Saudi Arabian Oil Company: Notes
Saudi Arabian Oil Company: Notes
NOTES:
OF
DESIGNED, INSTALLED, HYDROSTATICALLY TESTED,
COMMISSIONED AND PLACED INTO SERVICE
DAMPERS DAMPERS
CONSENT
AS PER NFPA12, SAES-B-014 AND SAES-B-019.
TTEN
5.ALL ABOVE GROUND PIPES UPTO ƒ" (20MM) DIA. SHALL
BE GALVANIZED SEAMLESS STEEL PIPE CONFORMING
WRI
TO ASTM A53, GRADE B, SCHEDULE 40 AND FITTINGS
SHALL BE MALLEABLE IRON GALVANIZED THREADED
FITTINGS CONFORMING TO CLASS 300.
THE
6.ALL ABOVE GROUND PIPES 1" (25MM) DIA AND
ABOVE SHALL BE CARBON STEEL A106, GRADE B,
THOUT
ERW/SEAMLESS, BEVEL END, SCHEDULE 80, AND
5620
FITTINGS SHALL BE BUTT WELDED FITTINGS ,
SEE NOTE-13 CONFORMING TO ASTM A234 GRADE WPB, SCHEDULE
WI
80 AND THEIR DIMENSION CONFORMING TO ASME
B16.9.
NG
DRAWI
7.ALL OPENINGS WITHIN THE PROTECTED AREA
SHALL BE PERMANNETLY SEALED OR EQUIPPED
WITH AUTOMATIC CLOSURES.
S
THI
ENSURE THE PROTECTED AREA IS SEALED PROPERLY.
12100
9.FOR CONTROL CABLINGS AS PER NFPA 70 AND 72,
FROM
REFER TO FIRE ALARM DRAWINGS.
NED
BE CONDUCTED AT THE SITE BEFORE STARTING
ANY WORK.
OBTAI
11. THIS IS A PROJECT PROPOSAL DRAWING ONLY.
DRAWINGS SHALL BE DEVELOPED FURTHER
DURING DETAIL DESIGN ENGINEERING
BE
12.ALL FIRE PROTECTION EQUIPMENST SHALL BE UL
LISTED/ FM APPROVED.
PART,SHALL
13.CO2 SHELTER SHALL BE OF 2MM THICK STEEL SHEET,
COVERING THE SIDES WITH ACCESS DOORS INFRONT OF
THE CYLIDERS.
N
I
FULL,OR
LEGEND
SEE NOTE-7
CO2 NOZZLE
N
CO2 CYLINDER
I ON
REPRODUCTI
CO2 SYSTEM PIPE
3300
CHECK VALVE
SAUDIARAMCO.NO
REFERENCE DRAWINGS
DWG. CONTROL FOR J.O.BI-10-00844-0001 PD-00ADCL
CO2 SYSTEM FP SCHEMATIC LAYOUT PA-00B127
OF
PROPERTY
DESIGN DATA SCHEDULE
SOLE
(INITIAL/ EXTENDED DISCHARGE)
3
FLOODING FACTOR 1.33 KG CO2/M
THE
HAZARD LENGTH 12.1 M
ARE
HAZARD WIDTH 3.3 M
N
HEREI
2
HAZARD AREA 40 M
0 1.0 2.0 3.0 4.0 5.0
3
HAZARD VOLUME 128 M
METERS
NED
AGENT CAPACITY INITIAL - 204 KG / EXTENDED - 260 KG SCALE: 1 : 50M
CONTAI
NUMBER OF CYLINDERS INITIAL - 5 No's / EXTENDED - 6 No's
REVISION VALIDATION
CYLINDER ARRANGEMENT DUTY (MAIN) / STANDBY (RESERVE)
THIS REVISION NO. IS COVERED, FOR ALL APPROVAL AND CERTIFICATION
REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:
STANDARDS NFPA 12, SAES -B-019
ON
NFORMATI
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)
I
C 07/01/21 ISSUED FOR 100% - PP
THE
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
10-00844-0001 CONSTRUCTION UNTIL CERTIFIED AND DATED
AND
1 CO2 FIRE SUPPRESSION SYSTEM PIPING LAYOUT DRAWING TYPE
-
SCALE 1 :50M CO2 FIRE SUP. SYS. PIPING LAY. FPS
NG
SH
DRAWI
EAST/WEST PIPELINE PUMP STATION #4
S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.
THI
K07 B PA-00B123 001 C
Saudi Aramco 2615 ENG. (05/05)