles to predetermined drift angles as elastic stiffness, and the ductility expected for the given
defined in Sections 5.2 through 5.5. The displacement lateral-load-resisting system. Specification of suitable
history applied to the test module shall allow the recording limiting drifts for the test modules requires interpretation
of the important features associated with drift angles as and allowance for uncertainties in the assumed ground
defined in Sections 5.9, 5.10, and 6.2.6 through 6.2.9. If the motions and structural properties.
module consists of coupled walls, approximately equal drift In IBC 2003, the design seismic shear force applied at the
angles (within 5% of each other) shall be applied to the top base of a building is related directly to its weight and the
of each wall and at each floor level. Where an axial load is design elastic response acceleration, and inversely to a
applied to the test module simultaneously with the lateral response modification factor R. The R factor increases with
displacements, that axial load shall be applied before the the expected ductility of the lateral-force-resisting system of
lateral displacements and kept approximately constant the building. Special structural walls that satisfy the require-
(within 5%) throughout the lateral load sequence. ments of 21.2 and 21.7 of ACI 318 are assigned an R value
of 6 when used in a building frame system, and a value of 5
when used in a bearing wall system. They are also assigned
R5.1
limiting story drift angle demands that are dependent on the
For uncoupled walls, applying lateral displacements at
hazard to which the building is exposed. When the design
the top of the wall only is generally adequate provided that
seismic shear force is applied to a building, the building
the joints between panels do not open. For coupled walls,
experiences nonlinear behavior, and the resultant computed
however, where there are changes in wall properties, axial drifts (the design story drifts) should be less than a specified
loads, coupling element stiffness or strength down the height allowable drift. Additional guidance is given in FEMA 356,
of the wall, or the coupled walls are on separated founda- where the deformations for rectangular walls with height-
tions, approximately equal displacements should be applied length ratios greater than 2.5 and flanged wall sections with
to each wall at each floor level. height-length ratios greater than 3.5 are to be assumed to be
controlled by flexural actions. When structural walls are
5.2 part of a building representing a substantial hazard to
Three fully reversed cycles shall be applied at each drift human life in the event of a failure, the allowable story drift
angle. The actuator stroke shall be sufficient to achieve drift angle demand for shear-controlled walls is 0.0075 radians,
angles of ±0.04 radians. and for flexure-controlled walls, it is a function of the plastic
ITG-5.1-14 ACI STANDARD
hinge rotation at the base of the wall. For flexure-controlled where hw is the height of the wall, and lw is the length of the
walls, values range up to a maximum of about 0.02 radians wall. The data from the tests of Hidalgo et al. (2002) suggest
for walls with confined boundary elements with low reinforce- that, while that form of the formula is correct, the lower limit
ment ratios and walls with shear stresses less than 3 f c′ . on drift can be decreased to 0.8, as specified in these
To compensate for the use of the R value, 1617.4.6 of IBC provisions, provided the use of that formula is limited to
2003 requires that the drift determined by an elastic analysis walls with height-length ratios equal to or greater than 0.5.
for the code-prescribed seismic forces be multiplied by a For wall height-length ratios less than 0.5, the behavior is
deflection amplification factor Cd to determine the design controlled by shear deformations, even for the elastic range
story drift, and the design story drift should be less than the of behavior (Fig. R2.2(c)), and Eq. (5-1) should not be used.
allowable limiting story drift angle. In building frame The upper value of 0.030 radians for the drift angle, as
systems, structural walls satisfying the requirements of 21.7 recommended by Seo et al. (1998), is optimistic because
of ACI 318 are assigned a Cd value of 5. Research (Uang their findings were based on data for walls with height-
and Maarouf 1993a,b), however, has found that design story length ratios equal to or less than 3.5. Subsequent tests (Ali
drift angles determined in the foregoing manner may be too and Wight 1990; Taylor et al. 1998) have shown that the
low. Drift angles of six times IBC-calculated values, rather upper drift angle limit of 0.0025 radians for height-length
than five, are more representative of the upper bounds to ratios equal to or greater than 3.0, as specified in Eq. (5-1),
expected drift angles. The value of 6 is also in agreement is a more realistic limit. To ensure that the performance of
with the finding that the drift angle of an inelastic structure unbonded post-tensioned precast walls is conceptually at
is approximately the same as that of an elastic structure with least equal to the performance of monolithic walls designed
the same initial period. For flexure-controlled walls, the to the minimum requirements of ACI 318, the minimum
value of 6/5 times the present IBC limits on calculated drift acceptable drift angle capacities, as defined by the foregoing
angle demand would lead to a limit on real drift angle for cast-in-place monolithic walls, were increased by 12.5%
demands of up to 0.024 radians. for hw /lw values of 0.5, and by 20% to a maximum value of
Duffy et al. (1993) reviewed experimental data for shear 3% for the upper minimum acceptable drift angle capacities.
