MBS1 Series Automatic Transfer Switch Manual V1.0

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

MBS1 Series Automatic Transfer Switch User Manual

MBS1 SERIES
AUTOMATIC TRANSFER SWITCH
USER MANUAL
MBS1 Series Automatic Transfer Switch User Manual

Version
No. Version Date Note
1 V1.0 2021-07-14 Original release.

Chongqing Mebay Technology Co.,Ltd


Add: No6-2,Building 4, Gangan Rd, Jiangbei District, Chongqing.
Tel:+86-23-6869 3061
Fax:+86-23-6765 8207
Web:http://www.mebay.cn
http://www.cqmb.cn
E_mail:sales@mebay.cn

1
MBS1 Series Automatic Transfer Switch User Manual

Symbol Description
Symbol Description

Remind operators to operate correctly, otherwise it may cause


Note the equipment not to work correctly.

It is indicated that potential hazards can damage equipment


Be care without proper precautions.

It is indicated if appropriate preventive measures are not taken,


potentially dangerous situations may result in death, serious
Warning personal injury or significant property losses.

2
MBS1 Series Automatic Transfer Switch User Manual

Warning
1. The installation, adjustment, repair and maintenance of the equipment must be
carried out by professionals.
2. Please read the complete operation manual before installing and operating this
product.
3. For any maintenance and commissioning of the equipment, it is necessary to be
familiar with all equipment, safety specifications and take preventive measures in
advance, otherwise personal injury or damage to relevant equipment may be
caused.
4. Many parts of this product, including printed circuit boards, work under online
voltage and cannot be touched. Only use insulated tools.
5. Do not touch unprotected components.
6. Before maintaining the product line, the following protective measures shall be
taken:
1)Disconnect all power supplies.
2)Turn the switch to the "0" position, and then hang and lock the padlock.
3)Put a "no closing" sign on the switch.

Be Care
1. Before powering up and configuring the product, ensure that the working voltage is
compatible with the power supply voltage range shown on the product nameplate.
2. If the operating voltage is inconsistent with the power supply voltage range, the
product may be damaged.
3. Failure to follow the instructions may cause damage to the equipment.

3
MBS1 Series Automatic Transfer Switch User Manual

Catalogue

1. Summary............................................................................................................................... 5

2. Model and meaning............................................................................................................. 5

3. Main technology parameters..............................................................................................6

4. Switch structure description............................................................................................... 7

5. Outline and installation dimensions.................................................................................. 8

6. Wiring instructions............................................................................................................. 10

7. Product installation............................................................................................................ 11

8. Test after installation.........................................................................................................13

Notes:
1. All rights reserved. No part of this duplication may be reproduced in any material
form (including photocopying or storing in any medium by electronic means or others)
without the written permission of the copyright holder.
2. MEBAY Technology reserves the rights to change the contents of this document
without prior notice.
4
MBS1 Series Automatic Transfer Switch User Manual

1.Summary
MBS1 series dual power switch, referred to as ATS (automatic transfer switch),
is an integrated three-stage switch with fire protection function. This series of
switches are PC level switches, which are composed of switch body and conversion
control. They are driven by electromagnetic coil and have electrical and mechanical
interlocking structure. They have fast conversion speed and can realize the rapid
switching of two power supplies. The power supply of conversion controller adopts
AC220V of common or standby power supply as the working voltage.
The product meets the standards: GB / T 14048.11, iec60947-6-1.

2. Model and meaning


1)Model description
MB S 1 - 100 GA - 4P - 100A
Firm Design Frame Product Rated
Category Poles
code code class code current

2)Field meaning
Field Meaning
Firm code MB:Chongqing Mebay Technology Co.,Ltd
Category S:PC Class Automatic Transfer Switch.
Design code 1
Frame class 100A,250A,630A,1600A,3200A
GA:Integrated three-stage,Fire type.
Product code
GA1:Integrated three-stage,Economic type,Dedicated to base station.
2P:2 Poles
Poles 3P:3 Poles
4P:4 Poles
Rated current 16A-3200A

5
MBS1 Series Automatic Transfer Switch User Manual

3.Main technology parameters


Model MBS1

Firm code 100 250 630 1600 3200

16 20 25 32 40 50 63 80 100 125 160 200 225 250 315 350 400 500 630 800 1000 1250 1600 2000 2500 3200
Rated current
Rated
insulation 690V 800V
voltage
Rated
concussion
8KV
withstand
voltage(Uimp)
Rated working
AC400V
voltage(Ue)
Using category AC-33B AC-33iB
Rated short-
circuit
8KA 17KA 26KA 67.5KA
connection
capacity
Rated short-
time withstand 5kA/60ms 10kA/60ms 12.6kA/60ms 30kA/60ms
current(Icw)
Transfer time I-
1.2s 1ss 0.6s 0.9s 0.9s
0 or 0-I
Transfer time I-
2.5s 2.1s 1.2s 1.8s 1.8s
II or II-I
Load off time 1.2s 1.1s 0.4s 0.6s 0.6s

