Micromaster 420: 0.12 KW - 11 KW
Micromaster 420: 0.12 KW - 11 KW
MICROMASTER 420
0.12 kW - 11 kW
Compact Operating Manual Issue 04/04
User Documentation
Warnings, Cautions and Notes Edition 04/04
NOTES
Before installing and commissioning, please read these safety instructions and
warnings carefully and all the warning labels attached to the equipment.
Make sure that the warning labels are kept in a legible condition and replace
missing or damaged labels.
Maximum permissible surrounding ambient temperature is 50°C.
MICROMASTER 420
2 Compact Operating Manual
Edition 04/04 Contents
Contents
1 Installation ............................................................................................................... 4
1.1 Clearance distances for mounting ............................................................................ 4
1.2 Mounting dimensions ................................................................................................ 4
2 Electrical Installation.............................................................................................. 5
2.1 Technical Specifications ........................................................................................... 5
2.2 Power Terminals ....................................................................................................... 6
2.3 Control terminals....................................................................................................... 6
2.4 Block diagram ........................................................................................................... 7
4 Communications..................................................................................................... 9
4.1 Establishing communications MICROMASTER 420 ⇔ STARTER.......................... 9
4.2 Establishing communications between the MICROMASTER 420 ⇔ AOP .............. 9
4.3 Bus interface (CB)................................................................................................... 10
6 Commissioning ..................................................................................................... 13
6.1 Quick commissioning .............................................................................................. 13
6.2 Commissioning the application ............................................................................... 15
6.2.1 Serial Interface (USS) ............................................................................................. 15
6.2.2 Selection of command source ................................................................................ 16
6.2.3 Digital input (DIN).................................................................................................... 16
6.2.4 Digital output (DOUT) ............................................................................................. 17
6.2.5 Selection of frequency setpoint............................................................................... 17
6.2.6 Analog input (ADC) ................................................................................................. 18
6.2.7 Analog output (DAC)............................................................................................... 18
6.2.8 Motor potentiometer (MOP) .................................................................................... 19
6.2.9 Fixed frequency (FF)............................................................................................... 19
6.2.10 JOG......................................................................................................................... 20
6.2.11 Ramp-function generator (HLG) ............................................................................. 20
6.2.12 Reference/limit frequencies .................................................................................... 21
