MBS1 SERIES
AUTOMATIC TRANSFER SWITCH
USER MANUAL
MBS1 Series Automatic Transfer Switch User Manual
Version
No. Version Date Note
1 V1.0 2021-07-14 Original release.
1
MBS1 Series Automatic Transfer Switch User Manual
Symbol Description
Symbol Description
2
MBS1 Series Automatic Transfer Switch User Manual
Warning
1. The installation, adjustment, repair and maintenance of the equipment must be
carried out by professionals.
2. Please read the complete operation manual before installing and operating this
product.
3. For any maintenance and commissioning of the equipment, it is necessary to be
familiar with all equipment, safety specifications and take preventive measures in
advance, otherwise personal injury or damage to relevant equipment may be
caused.
4. Many parts of this product, including printed circuit boards, work under online
voltage and cannot be touched. Only use insulated tools.
5. Do not touch unprotected components.
6. Before maintaining the product line, the following protective measures shall be
taken:
1)Disconnect all power supplies.
2)Turn the switch to the "0" position, and then hang and lock the padlock.
3)Put a "no closing" sign on the switch.
Be Care
1. Before powering up and configuring the product, ensure that the working voltage is
compatible with the power supply voltage range shown on the product nameplate.
2. If the operating voltage is inconsistent with the power supply voltage range, the
product may be damaged.
3. Failure to follow the instructions may cause damage to the equipment.
3
MBS1 Series Automatic Transfer Switch User Manual
Catalogue
1. Summary............................................................................................................................... 5
6. Wiring instructions............................................................................................................. 10
7. Product installation............................................................................................................ 11
Notes:
1. All rights reserved. No part of this duplication may be reproduced in any material
form (including photocopying or storing in any medium by electronic means or others)
without the written permission of the copyright holder.
2. MEBAY Technology reserves the rights to change the contents of this document
without prior notice.
4
MBS1 Series Automatic Transfer Switch User Manual
1.Summary
MBS1 series dual power switch, referred to as ATS (automatic transfer switch),
is an integrated three-stage switch with fire protection function. This series of
switches are PC level switches, which are composed of switch body and conversion
control. They are driven by electromagnetic coil and have electrical and mechanical
interlocking structure. They have fast conversion speed and can realize the rapid
switching of two power supplies. The power supply of conversion controller adopts
AC220V of common or standby power supply as the working voltage.
The product meets the standards: GB / T 14048.11, iec60947-6-1.
2)Field meaning
Field Meaning
Firm code MB:Chongqing Mebay Technology Co.,Ltd
Category S:PC Class Automatic Transfer Switch.
Design code 1
Frame class 100A,250A,630A,1600A,3200A
GA:Integrated three-stage,Fire type.
Product code
GA1:Integrated three-stage,Economic type,Dedicated to base station.
2P:2 Poles
Poles 3P:3 Poles
4P:4 Poles
Rated current 16A-3200A
5
MBS1 Series Automatic Transfer Switch User Manual
16 20 25 32 40 50 63 80 100 125 160 200 225 250 315 350 400 500 630 800 1000 1250 1600 2000 2500 3200
Rated current
Rated
insulation 690V 800V
voltage
Rated
concussion
8KV
withstand
voltage(Uimp)
Rated working
AC400V
voltage(Ue)
Using category AC-33B AC-33iB
Rated short-
circuit
8KA 17KA 26KA 67.5KA
connection
capacity
Rated short-
time withstand 5kA/60ms 10kA/60ms 12.6kA/60ms 30kA/60ms
current(Icw)
Transfer time I-
1.2s 1ss 0.6s 0.9s 0.9s
0 or 0-I
Transfer time I-
2.5s 2.1s 1.2s 1.8s 1.8s
II or II-I
Load off time 1.2s 1.1s 0.4s 0.6s 0.6s
Position indication
Electric key lock
Mechanism padlock
Switch body
Operate handle
Load side
NOTE:
1)Electric key lock:Control the inside controlling line power supply of the
switch,when the Electric lock open,the switch could be operated automatically
and remotely, when the electric lock closed,the switch could be operated by
handle only.
2)Operating handle: When operate the switch by the operating handle, the electric
lock must be closed.
3)Mechanic padlock:When inspection,firstly turn the switch to the'"0" position by
operation handle,then pull the padlock mechanism and close the padlock,then
the inspection can be arranged:(Pull the mechanism padlock will cut off the
inside controlling power supply of the switch. The switch couldn't be inelectric
position and also couldn't be manual operation.
4)Position indication:It means the position of the switch working estate( I ,0, I).
5)Controlling voltage: AC220V.
7
MBS1 Series Automatic Transfer Switch User Manual
400A-600A
100A 160A-250A
8
MBS1 Series Automatic Transfer Switch User Manual
2000A-3200A
9
MBS1 Series Automatic Transfer Switch User Manual
6.Wiring instructions
1)Terminal function description
Terminal Function Remarks
AC220V power output is only used as
101,106 AC220V,>1A
signal lamp power supply.
I-way working power input, 102: L, 103:
102,103 AC220V,>5A
N.
II channel working power input, 105:L,
104,105 AC220V,>5A
105: N.
Mode selection: short circuit is fully Automatic switching, mains
201,206
automatic and disconnection is manual. power priority.
External passive control input common
202
terminal.
After connecting with 202, circuit I is
203 External passive control.
closed.
BA series has no fire
After connecting with 202, circuit 0 is
204 fighting function.
closed (fire fighting).
After connecting with 202, circuit II is
205
closed.
301,306 Start the generator set remotely. Passive contact output.
Switch position feedback signal output
302
common terminal.
After closing, it is closed
303 I circuit closing feedback signal output.
with 302.
After closing, it is closed
304 0 circuit closing feedback signal output.
with 302.
After closing, it is closed
305 II circuit closing feedback signal output.
with 302.
The following functions are applicable to switches above 400A.
401,406 spare
Close after closing and
402,403 I-way position auxiliary terminal.
open after opening.
Close after closing and
404,405 II-way position auxiliary terminal.
open after opening.
501,506 spare
It is closed automatically
Manual / automatic mode indication
502,503 and disconnected
output.
manually.
Close when normal and
504,505 Padlock status output
open when pulled up.
10
MBS1 Series Automatic Transfer Switch User Manual
7.Product installation
1)Proofreading before installation
Product delivery
Check and confirm whether the product is the same as the product ordered
by yourself.
Check the voltage
11
MBS1 Series Automatic Transfer Switch User Manual
Check and confirm the voltage and the working voltage of the product.
Check and confirm whether the scope of use is consistent.
Install products
Follow the instructions in this file to install the product.
Install all external options.
Wiring the product
Connect the bus corresponding to the rated current of the switch.
Connect the control line and external indication line according to the wiring
diagram in the manual.
2)Operation method of wiring terminal
13