walls to define postpeak behavior and limiting drift angle That approach is reasonable because unbonded post-
capacities for monolithic walls with height-length (aspect) tensioned precast walls have shorter plastic hinging lengths
ratios between 0.25 and 3.5. Seo et al. (1998) re-analyzed (Thomas and Sritharan 2004) associated with the toe of the
the data of Duffy et al. (1993) together with data from tests wall than do monolithic walls.
conducted subsequent to the analysis of Duffy et al. (1993). To assess the reserve capacity of walls, testing should be
Duffy et al. (1993) established that for walls with aspect continued to displacements greater than those given by
ratios between 0.25 and 1.1 and web reinforcement satisfying Eq. (5-1) so that the mode of failure of the wall, or the drifts
ACI 318-05 requirements, there was a significant range of at which there is a substantial loss in lateral capacity and
behavior for which drift angle capacities were still reliable axial load capacity, can be established. It is possible that
in the postpeak response region. Typically the postpeak drift unanticipated and undesirable modes of failure may occur at
increased by 0.005 radians for a 20% degradation in drifts only slightly larger than those given by Eq. (5-1).
capacity under cyclic loading. For greater values of While testing to displacements greater than those given by
degradation, drifts were less reliable. That finding has also Eq. (5-1) is highly desirable, it may not be possible for at
been confirmed through tests conducted by Hidalgo et al. least two reasons: 1) some walls may exhibit drifts that
(2002) on walls with effective height-length ratios ranging exceed testing capabilities without loss in strength; and 2) a
between 0.35 and 1.0. Values of the drift angle of the walls reduction in axial load capacity may not become evident
at inclined cracking and at peak load capacity varied little during the lateral load test.
with web reinforcement. By contrast, drifts in the postpeak
range were reliable to a capacity equal to 80% of the peak 5.5
capacity and were 0.005 radians greater than the drifts at For coupled walls, hw /lw in Eq. (5-1) shall be taken as the
peak load capacity, provided the walls contained horizontal smallest value of hw /lw for any of the individual walls
and vertical web reinforcement equal to 0.25%. coupled.
From an analysis of the available test data and from
theoretical considerations for a wall rotating about a plastic R5.5
hinge at its base, Seo et al. (1998) concluded that the limiting The design capacity for coupled wall systems should be
drift angle at peak capacity increased almost linearly with developed by the drift angle corresponding to that for the
the height-length ratio of the wall. When the additional post- coupled wall with the least hw /lw value. For both cast-in-
peak load drift angle capacity for walls with adequate web place and precast coupled walls, the strength and deforma-
reinforcement was added to the drift angle at peak capacity, tion capacity of the coupling elements often determines the
then the total available drift angle capacity in percent was drift capacity. Again, it is highly desirable that testing be
given by continued to the drift angle given by Eq. (5-1) for the wall
with the greatest hw /lw and beyond that value to wall failure
1.0 ≤ 0.67[hw/lw] + 0.5 ≤ 3.0 to assess the reserve capacity of the coupled wall system. For
SPECIAL UNBONDED POST-TENSIONED PRECAST STRUCTURAL WALLS ITG-5.1-15
6.2.3 Details shall be provided of specified material properties CHAPTER 7—TEST MODULE
used for design, and measured material properties obtained ACCEPTANCE CRITERIA
by testing in accordance with Sections 5.6, 5.7, and 5.8.