6.2.13 Closed-loop motor control....................................................................................... 21
6.2.14 Inverter/motor protection......................................................................................... 22
6.2.15 Inverter-specific Functions...................................................................................... 23
6.3 Series commissioning ............................................................................................. 26
6.4 Parameter reset of factory setting........................................................................... 26
MICROMASTER 420
Compact Operating Manual 3
1 Installation Issue 04/04
1 Installation
15 mm 0 mm 15 mm
...
MICROMASTER 420
4 Compact Operating Manual
Issue 04/04 2 Electrical Installation
2 Electrical Installation
3 AC 200 V – 240 V
Order No. 2AC 11- 12- 13- 15- 17- 21- 21- 22- 23- 24- 25-
6SE6420- 2UC 2AA1 5AA1 7AA1 5AA1 5AA1 1BA1 5BA1 2BA1 0CA1 0CA1 5CA1
Frame Size A B C
Inverter Output kW 0.12 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3.0 4,0 5,5
Rating hp 0.16 0.33 0.5 0.75 1.0 1.5 2.0 3.0 4.0 5,0 7,5
Input Current A 0.6 1.1 1.6 2.1 2.9 4.1 5.6 7.6 10.5 13.1 17.5
Output Current A 0.9 1.7 2.3 3.0 3.9 5.5 7.4 10.4 13.6 17.5 22.0
Recommended A 10 10 10 10 10 16 16 20 25 32 35
Fuse 3NA 3803 3803 3803 3803 3803 3805 3805 3807 3810 3812 3814
2
mm 1,0-2,5 1,0-2,5 1,0-2,5 1,0-2,5 1,0-2,5 1,0-6,0 1,0-6,0 1,0-6,0 2,5-10 2,5-10 4,0-10
Input Cable
AWG 17-13 17-13 17-13 17-13 17-13 17-9 17-9 17-9 13-7 13-7 11-7
2
mm 1.0-2.5 1.0-2.5 1.0-2.5 1.0-2.5 1.0-2.5 1.0-6.0 1.0-6.0 1.0-6.0 1.5-10 2.5-10 4.0-10
Output Cable
AWG 17-13 17-13 17-13 17-13 17-13 17-9 17-9 17-9 15-7 13-7 11-7
Nm 1.1 1.5 2.25
Tightening Torque
(lbf.in) (10) (13.3) (20)
3 AC 380 V – 480 V
Order No. 2AD 13- 15- 17- 21- 21- 22- 23- 24- 25- 27- 31-
6SE6420- 2UD 7AA1 5AA1 5AA1 1AA1 5AA1 2BA1 0BA1 0BA1 5CA1 5CA1 1CA1
Frame Size A B C
Inverter Output kW 0.37 0.55 0.75 1.1 1.5 2.2 3.0 4.0 5,5 7,5 11,0
Rating hp 0.5 0.75 1.0 1.5 2.0 3.0 4.0 5.0 7,5 10,0 15,0
Input Current A 1.1 1.4 1.9 2.8 3.9 5.0 6.7 8.5 11.6 15.4 22.5
Output Current A 1.2 1.6 2.1 3.0 4.0 5.9 7.7 10.2 13.2 19.0 26.0
Recommended A 10 10 10 10 10 16 16 20 20 25 32
Fuse 3NA 3803 3803 3803 3803 3803 3805 3805 3807 3807 3810 3814
2
mm 1,0-2,5 1,0-2,5 1,0-2,5 1,0-2,5 1,0-2,5 1,0-6,0 1,0-6,0 1,5-6,0 2,5-10 4,0-10 6,0-10
Input Cable
AWG 17-13 17-13 17-13 17-13 17-13 17-9 17-9 15-9 13-7 11-7 9-7
2
mm 1.0-2.5 1.0-2.5 1.0-2.5 1.0-2.5 1.0-2.5 1.0-6.0 1.0-6.0 1.0-6.0 1.5-10 2.5-10 4.0-10
Output Cable
AWG 17-13 17-13 17-13 17-13 17-13 17-9 17-9 17-9 15-7 13-7 11-7
Nm 1.1 1.5 2.25
Tightening Torque
(lbf.in) (10) (13.3) (20)
MICROMASTER 420
Compact Operating Manual 5
2 Electrical Installation Issue 04/04
L3
L2/N
L1/L
U V W
MICROMASTER 420
6 Compact Operating Manual
Issue 04/04 2 Electrical Installation
PE L/L1, N/L2
+10 V or
1 L/L1, N/L2, L3
0V or
2 L1, L2, L3
≥ 4.7 kΩ ADC+
3 A/D BOP link
ADC-
4 RS232
External 24 V 150.00
Hz
I Fn
0 P
DIN1 DIN1
Jog
BOP/AOP
5 5
DIN2 DIN2
6 6 ~
DIN3 DIN3
7 7 =
+
DC-link connection
_ 24 V PNP
Output +24 V
max. 100 mA
or
8 (isolated) DC+
NPN Output 0 V
max. 100 mA
9 9 (isolated) CPU DC−
RL1-B
30 V DC / 5 A (resistive)
250 V AC / 2 A (inductive) Relay 10RL1-C
11
DAC+ =
0 - 20 mA 12 D/A
max. 500 Ω DAC- 3~
13
Not
60 Hz
P+ used
50 Hz
14 RS485 COM link
1 2
N-
The analog input circuit can be DIP switch
alternatively configured to 15
provide an additional digital PE U,V,W
input (DIN4): CB
automatic
2 Option
DIN4 3
M
4
+ - 9
24 V
MICROMASTER 420
Compact Operating Manual 7
3 Factory setting Issue 04/04
3 Factory setting
The MICROMASTER 420 frequency inverter is set in the factory so that it can be
operated without any additional parameterization. To do this, the motor parameters
set in the factory (P0304, P0305, P0307, P0310), that correspond to a 4-pole 1LA7
Siemens motor, must match the rated data of the connected motor (refer to the
rating plate).
