PROTECTION RELAY
R E L A Y T E C H N I C A L D A T A ANGKE 1
Relay name (-F871L) OH5MPU Rated current sec. 5 Amp
Relay Type 6MD10 Rated voltage sec. (L-L) 100-125 VAC
Manufacturer SIEMENS Rated frequency 50 Hz
Product Code MLFB 7SD61055BB993BA0 Aux. Voltage 110 VDC
Serial No. BF1806510123 CT Ratio 4000/5
Firmware version V04.62.03 VT Ratio 150/0.1 kV
Bootsystem/P-Set V02.06.00/V04.62.03
For testing purpose Feeder +ESF 235 (at GI 150kV Angke) is kept as Local End Relay and B01+R2 (at GI 150kV
Muara Karang) Feeder as Remote End Relay.
Relay Address:
Side which Action on relay Angke 1 display Action on relay Muara Karang 1
current Current display
Phase
injected injected
injected
(Amps) LED Master Trip CB LED Master Trip CB
Operate Operate Operate Operate
Injected 0,58 Led OK (F 86 L) OK Led OK OK (CB A
L1
From 1,2,3 1,2,3 CB AB)
Angke 1 0,58 Led OK (F 86 L) OK Led OK OK (CB A
L2
1,2,4 1,2,4 CB AB)
0,58 Led OK (F 86 L) OK Led OK OK (CB A
L3
1,2,5 1,2,5 CB AB)
Side which Action on relay Angke 1 display Action on relay Muara Karang 1
current Current display
Phase
injected injected
injected
(Amps) LED Master Trip CB LED Master Trip CB
Operate Operate Operate Operate
Injected
1,1 Led OK (F 86 L) OK Led OK OK (CB A
From L1
1,2,3 1,2,3 CB AB)
Muara
1,1 Led OK (F 86 L) OK Led OK OK (CB A
Karang 1 L2
1,2,4 1,2,4 CB AB)
1,1 Led OK (F 86 L) OK Led OK OK (CB A
L3
1,2,5 1,2,5 CB AB)
Binary
Assignment Tested Remarks
Output
BO1 Trip Command L1 OK Assign to KTR
BO2 Trip Command L2 OK Assign to KTS
BO3 Trip Command L3 OK Assign to KTT
BO4 Auto Reclose Command OK
BO5 General Trip Command OK Assign to Master Trip F 86 L
7. Function Test :
No Description Result
1 Trip Contact Ok
2 Signal Contact Ok
3 LED Indication Ok
4 Binary Input Ok
5 Push Button Ok
6 LCD Display Ok
8. Test Equipment :
Description Remarks
Test Kit Secondary
Manufacture Omicron
Type CMC-356
Serial Number
Name
Date: