NOTES:
1.ALL DIMESNIOSN ARE IN MILLIMETERS & ELEVATIONS
ARE IN METERS UNLESS OTHERWISE NOTED.

2.ALL PIPE SIZES SHOWN ARE IN NOMINAL DIAMETER


IN INCHES UNLESS OTHER WISE NOTED.

3. EXISTING HALON SYSTEM SHALL BE DEMOLISHED AND


REPLACED WITH CO2 FIRE SUPPRESSION SYSTEM.

OF
4.CARBON DIOXIDE SUPPRESSION SYSTEM SHALL BE
DESIGNED, INSTALLED, HYDROSTATICALLY TESTED,

CONSENT
COMMISSIONED AND PLACED INTO SERVICE AS PER
NFPA12, SAES-B-014 AND SAES-B-019.
TO FACP
5.CAPACITIES , PIPE SIZES AND PIPE ROUTING SHOWN
ARE PRELIMINARY. DRAWINGS SHALL BE DEVELOPED
FURTHER IN DETAIL DURING DETAIL DESIGN

TTEN
ENGINEERING.

PS 6.ALL ABOVE GROUND PIPES UPTO ƒ" (20MM) DIA. SHALL

WRI
MAIN CYLINDERS BE GALVANIZED SEAMLESS STEEL PIPE CONFORMING
TO ASTM A53, GRADE B, SCHEDULE 40 AND FITTINGS

•" INITIAL DISCHARGE MANIFOLD (BY VENDOR) SHALL BE MALLEABLE IRON GALVANIZED THREADED

THE
FITTINGS CONFORMING TO CLASS 300.

S TO FACP 7.ALL ABOVE GROUND PIPES 1" (25MM) DIA AND

THOUT
ABOVE SHALL BE CARBON STEEL A106, GRADE B,
ERW/SEAMLESS, BEVEL END, SCHEDULE 80, AND
E E E E E FITTINGS SHALL BE BUTT WELDED FITTINGS ,
…" (SEE NOTE-11)
CONFORMING TO ASTM A234 GRADE WPB, SCHEDULE

WI
CPG CPG CPG CPG CPG 80 AND THEIR DIMENSION CONFORMING TO ASME
B16.9.

NG
DRAWI
8.ALL OPENINGS WITHIN THE PROTECTED AREA SHALL
BE PERMANENTLY SEALED OR EQUIPPED WITH
AUTOMATIC DOOR CLOSURES/DAMPERS.
D
9. A ROOM INTEGRITY TEST SHALL BE PERFORMED TO

S
ENSURE THE PROTECTED AREA IS SEALED PROPERLY.

THI
•" 10.FOR CONTROL CABLES AS PER NFPA 70 AND 72,
REFER TO FIRE ALARM DRAWINGS.

FROM
CO2 CYLINDER
100 lbs (TYP.) 11.ALL TUBINGS SHALL BE OF STAINLESS STEEL OR
AS RECOMMENDED BY CO2 MANFACTURER.

NED
12.ALL FIRE PROTECTION EQUIPMENTS SHALL BE UL
LISTED/ FM APPROVED.

OBTAI
13.THIS IS A PROJECT PROPOSAL DRAWING ONLY.
DRAWINGS SHALL BE DEVELOPED FURTHER
EXTENDED DISCHARGE MANIFOLD (BY VENDOR)
DURING DETAIL DESIGN ENGINEERING
TURBINE ENCLOSURE

BE
LEGEND

PART,SHALL
CYLINDER
CPG CPG CPG CPG CPG CPG CPG PRESSURE
GAUGE

LOCK-OUT
VALVE WITH SWITCH

N
I
FULL,OR
PS PRESSURE SWITCH

BY VENDOR DISCHARGE NOZZLE

N
I
DAMPER

ON
REPRODUCTI
SELECTOR
RESERVE CYLINDERS S
SWITCH

INITIAL DISCHARGE MANIFOLD (BY VENDOR)

D DIFFERENTIAL CHECK VALVE

SAUDIARAMCO.NO
E E E E E
CHECK VALVE

CPG CPG CPG CPG CPG


E SOLENOID VALVE / ELECTRIC CONTROL HEAD

TYP. TYPICAL
D

REFERENCE DRAWINGS

OF
DWG. CONTROL FOR J.O.BI-10-00844-0001 PD-00ADCL
CO2 FIRE SUP.SYS. PIPING LAYOUT PA-00B109

PROPERTY
DESIGN DATA SCHEDULE

EQUIPMENT FT-4 TURBINE ENCLOSURE

EXTINGUISHING AGENT TYPE CO2 (CARBON DIOXIDE)

SOLE
TOTAL FLOODING SYSTEM
SYSTEM TYPE
(INITIAL/ EXTENDED DISCHARGE) EXTENDED DISCHARGE MANIFOLD (BY VENDOR)

DESIGN CONCENTRATION 50%

THE
3
FLOODING FACTOR 1.33 KG CO2/M

ARE
HAZARD LENGTH 12.1 M

HAZARD WIDTH 3.3 M


CPG CPG CPG CPG CPG CPG

N
HEREI
HAZARD HEIGHT 3.2 M

2
HAZARD AREA 40 M

3
HAZARD VOLUME 128 M

NED
SCALE: N.T.S

CONTAI
AGENT CAPACITY INITIAL - 204 KG / EXTENDED - 260 KG

NUMBER OF CYLINDERS INITIAL - 5 No's / EXTENDED - 6 No's REVISION VALIDATION

THIS REVISION NO. IS COVERED, FOR ALL APPROVAL AND CERTIFICATION


CYLINDER ARRANGEMENT DUTY (MAIN) / STANDBY (RESERVE) REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

ON
STANDARDS NFPA 12, SAES -B-019

NFORMATI
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

REV.NO. DATE REVISION DESCRIPTION

I
C 07/01/21 ISSUED FOR 100% - PP

THE
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
10-00844-0001 CONSTRUCTION UNTIL CERTIFIED AND DATED

1 CO2 SYSTEM - FIRE PROTECTION SCHEMATIC LAYOUT SAUDI ARABIAN OIL COMPANY

AND
-
SCALE N.T.S DRAWING TYPE
SH
CO2 SYSTEM FP SCH. LAYOUT FPS

NG
FT-4 TURBINE ENCLOSURE (ML-1/2/3)

DRAWI
EAST/WEST PIPELINE PUMP STATION #2

YANBU SAUDI ARABIA

S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
K05 B PA-00B108 001 C
Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-05