Further factory setting:
Command sources P0700 = 2 (Digital input, see Fig. 3-1)
Setpoint source P1000 = 2 (Analog input, see Fig. 3-1)
Motor cooling
P0335 = 0
Motor current limit
P0640 = 150 % I/O
Min. frequency Ack
P1080 = 0 Hz
Digital Inputs
Max. frequency
P1082 = 50 Hz
Analog input
Ramp-up time
P1120 = 10 s
Ramp-down time
< 4.7 k Ω
P1121 = 10 s
Control mode Fig. 3-1 Analog and Digital Inputs
P1300 = 0
Input/Output Terminals Parameter Function
Digital input 1 5 P0701 = 1 ON / OFF1 (I/O)
Digital input 2 6 P0702 = 12 Reverse ( )
Digital input 3 7 P0703 = 9 Fault reset (Ack)
Digital input 8 - Power supply Digital input
3/4 P1000 = 2 Frequency setpoint
Analog input
1/2 - Power supply Analog input
Output relay 10/11 P0731 = 52.3 Default identification
Analog output 12/13 P0771 = 21 Output frequency
MICROMASTER 420
8 Compact Operating Manual
Issue 04/04 4 Communications
4 Communications
STARTER
Menu, Options --> Set PG/PC interface -->
Select "PC COM-Port (USS)" --> Properties --
> Interface "COM1", select a baud rate
NOTE
The USS parameter settings in the
MICROMASTER 420 frequency inverter and
the settings in STARTER must match!
Table 4-1
AOP at the BOP link AOP at the COM link
MM420 parameters
- baud rate P2010[1] P2010[0]
- bus address – P2011
AOP parameters
- baud rate P8553 P8553
- bus address – P8552
Options
- direct connection No option necessary Not possible
- indirect connection BOP/AOP door mounting kit AOP door mounting kit
(6SE6400-0PM00-0AA0) (6SE6400-0MD00-0AA0)
MICROMASTER 420
Compact Operating Manual 9
4 Communications Issue 04/04
Baud rate is
automatically specified
by the master
MICROMASTER 420
10 Compact Operating Manual
Issue 04/04 5 BOP / AOP (Option)
MICROMASTER 420
Compact Operating Manual 11
5 BOP / AOP (Option) Issue 04/04
6 Now access level 3 is set and all level 1 to level 3 parameters are visible to the user.
MICROMASTER 420
12 Compact Operating Manual
Issue 04/04 6 Commissioning
6 Commissioning
START
Factory setting
User access level * 1
P0003 = 2
1 Standard: Allows access into most frequently used parameters
2 Extended: Allows extended access e.g. to inverter I/O functions
3 Expert (For expert use only)
Commissioning parameter * 0
P0010 = 1
0 Ready
1 Quick commissioning
30 Factory setting
NOTE
P0010 should be set to 1 in order to parameterize the data of the motor rating
plate.
Europe/ North America 0
P0100 =... 60 Hz
(enters the line supply frequency) 50 Hz
0 Europe [kW], frequency default 50 Hz
P0100 = 1, 2 1 North America [hp], frequency default 60 Hz
2 North America [kW], frequency default 60 Hz 50/60 Hz DIP switch
for frequency setting
NOTE
For P0100 = 0 or 1, the setting of switch DIP2(2)
P0100 = 0 determines the value of P0100 (refer to the
parameter list).
FU-spec.
P0304 =... P0304 =... Rated motor voltage
(Nominal motor voltage [V] from rating
plate)
The rated motor voltage on the rating
plate must be checked, regarding the
star/delta circuit configuration to ensure P0310 P0304
that it matches with the circuit
connection configured at the motor
terminal board
FU-spec.
P0305 =... P0305 =... Rated motor current
(Nominal motor current [A] from rating
plate)
FU-spec. P0307 P0305
P0307 =... P0307 =... Rated motor power P0308 P0311
(Nominal motor power [kW/hp] from
rating plate)
If P0100 = 0 or 2, value will be in kW. If
P0100 = 1, value will be in in hp.
FU-spec.
P0308 =... P0308 =... Rated motor cosPhi
(Nominal motor power factor (cos ϕ) from rating plate)
If the setting is 0, the value is automatically calculated
P0100 = 1,2: P0308 no significance, no entry required.
MICROMASTER 420
Compact Operating Manual 13
6 Commissioning Issue 04/04
FU-spec.
P0309 =... P0309 =... Rated motor efficiency
(Nominal motor efficiency in [%] from rating plate)
Setting 0 causes internal calculation of value.
P0100 = 0: P0309 no significance, no entry required.
Rated motor frequency 50.00 Hz
P0310 =...
(Nominal motor frequency in [Hz] from rating plate)
Pole pair number recalculated automatically if parameter is changed.
Rated motor speed FU-spec.
P0311 =...
(Nominal motor speed in [rpm] from rating plate)
Setting 0 causes internal calculation of value.
NOTE
For slip compensation, the input is absolutely necessary.
Motor cooling 0
P0335 =...
(Selects motor cooling system used)
0 Self-cooled: Using shaft mounted fan attached to motor
1 Force-cooled: Using separately powered cooling fan
Motor overload factor 150 %
P0640 =...
(Motor overload factor in [%] relative to P0305)
This defines the limit of the maximum output current as a % of the rated motor
current (P0305).
Selection of command source 2
P0700 =...
0 Factory default setting
1 BOP (keypad)
2 Terminal
4 USS on BOP link
5 USS on COM link
6 CB on COM link
Selection of frequency setpoint 2
P1000 =...
1 MOP setpoint
2 Analog setpoint
3 Fixed frequency
4 USS on BOP link
5 USS on COM link
6 CB on COM link
Min. frequency 0.00 Hz
P1080 =...
(enters the minimum motor frequency in Hz)
Sets minimum motor frequency at which motor will run irrespective of frequency
setpoint. The value set here is valid for both clockwise and anticlockwise rotation.
Max. frequency 50.00 Hz
P1082 =...
(enters the maximum motor frequency in Hz)
Sets maximum motor frequency at which motor will run irrespective of the
frequency setpoint. The value set here is valid for both clockwise and
anticlockwise rotation.
Ramp-up time 10.00 s
P1120 =...
(enters the ramp-up time in s)
Time taken for motor to accelerate from standstill up to maximum motor
frequency (P1082) when no rounding is used.
Ramp-down time 10.00 s
P1121 =...
(enters the deceleration time in s)
Time taken for motor to decelerate from maximum motor frequency (P1082) down
to standstill when no rounding is used
OFF3 ramp-down time 5.00 s
P1135 =...
(enters the fast stop ramp-down time in s)
Defines ramp-down time from maximum frequency to standstill for OFF3
command.
MICROMASTER 420
14 Compact Operating Manual
Issue 04/04 6 Commissioning
Control mode 0
P1300 =...
(enters the required control mode)
0 V/f with linear characteristic
1 V/f with FCC
2 V/f with parabolic characteristic
3 V/f with programmable characteristic
End of quick commissioning 0
P3900 = 1
(start of the motor calculation)
0 No quick commissioning (no motor calculations)
1 Start quick commissioning with factory reset
2 Start quick commissioning
3 Start quick commissioning only for motor data
NOTE
For P3900 = 1,2,3 → P0340 is internally set to 1 and the appropriate data
calculated (refer to the parameter list P0340).
Factory setting
User access level * 1
P0003 = 3
1 Standard (Allows access into most frequently used parameters)
2 Extended (Allows extended access e.g. to inverter I/O functions)
3 Expert (for expert use only)
MICROMASTER 420
Compact Operating Manual 15
6 Commissioning Issue 04/04
DIN channel
Kl.8 P24 Function of DIN 1
Debounce time: DIN 0 ... 99
0 ... 3 P0701 (1)
Kl.9 0 V P0724 (3)
24 V T 0 0
Function
&
...
99
0V
r0722
r0722
CO/BO: Bin.inp.val
MICROMASTER 420
16 Compact Operating Manual
Issue 04/04 6 Commissioning
MOP
Sequence control
ADC
FF P1000 = 12 Additonal
setpoint
USS Setpoint Motor
BOP link channel control
USS P1000 = 12 Main
COM link setpoint
CB
COM link
MICROMASTER 420
Compact Operating Manual 17
6 Commissioning Issue 04/04
ADC channel
P0757
P0758
P0759
P0760
r0754
KL1 P0756 P0753 P0761
+10 V
P1000 = 2
KL3 ADC
A ADC ADC
KL4 scaling dead Setpoint
D type zone
r0752
P0704 = x
1
1.7 V
Function
0
3.9 V r0722
r0722.3
DAC channel
P0777
P0788
P0779
P0780
r0774
P0773 P0781
MICROMASTER 420
18 Compact Operating Manual
Issue 04/04 6 Commissioning
USS on P0719 = 0, P0700 = 5, P1000 = 1 USS control word USS control word
or
COM link P0719 = 51 r2036 Bit13 r2036 Bit14
P0719 = 0, P0700 = 6, P1000 = 1 CB control word CB control word
CB or
P0719 = 61 r2090 Bit13 r2090 Bit14
MICROMASTER 420
Compact Operating Manual 19
6 Commissioning Issue 04/04
6.2.10 JOG
JOG frequency right 5.00 Hz
P1058 =...
