Saudi Arabian Oil Company: Notes

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

SAUDIARAMCO.

NOTES:
1.ALL DIMESNIOSN ARE IN MILLIMETERS & ELEVATIONS
ARE IN METERS UNLESS OTHERWISE NOTED.

2.ALL PIPE SIZES SHOWN ARE IN NOMINAL DIAMETER


TO FACP IN INCHES UNLESS OTHER WISE NOTED.

3. EXISTING HALON SYSTEM SHALL BE DEMOLISHED AND


REPLACED WITH CO2 FIRE SUPPRESSION SYSTEM.

OF
4.CARBON DIOXIDE SUPPRESSION SYSTEM SHALL BE
PS DESIGNED, INSTALLED, HYDROSTATICALLY TESTED,

CONSENT
COMMISSIONED AND PLACED INTO SERVICE AS PER
MAIN CYLINDERS
NFPA12, SAES-B-014 AND SAES-B-019.

•" INITIAL DISCHARGE MANIFOLD (BY VENDOR) 5.CAPACITIES , PIPE SIZES AND PIPE ROUTING SHOWN
ARE PRELIMINARY. DRAWINGS SHALL BE DEVELOPED
S TO FACP FURTHER IN DETAIL DURING DETAIL DESIGN

TTEN
ENGINEERING.

6.ALL ABOVE GROUND PIPES UPTO ƒ" (20MM) DIA. SHALL


E E

WRI
BE GALVANIZED SEAMLESS STEEL PIPE CONFORMING
TO ASTM A53, GRADE B, SCHEDULE 40 AND FITTINGS
CPG CPG SHALL BE MALLEABLE IRON GALVANIZED THREADED

THE
FITTINGS CONFORMING TO CLASS 300.

7.ALL ABOVE GROUND PIPES 1" (25MM) DIA AND

THOUT
ABOVE SHALL BE CARBON STEEL A106, GRADE B,

D ERW/SEAMLESS, BEVEL END, SCHEDULE 80, AND


FITTINGS SHALL BE BUTT WELDED FITTINGS ,
CONFORMING TO ASTM A234 GRADE WPB, SCHEDULE

WI
80 AND THEIR DIMENSION CONFORMING TO ASME
•"
B16.9.

NG
CO2 CYLINDER

DRAWI
8.ALL OPENINGS WITHIN THE PROTECTED AREA SHALL
100 lbs (TYP.) BE PERMANENTLY SEALED OR EQUIPPED WITH
AUTOMATIC DOOR CLOSURES/DAMPERS.

9. A ROOM INTEGRITY TEST SHALL BE PERFORMED TO

S
ENSURE THE PROTECTED AREA IS SEALED PROPERLY.

THI
10.FOR CONTROL CABLES AS PER NFPA 70 AND 72,
REFER TO FIRE ALARM DRAWINGS.

FROM
EXTENDED DISCHARGE MANIFOLD (BY VENDOR)
DIESEL GENERATOR
11.ALL TUBINGS SHALL BE OF STAINLESS STEEL OR
AS RECOMMENDED BY CO2 MANFACTURER.

NED
12.ALL FIRE PROTECTION EQUIPMENTS SHALL BE UL
LISTED/ FM APPROVED.

OBTAI
13.THIS IS A PROJECT PROPOSAL DRAWING ONLY.
CPG CPG CPG DRAWINGS SHALL BE DEVELOPED FURTHER
DURING DETAIL DESIGN ENGINEERING

BE
LEGEND

PART,SHALL
CYLINDER
CPG PRESSURE
GAUGE

BY VENDOR LOCK-OUT
VALVE WITH SWITCH

N
I
PS PRESSURE SWITCH

FULL,OR
RESERVE CYLINDERS
DISCHARGE NOZZLE
INITIAL DISCHARGE MANIFOLD (BY VENDOR)

N
I
DAMPER

ON
REPRODUCTI
SELECTOR
E E S
SWITCH

CPG CPG

D DIFFERENTIAL CHECK VALVE

SAUDIARAMCO.NO
D
CHECK VALVE

E SOLENOID VALVE / ELECTRIC CONTROL HEAD

TYP. TYPICAL

REFERENCE DRAWINGS
DESIGN DATA SCHEDULE

OF
DWG. CONTROL FOR J.O.BI-10-00844-0001 PD-00ADCL
EQUIPMENT EMERGENCY DIESEL GENERATOR
CO2 FIRE SUP.SYS. PIPING LAYOUT PA-00B107

PROPERTY
EXTENDED DISCHARGE MANIFOLD (BY VENDOR)
EXTINGUISHING AGENT TYPE CO2 (CARBON DIOXIDE)

TOTAL FLOODING SYSTEM


SYSTEM TYPE
(INITIAL/ EXTENDED DISCHARGE)

DESIGN CONCENTRATION 50%

3
FLOODING FACTOR 1.60 KG CO2/M

SOLE
CPG CPG CPG
HAZARD LENGTH 6.5 M

THE
HAZARD WIDTH 2.2 M

HAZARD HEIGHT 2.1 M

ARE
2
HAZARD AREA 14.3 M

3
HAZARD VOLUME 30.0 M

N
HEREI
AGENT CAPACITY INITIAL - 60 KG / EXTENDED - 109 KG

NUMBER OF CYLINDERS INITIAL - 2 No's / EXTENDED - 3 No's

NED
CYLINDER ARRANGEMENT DUTY (MAIN) / STANDBY (RESERVE) SCALE: N.T.S

CONTAI
STANDARDS NFPA 12, SAES -B-019
REVISION VALIDATION

THIS REVISION NO. IS COVERED, FOR ALL APPROVAL AND CERTIFICATION


REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

ON
NFORMATI
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

REV.NO. DATE REVISION DESCRIPTION

I
C 07/01/21 ISSUED FOR 100% - PP

THE
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
10-00844-0001 CONSTRUCTION UNTIL CERTIFIED AND DATED
1 CO2 SYSTEM - DIESEL ENGINE GENERATOR
SAUDI ARABIAN OIL COMPANY

AND
-
SCALE N.T.S
SH DRAWING TYPE

CO2 SYSTEM FP SCH. LAYOUT FPS

NG
DIESEL GENERATOR

DRAWI
EAST/WEST PIPELINE PUMP STATION #1

YANBU SAUDI ARABIA

S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
K04 B PA-00B106 001 C
Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-05