The requirements of this chapter apply to each module of
the test program and not to an average of the results of the
6.2.4 A description shall be provided of the test setup,
program. Figure R7.1 illustrates the primary intent of this
including fully dimensioned diagrams and photographs. clause for Sections 7.1.3 and 7.1.4, Items (1) and (2).
used in the joint grout. Because the grouts used for the joints R8.1—Referenced standards and reports
of the walls of the prototype building and those used for the American Concrete Institute
joints of the modules are likely to have the same maximum 318-05 Building Code Requirements for Structural
aggregate size, the limiting slip for a one-third scale test Concrete
module is also likely to be the limiting slip for the prototype T1.1 Acceptance Criteria for Moment Frames Based on
walls. Structural Testing
With the maximum relative slip on horizontal joints limited T1.2 Special Hybrid Moment Frames Composed of
to 0.06 in. during testing and the stress in the prestressing Discretely Jointed Precast and Post-Tensioned
steel limited to 0.9 times its yield stress at one half or more Concrete Members
of the displacement specified in Eq. (5-1), joint openings
after testing is complete are unlikely to exceed 0.03 in., American Society of Civil Engineers (ASCE)
provided that an appropriate initial prestress level is used ASCE/SEI 7-05 Minimum Design Loads for Buildings and
for the unbonded tendons. Other Structures
Center of Excellence for Airport Technology, University of from the PRESSS Five-Story Precast Concrete Test
Illinois at Urbana-Champaign, Mar., 433 pp. Building,” PCI Journal, V. 44, No. 6, Nov.-Dec., pp. 42-67.
ACI Committee 440, 1979, “Models of Concrete Struc- Schultz, A. E., and Magana, R. A., 1996, “Seismic
tures—State of the Art,” Concrete International, V. 1, No. 1, Behavior of Connections in Precast Concrete Walls,” Mete A.
Jan., pp. 77-95. Sozen Symposium, SP-162, J. K. Wight and M. E. Kreger,
Ali, A., and Wight, J. K., 1990, “Reinforced Concrete eds., American Concrete Institute, Farmington Hills, MI,
Structural Walls with Staggered Opening Configurations pp. 273-311.
Under Reversed Cyclic Loading,” Report No. UMCE 90-05, Seo, S-Y.; Lee, L.-H.; and Hawkins, N. M., 1998, “The
Department of Civil Engineering, University of Michigan, Limiting Drift and Energy Dissipation Ratio for Shear Walls
Ann Arbor, MI, Apr. Based on Structural Testing,” Journal of the Korean
Duffy, T. A.; Goldman, A.; and Farrar, C. R., 1993, “Shear Concrete Institute, V. 10, No. 6, Dec., pp. 335-343.
Wall Ultimate Drift Limits,” Report NUREG/CR-6104, Sezen, H., and Moehle, J. P., 2002, “Seismic Behavior of
LA-12649-MS, U.S. Nuclear Regularity Commission. Shear-Critical Reinforced Concrete Building Columns,”
Hidalgo, P. A.; Ledezma, C. A.; and Jordan, R. A., 2002, Proceedings of Seventh U.S. National Conference on Earth-
“Seismic Behavior of Squat Reinforced Concrete Shear quake Engineering, Boston, MA, EERI, Oakland, CA.
Walls,” Earthquake Spectra, V. 18, No. 2, May, pp. 287-308. Soudki, K. A.; Rizkalla, S. H.; and LeBlanc, B., 1995a,
“Horizontal Connections for Precast Concrete Shear Walls
Hutchinson, R. L.; Rizkalla, S. H.; Lau, M.; and Heuvel, M.,
Subjected to Cyclic Deformations Part 1: Mild Steel Connec-
1991, “Horizontal Post-Tensioned Connections for Precast
tions,” PCI Journal, V. 40, No. 4, July-Aug., pp. 78-96.
Concrete Bearing Shear Walls,” PCI Journal, V. 36, No. 3,
Nov.-Dec., pp. 64-76. Soudki, K. A.; Rizkalla, S. H.; and Daikiw, R. W., 1995b,
“Horizontal Connections for Precast Concrete Shear Walls
Kurama, Y. C., 2002, “Hybrid Post-Tensioned Precast
Subjected to Cyclic Deformations Part 2: Prestressed
Concrete Walls for Use in Seismic Regions,” PCI Journal,
Concrete,” PCI Journal, V. 40, No. 5, Sept.-Oct., pp. 82-96.