Control voltage AC220V (176~265)V


Motor starting 400
325W 355W 440W 600W
rated power W
200W
Normal rated
62W 74W 90W 98W 120W
power of motor
10000 8000 6000 3000 3000
Mechanical life
1500 1000 1000 500 500
Electrical life
Power
frequency
interference 2000V/min
withstand
voltage
Degree of
IP20
protection
<2000m
Altitude
Working
Temperature: - 25 ~ + 70 ℃, humidity: 20 ~ 90%
conditions
Storage
Temperature: -30~+80℃, humidity: 20 ~ 90%
conditions
Installation
Class IV
category
class of
Class III
pollution
Net weight kg
3.4 6 7.6 15.9 16.8 36 36 37 39 55 61 67
4 poles
Note: the weight is for reference only, please refer to the real object.
6
MBS1 Series Automatic Transfer Switch User Manual

4.Switch structure description


Control voltage

Model and specification

Position indication
Electric key lock

Mechanism padlock

Switch body

I line for main power


101-106 control power input
and output terminal
II line connected for
emergency power
201 -206 Switch
controlling terminal

301 -306 Switch working


status indication terminal

Operate handle

Load side

NOTE:
1)Electric key lock:Control the inside controlling line power supply of the
switch,when the Electric lock open,the switch could be operated automatically
and remotely, when the electric lock closed,the switch could be operated by
handle only.
2)Operating handle: When operate the switch by the operating handle, the electric
lock must be closed.
3)Mechanic padlock:When inspection,firstly turn the switch to the'"0" position by
operation handle,then pull the padlock mechanism and close the padlock,then
the inspection can be arranged:(Pull the mechanism padlock will cut off the
inside controlling power supply of the switch. The switch couldn't be inelectric
position and also couldn't be manual operation.
4)Position indication:It means the position of the switch working estate( I ,0, I).
5)Controlling voltage: AC220V.
7
MBS1 Series Automatic Transfer Switch User Manual

5.Outline and installation dimensions


1)16A~1600A installation diagram( 2 input 1 output )

400A-600A

100A 160A-250A

2)16A~1600A installation dimensions( 2 input 1 output )

8
MBS1 Series Automatic Transfer Switch User Manual

3) 2000A~3200A installation diagram(2 input 1 output)

2000A-3200A

4)2000A~3200A installing dimensions(2 input 1 output)

9
MBS1 Series Automatic Transfer Switch User Manual

6.Wiring instructions
1)Terminal function description
Terminal Function Remarks
AC220V power output is only used as
101,106 AC220V,>1A
signal lamp power supply.
I-way working power input, 102: L, 103:
102,103 AC220V,>5A
N.
II channel working power input, 105:L,
104,105 AC220V,>5A
105: N.
Mode selection: short circuit is fully Automatic switching, mains
201,206
automatic and disconnection is manual. power priority.
External passive control input common
202
terminal.
After connecting with 202, circuit I is
203 External passive control.
closed.
BA series has no fire
After connecting with 202, circuit 0 is
204 fighting function.
closed (fire fighting).
After connecting with 202, circuit II is
205
closed.
301,306 Start the generator set remotely. Passive contact output.
Switch position feedback signal output
302
common terminal.
After closing, it is closed
303 I circuit closing feedback signal output.
with 302.
After closing, it is closed
304 0 circuit closing feedback signal output.
with 302.
After closing, it is closed
305 II circuit closing feedback signal output.
with 302.
The following functions are applicable to switches above 400A.

401,406 spare
Close after closing and
402,403 I-way position auxiliary terminal.
open after opening.
Close after closing and
404,405 II-way position auxiliary terminal.
open after opening.
501,506 spare
It is closed automatically
Manual / automatic mode indication
502,503 and disconnected
output.
manually.
Close when normal and
504,505 Padlock status output
open when pulled up.

10
MBS1 Series Automatic Transfer Switch User Manual

2)Typical application wiring diagram

7.Product installation
1)Proofreading before installation

Product delivery
Check and confirm whether the product is the same as the product ordered
by yourself.
Check the voltage
11
MBS1 Series Automatic Transfer Switch User Manual

Check and confirm the voltage and the working voltage of the product.
Check and confirm whether the scope of use is consistent.
Install products
Follow the instructions in this file to install the product.
Install all external options.
Wiring the product
Connect the bus corresponding to the rated current of the switch.
Connect the control line and external indication line according to the wiring
diagram in the manual.
2)Operation method of wiring terminal

3)Installation method description

Best installation method Correct installation method

Correct installation method Incorrect installation method


12
MBS1 Series Automatic Transfer Switch User Manual

8.Test after installation


1) Connect the common power supply (I) and standby power supply (II) to
the copper bar of the corresponding terminal block;
2) Automatic debugging
(1)The common power supply is powered, the standby power supply
is powered, and the switch I is connected;
(2)The common power supply loses power, the standby power supply
has power, and the switch II is connected;
(3)The common power supply is energized, and the switch I is
connected;
3)Remote control commissioning
(1)Jog button SB1, then switch I is connected;
(2)Jog button SB2, then switch II is connected;
4) Automatic / remote control (manual) test
(1) Pull the function selection switch to the automatic position: the
switch shall act according to the requirements of Article 2;
(2)Pull the function selection switch to the remote control (manual
position): the switch shall act according to the requirements of Article
5)When the switch is in the on state of circuit I or II wiring, the signal lamp
on the panel shall make corresponding indication;
6)After the test, first turn off the power supply and turn the switch to "0"
position with the handle.

Chongqing Mebay Technology Co.,Ltd


Add: No6-2,Building 4, Gangan Rd, Jiangbei District, Chongqing.
Tel:+86-23-6869 3061
Fax:+86-23-6765 8207
Web:http://www.mebay.cn
http://www.cqmb.cn
E_mail:sales@mebay.cn

13

You might also like