Frequency in Hz when the motor is being
jogged in the clockwise direction of rotation. JOG
f1
t
P1120 P1121
MICROMASTER 420
20 Compact Operating Manual
Issue 04/04 6 Commissioning
V
Linear V/f
Boost voltage
Vmax
Validity range
Vn e
ag ON
(P0304) olt
u tv OFF t
tp
Ou f
actual VBoost
VConBoost,100 f
V/ )
al = 0 t
m
or 0 P1310 active
N 130
VConBoost,50 (P 1
0 t
f
0 fBoost,end fn f max
(P1316) (P0310) (P1082)
MICROMASTER 420
Compact Operating Manual 21
6 Commissioning Issue 04/04
MICROMASTER 420
22 Compact Operating Manual
Issue 04/04 6 Commissioning
r0027
2 Motor F0011
i2t
P0305 r0034
temp. I_max reduction
t
( i2 t ) reaction
r0021 A0511
P0610
P0310
P0335
P0614
Warning threshold
Flying start 0
P1200 =...
Starts inverter onto a spinning motor by rapidly changing the output frequency of the
inverter until the actual motor speed has been found.
0 Flying start disabled
1 Flying start is always active, start in direction of setpoint
2 Flying start is active if power on, fault, OFF2, start in direction of setpoint
3 Flying start is active if fault, OFF2, start in direction of setpoint
4 Flying start is always active, only in direction of setpoint
5 Flying start is active if power on, fault, OFF2, only in direction of setpoint
6 Flying start is active if fault, OFF2, only in direction of setpoint
Motor-current: Flying start (entered in %) 100 %
P1202 =...
Defines search current used for flying start.
Search rate: Flying start (entered in %) 100 %
P1203 =...
Sets factor by which the output frequency changes during flying start to synchronize with
turning motor.
Automatic restart 0
P1210 =...
Configures automatic restart function.
0 Disabled
1 Trip reset after power on
2 Restart after mains blackout
3 Restart after mains brownout or fault
4 Restart after mains brownout
5 Restart after mains blackout and fault
6 Restart after mains brown/blackout or fault
MICROMASTER 420
Compact Operating Manual 23
6 Commissioning Issue 04/04
0 t
6.2.15.4 DC braking
f
fact
fset
MICROMASTER 420
24 Compact Operating Manual
Issue 04/04 6 Commissioning
P2261
MOP
r2273
r2294
P2254 P2291 0
ADC Motor
PID PID PID control
P2253 PID 1
PID SUM RFG PT1
FF −
∆PID
P2269
P2270
P2292
USS PIDOutput
P2267
BOP link
USS PID PID
P2264
COM link PT1 SCL
Example:
Parameter Parameter text Example
P2200 BI: Enable PID controller P2200 = 1.0 PID controller active
P2253 CI: PID setpoint P2253 = 2224 PID-FF1
P2264 CI: PID feedback P2264 = 755 ADC
P2267 Max. PID feedback P2267 Adapt to the application
P2268 Min. PID feedback P2268 Adapt to the application
P2280 PID proportional gain P2280 Determined by optimizing
P2285 PID integral time P2285 Determined by optimizing
P2291 PID output upper limit P2291 Adapt to the application
P2292 PID output lower limit P2292 Adapt to the application
MICROMASTER 420
Compact Operating Manual 25
6 Commissioning Issue 04/04
Commissioning parameter 0
P0010=30
30 Factory setting
Factory reset 0
P0970 = 1
0 disabled
1 Parameter reset
The drive inverter carries-out a parameter reset (duration, approx. 10 s) and then
automatically exits the reset menu and sets:
P0970 = 0 : disabled
END P0010 = 0 : ready
MICROMASTER 420
26 Compact Operating Manual
Issue 04/04 7 Displays and messages
OFF
ON
approx. 0.3 s, flashing
approx. 1 s, twinkling
MICROMASTER 420
Compact Operating Manual 27
MICROMASTER 420 Compact Operating Manual
Regional Contacts
Please get in touch with your contact for Technical Support in your Region for questions
about services, prices and conditions of Technical Support.
America
Tel: +1 423 262 2522
Fax: +1 423 262 2589
Email: simatic.hotline@sea.siemens.com
Asia / Pacific
Tel: +86 1064 757 575
Fax: +86 1064 747 474
Email: adsupport.asia@siemens.com
Internet Address
Customers can access technical and general information under the following address:
http://www.siemens.de/micromaster
Siemens AG
Bereich Automation and Drives (A&D)
Geschäftsgebiet Standard Drives (SD)
Postfach 3269, D-91050 Erlangen © Siemens AG, 2004
Bundesrepublik Deutschland Änderungen vorbehalten