V. 47, No. 5, Sept.-Oct., pp. 36-59.
Soudki, K. A.; West, J. S.; Rizkalla, S. H.; and Blackett,
Kurama, Y. C.; Pessiki, S.; Sause, R.; and Lu, L.-W.,
B., 1996, “Horizontal Connections for Precast Concrete
1999, “Seismic Behavior and Design of Unbonded Post-
Shear Wall Panels Under Cyclic Shear Loading,” PCI
Tensioned Precast Concrete Walls,” PCI Journal, V. 44, No. 3,
Journal, V. 41, No. 3, May-June, pp. 64-80.
May-June, pp. 72-89.
Stanton, J. F., and Nakaki, S. D., 2002, “Design Guidelines
Kurama, Y. C.; Weldon, B; and Shen, Q., 2004, “Experi- for Precast Concrete Seismic Structural Systems—Unbonded
mental Evaluation of Unbonded Post-Tensioned Hybrid Post-Tensioned Split Walls” PRESSS Report No. 01/03-09,
Coupled Wall Subassemblages,” Proceedings, 13th World UW Report SM 02-02, Department of Civil Engineering,
Conference on Earthquake Engineering, Vancouver, BC, University of Washington, Seattle, WA, Feb., pp. 3-1 to 3-19.
Canada. Taylor, C. P.; Cote, P. E.; and Wallace, J. W., 1998, “Design
Melek, M.; Wallace, J. W.; and Conte, J. P., 2003, “Exper- of Slender Reinforced Concrete Walls with Openings,” ACI
imental Assessment of Columns with Short Lap Splices Structural Journal, V. 95, No. 4, July-Aug., pp. 420-433.
Subjected to Cyclic Loads,” PEER Report No. 2003/04, Thomas, D. J., and Sritharan, S., 2004, “An Evaluation of
Pacific Earthquake Engineering Research Center, Berkeley, Seismic Design Guidelines Proposed for Precast Jointed
CA, Apr., 176 pp. Wall Systems,” ISU-ERI-Ames Report ERI-04643,
Paulay, T., and Priestley, M. J. N., 1992, “Philosophy of Department of Civil, Construction and Environmental
Capacity Design,” Seismic Design of Reinforced Concrete Engineering, Iowa State University, Ames, IA, June.
and Masonry Buildings, John Wiley and Sons, Inc., New Uang, C.-M., and Maarouf, A., 1993a, “Seismic Displace-
York, pp. 38-46. ment Amplification Factor in Uniform Building Code,”
PCI Ad Hoc Committee on Precast Walls, 1997, “Design SEAONC Research Bulletin Board BB93-3, June, pp. B1-B2.
for Lateral Force Resistance with Precast Concrete Shear Uang, C.-M., and Maarouf, A., 1993b, “Displacement
Walls,” PCI Journal, V. 42, No. 2, Mar.-Apr., pp. 44-65. Amplification Factor for Seismic Design Provisions,”
Priestley, M. J. N.; Sritharan, S.; Conley, J.; and Proceedings Structures Congress, V. 1, ASCE, Irvine, CA,
Pampanin, S., 1999, “Preliminary Results and Conclusions pp. 211-216.
®
American Concrete Institute
Advancing concrete knowledge
As ACI begins its second century of advancing concrete knowledge, its original chartered purpose
remains “to provide a comradeship in finding the best ways to do concrete work of all kinds and in
spreading knowledge.” In keeping with this purpose, ACI supports the following activities:
· Technical committees that produce consensus reports, guides, specifications, and codes.
· Periodicals: the ACI Structural Journal and the ACI Materials Journal, and Concrete International.
Benefits of membership include a subscription to Concrete International and to an ACI Journal. ACI
members receive discounts of up to 40% on all ACI products and services, including documents, seminars
and convention registration fees.
As a member of ACI, you join thousands of practitioners and professionals worldwide who share a
commitment to maintain the highest industry standards for concrete technology, construction, and
practices. In addition, ACI chapters provide opportunities for interaction of professionals and practitioners
at a local level.
www.concrete.org
®
American Concrete Institute
Advancing concrete knowledge